Public Works Department-PWD has published Supply, Installation, Testing And Commissioning Of Central Heating System Along With Allied Works At District Hospital Ganderbal.-2 Hot Water Generator 3 Horizontal Water Tube Type Hot Water Generator Complete With Combustion Equipments, Control . Submission Date for this Tender is 27-06-2022. Tanks and Cylinders Tenders in ganderbal Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 11-Jun-2022 | date extension | Date | 16-06-2022 |
2 | 16-Jun-2022 | date extension 2 | Date | 27-06-2022 |
Sl. No. | Item Description |
1 | Supply, Installation, Testing and Commissioning of |
2 | Hot Water Generator |
3 | Horizontal water tube type hot water generator complete with combustion equipments, control panel, controls, drain valve with piping and other accessories complete in all respects alongwith foundation as per OEM recommendations. |
4 | Capacity each 600,000 Kcal/ Hr |
5 | Boiler Chimeny |
6 | M. S hot water Generator flue duct of requireddiameter as per OEM of HWGmanufactured from 5 mm thick MS sheet with 10 mm thick MS base plate installed on cement concrete foundation and firmly clamped onto the building wall. |
7 | Pumps |
8 | Hot water Circulation Pumps |
9 | Hot Water Circulation Monoblock Pump complete with TEFC electric motor with "class F" insulation, pump with mechanical seal suitable for hot water application upto 90ºC alongwith butterfly valves (2 No), Y- strainer (1 No) NRV (1 No), Pressure gauge with stand pipe and gauge cocks (2 No), Temperature gauge (2 No). Pumps are to be mounted on common base frame duly grouted in cement concrete foundation. |
10 | Capacity 350 GPM at 40 m Head |
11 | Oil Transfer Pumps |
12 | Gear Oil Transfer Pump with 3 HP flame proof motor rating alongwithcommon base frame duly grouted in cement concrete foundation.Suction: 50 mm Delivery: 50 mmCapacity 50 LPM |
13 | Softwater Pumps |
14 | Soft Water Pumpcomplete with electric motor of 1 HP rating alongwithcommon base frame duly grouted in cement concrete foundation.Capacity 50 LPM at 15 m Head |
15 | Tanks |
16 | Mixing Tank |
17 | Hot water mixing tank made of 6/8 MM M.S. Plate with dished ends, manhole dully covered and necessary connections covered with 50mm thick glasswool insulationand finished with 24 Gauge Aluminium cladding and complete as per specifications and drawingwith structural support to raise the tank at least 300 mm above finish FL. |
18 | 4250 litres, size 1.4 M DIA X 2.75 M long. |
19 | Bulk oil tank |
20 | Bulk oil tank 20klcomplete of 6/8 mm MS plate with manhole dully covered to be laid underground as per specifications and drawings |
21 | 20000 litres, size 2.1 M DIA X 6 M long. |
22 | Day Oil Tank |
23 | Day oil tank of 5 MM M.S plate complete with manhole dully covered, Gauge Glass 9 Kw OilHeater, necessary connections and strucrural support for mounting oil tank and ladder made out of tubular MS Section complete as per specifications and drawing. |
24 | Capacity 990 litres,each size 1 m X 1 m X 1 m |
25 | Expansion Tank |
26 | Hot Water Expansion Tank of 4 mm M.S complete with manhole dully covered, necessary connections covered with 50mm thick glasswool insulation and finished with 24 Gauge Aluminium cladding and strucrural support for mounting Expansion tank |
27 | Capacity 2000 litres,each size 1.45 m X 1.45 m X 1.0 m |
28 | Soft Water Tank |
29 | Soft water tank of HDPE (tripple layer) with necessary connections Capacity 1000 litres |
30 | Water Softener |
31 | Water Softener havingsteel body with accessories viz softner pump, valve, requisite brine tank etc. complete in all respect alongwith cement concrete foundation. Capacity 1500 litres/hr |
32 | Hot Water Radiators |
33 | Steel panel heating radiators with working pressure ranging from 10-13 bar having working temperature at 110 c ,complete with Top grilles and side covers as standard alongwith inlet valve, outlet valve, air purge valve and threaded plug as per OEM Inlet Water Temp: 75ºC Outlet Water Temp: 65ºC Room Temp: 22 ºC |
34 | 1000 Kcal/Hr (Double Panel Double Convector) |
35 | 1500 Kcal/Hr (Double Panel Double Convector) |
36 | 2000 Kcal/Hr (Double Panel Double Convector) |
37 | 2500 Kcal/Hr (Double Panel Double Convector) |
38 | 3000 Kcal/Hr (Double Panel Double Convector) |
39 | 3500 Kcal/Hr (Tripple Panel Tripple Convector) |
40 | 4000 Kcal/Hr (Tripple Panel Tripple Convector) |
41 | Hydronic Hi-Wall Units |
42 | Hydronic Hi-Wall Units complete with inlet outlet/ outlet valves, Y-strainer and copper piping and fittings etc. Inlet Water Temp: 75 oC Outlet Water Temp: 65 oC Room Temp: 22 oC |
43 | 6000 Kcal/Hr |
44 | M.S. Piping (Hot water) |
45 | Mildsteel ERW hot water piping of class ‘C’ (above/underground) complete with fittings like elbow, Tee, bends, flanges etc alongwith structural supports as per norms and two coats of red oxide primer follwed by two or more coats of butiminous paint complete in all respects. |
46 | 300 mm DIA |
47 | 250 mm DIA |
48 | 200 mm DIA |
49 | 150 mm DIA |
50 | 125 mm DIA |
51 | 100 mm DIA |
52 | 80 mm DIA |
53 | 65 mm DIA |
54 | 50 mm DIA |
55 | 40 mm DIA |
56 | 32 mm DIA |
57 | 25 mm DIA |
58 | 20 mm DIA |
59 | M.S. Piping (Chilled Water) |
60 | 100 mm DIA |
61 | 80 mm DIA |
62 | 65 mm DIA |
63 | 50 mm DIA |
64 | 40 mm DIA |
65 | Pipe insulation (Hot water) |
66 | Elastrometric Closed Cell Nitrile with Glass Clothas per specifications. |
67 | 250 mm DIA |
68 | 200 mm DIA |
69 | 150 mm DIA |
70 | 125 mm DIA |
71 | 100 mm DIA |
72 | 80 mm DIA |
73 | 65 mm DIA |
74 | 50 mm DIA |
75 | 40 mm DIA |
76 | 32 mm DIA |
77 | 25 mm DIA |
78 | 20 mm DIA |
79 | Glasswool pipe sections of 80Kg/CuM density insulationalong with chicken mesh and Aluminium cladding of 26 Gauge as per specifications. |
80 | 300 mm DIA |
81 | 250 mm DIA |
82 | 100 mm DIA |
83 | 80 mm DIA |
84 | Glasswool pipe sections of 80Kg/CuM density insulationalong with chicken meshand tar felt as per specifications. |
85 | 250 mm DIA |
86 | Pipe insulation (Chilled water) |
87 | Elastrometric Closed Cell Nitrile with Glass Clothas per specifications. |
88 | 100 mm DIA |
89 | 80 mm DIA |
90 | 65 mm DIA |
91 | 50 mm DIA |
92 | 40 mm DIA |
93 | Underground/ Above Ground (Oil Line) |
94 | 4mm thick pypekote insulation. |
95 | 50 mm DIA |
96 | 40 mm DIA |
97 | 25 mm DIA |
98 | 20 mm DIA |
99 | M.S. Piping (Galvanised) |
100 | Mildsteel ERW (Galvanised) water piping of class ‘B’ complete with fittings elbow, Tee, bends, flanges etc alongwith structural supports as per norms etc as per specifications anddrawings. |
101 | 25 mm DIA |
102 | Air Handling Units (TFA) |
103 | Eurovent certified air handling units comprising of following specifications: Double skinned panels of 50mm thickness with internal insulation material PUF with 38±2 kg/m³ density sandwiched between two sheets and fixed to extruded aluminium structural framework with thermal break profile. Inner Sheet shall be 0.60 mm thick of Plain GSS. Outer Sheet shall be 0.60mm thick of Precoated GSS. The entire framework shall be mounted on GSS Channel base. Access doors shall be double skin type. Condensate drain pan shall be of 1.2mm SS with 13mm thick nitrile rubber insulation. Fan section complete with forward/ Backward curved DIDW type centrifugal fans of 100% capacity each, TEFC squirrel cage induction motor suitable to operate on 415+10%V, 50Hz,3 phase AC power supply and belt drive package. Filter section complete with pre filter of efficiency 90% down to 10 microns and fine filter of 99% efficiency down to 3 microns. Air handling units shall be provided with separate heating and cooling coils, adequate vibration isolation pads, fire retardent flexible canvass connections made out of canvass sleeve and drain piping upto drain trap. The Air Handling shall be of following parameters.Rows of Heating Coil: 6 Rows of Cooling Coil: 4, Static pressure drop: 50 mm Wg |
104 | 4000 CFM |
105 | 3000 CFM |
106 | 2000 CFM |
107 | Electric Panel for Air Handling units |
108 | Electrical Panel Board for AHU made of 16 gauge sheet duly epoxy painted and complete with Cu bus bar, voltmeter, ammemeter, indicating lights, selector switch, incomming/ outgoing isolators, single phase preventors, MCB, Relay etc. as recommended by OEM |
109 | Duct with allied items |
110 | Ducting (For TFA) |
111 | Galvanised Sheet metal ducting with neoprene gaskets, supports, hangers, nuts, bolts, washers etc. complete in all respects. |
112 | 1.0 mm |
113 | 0.8 mm |
114 | 0.63 mm |
115 | Duct Insulation/Acoustic Lining |
116 | Duct insulation/ acoustic lining of Elastrometric Nitrile Insulation alongwith adhesive etc. As per requirement complete in all respects as per Specifications. |
117 | 19 mm thick. |
118 | Grilles/Diffusers |
119 | Extruded aluminium supply and return air grilles/diffusers duly powder coated as per specifications and drawings. |
120 | Aluminium grilles with damper |
121 | Aluminium diffusers with damper |
122 | Fresh Air Louvers |
123 | Extruded aluminium louvres with frame bird screeen mesh, pre-filter with frame, mounting arrangement etc. as per specifications and drawings. |
124 | Motorised Fire Damper |
125 | Galvanised sheet fire damper as per specifications and drawings including control cabling upto fire panel as per specifications and drawings. |
126 | Actuators |
127 | Electronic type actuator havingan overload proof D.C. motor with suitable gear train as per Specifications of Section A. |
128 | Valves |
129 | Butterfly Valve |
130 | 250 mm DIA |
131 | 100 mm DIA |
132 | 80 mm DIA |
133 | 65 mm DIA |
134 | 50 mm DIA |
135 | Ball Valve |
136 | 50 mm DIA |
137 | 40 mm DIA |
138 | 32 mm DIA |
139 | 25 mm DIA |
140 | 20 mm DIA |
141 | Y-Strainers |
142 | G.M. Y Strainer with Flanges etc. complete as per specification of the following sizes. |
143 | 50 mm DIA |
144 | 40 mm DIA |
145 | Non- Return Valves |
146 | G.M. Non Return Valve with Flanges etc. complete as per specification of the following sizes. |
147 | 50 mm DIA |
148 | Motorised valves |
149 | 3- way motorised valve complete with actuator, thermostat, flanges, nuts, bolts and gaskets as required. The valves shall be interconected with thermostat inside the room/ corridoor for temperature settings as required. |
150 | 40 mm DIA |
151 | Misc. Items |
152 | Pressure GaugesGlycerine fillied as per specifications (100 mm Dial) |
153 | Thermometer as per specifications(100 mm Dial) |
154 | Air release valveswith isolation ball valves (25mm) |
155 | Electrical |
156 | Main Panel for central heating |
157 | Supply,Installation,Testing & Commissioning of motor control center for hot water generators,chillers and the pumps.The panel shall be indoor free standing floor mounted sheet metal clad cubicle dead front type dust and vermin proof fabricated out of 14 SWG sheet complete with shrouded aluminum bus bars of TPN + E. The incoming & outgoing feeder shall be accommodated in a modular multitier arrangement, adequate sized cable alley, painting, earthing, numbering, danger plate etc. as required.The panel shall comprise of the following and shall have minimum 20% spare capacity. Incoming: One no.250 A TP&N MCCB, 250 Amp on load changeover, one No. Voltmeter (0-500 v) with 3 way selector switch,One No. of 0-250 AMPS ammeter with selector switch ,Three Nos. of phase indication lamps and 300 A TPN&E Al.Bus bar .Outgoing:Two No"s. 63 A TP&N MCCB for hot water pumps each MCCB compartment shall be equipped with suitable range ammeter, ammeter selector switch separate single phase preventer, on /off / trip indicating lights, Star -Delta starter for Two No"s 20 HP motors, Two Nos. 32 A TP&N MCCB for HWG with on indicating light, Two Nos. 32 A TP&N MCB with DOL Starter for fuel pumps with on indicating lights,Each MCB compartment shall be equipped with suitable range ammeter, ammeter selector switch, separate single phase preventer, on /off/trip indicating lights. 02 hp DOL starter forMotor for soft/ Raw waterpumps, 63 Ampare TP&N MCCB for heaters (02 No"s)each MCCB compartment shall be equipped with suitable single phase preventer on/off/trip indicating lights.Spares : Two 63A TP&N MCCB, Two 32A TP&N MCB. |
158 | Cable Try |
159 | 300 mm wide Perforated cable tray of 2 mm thickness and supported from ceiling the wall duly painted as per site condition |
160 | Conduits |
161 | MS conduit pipes |
162 | Electrical cable |
163 | Providing and fixing PVC insulated unarmoured copper conductor cables from main panel board to various equipments through walls/ceiling with appropriate clamps and fixing arrangements, cable tray etc. as per specifications |
164 | 4 Core -10 sqmm |
165 | 4 Core - 4 sqmm |
166 | 3 Core - 2.5 sqmm |
167 | 2 Core - 1.5 sqmm |
168 | Earthing |
169 | Earthing Pit |
170 | Earthing for various equipments inside boiler house using copper plate electrode of size 600 x 600x 3 mm placed in 1000 x 1000x 1800 mm pit filled with charcoal & salt by copper strip of size20 x 3 mm alongwith perforated G.I pipe as per specifications. |
171 | Earthing Strip |
172 | Copper strip of size 20x3 mm from earthing electrode to the Panel, Stabilizer, boiler and pumps using proper fastners concealed under floor. |