Health and Family Welfare Government Departments Closing in 0 days TDR #32287875

Internal Electrical Works For Block Public Health Unit For Bangitola R.H Kaliachak-Ii Block, Malda.

Issued by Government Departments · kaliachak, West Bengal
Tender Value
Ref. Documents
Estimated cost
Bid Submission
03 Jun 2022
0 days left
EMD
15000
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
kaliachak → West Bengal
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Internal Electrical Works For Block Public Health Unit For Bangitola R.H Kaliachak-Ii Block, Malda.

BOQ

Name of Work: BOQ FOR INTERNAL ELECTRICAL WORKS FORBLOCK PUBLIC HEALTHUNIT FOR BANGITOLA RH KALIACHAK-II, MALDA.
Sl. No. Item Description
1Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate flushed in wall incl. mending good damages to original finish i)Average run 8 mtr
2Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper condutor single core cable in surface / recessed PVC conduit 2 way modular switch,modular plate,suitable GI box and earthing the point with 1.5 sq.mm .FRLS PVC insulated copper conductor single core cable etc as required.
3Supplying and Drawing 1.1 KV single core stranded \"FR\" PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required.b) 3 x 22/0.3 (1.5 sqmm)
4s)2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC
5v)2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC
6y) 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC
7g1) 4x126/0.4 (16 sqmm) + 2x80/0.4 (10 sqmm) as ECC [UPS]
8Supplying and fixing polythene pipe complete with fittings as necy.. under ceiling/beam, bound with 22 SWG GI binding wire incl. supplying and drawing 1x18 SWG GI Wire as fish wire inside the pipes and fittings and providing 50 mm dia disc of MS sheet (20 SWG) having colour paint at one face fastened at the load point end of the polythene pipe with fish wire (synchronizing with roof/beam casting work of building construction).b)19mm dia 3mm thick Polythene Pipe
9c)25mm dia 3mm thick Polythene Pipe
10d) 32mm dia 3mm thick Polythene Pipe
11Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI \"U\" hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles.6a) 19 mm dia 3 mm thick polythene pipe without earth continuity wire
12Cutting Channel of size (43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI \"U\" hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles,.7a)25 mm dia 3 mm thick polythene pipe without earth continuity wire
13Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works. a)100 mm x 100 mm x 65 mm
14b)150 mm X 100 mm X 65 mm
15c)415 mm X 200 mm X 65 mm
16Supply & Fixing Bakelite / Perspex top cover on existing Inspection board by Brass screws. a)100 mm x 100 mm x 65 mm
17b)150 mm X 100 mm X 65 mm
18c)415 mm X 200 mm X 65 mm
19Supplying and fixing PVC casing-capping [Precision Make] on wall or ceiling, incl. necy.. PVC fittings etc. and mending good damages to building works. a).20x10mm Size
2025x10mm Size
21Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish. 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC. i)On Board
22Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [Separate 6A Plug Point]
23Supply & Fixing 240 V, 6A, 5 pin Modular type plug socket (Brand approved by EIC), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [CPU Board]
24Supply & Fixing 240 V 6 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required [CPU Board]
25Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [Separate 16A Plug Point]
26Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [CPU Board]
27Supply & Fixing 240 V 16 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required [CPU Board]
28Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. [AC Socket Board]
29Supply & Fixing 240 V, 20A/25 A, 3 pin Modular type plug socket with 20/25A Modular switch (Brand approved by EIC) type SP MCB (C-Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [Autoclav & Biochem Analyzer Board]
30Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc [AC Starter Board]
31Supply & Fixing 240 V, 3 nos. 16 A, 3 pin Modular type plug socket with 3 nos. 16A Modular type switch (Brand approved by EIC), 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 12 Module GI Modular type switch board with 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [Separate 6/16A Board]
32Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. [AC Socket Board]
33Supplying & Fixing GI Modular Switch Board of the following sizes complete with top cover plate flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works.(a) 2 Module
34(b) 4 Module
35Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. (f) 2 Row 18 Module ( for CPU Board--3 Nos. 6A 5 Pin Socket with Switch+1 No. 16A Socket With Swich)
36Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Legrand / Havells / Siemens). 8 way
37Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Legrand / Havells/Siemens). 6 way
388 way
39Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment 4 Way
40Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachmenta) 6 Way Horizontal
41b)8 Way Horizontal
42c)8 Way Vertical
43Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection (Legrand / Havells/Siemens). 160 A [Make-Legrand/Siemens/Havells] [VTPN I/C]
44Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Legrand / Havells / Siemens).6 amps to 32 ampsa)Single pole 6-32A
45b)Four pole 6-32A
46c)Triple Pole 20A [[VTPN O/G]
47d)Triple Pole 40A [VTPN O/G to UPS]
48e)Triple Pole 63A [VTPN O/G to NDB 1,2]
49f)TPN MCB 40A [EDB I/C]
50g)TPN MCB 63A [NDB 1,2 I/C]
51Supplying and fixing 415V, TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nutsbolts etc (L&T/Havells/HPL) 160A
52Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
53Supplying & Fixing of Box type fan clamp of 150mm dia & 80mm depth made of 16 SWG CRCA sheet with one end duly sealed by cover, properly welded, incl. S&F 12mm dia 600mm long MS rod duly bent by heat treatment at the centre position of rod to grip fan bobbin properly, incl. binding the rod and fan box with reinforcement by 22 SWG steel binding wire, incl. supplying & covering the box with alkathene sheet, placed in order to prevent concrete from entering the box.
54Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessaryconnection as required by 2x1.5 sqmm flexible copper wire.
55Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter: 30 cm (12\")
56Supply & Fixing louver shutter on wall with necy.. bolts & nuts (6 mm dia x 62 mm long) a) For Al :30 cm Exhaust fan (12\")
57Supplying & Fixing 240 V AC Buzzer (Ancho) on HW board incl. S&F HW board
58a) Supply of Fans : Supply of 48 inch sweep ceiling fan Similar to --Crompton Greaves make (UD & MA Page-23 item no-70)
59b)Supply of Fans :Supply of 12inch sweep heavy duty exhaust fan Similar to-Crompton Greaves make (UD & MA Page-14 item no-5)
60Laying on Wall / surface with Saddles / clamps Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting
61CABLE TERMINATIONSupplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : a) For 3½ core upto 35 sqmm
62b) For 3½ core upto 50 sqmm
63Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials a) 3½ core 35 sqmm cable
64b) 3½ core 50 sqmm cable
65a) Supplying of 1.1 KV. Grade PVC insulated conductor of following cables (make: Polycab/Gloster/Havells) 35 sqmm3½ core
66b) Supplying of 1.1 KV. Grade PVC insulated conductor of following cables (make: Polycab/Gloster/Havells) 50 sqmm3½ core
67EARTHING: Soil Excavation :Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil
68Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:By TATA-Medium GI pipe
69Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe
70Extra for treatment of soil by using salt & charcoal or coke for plate electrode
71Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
72Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. a) Solid GI wire. No. 8 SWG
73b) Solid GI wire. No. 6 SWG
74SOCKETSupply & Fixing RJ45 sitable for CAT6 cable (Brand approved by EIC) with PVC board and top cover plate on wall and making necessary connections & testing as required
75SOCKET Supply & Fixing Telephone socket (RJ11) Modular type (Brand approved by EIC) with PVC board and top cover plate on wall and making necessary connections & testing as required.
76GI BOX Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages tobuilding works (a) 4 Module
77CABLE Supplying & Drawing 2-pair Telephone cables with high density polyethylene insulated solid annealed high conductivity bare copper of dia 0.5mm in prelaid PVC rigid conduit / in polythene pipe embeded in wall.
78Supplying & Drawing LAN cable (CAT6) (Brand approved by EIC) in prelaid PVC rigid conduit/ in polythene pipe embeded in wall.
79Supplying and fixing of the following sheet steel clad wall / recess mounting telephone tag blocks of krone make constructed from 14 SWG sheet steel finished with red oxide coating of two coats of paint with hinged gasketted powder coated door and complete.a) 05 pairs
80b) 15 pairs
81Supplying of LED Batten light fitting (Philips make, model - BN021C LED20S PSU CW GR S2 (KMDA Vetted)
82Supply & Delivery at site 15 watt LED Bulb (Philips/havells make model-New Adore 15W E27 CDL Ball Lamp), as per direction of EIC. (Analysed rate) [KMDA Vetted]
83Supplying of 36watt LED Outdoor Type Luminiares along with all accessories complete as required.(Similar to Philips-model no- BRP046 LED 36W MR SI PSU) (Approved Rate)
84Fixing only single /twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener
85Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
86Fixing only lamp
87Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc.
88WBSEDCL Service change
89Applicable GST @ 12%
90Labour wellfare CESS @ 1%

AI Tender Summary

OUR REF NO 32287875
AUTHORITY Government Departments
TENDER VALUE Ref. Documents
LAST DATE 03-06-2022
Authority
Authority Name Health And Family Welfare Department
Work Description Internal Electrical Works For Block Public Health Unit For Bangitola R.H Kaliachak-Ii Block, Malda.
Basic Detail
Tender No DHFWS/NHM/DCE /999/NIeT-06/22-23/2ndCall
Bidding Type Tender
Location
City kaliachak
State West Bengal
Key Dates
Publish Date 19 May 2022
Submission Date 03 Jun 2022
Open Date 06 Jun 2022
Finance
Tender Value Ref. Documents
Tender Fee Ref. Documents
EMD 15000
Exemption Not Available
Document List
ff32b2fa-cfc8-4c70-967d-f0f5d6e030c5.html
BOQ_744162.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

May 19, 2022
11:30 IST

Tender Published

Tender notice published.

Completed
Jun 03, 2022
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Jun 06, 2022

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

ff32b2fa-cfc8-4c70-967d-f0f5d6e030c5.html

xls

BOQ_744162.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders