Food Corporation Of India-FCI has published Supply Installation Testing And Commissioning Of Diesel Generator Set Of 125 Kva Along With Amf Panel At Zonal Qc Lab Fci Raipur 2Nd Call As Per Attached Tender Documents. Submission Date for this Tender is 31-05-2022. Diesel Generators Tenders in raipur Chhattisgarh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Sub Head "A" Equipment |
2 | Supply, Installation, testing andcommissioning of 125 kVA Silent type Liquidcooleddieseldrivengenerating set conforming to CPCB 2 / latestnormscomprisingofradiator,4strokemulti cylinder engine of suitable BHP to deliverratedkVAatprevailingsite conditions equipped with flywheel, residential type silencer, fuel governor, fuelpump,builtinfueltank,electric startingequipmentwithrequirednos of suitable AH sealed maintenance free batteriesetc.,directlycoupledto125 kVA0.8PF,alternatorsuitablefor3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternatortocontrolpanel,acoustic enclosure, etc.as specified and consisting of the followings and AMF panel as per specification given below etc. as required. |
3 | Diesel Engine: One number Diesel Engine multi-cylinder,four stroke, liquid cooled, electric start, turbo charged typeengine suitable for developingtherequiredBHPat1500 rpm, suitable for above output of alternatorat40ºC,50%RHandat 1000MetreMSLandconformingto BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10%overloadingfor onehour after 12 hours of continuous operation completewith common baseframe, Anti vibration mountings, radiator, starting equipment,batteries, residential type silencer and other accessories etc. as required and as specifiedinthedetailedspecification enclosed. Category reference KOEL Green DG Set (Model No. KG1-125WS) (or equivalent Cummins / Mahindra/Eicher specifications) |
4 | Engine mounted instrument panel fitted with and having digital display for the following: Start- stop switch with Key, Water/ liquid temperature indication, lubrication oil presuure indication, Lubrication oil temperature indication, Battery charging Indication, RPN indication, Over Speed indication, Low lubrication oil trip indication, engine Hours indication. |
5 | Alternator: One number synchronous alternator ratedat125kVA,415 voltsat1500 rpm, 3phase,50Hz.ACsupply with 0.8 lagging power factor at 40ºC, 50% RH and at 1000 Metre MSL. The alternatorshallbehavingSPDP enclosure,brushless,continuousduty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class F/H insulation |
6 | Base Frame & Foundation: Both the engine and alternator shall be mountedonsuitablebaseframemade of MSchanneldwithnecessary reinforcementwhichshallbeinstalled on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.(Cost of making foundation needs to be provide seperately at sr. no. 7 of this BoQ) |
7 | Fuel tank: Inbuiltdailyservicefueltankaspe manufactures specification complete withallstndardaccessoriesandfuel pipingbetweenfueltankanddiesel engine,complete with valves, levelindicatorandacessoriesas required as per specification attached. |
8 | Exhaust system: Dry exhaust mainfold with hospital exhaustsilencerandcatalytic convertor |
9 | Starting System: 12V/24V DC starting system comprisingofstartermotor,voltage regulatorandarrangementforinitial excitation, complete with required nos of suitable batteries as required and as per specification. |
10 | Acoustic Enclosure: Acousticandweatherproofenclosure witharrangementforfreshairintake forcoolingoftheengineand alternator,extraction,discharginghot airintotheatmosphereasper specification attached. |
11 | AMF Panel: Supplying, installation, testing and commissioning of automatic mains failure control including auto By pass panel, suitable for 125KVA silent type DG ste complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panelto diesel Engine and else where if required all complete and inter locking includingthe following |
12 | 200Amps.FourpoleMCCB, Ics=35kA @ 415Volt or Ics=25kA @433Voltswithrotaryoperating mechanism with phase barriers - 2 nos. (For mains and alternator) |
13 | 255A,AC-IFPpowercontactor with add on block (L&T model MCX- 34) - 2 sets (For mains and alternator) with interlocking arrangement. |
14 | Microprocessorbasedautomatic mains failure function unit for emergency and stand by power supply system having under voltage, over voltageandsinglephasingprotection and other standard features - 1 no. |
15 | Micro processor based IDMT relay for three phase over current + earth fault - 1 set. |
16 | Energyanalyserunittoindicate, current,voltage,frequency,power factor and kWh |
17 | Phase indication lamps for DISCOM and Generator - 1 Set |
18 | Emergencytripswitch, Auto/Manual/Offselectorswitch, trickle/boost charger switch and SMPS battery charger unit complete with transformer, rectifier, DC Voltmeter and ammeter, off and boost and current adjustment etc. - 1 Set |
19 | BakeliteHRCfuses/ MCBandcontrol wiring for the entire system - 1 Set |
20 | Indicating lamps for load on mains and load on set - 1 Set |
21 | Fuse for instruments - 1 Set |
22 | Sub Head "B" Earthing |
23 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required. |
24 | Supplying and laying 25 mm X 5 mm G.l strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.l. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.l. nut bolt & spring washer spaced at 50mm) |
25 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required. |
26 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
27 | Sub Head "C" Miscellaneous Items |
28 | Providing foundation and platform for the 125 kVA Silent type DG set so as to place the above mentioned DGSet conforming to clause 2.5.1of General specifications for Electrical Works Part - VII DG Sets 2013 |