Revamped Reforms-Based And Results-Linked, Distribution Sector Scheme Infrastructure Work Under Loss Reduction In Kesco, Kanpur

Tender Notice

32218742
Revamped Reforms-Based And Results-Linked, Distribution Sector Scheme Infrastructure Work Under Loss Reduction In Kesco, Kanpur
Indian
Uttar Pradesh
12-05-2022
26-05-2022
26-05-2022

Tender Details

Revamped Reforms-Based And Results-Linked, Distribution Sector Scheme Infrastructure Work Under Loss Reduction In Kesco, Kanpur

Key Value

Document Fees
INR 29500 /-
EMD
INR 50000000.0 /-
Tender Value
INR 590 Crore /-

Attachment

FileName File Description File Size
3RDSSInfraSBDPart3.pdf Tender Document 1.6 MB
4RDSSInfraSBDPart4Convert.pdf Tender Document 7.7 MB
AdditionalTechSpec.pdf Tender Document 4.1 MB
BOQ_1120684.xls Tender Document 568.0 KB
NITofRDSS.pdf Tender Document 608.5 KB
Replyofprebidqueries.pdf Tender Document 1.3 MB
RevisedFeederwiseandDTWis.pdf Tender Document 8.5 MB
TenderDrawings.pdf Tender Document 14.5 MB
Tendernotice_1.pdf Tender Document 598.6 KB
05c735c6-f457-4caf-a386-902fc8b7d4d3.html Tender Notice 59.3 KB
1RDSSInfraSBDPart1.pdf Tender Document 2.1 MB
2ARDSSInfraSBDPart2SoW.pdf Tender Document 2.1 MB
2BRDSSInfraSBDPart2TS.pdf Tender Document 12.4 MB

Other Information

Attachments
Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

BOQ Items

Name of Work:
Sl. No. Item Description
1Supply of1.1_KV XLPE insulated PVC sheathed armoured Aluminum Cable in high loss area
22Cx6 sqmm
32Cx10 sqmm
44Cx16 sqmm
54Cx25 Sqmm
6Supply of 9.5 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 37 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
7Supply of 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
8Supply of New Galvanised Stay Set with anchor plate (200x200x6mm), 50x8mm stay clamp, Stay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work.
9Supply of Spike Earthing 2540mm longmade of 20mm GI solid Rod.
10Supply of Hot Dip galvanized G.I. Wire Earthing Coil
11Supply of 6 SWG GI wire
12Supply of 8 SWG GI wire
13Supply of AERIAL BUNCHED XLPECABLE 3x95+1x70+1x16 sqmm
14Supply of AERIAL BUNCHED XLPECABLE 3x120+1x70+1x16 sqmm
15Supply of AERIAL BUNCHED XLPECABLE 3x150+1x120+1x16 sqmm
16Supply of LT Pole Clamps with nut & bolts for Laying ABC
17Supply of Dead End clamps with Eye-Hook (Insulated)
18Supply of Suspension clamps with Eye-Hook (Insulated)
19Supply of LT insulation Piercing Connectors of 25-150 sqmm size for energizing distribution Kiosk/box
20Supply of LT insulation Piercing Connectors of 25-120sqmm size for energizing distribution Kiosk/box
21Supply of LT insulation Piercing Connectors of 25-95sqmm size for energizing distribution Kiosk/box
22Supply of L.T. Neutral Bare Connector.
23Supply of 1X25 mm^2 XLPE/PVCinsulated AL. cable for energising the distribution boxes/Kiosk
24Supply of Single Phase Distribution Box with clamps with lug.
25Supply of Three Phase Distribution Box with clamps with lug.
26Supply of Pre-fabricated steel items like V cross arm, top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, transformer mounting structure etc made of MS Channels (100x50x6mm), MS angle (65x65x6mm), MS flats (65x8mm) of given size duly galvanisedfor over head structures as per technical specification, approved drawings and scope of work.
27Supply ofMS Nuts, Bolts with Washers duly galvanised as per technical specification, approved drawings and scope of work (off size).
28Supply of 11 KV polymer/porcelain Disc insulator 70 KN along with suitable hardware fittings
29Supply of 11 KV Polymer /porcelain Pin Insulators 10 KN with GI PIN
30Supply of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog
31Supply of CI Packing (Galvanised) as per site requirement.
32Supply ofDanger Plate
33Supply ofG.I. Barbed Wire
34Supply of 12 kV, 1600 A, 350MVA, 25kA for 3 seconds, 3-ph, indoor typeVacuum Circuit breaker along with 12 kV, 1-Phase, 400-200/5-5 3 Nos indoor type Current Transformer, indoor mounting type control panel for feeder protection, control cabling between VCB and indoor control panel (SCADA Compatible & 61850 protocol compliant protection relays)and required accessories, bi-metallic clamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay & accessories complete for feeder breaker protection along with adopter panelas per technical specifications, approved drawings and scope of works .(Outgoing Panel)
35Supply of G.I. Pipe 6" dia. with Clamps etc.
36Supply of11KV XLPE 3 phase power cable armored,aluminium conductor,standard as per technical specification,approved drawing and scope of works 3Cx185 sqmm
37Supply of Heat Shrinkable Jointing Kit Outdoor /indoor for 11 KV 3x185 sq. mm XLPE Cable
38Supply of Heat Shrinkable Jointing Kit Outdoor for 11 KV 3x185 sq. mm XLPE Cable
39Supply of Heat Shrinkable Jointing Kit indoor for 11 KV 3x185 sq. mm XLPE Cable
40Supply of 11KV Straight through Joint 3x185 sqmm XLPE Cable
41Supply of L.T Aluminum armored XLPE single core cable size
421X630 Sq mm.
431X400 Sq mm.
44Supply of Al Crimping lugs (630/400/) Sq mm. for all cables ofDistribution Transformers (Any rating)
45Supply of 1100 Grade. PVC sheathed steel strip armored, aluminum conductorLT XLPE insulated cable size
463.5 CX240 Sq mm. XLPE
473.5 CX120 Sq mm. XLPE
483.5 CX70 Sq mm. XLPE
49Supply of Cable end termination using total double compersation Brassglands and crimping type aluminum thimbles size for L.T. cables.
503.5 CX240 Sq mm. XLPE
513.5 CX120 Sq mm. XLPE
523.5 CX70 Sq mm. XLPE
53Supply ofHDPE pipe 110 mm dia to be laid by horizontal drilling for under ground piping (trenchless) at road cross of above cable.
54Supply of GI Pipe for external area of small cable to houses
5550mm dia
5640 mm dia
57Supply of PVC pipe heavy gauge 40 mm dia (under ground area) pipe for small cable to houses
58Supply of G.I. Strip of size 25x3 sqmm for making connection between Type-B/C Panel and earth rod
59Supply ofType LT Distribution Box with a rupturing capacity of 50 KA at 415 volt Called for Individual items (CPRI approved manufacturer) Openable in front & back suitable for 3 Phase, four wire, 50 Hz AC Supply & an ambient temperature of 45 deg. C. The Cubical should be weather proof, Dust proof, Bremen proof and in closer protection shall be IP-65 as per IS 2147- 1962 and IS-8623 the panels & switches boards shall be fabricated out of 2 mm CRCA Sheet Steel & Provided with 2 mm Hinged door Including suitable Foundation, MAIN LT PANEL AT SUBSTATION- 1000 & 630 KVA (Type A-1) Incomer - 1 No. 1250 Amp. TP MDO ACB with inbuilt MPR Released with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM) with control MCBs) (Outgoing - 4 sets of 400 amp. TP MCCB with spreader & Extended handle) (2 sets of 250amp. TP MCCB with spreader & Extended handle)(2 sets of 100 0amp. TP MCCB with spreader & Extended handle)
60Supply of Outdoor Type LT Distribution Box with a rupturing capacity of 50 KA at 415 volt Called for Individual items (CPRI approved manufacturer) Openable in front & back suitable for 3 Phase, four wire, 50 Hz AC Supply & an ambient temperature of 45 deg. C. The Cubicle should be weather proof, Dust proof, Bremen proof and in closer protection shall be IP-65 as per IS 2147- 1962 and IS-8623 the panels & switches boards shall be fabricated out of 2 mm CRCA Sheet Steel & Provided with 2 mm Hinged door Including suitable Foundation, MAIN LT PANEL AT SUBSTATION- 400 KVA (Type A-2) (Incomer - 1 set of 800 amp.ACB with inbuilt MPR Released with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM) with control MCBs) (Outgoing - 6 sets of 250 amp. TP MCCB with spreader & Extended handle (5No.+1No. Capacitor panel)) (2 sets of 100 amp. TP MCCB with spreader & Extended handle)
61Supply of Outdoor Type LT Distribution Box with a rupturing capacity of 50 KA at 415 volt Called for Individual items (CPRI approved manufacturer) Openable in front & back suitable for 3 Phase, four wire, 50 Hz AC Supply & an ambient temperature of 45 deg. C. The Cubical should be weather proof, Dust proof, Bremen proof and in closer protection shall be IP-65 as per IS 2147- 1962 and IS-8623 the panels & switches boards shall be fabricated out of 2 mm CRCA Sheet Steel & Provided with 2 mmHinged door Including suitable Foundation, MAIN LT PANEL AT SUBSTATION- 250 KVA (Type A-3) (Incomer - 1 set of 630 amp. ACB with inbuilt MPR Released with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM) with control MCBs)) (Outgoing - 5 sets of 250 amp. TP MCCB with spreader & Extended handle (4No.+1No. Capacitor panel)) (2 sets of 100 amp. TP MCCB with spreader & Extended handle)
62Supply of Outdoor Type LT Distribution Box with a rupturing capacity of 50 KA at 415 volt Called for Individual items (CPRI approved manufacturer) Openable in front & back suitable for 3 Phase, four wire, 50 Hz AC Supply & an ambient temperature of 45 deg. C. The Cubical should be weather proof, Dust proof, Bremen proof and in closer protection shall be IP-65 as per IS 2147- 1962 and IS-8623 the panels & switches boards shall be fabricated out of 2 mm CRCA Sheet Steel & Provided with 2 mm Hinged door Including suitable Foundation, MAIN LT PANEL AT SUBSTATION- 160 KVA (Type A-4) (Incomer - 1 set of 400 amp. ACB with inbuilt MPR Released with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM) with control MCBs) (Outgoing - 4 sets of 250 amp. TP MCCB with spreader & Extended handle (3No.+1No. Capacitor panel)) (2 sets of 100 amp. TP MCCB with spreader & Extended handle)
63Supply of Outdoor type feeder pillar panel to be made of 2mm. CRCA sheet & covers will be 2 mm CRCA sheet duly powder coated paint including suitable foundation with 400 amp. Aluminum Bus bar(Type B-1) with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM)having : 1 no Incomer 250amp. TP MCCB and 6 No.out-going 100 amp. TP MCCB with spreader & Extended handle.
64Supply of Outdoor type feeder pillar panel to be made of 2mm. CRCA sheet & covers will be 2 mm CRCA sheet duly powder coated paint including suitable foundation with 300 amp. Aluminum Bus bar (Type B-2) with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM)having :1 no Incomer 250amp. TP MCCB and 5 No.out-going 100 amp. TP MCCB spreader & Extended handle.
65Supply of Outdoor type feeder pillar panel to be made of 2mm. CRCA sheet & covers will be 2 mm CRCA sheet duly powder coated paint including suitable foundation with 300 amp. Aluminum Bus bar(Type B-3) with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM)having :1 no Incomer 250 amp. TP MCCB and 4 No.out-going 100amp. TP MCCB spreader & Extended handle.
66Supply of lockable distribution box along withbar lock of size 450x450mm including suitable foundation with bus baramp. 140TPN to feed up to 10 houses (Type C). Panel to be made of 2mm. CRCA sheet
67Supplyof GI pipe of 40 mm dia under ground (For street light)
68Supply junction box on STP/PCC pole with 900 mm long GI pipe 25 mm dia with clamp (for street light connection)
69Supply ofGI Pipe 40mm dia B-Class 40 feet longfor earthing of Type A and B panels
70Supply of G.I . Pipe Chemical Earthing (electrode 3 mtr long 80 mm inner dia along with Chemical powder)
71Supply of G.I.Strip of Size 50X6mmfor connecting the Panels A& B type Panels.
72Supply of M.S Flat of Size 25X3mmfor connecting the Panels C- type Panels.
73Supply of Steel Structure of size 65x65x6 mm (M.S. Angle )
74Supply of Single phase polycarbonate meter box
75Supply of Three Phase polycarbonate meter box
76Supply of 12.65 KV,3960 KVAr, 3-Ph ,50 C/s ,Outdoor type Capacitor bank having two variable step of 792KVAr & Two variable steps of 1188KVAr . Bank shall be complete with capacitors unit of 264/396 KVAr ,Aluminimum busbars, Pin&Post insulators ,Expulsion fuse along with 11 KV Aluminium Wound Dry type Series reactors , 6 Nos .52 KVr for 792 KVr step, 6nos 0.79KVr for 1188 KVr step,1 Nos 11 KV 3 Ph Oil Cooled RVT , 4 Nos 12 KV, 3 Ph Outdoor type metal enclosed vaccum Capacitor Switches , 1 Nos 11 KV,400 Amp, Off Load Isolater with earth switch and mounting structure , 3 nos 9 KV,10 KAstation Class lightingh Arrestor, 1 Nos Indoor type Automatic Control Unit , 1 set of Hot Dip galvanised structures for complete system , and 1 set of Control Cable lugs thimble , Juntion Box etc.
77Supply of 11 kV ACS dog covered conductor with all accessories.
78ERECTION PART
79Armoured Consumer Cabling in High Loss Areas
80Erection/Laying of 1.1_KV XLPE insulated PVC sheathed armoured Aluminum Cablefrom exisitng LT line/pole to Consumer meter including proper lugging.
812Cx6 sqmm
822Cx10 sqmm
834Cx16 sqmm
844Cx25 Sqmm
85Replacement of Bare conductors/ Damaged A.B. Cable with AB cables
86Excavation of additional pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications:
879.5 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 37 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
88Excavation of additional pole pit (of depth 1/6th of pole length) in soft rock/ mettalic road/ RCC / khranjaas per scope of work, approved drawings and specifications:
899.5 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 37 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
90Erection of following types of poles for LT overhead line by providing and installing danger plate,red oxide & aluminium paint, pole numbering including cement concrete foundation or refilling by bolders using cement concreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) or/and 200 mm average size bolders mixed with excavated earth etc as per scope of work, approved drawings and specifications:
919.5 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 37 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985) cement concreting 0.5 cmt
92Excavation of stay pit in following type of soils,as per scope of work, approved drawings and specifications:
93Normal soil
94Soft rock soil/soft rock/ mettalic road/ RCC / kharanja
95Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (2 Nos.) and 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per technical specifications, approved drawings and scope of works.
96Dismantling/Removal of existing LT bare conductor line or damaged A.B. cable & fixtures including damaged poles, depositing to stores of employer and erection, testing & commissioning of new aerial bunched XLPE cable,tension clamps for dead end, suspension clamps, clamps for neutral, piercing connectors type-I & type-II, 16 mm dia MS nuts & bolts, pole clamps, etc. as required as per technical specification, approved drawings and scope of work:
97Erection of AERIAL BUNCHED XLPECABLE 3x95+1x70+1x16 sqmm with all assecessiories.
98Erection of AERIAL BUNCHED XLPECABLE 3x120+1x70+1x16 sqmm with all assecessiories.
99Erection of AERIAL BUNCHED XLPECABLE 3x150+1x120+1x16 sqmm with all assecessiories.
100Erection of Single Phase Distribution Box with clamps, Lug and all accessories.
101Erection of Three Phase Distribution Box with clamps Lug and all accessories.
102Erection, testing & commissioning of earthing by inserting GI Earthing spike 2540 mm long made of 20mm solid Rod as per approved drawings, scope of work and technical specifications
103Erection, testing & commissioning of earthing coil
104Erection of 6 SWG GI wire for earthing by providing GI nut, bolts & washers, turn buckle etc as per approved drawings, scope of work and technical specifications
105Shifting of Existing consumer connection from existing bare conductor line/damaged A.B. cable line to newly erected AB Cable line
106Single Phase Connection
107Three Phase Connection
108Strengthening of existing damaged pole by providing and welding 1.2mtr long 3 No MS angle 65*65*6mm and carrying out required grouting and pole plinth activities as per approved drawing and technical specification.
10911 KV Feeder Bifurcation by constructing 11 KV Over Head Line
110Survey, route alignment & pole spotting, preparation of survey report and uploading in the web portal after approval of Project Manager
111Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications:
11211 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
1139.5 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 37 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
114Excavation of pole pit (of depth 1/6th of pole length) in soft rock/ metallic road/ RCC / kharanjaas per scope of work, approved drawings and specifications:
11511 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
1169.5 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 37 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
117Erection of following types of poles for 11 KV overhead line by providing and installing danger plate, anti-climbing devices (barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, pole numbering including cement concrete foundation or refilling by bolders using cement concreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) or/and 200 mm average size bolders mixed with excavated earth etc as per scope of work, approved drawings and specifications:
11811 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985) cement concreting 0.65 cmt
1199.5 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 37 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985) cement concreting 0.5 cmt
120Erection, testing & commissioning of pre-fabricated steel items like V cross arm, top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures and MS nuts, bolts & washers all (galvanized)including painting by red oxide & aluminium paint as per technical specification, approved drawings and scope of work.
121Earthing arrangement as per technical specificatons,approved drawings and scope of work.
122Excavation, erection, testing & commissioning of Spike Earthing of2540 mm long with 20mm solid Rod
123Excavation, erection, testing & commissioning of Earthing Coil
124Erection of 8 SWG GI wire for earthing and guarding by providing GI nut, bolts & washers, turn buckle etc
125Erection of 6 SWG GI wire for earthing and guarding by providing GI nut, bolts & washers, turn buckle etc
126Excavation of stay pit in following type of soils,as per scope of work, approved drawings and specifications:
127Normal soil
128Soft soil/soft rock/ metallic road/ RCC / khranja
129Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (2 Nos.) and 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per technical specifications, approved drawings and scope of works.
130Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work.
13111 kV Pin insulator with GI pin
13211 kV Disc insulator 70KN with strain hardware
133Laying out, tensioning, binding of conductor and tightening of stays and stringing, testing and commissioning of ACSRConductor of following sizes including jointing sleeves, helical formed fittings, jumpering and by providing & erecting PG Clamps etc as required as per approved drawings, scope of work and technical specifications
1346/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog
135Erection of 12 kV, 1600 A, 350MVA, 25kA for 3 seconds, 3-ph, indoor typeVacuum Circuit breaker along with 12 kV, 1-Phase, 400-200/5-5 3 Nos indoor type Current Transformer, indoor mounting type control panel for feeder protection, control cabling between VCB and indoor control panel (SCADA Compatible & 61850 protocol compliant protection relays)and required accessories, bi-metallic clamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay & accessories complete for feeder breaker protection along with adopter panelas per technical specifications, approved drawings and scope of works .
13611 KV Feeder Bifurcation by laying Under Ground Cable
137Survey, route alignment & pole spotting and detection of existing electrical/telephonic cable/and other utilites of public utilites departments with the help of utilitiy dectector andpreparation of survey report and uploading in the web portal after approval of Project Manager.
138Excavation of additional pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications:
13911 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
140Excavation of additional pole pit (of depth 1/6th of pole length) in soft rock/soft rock/ mettalic road/ RCC / khranjaas per scope of work, approved drawings and specifications:
14111 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
142Erection of following types of poles for 11 KV overhead line by providing and installing danger plate, anti-climbing devices (barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, pole numbering including cement concrete foundation or refilling by bolders using cement concreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) or/and 200 mm average size bolders mixed with excavated earth etc as per scope of work, approved drawings and specifications:
14311 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985) cement concreting 0.65 cmt
144Excavation of stay pit in following type of soils,as per scope of work, approved drawings and specifications:
145Normal soil
146Soft rock soil/soft rock/ mettalic road/ RCC / khranja
147Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (2 Nos.) and 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per technical specifications, approved drawings and scope of works.
148Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work.
14911 kV Pin insulator with GI pin
15011 kV Disc insulator 70KN with strain hardware
151Erection, testing & commissioning of pre-fabricated steel items like V cross arm, top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures and MS nuts, bolts & washers including painting by red oxide & aluminium paint as per technical specification, approved drawings and scope of work.
152Earthing arrangement as per technical specificatons,approved drawings and scope of work.
153Excavation, erection, testing & commissioning of Spike Earthing of2540 mm long with 20mm solid Rod
154Excavation, erection, testing & commissioning of Earthing Coil
155Erection of 8 SWG GI wire for earthing and guarding by providing GI nut, bolts & washers, turn buckle etc
156Laying of 11kV cable through HDD method (including cable length mounted upto pole top minus cable length laid inside G.I. Pipe)including digging of pit
157Digging of Trench .6 mtr wide .9 mtr to 1.5 mtr deep for laying of Pipe and Cable
158NORMAL SOIL
159SOFT ROCK /kharanja
160HARD ROCK/metallic road/RCC
161Laying of GI Pipe 6" dia in above digged trench and also for raising Cable on double Pole/Structure Laying of 11 KV Cable 3x185 sqmm
162Laying of 11 kv Cable through above Pipe
163Laying of Cable in above digged trench and also mounting Upto line by using bricks/ sand &stone pad as per REC norms
164Making andMounting of heat shrinkable jointing kit outdoor/ indoor for 11 KV 3x185 sqmm XLPE Cable
165Digging suitable Pit and making straight through and joint 11 KV 3x185 sqmm
166Making of Straight Through joint and Construction of RB Pit 3x1x1 mtr. with 9 inch thick side wall and 6 inch thick RCC bed along with RCC Trench Cover in Three Parts duly plastered and finsihed for housing St. through joint. box and filled with sand.
167Road restoration Charges against thepermission from concerning department like nagar nigam, pwd, NHAI etc
168NORMAL SOIL
169SOFT ROCK /khranja
170HARD ROCK/metallic road/RCC
171Erection of 12 kV, 1600 A, 350MVA, 25kA for 3 seconds, 3-ph, indoor typeVacuum Circuit breaker along with 12 kV, 1-Phase, 400-200/5-5 3 Nos indoor type Current Transformer, indoor mounting type control panel for feeder protection, control cabling between VCB and indoor control panel (SCADA Compatible & 61850 protocol compliant protection relays)and required accessories, bi-metallic clamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay & accessories complete for feeder breaker protection along with adopter panelas per technical specifications, approved drawings and scope of works .
172Conversion of Exisiting LT Bare Conductor Line into LT Under Ground Network.
173Erection ofL.T Aluminum armored XLPE single core cable
174Installation of L.T Aluminum armored XLPE single core cable size 1X630 Sq mm.
175Installation of L.T Aluminum armored XLPE single core cable size 1X400 Sq mm.
176Al Crimping lugs (630/400/240/120/70) Sq mm.
177Erectionof Cable end termination using total double compersation Brassglands and crimping type aluminum thimbles size
1783.5 CX240 Sq mm. XLPE
1793.5 CX120 Sq mm. XLPE
1803.5 CX70 Sq mm. XLPE
181Laying, testing and commissioning of 1100 volts grade, PVC sheathed steel strip armored aluminum conductor LT XLPE Insulated Cable of sizes 3.5 CX70/3.5 CX120/3.5 CX240 Sq mm.to be laid under ground in HDPE Pipes
182Digging of trenchbyMaking pits after due survey with the help of utility detector of existing electrical/telephonic cable/and other utilites of public utilites departmentand laying of cables of size 3.5 CX70/3.5 CX120/3.5 CX240 Sq mm. XLPE by manual drill (by making moles)
183Digging of trenchbyMaking pits after due survey with the help of utility detector of existing electrical/telephonic cable/and other utilites of public utilites departmentand laying of cables of size 3.5 CX70/3.5 CX120/3.5 CX240 Sq mm. XLPE through HDD method with the help of HDD Machine
184Digging of trench by open trench method after due survey with the help of utility dectector of existing /telephonic cable and other utilites of public utilites departmentand laying of cables of size 3.5 CX70/3.5 CX120/3.5 CX240 Sq mm. XLPE
185Back filling and restoring the road to make as original including supply of all material and RoW permission required from the land owner authority(nagar nigam, PWD, NHAI etc) for all L.T. cables, pipe and service cables concerned with a single D.T.
186Laying of HDPE pipe of various sizes by horizontal drilling for under ground piping (trenchless) for above cable at road crossing min. depth of pipe shall be 1.5 mtr. Below surface 110 mm. dia.
187Laying of GI Pipe of 50mm dia (External area)
188Laying of GI Pipe of 40mm dia (External area)
189Laying of PVC pipe heavy gauge 40 mm dia (under ground area)
190Erection of G.I. Strip/M.S. Strip of size 25x3/50x6 sqmm connecting Type A/B/C pannel with spike rod/ chemical earthing/deep bore earthing arrangement including required bolting/welding
191Dismantling of Existing LT overhead line including STP poles, bare conductor/A.B. Cable, pole accessories and transportation of Dismantled materials to KESCO Store.
192Laying of Aluminum armored XLPEs cables size 2X6 Sq mm. upto consumer meter
193Laying of Aluminum armored XLPEs cables size 2X10 Sq mm. upto consumer meter
194Laying of Aluminum armored XLPEs cables size 4X16 Sq mm. upto consumer meter
195Laying of Aluminum armored XLPEs cables size 4X25Sq mm. upto consumer meter
196Installation, Testing & Commissioning of Outdoor Type LT Distribution Box with a rupturing capacity of 50 KA at 415 volt Called for Individual items (CPRI approved manufacturer) Openable in front & back suitable for 3 Phase, four wire, 50 Hz AC Supply & an ambient temperature of 45 deg. C. The Cubical should be weather proof, Dust proof, Bremen proof and in closer protection shall be IP-65 as per IS 2147- 1962 and IS-8623 the panels & switches boards shall be fabricated out of 2 mm CRCA Sheet Steel & Provided with 2 mmHinged door Including suitable Foundation, MAIN LT PANEL AT SUBSTATION- 1000 & 630 KVA (Type A-1) Incomer - 1 No. 1250 Amp. ACB with inbuilt MPR Released with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM) with control MCBs) (Outgoing - 4 sets of 400 amp. TP MCCB with spreader & Extended handle) (2 sets of 250amp. TP MCCB with spreader & Extended handle)(2 sets of 100 0amp. TP MCCB with spreader & Extended handle)
197Installation, Testing & Commissioning of Outdoor Type LT Distribution Box with a rupturing capacity of 50 KA at 415 volt Called for Individual items (CPRI approved manufacturer) Openable in front & back suitable for 3 Phase, four wire, 50 Hz AC Supply & an ambient temperature of 45 deg. C. The Cubicle should be weather proof, Dust proof, Bremen proof and in closer protection shall be IP-65 as per IS 2147- 1962 and IS-8623 the panels & switches boards shall be fabricated out of 2mmCRCA Sheet Steel & Provided with 2 mm Hinged door Including suitable Foundation, MAIN LT PANEL AT SUBSTATION- 400 KVA (Type A-2) (Incomer - 1 set of 800 amp.ACB with inbuilt MPR Released with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM) with control MCBs) (Outgoing - 6 sets of 250 amp. TP MCCB with spreader & Extended handle (5No.+1No. Capacitor panel)) (2 sets of 100 amp. TP MCCB with spreader & Extended handle)
198Installation, Testing & Commissioning of Outdoor Type LT Distribution Box with a rupturing capacity of 50 KA at 415 volt Called for Individual items (CPRI approved manufacturer) Openable in front & back suitable for 3 Phase, four wire, 50 Hz AC Supply & an ambient temperature of 45 deg. C. The Cubical should be weather proof, Dust proof, Bremen proof and in closer protection shall be IP-65 as per IS 2147- 1962 and IS-8623 the panels & switches boards shall be fabricated out of 2mm Sheet Steel & Provided with2mmHinged door Including suitable Foundation, MAIN LT PANEL AT SUBSTATION- 250 KVA (Type A-3) (Incomer - 1 set of 630 amp. ACB with inbuilt MPR Released with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM) with control MCBs)) (Outgoing - 5 sets of 250 amp. TP MCCB with spreader & Extended handle (4No.+1No. Capacitor panel)) (2 sets of 100 amp. TP MCCB with spreader & Extended handle)
199Installation, Testing & Commissioning of Outdoor Type LT Distribution Box with a rupturing capacity of 50 KA at 415 volt Called for Individual items (CPRI approved manufacturer) Openable in front & back suitable for 3 Phase, four wire, 50 Hz AC Supply & an ambient temperature of 45 deg. C. The Cubical should be weather proof, Dust proof, Bremen proof and in closer protection shall be IP-65 as per IS 2147- 1962 and IS-8623 the panels & switches boards shall be fabricated out of 2 mm CRCA Sheet Steel & Provided with 2 mm Hinged door Including suitable Foundation, MAIN LT PANEL AT SUBSTATION- 160 KVA (Type A-4) (Incomer - 1 set of 400 amp. ACB with inbuilt MPR Released with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM) with control MCBs) (Outgoing - 4 sets of 250 amp. TP MCCB with spreader & Extended handle (3No.+1No. Capacitor panel)) (2 sets of 100 amp. TP MCCB with spreader & Extended handle)
200Installation, Testing & Commissioning of Outdoor type feeder pillar panel to be made of 2mm. CRCA sheet & covers will be 2 mm CRCA sheet duly powder coated paint including suitable foundation with 400 amp. Aluminum Bus bar(Type B-1) with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM)having : 1 no Incomer 250amp. TP MCCB and 6 No.out-going 100 amp. TP MCCB with spreader & Extended handle.
201Installation, Testing & Commissioning of Outdoor type feeder pillar panel to be made of 2mm. CRCA sheet & covers will be 2 mm CRCA sheet duly powder coated paint including suitable foundation with 300 amp. Aluminum Bus bar (Type B-2) with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM)having :1 no Incomer 250amp. TP MCCB and 5 No.out-going 100 amp. TP MCCB spreader & Extended handle.
202Installation, Testing & Commissioning of Outdoor type feeder pillar panel to be made of 2mm. CRCA sheet & covers will be 2 mm CRCA sheet duly powder coated paint including suitable foundation with 300 amp. Aluminum Bus bar(Type B-3) with (On/Off Indicating light) (Metering on Incomer- 1 set of Digital Ammeter with ASS) (1 set of Digital Voltmeter with VSS) (1 set of LED type Phase Indication light (22.5 MM)having :1 no Incomer 250 amp. TP MCCB and 4 No.out-going 100amp. TP MCCB spreader & Extended handle.
203Installation, Testing & commissioning of lockable distribution box along with bar lock of size 450x450 mm including suitable foundation with bus bar 140 amp. TPN to feed up to 10 houses (Type C).Panel to be made of 2mm. CRCA sheet
204Installation of2x10 sq mm. XLPE cable (for street light)
205Installation and laying of GI pipe of 40 mm dia under ground (For street light)
206Installation of junction box on STP/PCC pole with 900 mm long GI pipe 25 mm dia with clamp (for street light connection)
207Boring upto 39 feet and erection of GI Pipe 40mm dia B-Class 40 feet long for connection with Type-A and B panel along with supply of G.I. Strip of size 50x6 sqmm
208Erection/Pegging of M.S.EARTH spike ROD 2540X20 MM
209Erection of G.I. Pipe chemical earthing electrode 3 mtr long 80 mm inner dia along with Chemical powder
210Preparation and submission of 2 sets of detailed printed drawing/auto cad drawing / PDF (along with digital copy) of L.T. network of each D.T. depicting location of L.T. cables and all panels(Type-A,B and C) and separate list for all connections on Type C panels in excel format
211Erection of Single phase poly carbonate meter box after removal of existing meter box and connections of meters with armoured cable laid along with resealing of meter with seals provided by Kesco
212Erection of Three phase poly carbonate meter box after removal of existing meter box and connections of meters with armoured cable laid along with resealing of meter with seals provided by Kesco
213Reconductoring of 11 kV OH line.
214Excavation of additional pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications:
21511 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
216Excavation of additional pole pit (of depth 1/6th of pole length) in soft rock/soft rock/ mettalic road/ RCC / khranjaas per scope of work, approved drawings and specifications:
21711 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
218Erection of following types of poles for 11 KV overhead line by providing and installing danger plate, anti-climbing devices (barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, pole numbering excluding cement concrete foundation or refilling by bolders using cement concreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) or/and 200 mm average size bolders mixed with excavated earth etc as per scope of work, approved drawings and specifications:
21911 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985) cement concreting 0.65 cmt
220Excavation of stay pit in following type of soils,as per scope of work, approved drawings and specifications:
221Normal soil
222Soft rock soil/soft rock/ mettalic road/ RCC / khranja
223Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (2 Nos.) and 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per technical specifications, approved drawings and scope of works.
224Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work.
22511 kV Pin insulator with GI pin
22611 kV 70KN Disc insulator with strain hardware
227Dismantling of existing overhead line conductor & fittings and depositing to KESCo store, Laying out, tensioning, binding of new conductor and tightening of stays and stringing, testing and commissioning of ACSRConductor of following sizes including jointing sleeves, helical formed fittings, jumpering and by providing & erecting PG Clamps etc as required as per approved drawings, scope of work and technical specifications
2286/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog by replacing existing racoon/rabbit condcutor
229Erection, testing & commissioning of pre-fabricated steel items like V cross arm, top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures and MS nuts, bolts & washers all galvanized including painting by red oxide & aluminium paint as per technical specification, approved drawings and scope of work.
230Earthing arrangement as per technical specificatons,approved drawings and scope of work.
231Excavation, erection, testing & commissioning of Spike Earthing of 2540 mm long with 20mm solid Rod
232Excavation, erection, testing & commissioning of Earthing Coil
233Erection of 8 SWG GI wire for earthing and guarding by providing GI nut, bolts & washers, turn buckle etc
234Strengthening of existing damaged pole by providing and welding 1.2mtr long 3 No MS angle 65*65*6mm and carrying out required grouting and pole plinth activities as per approved drawing and technical specification.
235Reconductoring of 11 kV UG line.
236Survey, route alignment & pole spotting and detection of existing electrical/telephonic cable/and other utilites of public utilites departments with the help of utilitiy dectector andpreparation of survey report and uploading in the web portal after approval of Project Manager.
237Excavation of additional pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications:
23811 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
239Excavation of additional pole pit (of depth 1/6th of pole length) in soft rock /soft rock/ mettalic road/ RCC / khranjaas per scope of work, approved drawings and specifications:
24011 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985)
241Erection of following types of poles for 11 KV overhead line by providing and installing danger plate, anti-climbing devices (barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, pole numbering excluding cement concrete foundation or refilling by bolders using cement concreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) or/and 200 mm average size bolders mixed with excavated earth etc as per scope of work, approved drawings and specifications:
24211 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) and bottom Galvanized as perIS 2629 (1985) cement concreting 0.65 cmt
243Excavation of stay pit in following type of soils,as per scope of work, approved drawings and specifications:
244Normal soil
245Soft rock soil/soft rock/ metallic road/ RCC / kharanja
246Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (2 Nos.) and 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per technical specifications, approved drawings and scope of works.
247Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work.
24811 kV Pin insulator with GI pin
24911 kV Disc insulator 70 KN with strain hardware
250Erection, testing & commissioning of pre-fabricated steel items like V cross arm, top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures and MS nuts, bolts & washers duly galvanizedincluding painting by red oxide & aluminium paint as per technical specification, approved drawings and scope of work.
251Earthing arrangement as per technical specificatons,approved drawings and scope of work.
252Excavation, erection, testing & commissioning of Spike Earthing 2540 mm long with 20mm solid GI Rod
253Excavation, erection, testing & commissioning of Earthing Coil
254Erection of 8 SWG GI wire for earthing and guarding by providing GI nut, bolts & washers, turn buckle etc
255Laying of 11kV cable through HDD method including digging of pit
256Digging of Trench .6 mtr wide .9 mtr to 1.5 mtr deep for laying of Pipe and Cable
257NORMAL SOIL
258SOFT ROCK/ kharanja
259HARD ROCK / metallic road/ RCC
260LAYING OF GI Pipe 6" dia in above digged trench and also for raising Cable on double Pole/Structure Laying of 11 KV Cable 3x185 sqmm
261Laying of 11 kv Cable through above Pipe
262Laying of Cable in above digged trench and also mounting Upto line by using bricks/ sand &stone pad as per REC norms
263Making andMounting of heat shrinkable jointing kit for 11 KV 3x185 sqmm XLPE Cable
264Digging suitable Pit and making straight through joint 11 KV 3x185 sqmm
265Making of Straight Through joint andConstruction of RB Pit 3x1x1 mtr. with 9 inch thick side wall and 6 inch thick RCC bed along with RCC Trench Cover in Three Parts duly plastered and finsihed for housing St. through joint. box and filled with sand.
266Road restoration Charges
267NORMAL SOIL
268SOFT ROCK / kharanja
269HARD ROCK / metallic road/ RCC
270INSTALATION OF CAPACITOR BANK 3.96MVAr
271Erection of12.65 KV,3960 KVAr, 3-Ph ,50 C/s ,Outdoor type Capacitor bank having two variable step of 792KVAr & Two variable steps of 1188KVAr . Bank shall be complete with capacitors unit of 264/396 KVAr ,Aluminimum busbars, Pin&Post insulators ,Expulsion fuse along with 11 KV Aluminium Wound Dry type Series reactors , 6 Nos .52 KVr for 792 KVr step, 6nos 0.79KVr for 1188 KVr step,1 Nos 11 KV 3 Ph Oil Cooled RVT , 4 Nos 12 KV, 3 Ph Outdoor type metal enclosed vaccum Capacitor Switches , 1 Nos 11 KV,400 Amp, Off Load Isolater with earth switch and mounting structure , 3 nos 9 KV,10 KAstation Class lightingh Arrestor, 1 Nos Indoor type Automatic Control Unit , 1 set of Hot Dip galvanised structures for complete system , and 1 set of Control Cable lugs thimble , Juntion Box etc. along with Civil foundation and Earthing of structure and LA with Pipe Earthing.
272Erection of 11 Kv XLPE insulated 3x185 sqmm Armoured
273Erection of Heat shrinkable Jointing Kit for 11 KV 3x185 sqmm XLPE Cable
274Heat shrinkable Jointing kit for 11 KV 3x185 XLPE Cable-Indoor/Outdoor termination Kit
275Erection of 12 kV, 1600 A, 350MVA, 25kA for 3 seconds, 3-ph, indoor typeVacuum Circuit breaker along with 12 kV, 1-Phase, 400-200/5-5 3 Nos indoor type Current Transformer, indoor mounting type control panel for feeder protection, control cabling between VCB and indoor control panel (SCADA Compatible & 61850 protocol compliant protection relays)and required accessories, bi-metallic clamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay & accessories complete for feeder breaker protection along with adopter panelas per technical specifications, approved drawings and scope of works .
276Layingof11 kV ACS dog covered conductor with all accessories.