Educational and Research Institute Government Departments Closing in 0 days TDR #32122282

Construction Of 11Kv Electrical Sub Station Building In The Campus Of Anjanthali Farm, Mhu, Karnal Construction Of 11Kv Electrical Sub Station Building In The Campus Of Anjanthali Farm, Mhu, Karnal

Issued by Government Departments · karnal, Haryana
Tender Value
17.38 Lakhs
Estimated cost
Bid Submission
26 May 2022
0 days left
EMD
34760
Bank guarantee accepted
Document Fee
1180
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
karnal → Haryana
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Construction Of 11Kv Electrical Sub Station Building In The Campus Of Anjanthali Farm, Mhu, Karnal Construction Of 11Kv Electrical Sub Station Building In The Campus Of Anjanthali Farm, Mhu, Karnal

BOQ

Name of Work:Construction of 11KV Electrical sub station building (40’ x 22’) in the campus of Anjanthali Farm, MHU, Karnal (Civil + Internal Electrical Works)
Sl. No. Item Description
1Description and details
2Sub-Head - 1 (Civil Work) HSR ITEM NO. 4.14.1 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (notexceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. 4.14.1 All kinds of soil.
3HSR ITEM NO. 6.1.61 :4: 8 ( 1 Cement : 4 coarse sand (zone-Ill) : 8 graded cum stone aggregate 40 mm nominal size
4HSR ITEM NO. 6.1.81:5:10 (1 cement : 5 fine sand : 10 graded stone cum aggregate 40 mm nominal size).
5HSR ITEM NO. 6.14 Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement-All work up to plinth level:6.14.11 : 1. 5: 3 ( 1 cement : 1. 5 coarse sand (zone-Ill): 3 cum graded stone aggregate 20 mm nominal size)
6HSR ITEM NO. 6.14 Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement-All work up to plinth level:plete.6.14.21 :2:4 (1 cement : 2 coarse sand (zone-Ill) : 4 graded stoneaggregate 20 mm nominal size).
7HSR ITEM NO. 6.15.1 Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor four level, excluding cost of centering, shuttering, finishing and reinforcement : 6.15.1 1:1.5:3 (1 cement : 1.5 coarse sand(zone)
8HSR ITEM NO. 6.16 Reinforced cement concrete work in beams, suspended floors, cum roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor four level, excluding the cost of centering, shuttering, finishing and reinforcement with 1: 1.5:3 (1 cement : 1.5 coarse sand(zone-111) : 3 graded stone aggregate 20 mm nominal size).
9HSR NO. 6.33Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc.complete in all respect below plinth level.Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding & placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement. 6.33.6Thermo-Mechanically Treated bars of grade Fe-500D or more.
10HSR NO. 6.29 Centering and shuttering including strutting, propping etc. and removal of form work for :6.29.1 Foundations, footings, bases for columns
11HSR NO. 6.30Centering and shuttering including strutting, propping etc. and removal of form for6.30.3 Suspended floors, roofs, landings, balconies and
12HSR NO. 6.30 Centering and shuttering including strutting, propping etc. and removal of form for6.30.5Lintels, beams, plinth beams, girders, bressumers and cantilevers
13HSR NO. 6.30Centering and shuttering including strutting, propping etc. and removal of form for6.30.6Columns, Pillars, Piers, Abutments, Posts and Struts.
14HSR NO. 10.3Supplying and providing of Tangri River Sand under floors Including watering and compaction in 25cm layers, dressing etc. complete In all respects (As per item 10.2)
15HSR NO. 10.1Providing and laying of base course of floors consisting of 100 mm thick cement 1 :8: 16 and 100 mm sand or stone filling.
16HSR NO. 10.7Providing and laying of conglomerate floor 50mm thick cement concrete topping 1 :2:4
17HSR NO. 7.21 Brick work with common burnt clay non-modular bricks of class designation 7.5 in foundation and plinth in: 7.21.2 Cement mortar 1:6 (1 cement: 6 coarse sand)
18HSR NO. 7.22Brick work with common burnt clay non-modular bricks of classdesignation 7 .5 in superstructure above plinth level up to floor IV level in all shapes and sizes in :7.22.2Cement mortar 1:6 (1 cement: 6 coarse sand)
19HSR NO. 13.29Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. 13.29.2In gratings, frames, guard bar, ladder, railings, brackets, gates and similar work
20HSR NO. 11.4 10+ mm thick cement plaster1 :3 (1 cement: 3 fine sand)11.4.2 1 :3 (1 cement: 3 fine sand)
21HSR NO. 11.512 mm cement plaster of mix : 11.5.3 1 :4 (1 cement: 4 fine sand)
22Second Storey
23HSR NO. 11.615 mm cement plaster on the rough side of single or half brick wall of mix : 11.6.11 :4 (1 cement: 4 fine sand)
24HSR NO. 7.28Half brick masonry with common burnt clay non-modular bricks of class designation 7 .5 in superstructure above plinth level up to floor IV level7.28.2Cement mortar 1 :4 ( 1 cement :4 coarse sand)
25HSR NO. 11.60Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
26HSR NO. 11.64Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade:11.64.1 New work (two or more coats) over and including water thinnable priming coat with cement primer
27HSR NO. 11.96 Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: 11.96.1New work (Two or more coats applied @ 1.43 litre/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
28HSR NO. 13.37 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointedtogether at the end by end locks, mounted on specially designed pipe shaftwith brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing andfixing necessary 27.5 cm long wire springs manufactured from high tensilesteel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. topcover of required thickness for rolling shutters.13.37.180x1 .25 mm M.S. laths with 1.25 mm thick top cover
29HSR NO. 13.39.1Extra for providing mechanical device chain and crank operation for operating rolling shutters. 13.39.1 Exceeding 10.00 sqm and up to 16.80 sqm in the area
30HSR NO. 6.13Making plinth protection 50mm thick of cement concrete 1 :3:6cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing &finishing the top smooth.
31Sub-Head - 2 (EI Work)HSR ITEM NO:- 23.3.6Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 23.3.6.11 run of Size 1.50 Sqmm(1/1.40mm)
32HSR ITEM NO:- 23.3.6.3 1 run of Size 4 Sqmm(1/2.24mm)
33HSR ITEM NO:- 23.4COPPER WIRING WITH MODULAR SWITCHES IN PVC CONDUIT 23.4.1 Wiring for Light/Fan/call bell point with modular type switch/socket and GIbox, Modular type face plate etc in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick PVC conduit pipe. 23.4.1.1 Group A
3423.4.1.2 Group B
3523.4.1.3 Group C
36HSR ITEM NO:- 23.4.4Wiring in PVC conduit system for 3-pin 5amp. Plug point by using 2 no 1.5 sqmm FRLS copper wire and 1 no 1.5 Sqmm FRLS copper wire , includingproviding 1 no 5/6 Amp 3/5 pin Modular type socket and 1 no 5/6 Amp Modular type switch required GI Box ,modular face plate etc complete as required. 23.4.4.1 Group A
3723.4.4.2 Group B
3823.4.4.3 Group C
39HSR ITEM NO:- 23.4.5 Wiring in PVC conduit system for 3-pin 15amp. Plug point by using 2 no 4 sqmm FRLS copper wire and 1 no 4 Sqmm FRLS copper wire for earthling , including providing 1 no 15/16 Amp 3/6 pin Modular socket and 1 no 15/16 Amp Modular switch required GI Box , modular face plate etc complete as required. 23.4.5.2 Group B
4023.4.5.3 Group C
41HSR ITEM NO:- 23.7.6Supply and erection of PVC CONDUIT ISi marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. 23.7.6.2 PVC pipe of 25 mm dia.
42HSR ITEM NO:- 23.22.4 Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. 23.22.4.4 SPN DB Double Door 16 way ( 2 incoming and 14 outgoing)
4323.22.5 Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:-23.22.5.16 amp. to 32 amp Single Pole
4423.22.5.36 amp. to 32 amp Double POLE
45HSR ITEM NO:- 24.1EARTHING AND LIGHTENING ARRESTOR24.1.1Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required.
4624.1.2Extra for using salt and char coal/coke for pipe earth electrode as required.
4724.1.8Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for metre 108 connections etc. as required with all labour and material.
48HSR ITEM NO:- 20.71Supply, erection, testing of Ceiling fans IS marked (as per IS code 374) with suitable GI pipe complete in all respects complete as per directions of Engineer-in-charge.20.71.1 48\" (1200mm)
4920.71.2 56\" (1400mm)
5020.72Supplying, errection, testing of Exhaust fan (as per IS code 374) having a capacity of 45 cubic metre per minute complete with suitable G.I sheet ducting in structure confirming to latest IS specifications complete in all respect to satisfaction of Engineer-in-charge.
51NS:-S/E of 40W/4\" LED Batton.
52NS:-S/E of 42 W full Window glare free diffuse LED Panel. (2\" X 2\")having cool day light.
53NS:-Supply and erection of style LED Panel 15 W

AI Tender Summary

OUR REF NO 32122282
AUTHORITY Government Departments
TENDER VALUE 17.38 Lakhs
LAST DATE 26-05-2022
Authority
Authority Name MAHARANA PRATAP HORTICULTURE UNIVERSITY
Work Description Construction Of 11Kv Electrical Sub Station Building In The Campus Of Anjanthali Farm, Mhu, Karnal Construction Of 11Kv Electrical Sub Station Building In The Campus Of Anjanthali Farm, Mhu, Karnal
Basic Detail
Tender No 2022/09 Substation Building
Bidding Type Tender
Location
City karnal
State Haryana
Key Dates
Publish Date 06 May 2022
Submission Date 26 May 2022
Open Date 27 May 2022
Finance
Tender Value 17.38 Lakhs
Tender Fee 1180
EMD 34760
Exemption Not Available
Document List
Tendernotice_1.pdf
SubStationDNIT.pdf
BOQ_288400.xls
a899f01a-978a-462e-b956-3900fbee764a.html

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

May 06, 2022
11:30 IST

Tender Published

Tender notice published.

Completed
May 26, 2022
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
May 27, 2022

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
pdf

Tendernotice_1.pdf

pdf

SubStationDNIT.pdf

xls

BOQ_288400.xls

html

a899f01a-978a-462e-b956-3900fbee764a.html

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders