Military Engineer Services-MES has published Repair / Maint Of Dg Set, Amf Panel Stabilizing, Apfc Panel And Other Misc Works At Darjipura Af Stn Baroda. Submission Date for this Tender is 30-05-2022. Diesel Generators Tenders in baroda Gujarat. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 23-May-2022 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 30-05-2022 |
Sl. No. | Item Description |
1 | M&L for annual maintenance/ servicing and repair of standby DG Set of following capacity i.e KVA maintenance schedule prescribed in repair and maintenance mannual (Repair & maintenance should be carried out by the manufacture"s authorised mechanic from the servicing centre)including fixing charges for replacement of parts specified in relevent item here in after: NOTE : Servicing of DG set to be carried out by engineers ofauthorised dealer/service centre of kirlosker/greaves /cummins only Parts /components for replacement shall be measured and paid for seperately. |
2 | 100 KVA |
3 | 82.5 KVA |
4 | 50 KVA |
5 | 40 KVA |
6 | 30 /35 KVA |
7 | 25 KVA |
8 | 20 KVA |
9 | Checking and servicing/ repair and maintenance of :- (i) Lubricant oil leaking. (ii)Operation of oil heater and repair to lubricant oil leaking and cooling system leaking, radiator air restriction operation of coolant heater, hoses and connection, belt connection and tension. Fan hub drive pully and water pump heat exchanger, zinc anode plug motor operation louver and cleaning of water separator and cooling system. (iii)Leaking in air intake system,air cleaner restriction piping and connection. (iv)Fuel line and connection, fuel transfer pump, draining out fuel sidement from tank. (v)Leakage in exhaust system and exhaust restriction, drain out condensate trap, torquing to exhaust manifold and turbo charger capscrew. (vi)Battery charging system level up electrolyte and specific gravity, repair and maintenance of safety control and alarm. (vii)Cleaning of engine lighting of all nut bolt washer and unusual vibration. (viii)Air inlet and outlet for restriction and proper connection to electric connection , operation of generator heater strip greasing to all bearing and movable part, measurement and recording winding resistance cleaning up complete generator. (ix)Complete reset switch in automatic lightning of connection, instrumentation. |
10 | Labour only for attending the DG set with AMF Panel complaints carried out by manufacture"s authorised mechanic from the servicing centre without any delay with rectified the defects by carefuly opening and check the DG set parts which defects find out at site and replace the defected parts from the DG Setfor smooth functioning as directed and specified by the Engr in charge at site (Replacement item shall measured and paid seperately) |
11 | Supply only the following spares in replacement/ fixing at site for DG sets |
12 | Fuel flexible pipe wire braded,1,1/4""to 3/8""PVC best quality. |
13 | Oil pressure gauge complete. |
14 | Oil pressure Switch complete. |
15 | Water temperature gauge |
16 | Ignition switch |
17 | Indicating lamp |
18 | Battery terminal heavy duty of brass. |
19 | Distilled water. |
20 | Coolant for radiator. |
21 | Oil filter |
22 | Fuel filter set. |
23 | Engine oil premium blue 20W 40 Make : Servo, Castrol or Equivalent make approved by GE. |
24 | Fan belt any capacityMake Fenner/ Dunlock or Equivalent make approved by GE. |
25 | Self starter 12 voltsMake:Lucas/ Tvs or Equivalent make approved by GE. |
26 | Self starter 24 volts Make:Lucas or Equivalent make approved by GE. |
27 | Air Filter Make Mico, Boss or Equivalent make approved by GE. |
28 | AVRfor 100 KVA DG Set |
29 | AVR 82.5KVA DG Set |
30 | AVRfor 50 KVA DG Set |
31 | AVRfor 40 KVA DG Set |
32 | AVR for up to 30 KVA DG Set |
33 | Asbesto rope |
34 | Battery lead 1.5 metre long, heavy duty, multi stranded copper conductor, PVC insulated 16 Sqmm single core. |
35 | Battery Charger |
36 | Dynamo 12 volts Make- Lucas or Equivalent make approved by GE. |
37 | Fuel injector pump |
38 | Radiator |
39 | Solenoid Valve |
40 | Vibration pad |
41 | DG SET coupling 30 to 82.5 KVA |
42 | M&L forcleaning and descaling of radiator assembly by using suitable chemical (MAC solution) and by blower fan and by injecting water in high pressure in water tubings so as to remove all dirts etc in the fins complete all as specified and directed for following capacity DG set:- |
43 | 100 KVA |
44 | 82.5 KVA |
45 | 50 KVA |
46 | 40 KVA |
47 | 35 KVA |
48 | 30 KVA |
49 | M&L for replacement of selector switch suitable for voltmeter/ammeterMake : AE/ Conzeve / HPL or Equivalent make approved by GE. |
50 | M&L for replacement of battery 12 volts,150 AH complete.Make: Exide Express/Gold or Equivalent make approved by GE. |
51 | M&L for replacement of battery 12 volts,180 AH complete.Make:Exide Express/Gold or Equivalent make approved by GE. |
52 | M&L for replacement of Drybattery 12 volts,100 AH complete.Make:ExideExpress/Gold or Equivalent make approved by GE. |
53 | Material and labour for Maintenance of AMF panel ofand cleaning of dust inside withblower, cleaning of moving part /contacts from CT cleaner, tightening of loose parts /electrical wires, cleaning of contractors, relays andjunction points, servicing/ adjustment of relay, complete testing of AMF relay with necessary settings and load management system complete with replacement of worn out unserviceable components /burnt wires thimbles /lugs complete tested For DG set up to 100 KVA complete all as specified and directed. Note :- Parts /components for replacement shall be measured and paid for seperately. |
54 | Supply only following spare parts in maintanance carried out above item No. 9.00in existing AMF panels. (Rate for fixing charges are deemed to be included in the above item): - |
55 | Supply failure timer |
56 | Restoration timer |
57 | Microprocessor based AMF Module incorporating of supply and restoring timer 3 impulse automatic engine start /stop/ logic & fails to start locknut Mains/generator voltage, frequency sensing |
58 | Diod 25 Amp thread type |
59 | Axillary contactor 3 phase suitable for AMF Panel |
60 | NC/No realay complete |
61 | Under voltage relay |
62 | Time Delay relay |
63 | CT"s coil 5/250 for 100 KVA DG Set |
64 | CT"s coil 5/150 for 82.5 KVA DG Set |
65 | CT"s coil 5/50 for up to 50 KVA DG Set |
66 | CT"s coil 5/50 for up to 25 KVA DG Set |
67 | Contactor 4 pole 250 Amps for 100 KVA DG set |
68 | Contactor 4 pole 200 Ampsfor upto 82.5 KVA DG set |
69 | Contactor 4 pole 63 Amps for upto 50 KVA DG set |
70 | Battary chargerin AMF Pamel |
71 | Controller for 82.5 KVA TO 200 KVA |
72 | Controller for 20 KVA TO 35 KVA |
73 | VMR 3 Phasefor 82.5KVA TO 100 KVA |
74 | Contactor relay for 82.5KVA TO 100 KVA |
75 | Contactor relay forfor 10KVA TO 50 KVA |
76 | HRC fuse for short circuit protecton |
77 | Material and labour for painting of AMF panel with cleaning of dust inside withblower, cleaning of moving part /contacts from CT cleaner, , cleaning of contactors, relays andjunction points for DG set up to 200 KVA complete all as specified and directed. |
78 | M&L in replacement for on load changeover switch of capacityincluding sheet enclosure andremoving old changeover switch any type and necessary fixing on wall/in LT panel. Make:Havells, C&S, L&T or equivalent make approved by GE. |
79 | 250 KVA |
80 | 100 KVA |
81 | upto 63 KVA |
82 | M & L for removing existing old rusted paint on DG set ofpainted complete with two coats of synthetic enamel paint to match with existing colour good finish of following capaity complete all as specified and directed. |
83 | 100 KVA |
84 | 82.5 KVA |
85 | 50 KVA |
86 | 40 KVA |
87 | 20 KVA |
88 | Repair & Maintenance of existing canopy of eco friendly DG Set above cleaning of internal & external parts, tightening of loose parts, replacing of unserviceable door locks and keys, replacing of damaged or burned inside sponge insulations and necessary spary painting with super enamelled paint of same colour of company pattern on indide and out side of canopy chamber after removing old painted/rusted surface complete all as directed. |
89 | Material and labour for providing wooden plank for battery of DG Sets complete all as specified and directed. |
90 | M & L for rewinding of DG set alternator of any capactity with existing size and gauge and adequate number of turns of super enamelled copper winding wire and bore conductor including varnishing insulating material drying baking heating and connection leads with thimble and making connection complete all as specified and directed. |
91 | Material and labour for shifting ofDG set of any Capacity from old platform to new platform including provision of crane for lifting DG set including making new connection for AMF Panel to existing main panel of all as directed by Eng - in -charge. |
92 | Repair and calibrationof Fuel pump Nozzle of any capacitycomplete all as specified and directed by Engr-in-Charge |
93 | M&L for Multifunction meter with scrolingreading for water temprature/ oil pressure, voltage/ Ampere/ Frequency/ KW/ KVA and Running hour counter |
94 | M&L for dismantling defectiveAmmeter and replacement of new ammeter digital type complete with CT"S Make:AE/Conzeve /HPL or equivalent make approved by GE. |
95 | M&L in replacement for frequency meter analog type E/Conzeve /HPL or equivalent make approved by GE. |
96 | Supply and fix in repair of unserviceable MCCB,s of following capacity :- |
97 | M&L forMCCB 250 A36 KA4 Pole |
98 | 200 Amps 4 pole 36 KA |
99 | 160 Amps 4 pole 36 KA |
100 | 125 Amps 4 pole 16 KA |
101 | 100 Amps 4 pole 16 KA |
102 | 63 Amps 4 pole 10 KA |
103 | Supply and fix in repair of unserviceable MCB,s of 100A 4 Pole complete all as specified and directed. |
104 | S&F in repair of u/s copper bus bar of any size of existing LT panel mounted on insulator incl cutting / drilling making connection and testingcomplete all as specified and directed. |
105 | Material and labour for reparing of LT panel door including replacementdoor handel, hinges, nut bolt, welding work complete all as specified and directed. |
106 | Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sqmm 3.5 core complete all as specified and directed. |
107 | Excavation in trenches not exceeding 1.5 metres wide and not exceeding 1.5 metres in depth for foundation etc and getting out in soft/loose/hard soil complete all as specified and as directed |
108 | Returning, filling in , including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as specified and as directed. |
109 | Removing excavated material not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed. |
110 | M&L for sand cushioning to PVC cable with using clean dry and natural river sand gently punning below/ around cable complete all as specified and directed. |
111 | Supply and laying re-inforced precast concrete cable cover class LV, Type 1 flat size 250mmx150mmx40mm complete all as specified and directed. |
112 | M&L for providing earthing complete with galvanised steel earth plate electrode 60 x 60cm x 6.0mm thick buried dirictlyin ground (Earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level,connected toand including galvanised earth strip 32 X 6mm mm size upto 7.5 meter long by means of bolts,nuts check nuts and washers of all galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-1 and connected to test point including necessary excavation/ earth work in any type of soil/rock strata,funnel with wire mesh and watering pipe(GI,light grade) 20mm dia,PCC pit with 50mm thick PCC cover etc. including testing on completing but excluding GI protection pipe for earthing lead complete all as specified and directed. |
113 | Material and labour for relacement of following old unserviceable parts and fixing new onefor 20 KVA DG Sets complete all as specified and directed by Engr-in-Charge : |
114 | Battery Charging AlternatorMake- Lucas/Autolek or Equivalent make approved by GE. |
115 | Starting Motor Repair Make- Lucas/Autolek or Equivalent make approved by GE. |
116 | Battery 88 AH Make Exide Express/Exide Gold |
117 | Fuel pipe |
118 | MCB 63 Amp 4 pole L&T/Havells/Schnieder |
119 | Contactor 3 pole 80 Amp Make- L&T/ABB/Siemens |
120 | 4 ST Switch Make- Lucasor Equivalent make approved by GE. |
121 | AMF Controller of any capacity Make- Deepsea/procomor Equivalent make approved by GE. |
122 | Stop Solenoid switch Make : Mahindra & Mahindra/Greaves/Kirloskar |
123 | TimerMake : L&T/Schniederor Equivalent make approved by GE. |
124 | M&L for annual maintenance/ servicing/ repairing, Testing and commissioningof 150 KVA Mico controller StabilizerNote :- (i) charges for replacement of parts/Component will be measured and paid separatelyunder relevant items. (ii) Servicing of Stabilizerto be carried out by engineers ofauthorised dealer/service centre(ii)IfAny Types of Nut & bolt,Any sizes of Gasket or Hydera Machineor any veh reqd for carrying stabilizer from site to workshop To & FroRate will be iclusive in thisquoted rate. |
125 | Supply and fixing the following spares in replacement/ fixing at site for Stabilizer :- |
126 | M& L for New Control Card installationwith Fabrication work |
127 | M&L for installation of Pressure capacity10 KG Motor |
128 | M&L forinstallationof Transformer internal BBT |
129 | M& Lfor installation ofDimmer Assembly |
130 | M&L forfixing Carbon brush |
131 | M& L for supplyTransformer Oil/Voltage stabilizer oil |
132 | Labour Charges forFilteration of voltage stabilizer oil for required strength complete all as specified and directed. |
133 | M & L for installation of Trasnformer Control type |