Public Works Department-PWD has published 1 Repair Maintenance Of Vrs. E And M Services Installed At Iti Vivek Vihar. 2 Sitc Of Ac And Desert Air Cooler At Civil Office M-2113, M-2112 Delhi. ( Sh- Repairing / Replacement Of Electrical Installations And Ac At Iti Shahdara Vivek Viha. Submission Date for this Tender is 09-05-2022. Electrical Maintenance Tenders in vihar Delhi. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | ITI Vivek Vihar Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. Group C |
3 | Supplying, installation, testing and commissioning of Window type Air Conditioner unit of 1.5 TR capacity and BEE 3 star rating suitable for operation on 230 Volt ± 10% 50 Hz, single phase AC supply with all accessories i.e. condensing coil, cooling coil, compressor, remote control complete etc. as reqd. |
4 | SITC of Automatic Voltage Stabilizer suitable for up to 2 TR capacity Air Conditioner with High/ Low Voltage trip and time delay relay, input voltage 170-270 Volts etc. as required. |
5 | Supply, Installation, Testing and Commissioning of stainless-steel Storage type Water Cooler 150 /150 Ltr. Capacity, Fully Stain less steel suitable for operation on 230 V + 10% 50HZ single phase A.C. Supply including, making water line and electrical connection etc. As required. |
6 | SITC of 1200 mm sweep ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing M.S flat Fan hook etc. as required. ISI Marked |
7 | Supplying, installation, testing and commissioning of electric RO System with UV ray protection and all other standard facilities with following basic specification: Capacity-50/60LPH Membrene-75/100 GPD (4Nos.) Input Power Rating- 230 Volt AC,50 Hz % of Rejection in TDS-90 %(Approx.) System Operation Voltage-24VDC |
8 | Less on Account of buy back of old dismantled material received from the work. Old Fittings |
9 | R.O./Water Cooler |
10 | Civil office M-2113 |
11 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 6 sq. mm |
12 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
13 | Supplying, installation, Testing and Commissioning of split type Air Conditioner unit of 2.0 TR capacity and BEE 3 star rating suitable for operation on 230 Volt ± 10% 50 Hz, single phase AC supply with all accessories i.e. condensing coil, cooling coil, compressor, remote control, 5 mtr. copper pipe, connection wire, Outdoor stand complete etc. as required. |
14 | SITC of Copper wound Automatic Voltage Stabilizer suitable for 2 TR capacity Air Conditioner with High/ Low Voltage trip and time delay relay, input voltage 170-270 Volts etc. as required. |
15 | Supplying & laying of refrigerant copper pipe of 5/8" & 1/4" size for liquid line of 2.0 TR Split AC with nitrile foam insulation on the complete length of copper pipes from indoor unit to outdoor unit pipe connections, 3 core 2.5 sq. mm copper conductor PVC insulated cable for indoor and outdoor connection and Heavy-Duty hard PVC drain pipe of size 25 mm Dia for Split type AC unit including binding/Clamping up to 10 mtr. etc. i/c breaking open wall for pipe outlets & making good the damages wherever necessary complete etc. as reqd. |
16 | Supplying, installation, Testing and Commissioning of Desert Air Cooler -Minimum of 70 Litres. |