Jammu And Kashmir Police Housing Corporation has published Construction Of Auditorium Block At Govt Degree College Bhaderwah By Way Of Electrification Works ( C No. 06 ) . Submission Date for this Tender is 10-05-2022. Electrification Work Tenders in bhaderwah Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI boxetc. as required. |
2 | supply and fixing of 5 inch dia Fan Box / concealed box with round sheet cover for covering the base and bottom and dual painted with red oxideMake:- Anchor/Indoasian/havells 0r equivalent |
3 | Providing Installation testing and commissioning ofCeiling Fans of approved brands with connections etc as required Make:- Anchor/Indoasian/havells |
4 | Supply & Fixing of additional Fan rods Make:- Anchor/Indoasian/havells |
5 | Supplying and fixing two module Stepped type electronic Fan Regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
6 | Supply installation & fixingof 100 Watt wall/ Ceiling Light , LED Lumanaire Focus light(Warm Light) including Connections etc as requiredFor auditorium |
7 | Supplying and fixing of 24x24 inch 36W slim LED Panel lights For auditorium |
8 | Supplying and fixing of1x25 watt LEDfiiting 4 feet long wall /surface mountingLUMINAIRE including connections etc as required |
9 | Supply & installation, of Conciel Boxfor LED Panelas required |
10 | Supply,installation,testing and commissioning of Ceiling LED Panel type 14 watt day milky fitting with connections as required |
11 | Supply,installation,testing and commissioning of Ceiling LED Panel type 10 watt day milky fitting with connections as required |
12 | Supply & Installation of Bulk Head Lights including connections,testing commissioning etc as required |
13 | Supply & Installation of Exhaust Fans With Metal Exhaust 300 mm(12") in the existing opening including connections,testing commissioning etc as required |
14 | Supply & Installation of WallFans With ABS blades and easy tilting mechanism,2200 RPM including connections,testing commissioning etc as required |
15 | Providing ,installation,testing and Commissioning of 100 watt LED Flood light with GI Pipe with connection etc as required |
16 | Supply and fixing ofCeiling rose on the existing junction box/wooden box including connections as required 1.33 |
17 | Supply and fixing Modular Blanking Plate on the existing modular plate and switch box excluding modular plateas required |
18 | SupplY , fixing, testing & commissioning of Call Bell which includes connections etc |
19 | Supply and fixing Indicator on the existing modular plate and switch box excludingas required |
20 | Supply & drawing 2 pair0.5 sqmm FR PVC Insulated annealed copper conductor,unarmoured Telephone cable in the existing surface/recessed steel/ PVC Conduit as required |
21 | Supplying and fixing of Telephone Socket outlet modular Switch/ Socket on the existing Modular Plate and switch box including connections but excluding modular plateas required |
22 | Supplying and fixing ofTVantenna Socket outlet modular Switch/ Socket on the existing Modular Plate and switch box including connections but excluding modular plates as required Make:- Anchor/ luminous/havells 0r equivalent |
23 | Supply & drawingco axial TV Cable RG 6 grade o.7 mm solid copper conductor PE insulated, shielded with fine tinned copper brand 7 protected with PVC sheath in the existing surface/recessed steel/PVC Conduit as required |
24 | supply and fixing of modular D-link Computer socket on modular zinc passivated box of 2 module (Make:D-Link) |
25 | Providing & Laying D-Link Cat-6 Computer wire in existing Conduit (Make:D-Link |
26 | Supply and fixing ofCeiling rose on the existing junction box/wooden box including connections as required |
27 | Supply and fixing Modular Blanking Plate on the existing modular plate and switch box excluding modular plateas required |
28 | Supplyinglaying & making outdoor connections & other jointing materials for 3.5X 240 sqmm LT Power Cable ,Almunium Conductor, ARMOURED |
29 | Supplyinglaying & making outdoor connections including aluminium lugs and other jointing materials for 3.5X 95 sqmm LT Power Cable ,Almunium Conductor, ARMOURED |
30 | Earth work/ Trench Cutting 60 cm X 60 cm for laying of75 mm dia PVC Pipe including laying of 300 sqmmArmoured cable and RE-fillingof trench |
31 | Providing and fixingAluminium Thimbles for making connections to 3.5 X 240/95sqmm Cable. |
32 | Supply ,instalation,fabrication and commissioning of Low voltage Double Door Main Panel on 415 volts 3 phase 50 htzs of 2mm thick CRCA / Sheet of powder size6x 6 x1.5 rft . a)Providing and fixing 400 amp TPN A1.Bus bar with required nos of thimbles etc (2 nos)b)400 amp 4 pole MCCB with35 ka breaking capacity (1 Nos) c)350 amp 4 pole change over switche)250 amp 4 pole MCCB WITH 35 KAbreaking capacity(2 nos)f)63 amp TPN (10 nos) g)VSS meter/switch h) ASS meter/ switch |
33 | Supply & Fixing of following size of medium class PVC Conduits along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduits as required |
34 | 25 mm |
35 | 40 mm |
36 | Supplying and fixingof following way horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
37 | 8 way (4 + 24) double door |
38 | 16 way SPNDB |
39 | Supply Installation, Testing & Commissioning of SPAREBOX. |
40 | Supply & Fixingfollowing sizeTPN |
41 | 63 amps TPN |
42 | Supply & Fixingfollowing size SPN |
43 | SPN 63 amps |
44 | 40 ampsSPN |
45 | 32 ampsSPN |
46 | Supplying and fixing of 5 amps to 32 amps rating 240/415 volts "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required of Approved Brand. |
47 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
48 | 1.5Sq. mm wire for Inverter |
49 | 2 x 2.5 Sqmm + 1 x 2.5 sqmm |
50 | 2 x 4 Sqmm + 1 x 4 sqmm |
51 | 2 x 6 Sqmm + 1 x 6 sqmm |
52 | 4 x 10Sqmm + 1 x 6 sqmmearth wire |
53 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc.& Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections for HEATING pointsetc. as required. |
54 | 6 Module (200mmX75mm) |
55 | 6 pin 15/16 A socket outlet&15/16 A switch |
56 | 5 pin 5/6 A socket outlet & 5/6 A switch |
57 | Supplying and fixing 3 Module(100mmX75mm)GI Box with modular plate & cover infront including providing 3 pin 5/6 A modularswitch /socketincluding connections etc. as reqd. |
58 | Supplying and fixing suitable size 8 module GI Box with modular plate & cover infront including providing 3 Nos 6 Amp modularsocket Controlled by 16 Amp Switch including connections etc. as reqd. |
59 | Supplying and fixing following 5 pin 5/6 A modularswitch /socket on the existing modular plate & swichbox including connections etc. as reqd. |
60 | Providing and fixing of2 way AC Box with MCB mounting and connections etc as required. |
61 | SITC OF INVERTER 2000 va with 150 AH Double Battery |
62 | Disposal of unwanted Mulba/ material from the site of work including Cheselling & repairing whereever required |
63 | S.I.T.C of Photo smoke detector.Make system Censor |
64 | S.I.T.C of Manual call boxwith hammer complete as req. |
65 | S.I.T.C of electronic hooter with audible range of 25-30mtr with suitable output wattage as req. Make |
66 | SITC of 6 zones solid-state main control panel suitable for wall mounting confirming to IS-2189 fabricated out of 16 guage CRCA sheet incorporating audio visual indication foreach zones & 2x12V sealed dry maint. Free battery not less than 07AH capacity & battery charger complete. |
67 | S/l of 2 x 1.5 sqmm dia PVC insulated copper conductor armoured cable directly on the surface complete as req. |
68 | 25 mmPVC Conduit |
69 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
70 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required. |
71 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc.complete as required. |
72 | Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required. |
73 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
74 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
75 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |