Special Repair To External Electric Supply By Conversion Of Lt Oh Line Into Lt Ug Cable At Lekha Nagar Colony Under Ge East Jabalpur Special Repair To External Electric Supply By Conversion Of Lt Oh Line Into Lt Ug Cable At Lekha Nagar Colony Under Ge Eas, jabalpur-Madhya Pradesh

Military Engineer Services-MES has published Special Repair To External Electric Supply By Conversion Of Lt Oh Line Into Lt Ug Cable At Lekha Nagar Colony Under Ge East Jabalpur Special Repair To External Electric Supply By Conversion Of Lt Oh Line Into Lt Ug Cable At Lekha Nagar Colony Under Ge Eas. Submission Date for this Tender is 02-06-2022. Overhead Line Tenders in jabalpur Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

32027200
Corrigendum : Special Repair To External Electric Supply By Conversion Of Lt Oh Line Into Lt Ug Cable At Lekha Nagar Colony Under Ge East Jabalpur Special Repair To External Electric Supply By Conversion Of Lt Oh Line Into Lt Ug Cable At Lekha Nagar Colony Under Ge Eas
Open Tender
Indian
Madhya Pradesh
jabalpur
02-06-2022

Tender Details

Special Repair To External Electric Supply By Conversion Of Lt Oh Line Into Lt Ug Cable At Lekha Nagar Colony Under Ge East Jabalpur Special Repair To External Electric Supply By Conversion Of Lt Oh Line Into Lt Ug Cable At Lekha Nagar Colony Under Ge East Jabalpur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-May-2022 CORRIGENDUM NO 1 Other 24-05-2022
2 25-May-2022 Corrigendum No. 02 Date 28-05-2022
3 28-May-2022 EXTENSION OF DATE Date 02-06-2022

Key Value

Document Fees
INR 1000 /-
EMD
INR 198000.0 /-
Tender Value
INR 1.23 Crore /-

BOQ Items

Name of Work: SPECIAL REPAIR TO EXTERNAL ELECTRIC SUPPLY BY CONVERSION OF LT OH LINE INTO LT UG CABLE AT LEKHA NAGAR COLONY UNDER GE EAST JABALPUR.
Sl. No. Item Description
1Supply and laying or fixing or passing in trenches/ on pole/ through pipes,1100 V grade XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor of following cross sectional areas and testing on completion complete all as specified and as directed :-
24 core X 10 sqmm
34 core X 16 sqmm
44 core X 25 sqmm
53.5 core X 50 sqmm
63.5 core X 120 sqmm
73.5 core X 150 sqmm
83.5 core X 185 sqmm
93.5 core X 240 sqmm
10Excavation in trenches, not exceeding 1.5m wide and exceeding 1.5m but not exceeding 3 m in depth for poles, laying of pipe, cable, erection of post and stays etc or n. exc.10 Sqm on plan and n. exc. 1.5m in depth etc and getting out in soft/loose soil complete all as specified and directed.
11Excavationin trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for poles, laying of pipe, cable, erection of post and stays etc or n. exc.10 Sqm on plan and n. exc. 1.5m in depth etc and getting out in soft/loose soil complete all as specified and directed.
12Returning, filling in excavated , including spreading, levelling, watering and well ramming in layers not exceeding 25cm of soft/loose soil complete all as specified and directed.
13Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point including spreading complete all as specified and directed.
14Supply and spreading clean and dry fine sand free from sharp materials (unwashed) laying in trenches around the cable for cushioning in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. (Note :- Punned thickness shall be measured.)
15Supply and laying un-reinforced precast concrete cable covers(ISI marked), Class LV type I, Flat, size 250 mm x 150 mm x 40 mm, complete all as specified and as directed.
16Demolition of cement concrete of any description (unreinforced) in ground floors and paving not exceeding 15 cm inthickness (below or above ground level) including removal of debristo out side MD land complete all as specified & directed.
17M&L for PCC (1:4:8) Type D-2 using 40 mm graded stone aggregate as in foundation, filling, mass concrete and sub base of floors, path/ paving etc complete all as specified & directed.
18M&L for PCC 1:3:6 Type C-1 using 20mm graded stone aggregate as in copings of pole etc and the like including weathering slightly rounded/ chamfered angles with & including necessary use and waste of form work for fair faces of concrete, complete all as specified and directed.
19Takingout / downold unserviceableundergroundcable from trenches, wall, floor etc. and removingfrom site, size upto 25 sqmm complete all as specified and directed.Note :- Excavation and earhworkfor taking outexisting old unserviceable cable shall be deemed to be included in the unit rate quoted by contractor
20Takingout / downold unserviceable undergroundcable from trenches, wall, floor etc. and removingfromsite, size 35 to 120 sqmm complete all as specified and directed. Note :-Excavation and earhworkfor taking out existing old unserviceable cable shall be deemed to be included in the unit rate quoted by contractor
21Takingout / down unserviceableundergroundcable from trenches, wall, floor etc. and removingfromsite, size 150 to 400 sqmm complete all as specified and directed.Note :- Excavation and earhworkfor taking out existing old unserviceable cable shall be deemed to be included in the unit rate quoted by contractor
22Material and labour for boring hole underthe road /path/ pavement/ hard standing ( width not more than 10 metre) with the help of Trenchless Technology using ultra sound technique and necessary machine with andincluding HDPE pipe of 110 mm boresuitable for 0.4 Mpa working pressure, HDPE pipe laidnot less than 1 metre belowavg ground level complete all as specified and directed.Note :- Cost of HDPE pipe as specified aboveshall bedeemed to be included in theunitrate quoted by the contractor.
23S&F cable route indicator/marker made up of PCC block in(1:3:6) Type C-1 using 20 mm gradedcrushed stone aggregate, of size 300 mm x 300 mm x 600 mm thick with " Danger/LT 433 VOLTS CABLE" embossedon cable route indicator /Marker including painting as percolour approved by GE and buried in ground 45 cm including necessaryexcavation , earthworkand formwork complete all as specified and directed.
24Supplying and fixing/ laying of GI pipe light grade in trenches/ under roads/ along pole/ wall including all necessary fittings & clamps made out of 25x3mm flat iron as required for cable protection etc complete all as specified and directed for following dia of pipe :-
25(a) 100 mm dia
26(b) 80 mm dia
27(c) 50 mm dia
28(d) 40 mm dia
29Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 2000x1500x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing ,degree of protectionIP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity aluminium bus bars of 1600 Amps,fixed with colour coated porcelain insulator sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on approx 75cm aboveGL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 2.30x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work, formwork and plaster/ rendering 15 mm thickin CM 1:4 on all sides of PCC platform upto 15cm below GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-150Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
30(iii) INCOMING Air circuit breaker 1250 Amps, 4 Pole,breaking capacity , 50 KA , ICU=ICS=ICW for 1 Sec of total sensitivity, fixed type, EF version inbuilt 6 NO+6NC aux contact, door ceiling frame, manually and electrically operated complete with 240 V shunt trip coil, closing coil and motor for electrical charging, C power S-1 Range, conforming to IS/IEC 6094-2, microprocesser base with testing through test button with cover through MODBUS potcall complete all as specified. Make:- Legrand Cat.No.669533 or equivalent of other Make- ABB or Schneider as approved by GE. (iv) OUTGOING (a) MCCB 4 Pole, 320 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 36 KA -02 Nos. Make:- LegrandCat.No.4220 62 or equivalent of other Make ABB or Schneider as approved by GE. (b) MCCB 4 Pole, 250 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 36 KA -04 No. Make:- Legrand Cat.No.4203 49 or equivalent of other MakeABB or Schneider as approved by GE. (c) MCCB 4 Pole, 200 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 36 KA -04 Nos. (For further extension) Make:- Legrand Cat.No.4202 48 or equivalent of other MakeABB or Schneider as approved by GE. (d) MCCB 4 Pole, 25 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 36 KA -01 Nos. (For further extension) Make:- Legrand Cat.No.4200 91 or equivalent of other Make ABB or Schneider as approved by GE.(e) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other MakeABB or Schneider as approved by GE. (v)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641 or equivalent as approved by GE & Power contactor Legrand Cat No. 412549 or equivalent as approved by GE -1 No.(vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase - 1 No.(vii) Digital frequency meter 40-60 Hz - 01 Set. (e)Power contactor, 3 Pole rating not less than 70A with 230 Coil - 01 No Make :- Legrand cat part No. 416143, Havells, L&T or equivalent as approved by GE.
31Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 900x1200x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing , degree of protectionIP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity aluminium bus bars of 400 Amps fixed with colour coated porcelain insulator sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on apporx 75cm above from GL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 1.20x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work and plaster/ rendering 15 mm thickin CM 1:4 on all sides of PCC platform upto 15cm below from GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-150Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
32(iii) INCOMING Thermal magnetic and microprocesser release MCCB 200 Amps, 4 Pole breaking capacity , 36 KA , with front operated locking device - 1No. Make:- Legrand Cat.No.4202 48 or equivalent of other MakeABB or Schneider as approved by GE. (iv) OUTGOING (a) MCCB 4 Pole, 63 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -05 Nos. Make:- LegrandCat.No.4200 13 or equivalent of other Make ABB or Schneider as approved by GE. (b) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other MakeABB or Schneider as approved by GE. (v)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641 or equivalent as approved by GE & Power contactor Legrand Cat No. 412549 or equivalent as approved by GE-1 No. (vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase - 1 No.(vii) Digital frequency meter 40-60 Hz - 01 Set.
33Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 1200x1000x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing , protection of enclose IP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity Aluminium bus bars of 500 Amps fixed with colour coated porcelain insulator (01 Set) sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on approx 75cm above from GL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 1.50x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work and plaster/ rendering 15 mm thickin CM 1:4 on all sides of PCC platform upto 15cm below from GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-200Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
34(iii) INCOMING Thermal magnetic and microprocesser release MCCB 250 Amps, 4 Pole breaking capacity , 50 KA , with front operated locking device - 1No. Make:- Legrand Cat.No.4203 49 or equivalent of other Make- Legrand orABB or Schneider as approved by GE. (iv) OUTGOING (a) MCCB 4 Pole, 63 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -05 Nos. Make:- LegrandCat.No.4200 13 or equivalent of other MakeABB or Schneider as approved by GE. (b) MCCB 4 Pole, 25 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -02 Nos. Make:- Legrand Cat.No.4200 11 or equivalent of other MakeABB or Schneider as approved by GE. (c) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other MakeABB or Schneider as approved by GE. (V)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641& Power contactor Legrand Cat No. 412549-1 No. (vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase - 1 No. (vii) Digital frequency meter 40-60 Hz - 01 Set.
35Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 1500x1200x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing , protection of enclose IP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity aluminium bus bars of 600 Amps fixed with colour coated porcelain insulator (01 Set) sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on approx 75cm above from GL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 1.80x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work and plaster/ rendering 15 mm thickin CM 1:4 on all sides of PCC platform upto 15cm below from GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-200Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
36(iii) INCOMING Thermal magnetic and microprocesser release MCCB 320 Amps, 4 Pole breaking capacity , 50 KA , with front operated locking device - 1No. Make:- Legrand Cat.No.4220 72 or equivalent of other MakeABB or Schneider as approved by GE. (iv) OUTGOING (a) MCCB 4 Pole, 63 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -07 Nos. Make:- LegrandCat.No.4200 13 or equivalent of other Make ABB or Schneider as approved by GE. (b) MCCB 4 Pole, 25 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -01 No. Make:- Legrand Cat.No.4200 11 or equivalent of other MakeABB or Schneider as approved by GE. (c) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other MakeABB or Schneider as approved by GE. (v)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641 or equivalent as approved by GE & Power contactor Legrand Cat No. 412549or equivalent as approved by GE-1 No.(vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase - 1 No. (vii) Digital frequency meter 40-60 Hz - 01 Set.
37Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 1200x1200x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing, degree of protectionIP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity Aluminium bus bars of 500 Amps fixed with colour coated porcelain insulator (01 Set) sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on approx 75cm above from GL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 1.50x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work and plaster/ rendering 15 mm thick in CM 1:4 on all sides of PCC platform upto 15cm below from GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-200Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
38(iii) INCOMING Thermal magnetic and microprocesser release MCCB 250 Amps, 4 Pole, breaking capacity , 50 KA , with front operated locking device - 1No. Make:- Legrand Cat.No.4203 79 or equivalent of other MakeABB or Schneider as approved by GE. (iv) OUTGOING (a) MCCB 4 Pole, 63 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -06 Nos. Make:- LegrandCat.No.4200 13 or equivalent of other Make ABB or Schneider as approved by GE. (b) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other MakeABB or Schneider as approved by GE. (v)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641 or equivalent as approved by GE & Power contactor Legrand Cat No. 412549 or equivalent as approved by GE -1 No. (vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase - 1 No.(vii) Digital frequency meter 40-60 Hz - 01 Set.
39Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 1500x1200x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing , degree of protectionIP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity Aluminium bus bars of 1200 Amps fixed with colour coated porcelain insulator (01 Set) sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on approx 75cm above from GL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 1.80x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work and plaster/ rendering 15 mm thickin CM 1:4 on all sides of PCC platform upto 15cm below from GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-200Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
40(iii) INCOMING Thermal magnetic and microprocesser release MCCB 630 Amps, 4 Pole, breaking capacity , 50 KA , with front operated locking device - 1No. Make:- Legrand Cat.No.4220 75 or equivalent of other MakeABB or Schneider as approved by GE. (iv) OUTGOING (a) MCCB 4 Pole, 250 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 36 KA -02 Nos. Make:- LegrandCat.No.4202 49 or equivalent of other MakeABB or Schneider as approved by GE.(b) MCCB 4 Pole, 200 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 36 KA -02 Nos. Make:- LegrandCat.No.4202 48 or equivalent of other Make ABB or Schneider as approved by GE. (c) MCCB 4 Pole, 63 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 25 KA -01 No. Make:- LegrandCat.No.4200 53 or equivalent of other Make ABB or Schneider as approved by GE.(d) MCCB 4 Pole, 25 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -01 No. Make:- LegrandCat.No.4200 11 or equivalent of other MakeABB or Schneider as approved by GE. (b) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other MakeABB or Schneider as approved by GE. (v)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641 or equivalent as approved by GE& Power contactor Legrand Cat No. 412549 or equivalent as approved by GE-1 No. (vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase - 1 No.(vii) Digital frequency meter 40-60 Hz - 01 Set.
41Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 900x1200x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing,degree of protectionIP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity Aluminium bus bars of 400 Amps fixed with colour coated porcelain insulator (01 Set) sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on approx 75cm above from GL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 1.20x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work and plaster/ rendering in CM 1:4 on all sides of PCC platform upto 15cm below from GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-200Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
42(iii) INCOMING Thermal magnetic and microprocesser release MCCB 200 Amps, 4 Pole, breaking capacity , 36 KA , with front operated locking device - 1No. Make:- Legrand Cat.No.4202 48 or equivalent of other Make ABB or Schneider as approved by GE. (iv) OUTGOING (a) MCCB 4 Pole, 125 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -01 Nos. Make:- LegrandCat.No.4200 16 or equivalent of other MakeABB or Schneider as approved by GE. (b) MCCB 4 Pole, 63 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -03 Nos. Make:- LegrandCat.No.4200 13 or equivalent of other MakeABB or Schneider as approved by GE. (c) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other MakeABB or Schneider as approved by GE. (v)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641 or equivalent as approved by GE & Power contactor Legrand Cat No. 412549 or equivalent as approved by GE-1 No.(vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase(set of three) - 1 No. (vii) Digital frequency meter 40-55 Hz - 01 Set.
43Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 900x1200x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing and 2mm thick CRCA steel sheet for non load bearing, degree of protectionIP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity aluminium bus bars of 400 Amps fixed with colour coated porcelain insulator (01 Set) sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on approx 75cm above from GL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 1.20x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work and plaster/ rendering 15 mm thickin CM 1:4 on all sides of PCC platform upto 15cm below from GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-200Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
44(iii) INCOMING Thermal magnetic and microprocesser release MCCB 200 Amps, 4 Pole, breaking capacity , 36 KA , with front operated locking device - 1No. Make:- Legrand Cat.No.4202 48 or equivalent of other MakeABB or Schneider as approved by GE. (iv) OUTGOING (a) MCCB 4 Pole, 125 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -02 Nos. Make:- LegrandCat.No.4200 16 or equivalent of other MakeABB or Schneider as approved by GE. (b) MCCB 4 Pole, 63 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -01 No. Make:- LegrandCat.No.4200 13 or equivalent of other MakeABB or Schneider as approved by GE.(c) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other Make ABB or Schneider as approved by GE. (v)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641or equivalent as approved by GE& Power contactor Legrand Cat No. 412549 or equivalent as approved by GE-1 No. (vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase - 1 No. (vii) Digital frequency meter 40-60 Hz - 01 Set.
45Supply, fabricating and erecting/ fixing / installation of outdoor LT panel with projected globe roof for rain water protection (feeder pillar box), CPRI approved outdoor type (approximate size 900x1200x600mm), weather and vermin proof suitably ventilated for 440 volts, 3 phase 4 wire system, AC supply, factory made fully compartmentalized made out of 3.15mm thick CRCA steel sheet for load bearing , degree of protectionIP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour, double door with both side opening alongwith locking arrangement, bus bar chamber to accommodate epoxy painted high conductivity Aluminium bus bars of 250 Amps fixed with colour coated porcelain insulator (01 Set) sleeves including phase indication neon lamps set, danger notice plate, necessary cable connections with suitable size of cable lugs and glands, internal wiring with suitable size copper conductor cable, panel shall be fixed/ mounted on approx 75cm above from GL on and including suitable size of Base Channel/ Angle Iron or any other section (Zinc metal coated) frame work/ support as per site requirement but not less than of angle iron frame of section 50x50x6mm including all necessary bolts, nuts and washers etc over and including PCC platform of size not less than 1.20x0.80x0.75M height (outer dimensions), 0.60M above GL and 0.15M below GL in PCC 1:2:4 type B2 using 40mm graded stone aggregate, foundation 150mm thick and 150mm extending on both sides of PCC platform in PCC 1:4:8 type D2 using 40mm graded stone aggregate including necessary excavation & earth work and plaster/ rendering 15 mm thickin CM 1:4 on all sides of PCC platform upto 15cm below from GL and two coats of white wash on plastered surfaces including prepration of surfaces etc including testing & commissioning with & including following fixtures/ fittings complete all as specified and directed:- (i)Ammeter of rating (0-200Amps) digital type with selector switch - 01 Set (ii) Volt meter of rating (0-600V) digital type with selector switch - 01 Set Make for Ammeter and Volt meter: AE/ L&T/ Legrand/ ABB as approved by GE.
46(iii) INCOMING Thermal magnetic and microprocesser release MCCB 125 Amps, 4 Pole, breaking capacity , 36 KA , with front operated locking device - 1No. Make:- Legrand Cat.No.4200 96 or equivalent of other Make ABB or Schneider as approved by GE. (iv) OUTGOING (b) MCCB 4 Pole, 63 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 16 KA -02 Nos. Make:- LegrandCat.No.4200 13 or equivalent of other Make ABB or Schneider as approved by GE. (c) MCB 2 Pole, 32 Amps - 01 No. Make:- Legrand Cat.No.4086 17 or equivalent of other MakeABB or Schneider as approved by GE. (v)Digital time switch including three phase power contactor 40 Amps.Make :- Legrand Cat No. 412641 or equivalent as approved by GE& Power contactor Legrand Cat No. 412549 or equivalent as approved by GE -1 No.(vi)Indicator lamp (LED type) & bakelite fuse showing R,Y,B phase - 1 No. (vii) Digital frequency meter 40-60 Hz - 01 Set.
47Dismantling and taking down street light fittings any size and re-fixing again after erecting of LT pole etc complete all as specified and directed.
48S&F junction box, in repair, of size 155 X 210 X 92 mm,made out of CRCA sheet 2 mm thick totally enclosed, dust and vermin proof, rain protected slanted roof top, door pasted with rubber gasket, water tight IP 65 protection single leaf shutter in front having proper lacking arrangements and painted with powder coating paint and suitable size of "connect well" stud terminal ( provision for socket bolting) - 05 Nos suitable for 415 volts, 50 Hz, 3 phase 4 wire internal wiring system including MCB SP,6 Amps-01 No. , clamp made out of MS flat 30 X 5 mm , nuts, bolts, washers etc complete and mounted on security light pole complete all as directed. Make:- Hensel cat part No. DK 1616 G (with terminal) or equivalent as approved by GE.
49Supply and fix,in repairs, 45 watt new generation energy saving and environmental friendly long life LED security light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP opening separate driver compartment with IP65 protection and impact resistance of IK07 on bldg wall with and including pipe bracket made out of GI tubing 32 mm bore medium grade ISI marked 1.20m long bent to shape & providing clamps 2 Nos made out of 50 x 6mm Flat iron/ MS clamps & 12mm dia bolts, nuts & washers etc and two coat painting of approved colour on brackets completely with and including synthetic enamel paint and connecting up with & including twin twisted copper flexible wireof suitable lengthcomplete all as specified & directed. Make:- Havells Cat part No. ENDURAPEARLNEOSL45WLED757PASYTOPC or equivalent model of make- Philips or Crompton or WIPRO or Bajaj as approved by GE.
50M&L for earthing in replacement complete with galvanised steel earth plate electrode 600x600x6.0mm thick directly burried in the ground (earth pit not less than 2.25M deep below ground level) with top edge of earth plate not less than 1.50M deep below normal ground level, connected to galvanised iron strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 40mm bore GI pipe light grade including necessary fittings for protection of earthing strip, watering pipe 20mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm graded crushed stone aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm graded crushed stone aggregate and internal surfaces of concrete chamber shall be given 12mm thick plaster in CM (1:4), funnel with wire gauge of 22 gauge (0.63 mm), 8 mesh per linear incl 50mm thick cover of RCC (1:2:4) type B-1 using 20mm graded crushed stone aggregate reinforced with 8mm dia TMT bars @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and providing connection points with MS/ GI bolts & washers as required and connection from earth test point to earth electrode with same GI earth strip alongwith protection pipe and testing on completion complete all as specified and directed. Note:- GI strip and protection pipe from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rates as quoted by the contractor.
51M&L for earthing in replacement complete with galvanised steel earth plate electrode 600x600x6.0mm thick directly burried in the ground (earth pit not less than 2.25M deep below ground level) with top edge of earth plate not less than 1.50M deep below normal ground level, connected to gi earth wire of size 4 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 40mm bore GI pipe light grade including necessary fittings for protection of earthing strip, watering pipe 20mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm graded crushed stone aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm graded crushed stone aggregate and internal surfaces of concrete chamber shall be given 12mm thick plaster in CM (1:4), funnel with wire gauge of 22 gauge (0.63 mm), 8 mesh per linear incl 50mm thick cover of RCC (1:2:4) type B-1 using 20mm graded crushed stone aggregate reinforced with 8mm dia TMT bars @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and providing connection points with MS/ GI bolts & washers as required and connection from earth test point to earth electrode with same GI earth strip alongwith protection pipe and testing on completion complete all as specified and directed. Note:- GI strip and protection pipe from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rates as quoted by the contractor.
52M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground and laid down through 20 mm PVC medium grade conduit complete with fixed to pole or any other indicated situation for loop earthing etc as required 4 mm dia galvanized iron or steel wire etc complete all as specified and directed.
53Supply and fix, in repair, MCB DB 4 way sheet metal enclosure triple pole and neutral, IP 43 with metal door, 415 Volts with 200 Amp rated copperbus bar of suitable size and common neutral link and earth bar all enclosed on standard steel sheet flush mouting type factory fabricated complete without MCB but with and includingenclosure, blank plate complete all as specified and directed .
54Supply and fixMCB DB 8 way sheet metal enclosure SPN, IP 43 with metal door, 240/ 415 Volts with 200 Amp rated copperbus bar of suitable size and common neutral link and earth bar all enclosed on standard steel sheet flush mouting type factory fabricated complete all as specified and directed.
55S&F 415 V, 10 KA "C" curve MCBTPN 63 Ampscurrent capacity,in the DB complete with connection, testing and commissioning complete all as specified and directed. Make:- Legrand Cat No. 4086 83 or equivalent model of make L&T/ Havells/ ABB as approved by GE.
56Supply & fix MCB SPN, 40 Amps,"C" series, 240 volts, 50Hz, 10kA complete all as specified & directed. Make:- Legrand Cat No. 4086 18 or equivalent model of make L&T/ Havells/ ABB as approved by GE.
57Supply & fix MCB SPN, 32 Amps,"C" series, 240 volts, 50Hz, 10kA complete all as specified & directed. Make:- Legrand Cat No. 4086 17 or equivalent model of make L&T/ Havells/ ABB as approved by GE.
58Supplying and fixing MCCB 4Pole, 160 Amps, Thermal Magnetic Release, Ics = 100% of Icu, 415 Volts with rupturing capacity 36 KA complete all as specified and directed. Make:- Legrand Cat.No.4203 37 or equivalent of other Make ABB or Schneider as approved by GE.
59Dismantling ACSR/AAC conductor of any size from LT poles or distribution span etc complete all as specified and directed.
60Dismantlingcross arms of MS channel or angle sections etc, any size, brackets, clamps, nuts, bolts, washers from LT poles or distribution span etc complete all as specified and directed.
61Dismantlingexisting unserviceable stay assembly and removing from site of work etc complete all as specified and directed.
62Dismantlingunserviceable earth wire ,guard wire with cradle of any size from LT over head line or service feeder or any distributionspan and removing from site of work etc complete all as specified and directed.
63Dismantling existing unserviceable insulators of any type or any size etc complete all as specified anddirected.
64DismantlingLT steel tubular poles and setting aside for re-use within 50 metres complete all as specified and directed. Note :- Excavation,earthwork, returning, filling, removal and PCC will be measured and paid for separately.
65M&L for PCC 1:2:4 type B-2 using 40 mm graded stone aggregate as in filling in surface channels and drains etc complete all as specified and directed.
66Schedule of credit amount of Rs. 1,23,200.00 to be deducted during AOC
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail