Military Engineer Services-MES has published Provisioning Of Smart Prepaid Automatic Meter Reading System And Billing Software For Private Parties In Mil Station Pithoragarh And Provn Of 160 Kva Dg Set For Oxygen Generation Plant At Mh In Mil Station Pithoragarh Provisioning Of Smart Prepaid Automat. Submission Date for this Tender is 16-05-2022. Diesel Generators Tenders in pithoragarh Uttarakhand. Bidders can get complete Tender details and download the document.




Tender Notice

31986805
Provisioning Of Smart Prepaid Automatic Meter Reading System And Billing Software For Private Parties In Mil Station Pithoragarh And Provn Of 160 Kva Dg Set For Oxygen Generation Plant At Mh In Mil Station Pithoragarh Provisioning Of Smart Prepaid Automat
Open Tender
Indian
Uttarakhand
pithoragarh
16-05-2022

Tender Details

Provisioning Of Smart Prepaid Automatic Meter Reading System And Billing Software For Private Parties In Mil Station Pithoragarh And Provn Of 160 Kva Dg Set For Oxygen Generation Plant At Mh In Mil Station Pithoragarh Provisioning Of Smart Prepaid Automatic Meter Reading System And Billing Software For Private Parties In Mil Station Pithoragarh And Provn Of 160 Kva Dg Set For Oxygen Generation Plant At Mh In Mil Station Pithoragarh

Key Value

Document Fees
INR 500 /-
EMD
INR 73000.0 /-
Tender Value
INR 36.50 Lakhs /-

BOQ Items

Name of Work: PROVISIONING OF SMART PREPAID AUTOMATIC METER READING SYSTEM AND BILLING SOFTWARE FOR PRIVATE PARTIES IN MIL STATION PITHORAGARH AND PROVN OF 160 KVA DG SET FOR OXYGEN GENERATION PLANT AT MH IN MIL STATION PITHORAGARH
Sl. No. Item Description
1DESCRIPTION OF ITEMS
2Phase I and Phase II (From Item 1.00 to 17.00 including sub items)
3Supply and Installation ofSmart Single Phase Meter with the following specifications: • AC Single Phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS 16444 and relevant IEC standards with inbuilt GPRS communication facility with self healing Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry. • Meter Should support the following data : 30 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, 30 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand • Meter should have connect / disconnect functionality operable from prepaid billing software • The meter should support open communication protocol DLMSwith the software MAKE: L&T, Schneider,Secure Note: (a) The contractor would be responsible from removing the existing meter, noting down the reading and depositing it with the MES. (b) It would be possible to run the meter in both prepaid and postpaid mode (c) The meters would carry 5 year warranty.
4Supply and Installation ofSmart Three Phase Meter with the following specifications: • AC Three Phase Four Wire, Tamper Proof, Static Meter of Class 1.0, 415 V, 50 Hz, 10 A-60 A conforming toIS:16444 and relevant IEC standards with inbuilt GPRS communication facility with self healing Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry. • Meter Should support the following data : 30 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, 30 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand • Meter should have connect / disconnect functionality operable from prepaid billing software • The meter should support open communication protocol DLMSwith the software MAKE:L&T, Schneider,Secure Note: (a) The contractor would be responsible from removing the existing meter, noting down the reading and depositing it with the MES. (b) It would be possible to run the meter in both prepaid and postpaid mode. (c) The meters would carry 5 year warranty.
5Supply and Configuration of the Web based Software with following modules: (i) Meter Data Management Module The meter data management module would be responsible for collecting the data from the concentrator and make the data available to the billing system.The meter data management system would capture and provide the following data: (a) 30 min instantaneous data from all the meters for seven parameters – Cumulative Energy, Cumulative Apparent Energy (as applicable), Power, Current, Voltage, Power Factor and Frequency (b) Monthly billing survey data for cum energy and max demand (ii) Postpaid /Prepaid Billing Module The billing module would collect the data from the meter data management module, calculate the energy consumption, calculate billing determinant and make energy data / billing data available to admin and end users. The billing module would include functionalities for tariff setup, bill format setup, bill adjustment, occupation billing and vacation billing. It would allow postpaid and prepaid functionality as required.
6(iii) Occupation and Vacation Module The system would support occupation / vacation and billing reports. the software would be collecting data from DCU. The software would provide access to staff as well as the occupant for the data. (iv) Web site: There would be a dedicated website for the AGE and BSO team to view all the data and information. The designated users in MES would have the admin access to the application. The MES staff would also have the access of the key information on an android mobiles app (for admin use). (v) Customer Portal The system would include a customer portal for the resident /occupant to log in and view their own energy / billing data. There would be android and iOS mobile apps for the user to monitor its own data and balance on regular basis.
7(vi) Energy Accounting Module The system would include features of energy accounting. The system would be able to account for total energy block wise, facility wise and would also allow calculations of unaccounted energy in case total energy meter is also available. (vii) Communication Module The system would provide communication of energy data and bills via print, email and sms methods. (viii) Meter Master Data The system would support meter master data repository. The system would support meter replacement process. (ix) Excel Export The system would support export of metering and billing data in excel format. Make: Innologix, SAP, Oracle, Secure Note: (a) The software would be hosted on MEITY (Ministry of Information Technology) approved GCC (Government Community Cloud) (b) The software would contains two year defect liability including all operating expenses such as GPRS charges, hosting charges etc.
8Provision of infrastructure for Vending system like computer PCdesktop with processor i-7, 9 Generation, 8-GB RAM, hard disk 1TB, 1-CD/DVD combo drive R/W type, 4-USB Port including 18.5" monitor of same make, video card, keyboard, cordless mouce, Make-HP/IBM/Lenevo with licensed Operating system (Window10 Professional), along with 1KVS capacity UPS all as specified.
9Provision of print, copy, scan, wireless Report Printer with 12 pages per minute capacity, 600 x 600 dpi with HP, REt, 1200 dpi effective output quality (600 x 600 x 2 dpi with REt, with duty cycle 3,000 single-sided pages per month for report printing complete as required, Make: HP LaserJet 1020 or equivelent in canon, Epson and Samsung printer all as specified.
10Silent engine generating set 160 KVA with accoustic enclosure as per CPCB norms 415 volts with to give a minimum of around 87 Amp real current (at 0.8 pf) from it"s alternator 3 phase 0.8 power factor 50 Hz, 1500 RPM self excited self regulated brushless AC generator including accoustic enclosure suitable for ambient condition and conforming to condition under IS 4722, BS 5514/ 2613 /5000 with and including the following:-
11(i) The capacity of Generator set shall be net after all due de-rating factors as per relevant ISI design (ii) The capacity of prime mover will be as per current rating of Alternator as per calculation/ recomendation of OEM net after all due de-rating factors as per relevant ISI design (iii) Rate quoted shall be deemed to be inclusive of cable and terminations form Generator to the AMF Panel, with necessary holes to wall including making good to disturbed surfaces so as to match with the existing finishes with neccessary foundation as recommended by OEM, all as specified and directed. (iv) The quoted rate shall be deemed to be inclusive of first fill of oil and final successful acceptance test (A) Alternator :-Standard design alternator to give a minimum of around 87 Amp real current net output at site after considering de-rating as per site conditions at 0.8 (lag) power factor AC,3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self excited self regulated screen protected drip proof IP 23 enclosure brushless design with winding in pole faces, insulating class "H" and voltage regulation of+/- 1% at rated voltage from no load to full load. The alternator shall be conforming to BS 2613/5000 and shall be imposition to generate supply with frequency regulation with in +/- 1% tolerance. The alternator will be suitable for tropical climate and shall generally conform to BS - 2613/5000/ IS – 4722 i) Insualation class - "H‘ "ii) Temparature rise Class - "H‘ iii) Excitation : Self Excited iv) Regulation performance: The voltage is kept constant with +/- 1%, manual voltage adjustment within +/- 5% v) Frequency regulation +/- 1%"
12(B) Diesel Engine: - Adequate capacity of Diesel engine as accosted by the accepting officer basing on manufacturers technical details water cooled to drive independently above alternator and after considering de-rating as per site conditions after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS - 5514 with an overload capacity of 10% for half an hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under i)Fly wheel with housing "ii) Cooling system :- Moulded radiator with fan & belts iii) Cooling Water pump : - Centrifugal type belt driven iv) Exhaust System :- Exhaust System complete with exhaust piping of 150mm dia with MS pipe light grade upto & outside and 1meter away from the enclosure, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure. Exhaust gas turbo charger type. Exhaust manifold Silencer : Residual type Bellows" "iv) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by electronic governor for 1% speed /frequency regulation, Fuel filters,Fuel hoses. v) Lub oil System : Lubricating oil filter Lubricating oil pump" "vi) Air Intake System : Air intake Manifold Air cleaner dry type vii) Governor :- Electronic Governor viii) Starting System :- Electric Self starter with maintenance free battery including battery charging alternator"
13"ix) Batteries :- Batteries of maintenance free of capacity as recommended by the manufacturer complete with copper conductor multi stranded leads of suitable length fromself starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified and Starter gear ring Start and stop push button, Ignition key / Switch Handling and operation : Salient features of accessories shall be as under: Radiator with blower fan" "Corrosion inhibitor coolant Paper element filters for fuel, lub oil and by pass Electronic governor controlled direct fuel injection system Fly wheel housing and fly wheel" x) Generator Monitoring Panel : - Comprising of all standard items as mentioned under this schedule or asper standardpractice iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolent temparature indicator, Battary volt display. xi) Safety Controls : - Engine low lube oil pressure high water temparature and over speeding of engine xii) Coupling arrangement : - Flexible coupling, fly wheel to suit flexible coupling "xiii) Accessories :- AVM Pads built in enclosure and for entire unit on platform. xiv) Base Frame : - Should be provided as OEM norms xv) Fuel Tank :- As oer OEM" xvi) MS pipe line to and from the fuel tank to the DG Set C) AMF Panel :- Factory made inbuilt type control cubical made out of 2mm thick CRCA sheet dust and vermin proof totally enclosed with front opening of 415 volts 3 -phase4 - wire AC 50 Hz, including powder coated, copper bus bar of one and half times the prescribed load of thealternator complete with internal wiring with PVC insulated single core copper conductor multi stranded wire of 1100 volts grade of suitable capacity, fuses, name plates consisting of 4 pole MCCBs and Contactors of capacity as recommended by the manufacturer. Detachable cable gland plates, all controls, indicators and standardstandard microprocessor based LED/LCD display for indicating voltage, current, frequency, speed, kW, kWH, pf, temperature, Battery voltage, etc all as per OEM norms.
14"g) Annuciation with indication lamps for : (i) Low lub oil pressure." " (ii) High Water Temparature. (iii) Engine over speed. (iv) Battery low voltage Controls :- a) Load on Indication b) Load off indication" "c) Engine start push button d) Engine stop push button e) Fault accept / reset push button" "f) Battary Charger : (i) Transformer (ii) Rectifier" " (iii) Restance (iv) DC Volt meter (v) DC Ammeter (vi) Charger rate selector switch" "D) Accoustic Enclosure:-Manufactured by OEM suitable for prescribed DG Set (i) NAL approved as per CPCB (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board" "(iii) The generating setbattaries and control panel should be inside the enclosure. (iv) Fuel tank should be out side the enclosure in the sub station building. (v) Construction Details/specification are as follows: a) Outer body :- CRCA Sheet of 1.6mm thick b) Doors :- CRCA sheet of 1.6 mm thick" "c) Sound Insulation :- As per OEM Norms vi) The accoustic should be composite in construction and fully assembled integral unit"
15"vii) The batteries should be placed inside the enclosure beside the DG Set on a suitable insulatedplat form viii) The fuel tank is to be located in Sub Station Building and cost of the fuel lines is deemed to be included in the offer." "ix) The DG Set should be provided with external Emergency stop push button x) The enclosure should be suitably illuminated by CFL/FTL Lamp fittings. xi) The noise level should be 75 dba at 1m under free field conditions." xii) The acoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Gen set Green. The base frame should be painted with epoxy based black shade E) The coated rate includes excavation, removing of soft soil and PCC, Cement Concrete foundation, filling and mass concrete type B2 (1:2:4) using 40 mm graded aggregate of size not less than 4.6 x 2. 4 x 0.8 m for placing of DG Setcomplete all as specified and directed. F) The contactor will provide a suitable shed of Poly corbonate sheet in addition to above items alongwith it"s necessay support structure made up of suitable angle irons and Gi Pipes.
16M & L for earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground(earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 25x4 mm by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no 3 of SSR part I including Charcoal and rock salt with necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with CI Cover of 10 mm thick with MS rod 6mm dia 150mm long reinforcement, watering funnel with 15 mm dia light grade for watering and for protection of earth electrode 32 mm dia GI pipe all as specified and directed and tested on completion.
17Supply and laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminiumconductor of the below said sizes.
18(a)3.5 core 95 sqmm.
19(b) 3.5 core 150 sqmm.
20Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material (Epoxy Based) and accessories suitable for 3/4 core XLPE armoured Al conductor cable of size 95 sq mm
21Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material (Epoxy Based) and accessories suitable for 3/4 core XLPE armoured Al conductor cable of size 150 sq mm
22Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, laying of electrical cables, etc. and getting of soft/loose soil
23Returning, filling-in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm using excavated soil all as directed.
24Removing excavated materials to a distance not exceedcing 50 meters and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified
25Sand cushioning/sand covering for underground cable protection complete all as specified.(Note: Punned down thickness only shall be measured)
26Supply and laying sub class "B" bricks of old size (23x11x7cm) laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer-in-Charge
27Supply, lay of GI tubes light grade IS marked of 80 mm bore with all fittings laid in trenches/ fixed to wall/ laid in floor/ fixed structure etc for protection of cable complete all as specified and directed.
28Cutting of road/hard standing not exc to 30cm in width and not exc to 60cm in depth for removal/laying of GI steel water tubing including returning filling and making good the distrubed surfacs using 1:2:4 PCC type B1 using 20mm graded stone aggregate on top 100mm layer and fair finishing without using any extra cement all as specified and directed
29Phase III (Item 18 and 18.01 )
30Three year comprehensive maintenance including operating costs after two years of defect liability period. The service will include the following items: (a) Monthly sim charges for the DCU. The contractor would ensure supply of appropriate SIMs to ensure necessary signal availability. The contractor would change the sim or sim provider as required. In case of network issues, the contractor would liaison with the telecom service providers for necessary resolution. (b) recurring sms charges . the sms would be issued for the payments alert,low balance alarts and disconnection and connectiion alerts. (c) Software AMC. This would include necessary upgradations in the software such as support to the chrome browser changes, android version changes , iOS version changes. These changes happen on frequent basis and the software would support all the changes. (d) changes in the government tariff structure. the government tariff structure changes may required software upgrade. the same would be included in AMC scope of work.
31(e)remote server admin support ensuring adequate database backup,upgradation in the operating system,antivirus update , database upgrade etc.(f) reports developments - adittional reports as needed for the success of the project would be develop. (g) Software installation on any alternate /backup server if required. (h) communication network monitoring and support. (i)configuration of the repaired /replaced hardware in the system. (j) troble shooting and neccessary action to run the system as required. (k)software bug fixing as required.