Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry - 5 Nos. Along With Required Turnkey Works. , Cat ( A ) -Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry - 5 Nos Along With Requ, Raigad-Maharashtra

Tata Memorial Centre has published Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry - 5 Nos. Along With Required Turnkey Works. , Cat ( A ) -Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry - 5 Nos Along With Requ. Submission Date for this Tender is 08-08-2022. Kitchen Equipment Tenders in Raigad Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

31977795
Corrigendum : Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry - 5 Nos. Along With Required Turnkey Works. , Cat ( A ) -Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry - 5 Nos Along With Requ
Open Tender
Indian
Maharashtra
Raigad
08-08-2022

Tender Details

Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry - 5 Nos. Along With Required Turnkey Works. , Cat ( A ) -Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry - 5 Nos Along With Required Turnkey Works. , Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry At Actrec, Kharghar, Maharashtra As Per Tendered Technical Specifications , Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry At Tmh, Mumbai, Maharashtraas Per Tendered Technical Specifications , Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry At Bbci, Guwahati, Assam As Per Tendered Technical Specifications , Supply, Installation, Testing And Commissioning Of Linear Accelerator - Ring Gantry At Civil Hospital, Shillong, Meghalaya As Per Tendered Technical Specifications , Turnkey Works At Actrec , Civil Modification & Interior Works , Architectural & Structural Audit & Design Consultancy: Appointment Of Reputed, Govt Registered Architectural, Structural Designer Having Mre Than 10 Years Of Experiencedto Render Interior & Structural Design Consultancy For Improvemetn And Strucutral Rehabilitation Work As Per Aerbs Recommendation And Interior Works Matching The Existing Design, Considering The Following Scope Of Work. Study Of Available Structural Audit Reports Of The Referred Bunker Study Of The Existing Building Drawings, Structural System And History Of Repairs Visual Inspection The Bunkers Externally And Internally Tapping Exercise With The Use Of Hammer Assessment Of All Structural Elements ( Slabs, Beams, Columns, Rc Walls ) Conducting Necessary Non-Destructive Tests On Concrete Of Existing Bunkers Ultra Sonic Pulse Velocity - 15 Nos. Points / Bunker Re-Bound Hammer - Min 15 Nos. Points / Bunker Conducting Necessary Partial - Destructive Tests On Concrete Of Existing Bunkers Core Cut - 1 No. Points / Bunker Preparation Separate Structural Audit Reports Certifying Feasibility Of Proposedstructural Changes At The Existing Bunker ( Aerb Drawings ) Analysis & Design Of Structural Elements For Accommodating Proposed Structural Changes At The Existing Bunker ( Aerb Drawings ) Considering The Items Mentioned In The Boq. Preparing Ga / Schematic Structural Drawings For Proposed Revisions Getting Client’S Approval On Complete Set Of Ga / Schematic Drawings Sharing Design, Analysis And Ga / Schematic Drawings To Clint Appointed Structural Designer For Vetting And Incorporating Suggested Recomendationa And Implementing The Same Before Issuing The Gfc Drawings. Preparing Working Drawings ( Structural ) For Proposed Revisions Nominal Changes To Accommodate In The Drawing, If Any, As Per Client’S Requirement Visiting Site To Inspect The Execution Work. Total Visits - 3 Nos. Issuing Stability Certificate Only After Completion Of Work To Our Full Satisfaction. , Preparatory Civil , Preparation Of Existing Rcc Wall Or Brick Wall Surface, By Scrapping, Existing Finish / Paint Cleaning The Exposed Concrete Surface To Remove Any Fungus, Loosely Particles, Scales, By A Stiff Wire Brush, Clean By Water Wash The Entire Surface, Exposed The Damaged Concrete Surface With The Help Of Small Chisel And Hammer, Including Collecting, Stacking The Debris At The Site. , Carefully Removing Or Chiseling, Existing Plaster Of Thickness Up To 20 Mm From The Damaged Surface With The Help Of Small Chisel And Hammer Weighing Not More Than 5 Pound, Includingcollecting, Stacking & Carting Away The Debris From The Site Wherever Required As Directed By Site Incharge , Removing Existing Flooring & Skirting Tiles, Along With Backing And Bedding Mortar, Clean The Surface, Lifting & Shifting Debris To Ground Floor & Carting Away The Same Out Of Premises Etc. Complete. , Breaking & Removingexisting Rcc Wall By Mechanical Cutter Without Disturbing The Adjacent Structure, Or Any Other Concretemembers Including Cutting Ofreinforcement Bymeans Of Chisel &Hammervery Carefully, Properplatform To Collect The Debris , Lowering Down & Carting Away The Debris Etc. Complete. ( 30 Mm Thk ) , Demolishing The Existing Brick Wall Along With Plaster Bymeans Of Chisel &Hammervery Carefully, Properplatform To Collect The Debris , Lowering Down & Carting Away The Debris Etc. Complete. , Brick Wall 230 Mm Thick , Brick Wall 115 Mm Thick , Carefully Excavating In Any Kind Of Soil, In Existing Building In Or Out Sides, Including Necessary Shoring / Propping If Required And Including Carting Away The Debris Including Re-Making The Surface In Good As Same As Existing As Directed. Including Dewatering And Necessary Back Filling Complete , Dismantling Of Existing Wooden / Aluminium Doors And Handing Over To The Client As Directed By Pm. , Labor Charges For Shifting The Furniture Remove All The Cupboards And Shift The Same As Directed To Facilitate The Work. , Dismantling Existing Terrace Water Proofing Including Aap Membrane, Cleaning The Roof Top Free From Dust And Dirt With Mechanical Wire Brush Make It Receive New Concrete, Shifing Of Debries From Terrace To Ground And Carting Away Out Of Actrec Campus Complete As Directed And Instructed. , Construction Civil , Leveling And Filling Of Earth Below Foundation And Plinth Level With Quarry Dust Mixed With 5% Cement ( By Volume ) For The Depth Of 150 Mm. After Initial Fill Of 75 Mm Thick, Pour Water With Required Compacting, Watering Make The Sub Soil In Good Condition, Pour Water To Dampen The Dry Mix Enough To Cake Form. Similarly Fill Second Layer Of 75 Mm. Pour Water With Required Compacting After Each Stage Of Layer To Make The Mix Damp Enough To Become Solid Form , Providing And Laying P.C.C. M15 ( 1:2:4 ) Concrete In Foundation As Leveling Course 150 Mm Thick Including Necessary Form Work, Batching, Mixing, Placing, Consolidating Etc. Complete Including Wet Curing For Specified Time Period. , Supplying, Providing And Placing In Position Rmc M25 Reinforced Cement Concrete With 20Mm Downgraded Aggregates For Walls Of Accelerator And Maze Rooms Of Thickness Ranging From 300Mm To 600 Mm At All Levels Including Vibrating, Curing, Providing Construction Joints, Leaving Cut-Outs / Pockets For Placing Of Inserts / Embedment, Etc., Complete, Including Cost Of Providing Steel Form Work With Plywood Lining For All Shapes ( Including Scaffolding, Centering, Etc. ) , But Excluding The Cost Of Providing Reinforcement All As Per Specifications.Include Precautions To Control Heat Of Hydration And Obtaining A Homogeneous Compact Concrete. All Exposed Concrete Surface To Be Of Form Finish Complete As Directed And Instructed. , For Foundations , For Rcc Shielding , For Terrace Shieling , Providing And Fixing High Density ( 7.75Gm / Cc ) Steel Plate To The Existing Concrete Surface Using Holdfast And Hot Press Technique. Also, The Footing Required To Carry Weight Of Steel Plate Would Be Included As Per Approved Design By The Consultant. , Supply &Fabricating And Fixing Reinforcement For Rcc Work With High Yield Strength Ribbed Cold Twisted Tor Steel Of Variousdiametersand All Lengths Of Grade Fe 415 / Fe 500 Conforming To Bis Specification Including Cutting, Bending, Fabricating, Welding, Wastage And Placing In Position According To Drawings And Binding The Reinforcement With The Use Of 16 Gauge Galvanized Binding Wire Of Double Fold And Providing Precast Cement Cover Blocks For Main Reinforcements To Ensure Specified Cover According To Relevant Is Code.The Measurements Will Be In Accordance With Is Code 1200. , Supplying, Drilling / Cleaning Hole And Injecting Chemical Laced Heavy Duty Stainless Steel Anchor Fasteners Widely Used In Strucutral Reahabilitation Works To Support Re-Bars And Strenth Enough To Support Additional Concrete Throug Mechnical Drilling Into Exisitng Concrete Surface. The Application To Be Designed Separately For Rebars As Simply Supported, Moment Or Splice Connection As Per Indian Or European Standard Or Relevant Tested And Accepted Rebar Guidelines. Rebars. Of 20 Mm Dia 200-300Mm Depth. The Appointed Strucutral Designer Should Submit The Detailed Design Analysis Adopted, Complete As Directed And Instructed. , Providing And Doing Brick Work With Locally Available Good Bricks Of Class Designation 50, In Required Thickness Of Walls, In Cm 1: 4, Including Adding Polymer Admixtureat 500Ml Per Bag Of Cement, Racking The Joints, Cleaning, Carting Away The Wastages And Curing , For 230 Mm Thick , For 115 Mm Thick , Providign & Constructing Solid Cement Concrete Block Of M-10 Grade Of Required Thickness In Cm 1:6 With Scafolding, Labour Work At All Heights And Levels Including Wastage, Scafolding Etc Omplete As Directed And Instructed. , Providing And Doing Pressure Groiuting With Waterproofing Compound Or Structural Reapiring Compund As Per Manufacturers Specfication As Directed By The Structral Consultant, Withinsertion Of Pvc Nozzles With Drilling Holes At Regulaer Intervals On Exisit G Rcc Walls, Beams, Roof Slabs Etc Complete As Directed And Instructed. ( Cosnidered For Exsitng Rcc Walls Which Are Developed Cracks. ) , Providing & Applying Plaster At An Average Thickness Of 12 To 15 Mm In Exact Line & Level In The Proportion Of 1 : 4 Cement And Sand Mortar By Manual Mixing, With Addition Of Waterproofing Chemical @ 150 Ml And Harbourite 12 Mm Fine Fibrillated 100% Virgin Polypropylene Fibers @ 150 Gm Per Bag Of Cement Including Curing For At Least 7 Days, Carting Away A Debris, Cleaning ( Note: Waterproof Plaster Considered In Server Room Only ) , Filling Sunken Portion Of Roof With Brick Bat Mixed With Cm 1:6 And Complete As Directed And Instructed , Providing And Laying Integral Cement Based Water Proofing Treatment Including Preparation Of Surface As Required For Treatment Of Roofs, Balconies, Terraces Etc Consisting Of Following Operations: A ) Applying A Slurry Coat Of Neat Cement Using 2.75 Kg / Sqm Of Cement Admixed With Water Proofing Compound Conforming To Is. 2645 And Approved By Engineer-In-Charge Over The Rcc Slab Including Adjoining Walls Upto 300 Mm Height Including Cleaning The Surface Before Treatment. B ) Laying Brick Bats With Mortar Using Broken Bricks / Brick Bats 25 Mm To 115 Mm Size With 50% Of Cement Mortar 1:5 ( 1 Cement : 5 Coarse Sand ) Admixed With Water Proofing Compound Conforming To Is : 2645 And Approved By Engineer-In-Charge Over 20 Mm Thick Layer Of Cement Mortar Of Mix 1:5 ( 1 Cement :5 Coarse Sand ) Admixed With Water Proofing Compound Conforming To Is : 2645 And Approved By Engineer-In-Charge To Required Slope And Treating Similarly The Adjoining Walls Upto 300 Mm Height Including Rounding Of Junctions Of Walls And Slabs C ) After Two Days Of Proper Curing Applying A Second Coat Of Cement Slurry Using 2.75 Kg / Sqm Of Cement Admixed Jointless Cement Mortar Of Mix 1:4 ( 1 Cement :4 Coarse Sand ) Admixed With Water Proofing Compound Conforming To Is : 2645 And Approved By Engineer-In-Charge Including Laying Glass Fibre Cloth Of Approved Quality In Top Layer Of Plaster And Finally Finishing The Surface With Trowel With Neat Cement Slurry And Making Pattern Of 300X300 Mm Square 3 Mm Deep. E ) The Whole Terrace So Finished Shall Be Flooded With Water For A Minimum Period Of Two Weeks For Curing And For Final Test. All Above Operations To Be Done In Order And As Directed And Specified By The Engineer In- Charge : With Average Thickness Of 120 Mm And Minimum Thickness At Khurra As 65 Mm. , Miscellaneous Civil , Providing And Fixing Tiled False Ceiling Of Approved Materials Of Size 595 X 595 Mm In True Horizontal Level, Suspended On Inter Locking Metal Grid Of Hot Dipped Galvanized Steel Sections ( Galvanized @ 120 Grams Per Sqm, Both Side Inclusive ) Consisting Of Main T Runner With Suitably Spaced Joints To Get Required Length And Of Size 24X38 Mm Made From 0.30 Mm Thick ( Minimum ) Sheet, Spaced At 1200Mm Center To Center And Cross T Of Size 24X25 Mm Made Of 0.30 Mm Thick ( Minimum ) Sheet, 1200 Mm Long Spaced Between Main T At 600 Mm Center To Center To Form A Grid Of 1200X600 Mm And Secondary Cross T Of Length 600 Mm And Size 24X25 Mm Made Of 0.30 Mm Thick ( Minimum ) Sheet To Be Interlocked At Middle Of The 1200X600 Mm Panel To Form Grids Of 600X600 Mm And Wall Angle Of Size 24X24x0.3 Mm And Laying False Ceiling Tiles Of Approved Texture In The Grid Including, Required Cutting / Making, Opening For Services Like Diffusers, Grills, Light Fittings, Fixtures, Smoke Detectors Etc. Main T Runners To Be Suspended From Ceiling Using Gi Slotted Cleats Of Size 27 X 37 X 25 X 1.6 Mm Fixed To Ceiling With 12.5Mm Dia And 50 Mm Long Dash Fasteners, 4 Mm Gi Adjustable Rods With Galvanised Butterfly Level Clips Of Size 85X 30X 0.8 Mm Spaced At 1200 Mm Center To Center Along Main T, Bottom Exposed Width Of 24 Mm Of All T-Sections Shall Be Pre-Painted With Polyester Paint, All Complete For All Heights As Per Specifications, Drawings And As Directed By Engineer -In-Charge. , Supplying, Providing And Laying Vitrified Tiled Floor, Wall On Cement Screed Using 600 X 600 Mm Vitrified Tiles. Total Thickness Of Screed And Tiles To Be 30 Mm. Including Lying 125Mm High Skirting All Round. Laid Area Of Wall, Floor And Skirting Measured And Paid , Wall Tiling ( 1.8 Mtr Height ) - , Floor Tiling- , Providing And Fixing Floor Cover With Quick Access To Sub-Floor Utilities Galvanized Steel Chequer Plate For Cabling Modular Factory Finished Widely For Cabel Laying To Withstand Heacy Traffic Movemetn Of Heavy Matirials Thelid Has Been Designed To Withstand For Heavy Loading, All Lids Are Galvanized To Prevent Corrosion, With The Larger Lids Having Substantial Underbracing To Give The Required Strength, Complete As Directed And Instructed. , Providing And Applying Pest And Rodent Control For The Required In All Respect Including Guarantee For The 18 Months , Providing & Layi G Approved Shade Minimum 18Mm Thick Granite Slab In Flooring, Window Cills Etc Over Cement Morter Of 1:4 In Wastage, Labour. Complete As Directed And Instructed. , Provide And Fixing Wall Paneling Up To The Ceiling Height In Radiation Therapy Processing Room, Passage And The Control Room, Using 18 / 12Mm Thick High Quality Plywood Paneling With 4Mm Thick Veneer Finished, Cut To Shape And Size And Fixed To Wall In Straight Line Including All Supports, Screws Etc Complete As Per Direction Of Engineer-In-Charge. , P / F Trap Door In False Ceiling With Acp Panel In Shutter And Frame Fixed Ovwr 50X50x2 Mm Thick Aluminumhollow Swction With Epoxy Sealant As Per Manufacturer Specification Suspended From Ceiling With Suitable Ms Supporting System As Per Site Condition, Including P / F 32Mm Thick Insulation On Trap Door Complete As Directed And Instructed. , Painting , Providing And Applying Oil Based Internal Paint As Per The Manufacturers Specification To The Interior Surface Of Masonry Walls, Underside Of Roof Slabs In Ups Room , Control Room , Passages, Of Approved Colour And Shade With Minimum Two Coats Of Paint. Item To Include Preparing The Surface With Necessary Approved Fillers, Making Good By Touch Up Etc. To Give The Desired Finish , All Complete. Rate To Include Cost Of The Tools, Tackles, Labour, Equipment, Etc. ( Above Wall Tiling ) , Providing And Applying Exteriorpaint Widly Used To Mactch Exisitng Colour Schemewaterproofing Paint, Scrap And Clean The Surface, Applyprimer As Base Coat, Over The Primer Coat Apply Two Coats Or More Paint Approved Color As Per Manufacturers Sepecification All Inclusive Of Labour, Scafolding, Safety Precautions Etc Complete As Directed And Instructed. , Providing & Applyingenamel Paint To Wooden Or Steel Doors, Scrapping, Cleaningthe Surface, Washingandfillingthe Crevices With Approved Paste / Putty As Filling Sealant & Applying The Paint With One Metal Primer Base Coat, Two Top Coats Or More Over The Primer As Per Manufacturers Specification, Including, Labour, Scafolding, Safety Precaution Etc Complete As Directed Nd Instruted. , Furniture , Providing And Fixing 5W X 7H, 38 Mm Thick, Double Leaf Doors In Solid Hard Wood Core ( Phenyl Formaldehyde Bonded ) Flush Shutters Both Faces Commercial Ply Including Ist Class C.P.T.W. Lippings All Around, Lock Plate And Complete Hardware, Finished With Both Sides 1.0 Mm Thk. Laminate As Per Specifications With Grooves And Clear / Frosted Glass As Per Design / Detail Complete In All Aspects With Necessary Heacy Duty Hardware Fixtures To Mactch Exisitng Hardware Fixtures Already Installed To Maintain Unifarmity As Standerdization As Per Per The Furniture Drawing Complete As Directed And Instructed. , Repairing And Alterations To Existing Wooden Doors, By Changing Ss Hinges, Ss Fittings And Shutters To Be 40Mm Thick, Flush Type With Teak Veneers On Both Sides Open Type. Inclusive Of Fixing Heavy Duty Automatic Door A Closure, Two Doors Handles Per Shutter Concealed Night Latch Locking Device, Etc. Complete. , Floor-Mounted Storage Cupboards Within Bhabhatron Room; To Store: Accessories. ( Location: Tomotherapy Room Passage ) Size: 200 Cm Wide X 250 Cm High X 60 Cm Deep ( 19Mm Thick Commercial Grade Ply ) , Open Type Cabinetwith Shelves With 18 Mm Thick High Quality Plywood Laminated With 0.9Mm Thick Melamine Laminates On Both Side Of Approved Colour And Make With 1 Numbers Of Open Type Shelves 210Cmx200x50cm Size With 6 Horizontal And 3 Vertical Partitions Inside The Therapy Room With Partitions For Immobilization Devices, Electron Applicator And Cutouts. Type And Utility Should Match With The Existing Work Station. Provide Necessary Drawer-2 Nos And Shutter-2 Nos As Per The Requirement From The Radiation Physics Division. Edges Should Be Finished By Machine Press. All Finishes And Quality To Be Instructed By The Engineering - In – Charge. , Providing And Supplying Officers Chair With Net Back Revolving Type.The Contractor Shall Furnish One Year Warranty. Economically Designed And Mat Finish. , Changing Room Partition ( 3X4 ) , Electrival & Lv Works , Main Distribution Lt Panelsupply, Erection, Testing And Commisioining Of Cubicle Type Free Standing, Dust And Vermin Proof, Busbar Chambers, Shell Made Of 14Swg Crca Sheet, Doors Made Of 16Swg Crca Sheet With Powder Coating, Compartmentalised, Modular Type Ip 42 Protection, With Support Clamps And Angles Frames As Required As Per The Site Condition. Main Distribution Panel Consisting Of The Following. Incomer : 1 No 250A Tp 25Ka Mccb + Neutral Link With Built-In Adjustable O / L, S / C & E / F. Mccb With Rotary Handle Mechanism. Outgoings : 1No 125A Tp Mccb With Rotory Handile Machanism For Ups, 1No 100A Tp Mccb With Rotory Handile Machanism For Chiller, 1 No. 125 A Tpn Mccb For Hvac & 1 No 63A 25Ka Tpn Mcb With Mechanism For Hvac Unit. Busbar : Busbar Rating Shall Be 1.2 Sqmmper Amphere Formain Bus Bars With Aluminium .Incoming And Outgoing Cables Shall Be Top Of Bottom Entry Only. , Ups Output Panel Boardsupply, Erection, Testing And Commisioining Of Cubicle Type Free Standing, Dust And Vermin Proof, Busbar Chambers, Shell Made Of 14Swg Crca Sheet, Doors Made Of 16Swg Crca Sheet With Powder Coating, Compartmentalised, Modular Type Ip 42 Protection, With Support Clamps And Angles Frames As Required As Per The Site Condition. Ups Output Panel Consisting Of The Following. Incomer : 1No 125A Tp 25K Mccb + Neutral Link With Built In Adjustable O / L, S / C & E / F Mccb With Rotary Handle Mechanism Outgoings : 1Nos. 100A 25Ka Tp Mccb With Rotary Handle Mechanism, & 3Nos. 40A Tpn Mcb For Db Busbar : Busbar Rating Shall Be 1.2 Sqmmper Amphere Formain Bus Bars With Aluminium . Incoming And Outgoing Cables Shall Be Top Of Bottom Entry Only. , Electrical Wiring & Cabling , Distribution Boards Supply, Erection, Testing And Commissioning The Following Mcb Dbdouble Door Type, Ip 42 Powder Coated Comprising Of Fixed Flush With The Wall. The Cost Of Providing Adaptor Box Above The Db Shell Also Be Includeddistribution Box 8 Way 7Segment Mcb Dbi / C -63 Amp Fp Mcb - 1 Noo / G -63 Amp Dp Mcb -3 Nos O / G - 10 / 16A Sp Mcb - 18 Nos Including All Interconnections And Other Accessories Etc As Reqd , Supply, Installation, Testing Andcommissioning 100A Tpn Mccb With Water Proof Enclosure Including Earthing And All Other Required Accessories As Per Site Conditions. For Near Chiller , Supply, Installation, Testing And Commissioning 63A Tpn Mcb With Ms Enclosure Including Earthing And All Other Required Accessories As Per Site Conditions For Ac Outdoor Unit , Lt Cables Supply, Laying, Testing And Commissioning Of 1100V Pvc Insulated Xlpe And Sheathed Armoured Copper / Aluminium Conductor Cables Laid Overms Supports / Cable Racks / Fixing Of Walls Including Clamping The Cable To The Support In All Approved Manner As All , 4R 50Sq.Mm Copper Flexible Cable Truebeam Ups Incoming & Outgoing , 4R 25 Sq.Mm Copper Flexible Cable For Ups Input & Output And Machine , 1C 25 Sq.Mm Copper Flexible Cable For Earth , 4C 16 Sq.Mm Copper Flexible Cable For Chiller , 4C 10 Sq.Mm Copper Flexible Cable For Ac , 4C 6 Sq.Mm Copper Flexible Cable For Db , 12C 0.75Sqmm Copper Flexible Cable With Pvc Conduit For Chiller To Control Panel At Console Room & Warning Light , 1C 6Sq.Mm Copper Flexible Cable For Db Earthing , Cable Terminationssupply, Erection, Testing And Commissioning For The Following Sizes Of 1100V Pvc Insulated Cu / Al. Conductor Cables Including Providing Single Compression Type Cable Gland Copper Sockets For Copper Cables, Crimping Lugs, Insulation Tape Including Gland , 4R 50 Sq.Mm Copper Flexible Cable , 4C 25 Sq.Mm Copper Flexible Cable , 1C 25 Sq.Mm Copper Flexible Cable , 4C 16 Sq.Mm Copper Flexible Cable , 4C 10 Sq.Mm Copper Flexible Cable , 4C 6 Sq.Mm Copper Flexible Cable , Submain Ups And Raw Power Circuits , Supply & Laying Of 2R 2.5Sqmm 1R 2.5Pvc Insulated Frls Multistrand Copper Wire With 25Mm Dia Frpvc Conduit With All Accessories As Required As Per Site Conditions. , Supply & Laying Of4 Run 1.5Sqmm Pvc Insulated Multistrand Copper Wire With 20Mm Dia Pvc Conduit With All Accessories For Emergency Push Button Wiring. , Point Wiring Supply, Installation, Testing & Commissioning Of 3R 1.5Sqmm Pvc Insulated Frls Copper Wire With Frpvc Conduit Along With Modular6a One Wayswitch With Moulded Front Plate Gi Anodised Enclosure And Other Associated Accessories As Required As Per The Site. , Primary Point , Secondary Point , Dimmer Light Point With Dimmer , Sockets , Supply, Installation, Testing & Commissioning Of 1No13a Socket And 1No 6A Switch And With Moulded Frontplate Gianodised Enclosure And Other Associated Accessories In The Work Station As Required As Per The Site Conditions. ( Ups Power ) , Supply, Installation, Testing & Commissioning Of 1No 6 / 16A Socket And 1No Switch And With Moulded Frontplate Gianodised Enclosure And Other Associated Accessories In The Work Station As Required As Per The Site Conditions. , Installation Of Light Fittings , Supply, Erection, Testing And Commissioning Of 2 X 2Led 36 Watts Recessed Mounting Fitting With All Accessories And Interconnecting With 3 R 1.5 Sqmm Pvc Insulated Frls Copper Wire Manufactured, Used Widely Across Campus To Match Exsitng Pattern And Design As Standerdization Complete As Directed Nd Instructed. , Supply, Erection, Testing And Commissioning Ofled 18 Watts Recessed Mounting Down Light Fitting With All Accessories And Interconnecting With 3 R 1.5 Sqmm Pvc Insulated Frls Copper Wire Manufactured, Used Widely Across Campus To Match Exsitng Pattern And Design As Standerdization Complete As Directed Nd Instructed , Supply, Erection, Testing And Commissioning Of Single3w Recessed Fixed Type Led Fitting With Electronics Ballast And All Accessories And Interconnecting With 3 Core 1.5 Sqmm Pvc Insulated Frlscopper Wire And Fixing The Same In The Ceiling. , Data, Voice & Network , Supply, Laying, Testing And Commissioning Of Cat - 6 Utpcable With Fr Pvc Conduit And All Accessories As Required. , Supply, Fixing, Testing And Commissioning Of Information Outlet For Cat-6 Utp Cable Quader Front Plate With Back Box And All Accessories As Required. , Supply, Fixing, Testing And Commissioning Oftelephone Outletfront Plate With Back Box And All Accessories As Required. , Supply, Fixing, Testing And Commissioning Of 4U Communication Rack , Supply, Fixing, Testing And Commissioning Of 6U Communication Rack , Supply & Fixing Of 24Port Patch Panel And 10 / 100 / 1000 Mbps Base T Switch With 24 Port Patch Panel , Supply, Fixing, Testing And Commissioning Of Cat-6 Telephone Cable . , Supply & Fixing Of 24Port Patch Panel And 10 / 100 / 1000 Mbps Base T Switch With 24 Port Patch Panel , Earthing , Supply And Installation Of 4 Way Earth Bus With Accessories As Required , Supply, Installation, Testing & Commissioning Of Copper Earthing With 600X600x3mm Copper Plate And 25X6mm Copper Flat Bar Confirmingis:3043 With The Provision For Watering & Inspection Chamber. , Perforeated Type Gi Cable Tray , Supplying, Fabricating, Erecting And Connecting The Following 1.6Mm Thickness Gi Perforated Type Cable Trays With Necessary Supports, Tees, Elbows, Bends, Bolts And Nuts And Any Other Associated Accessories To Complete The Job.-150Mm ( Wide ) X 50Mm ( Collar Height ) , Supply & Fixing Of 50 Mm Pvc Pipe For Cc Tv, Irm And Speaker Cable Pulling , Warning Light Supplyfixing Testing & Commissioning Of Warning Light, Led Green, Yellow, Red, + Power Supply . , Emergency Stop Switch Supplyfixing Testing & Commissioning Of Emergency Switch, 3 No. No, Element With Box , Supply Fixing & Commissioning Of Lmo Switch Indicator &Buzzer, Ss Plate With All Accessories , Supply, Laying, Testing And Commissioning Of 1100V Pvc Insulated Xlpe And Sheathed Armoured Copper / Aluminium Conductor Cables Laid Overms Supports / Cable Racks / Fixing Of Walls Including Clamping The Cable To The Support In All Approved Manner As All , 4C 10 Sq.Mm Copper Flexible Cable For Ac , 1C 6Sq.Mm Copper Flexible Cable For Db Earthing , Supply, Installation, Testing And Commissioning 63A Tpn Mcb With Ms Enclosure Including Earthing And All Other Required Accessories As Per Site Conditions For Ac Outdoor Unit , Supply Testing & Commissioning Of Panasonic Make Telephone Instument With Caller Id , Cctv The Camera Should Be Compitable With Exisitng Cctv System As Standerdization, Sample Must Be Got Approved Before Supply In Bulk. , 16 Channel Dvr Ful Hd , Hd Outdoor Bullet Camera , Hd Dome Camera , Wd Hard Disk ( Dvr ) 1Tb , Moniter ( 19.5Inch ) , Camera Power Supply ( 10Amp ) , Sdmi Cable ( 3 Meter ) , Bnc Conector , Dc Pin Conector , Wire 3+1 ( Heavy Wire ) Per / Meter , Junction Box For Camera , Tack / Tack Back System , Supply, Fixing, Testing & Commissioning Of Tack / Tack Back Systems Comprises Of Console With Mike ( Inbled Amp. ) Ceiling Speaker Or Wall Mount Speaker - 1 No. , Supply And Laying Of Two Core Screened Cable , Audio System For Playing Soft Music Inside The Treatment Room, Control Console, Patient Waiting Area Also To Be Supplid. , Supply Testing Commissioning Of Token Display System , Firefighting Works -All Devises Should Be Compitable With Exisitng System As Standerdization, Sample Must Be Got Approved Before Supply In Bulk. Supply, Installation, Testing & Commissioning: , Smoke Detectors Bunker - 8 Nos; Maze - 2 Nos; Ups - 2 Nos. , Response Indicator. , Manual Call Bell , Hooter , Cu. Ar. 1.5 Sq.Mm. Cable , Fire Extinguisher - 5Kg Bunker - 4 Nos; Ups - 1 No. , Hvac Works , Supply, Installation, Testingandcommissioningofaircooledscroll Chilling Machines Having Actual Capacity Of 38.4 Tr At Chilled Water Inlet / Outlet Temperature Of 12.0 Deg. C / 7 Deg. C Having Evaporator Fouling Factorof0.000018M2.K / W Suitable For Operation On Refrigerant R- 407C Or Eco Friendly Gascomprising The Following Complete As Required. Chiller Capacity Should Not Less Than 38.4Tr ( Followingsafetyfactorwillinbuiltwithchillerunit-Sppr, Under / Over Load Protection, Phase Reverse Protection, Hp / Lp Trip Signal Interlocking, Auto / Manual Test Mode Facility / Run Time Equalization For Multiple Compressor, Password Access For Authorized Handling, Pt-100 Rtd Sensor For Chiller Unit, Interlocking For Chilled Water Flow Swtich ) 135Kw ( 38.4Tr ) , Air Handling Units Supply, Installation, Testingandcommissioningoffactorybuiltfloor Mounted-Doubleskintypehorizontal / Verticalairhandlingunits Made Of43+2Mm Thick Panels Consisting Ofpreplasticizedg.I. Casing Of Thickness 0.8 Mm Outside Layer And 0.8 Mm Plane Gi At Inside Layer With Cfc-Free P.U. Insulation Of Density 42 ( +5% ) Kg / M3 Factory Injectedbetweenthem Byinjectionmouldingmachine, Completewith Didwbackwardcurvedcentrifugalfanwithvfdstarterdriven, Suitablefor50mm Wgstaticpressure, Coilsectionwithaluminium Blue Finned Copper Tubes ( Tubes Thickness Not Less Than 0.41Mm ) Cooling Coil Of 6 Row Deep, Filter Section With 50Mm Thick Washable Synthetic Type Air Pre Filters, Belt Drive Package With Tefc Drive Motor Suitable To Operate At 415 ± 10% Volts, 50Hz, 3 Phase Ac Supply, Motor Should Be Compatible With Vfd, Drain Connections, Stainless Steel ( 18G ) Drain Pan, Necessary Vibration Isolation Pads & Accessories:And Piping As Per The Norms Duly Insulated With Requires Thick Nitrile Rubber. Ahu Starterpanelshouldhavevfdandvfdbypassoption, Should Have Plc Based Control And Plc Bypass Control For Manual Mode. Panel Should Provide With Heater Control. Note:- Temp And Rh Sensor To Be Included With Control Wiring. Noadditional Cost Will Be Given For The Same. 30.5 Tr -12200Cfm-50Mm Tsp ( 1 Working +1 Standby Motor ) , Supply, Installation, Testing And Commissioningof Fcu 2 Tr , Supply, Installation, Testing And Commissioningof Primary Pump-102Usgpm-15M Head. , Supply, Installation, Testing And Commissioningof Expansion Tank ( 100 Ltr ) With Air Separator, Air Vent And Pressure Maintaining Pumping Unit. , Supply, Installation, Testing And Commissioning Of Chilled Water Ms Pipe With Supports, Hardware Etc. , 80 Mm Dia With 32Mm Nitrile Insulation With 26G Al Cladding , 25 Mm Dia With 19Mm Nitrile Insulation With 26G Al Cladding , Pvc Drain Pipe Having Pressure Holding Of 8Kg / Cm2drain Piping Complete With All Accessories With 9Mm Nitrile Rubber Insulation With Supports , 32Mm Dia , 25Mm Dia , Supply, Installation, Testing And Commissioningof Valves & Guages As Follows With 32Mm Nitrile Insulation For Chw Line: , Butterfly Valve , 80Mm Dia , 25Mm Dia , Y-Strainer , 80Mmdia , 25Mm Dia , Flexible Connection80mmdia , Nrv Valve80mmdia , 3-Way Valve , 80Mm Dia , 25Mm Dia , Ball Valve 25Mm Dia , Airvent With Ball Valve , Temperature Gauge , Pressure Gauge , Sitc Of Gi Sheet Metal Rectangular Duct With Support, Hangers, Rods, Frames, Anchor Fastners, Etc. , 24 Gauge , 22 Gauge , Supplying & Erecting Accoustic Insulation Lining On The Ducts Having 15Mm Thick Open Cell Nitrile Rubber Armasound To Reduce Noise , Supplying & Erecting Thermal Insulation On The Ducts Having 19 Mm Closed Cell Nitrile Rubber. Exposed Duct Should Cover With 26G Al Cladding , Sitc Of Canvass Connection For Ahu Machines , Sitc Of Control Cabling In Between For Fcu And Ahuunits , Sitc Of Fire Damper , Sitc Of Fire Actuator , Sitc Of Supply / Return Air Grill With Vcd , Supply, Installation And Commissioning Of Duct Strip Heaters With Thyristor Control Of Necessary Capacity Made Of Ss Strip ( Finned / Finless Tubular Type ) Complete With Rh Sensor, Industrial Grade Heating Elements, Protection Against Overheating, On / Trip Status, Air Flow Switch, Grounding Terminals, Terminals For Power & Control, Intermediate Control Wiring For Integration Etc. For Full Automation Working To Achieve Rh Level Of 40-60% Non-Condensing In The Treatment Room. ( Rating / Capacity Considered To Be Specified By The Bidder ) , Dismantling Of Existing Hvac Systems - Ahu, Piping, Valves , Ducting / Copper Piping / Drain Piping / Units / Hi Wall Split Unit All Complete As Per Instruction As Nad Directed By Oic-Es , Supply And Fabrication Of Ms Structure Include One Coat Primer And One Coat Enamal Paint. , Dismantling & Re-Installing Exisitng Ac Chiller Plant Including Its Roofing At Terrace Including Disconnection Of Chilled Water Ms Pipe Lines, Extending Same Till New Location, With Required Insulation And Necessarru Hardware As Directed And Instructructed. , Turnkey Works At Tmh Mumbai , Civil Works :- , Labour Charge Only For Removing And Re-Fixing Available Door Shutter With Necessary Modification Including Cutting The Existing Shutter Providing Leeping Patti All Around The Shutter If Required Including Removing And Refixingavailbale Old Hinges, Mortice Lock, Tower Bolts Ect. Fixing Aligning The Door Shutter In Proper Plumb And Level Etc. Complete Allonly Fixing Available Door Shutter With Necessary Repairing , Removing Existing False Ceiling Of Any Material And Any Size With All Necessary Allied Works, Removing Out Debris Out Of Tmh Premises , Labour Charges Only For Carefully Removing And Taking Out Existing Wooden Partitions ( Partly Glazed, Partly Panneled Or Fully Panneled With Shutters Glazing Etc. At All Floor Levels And Locations Including Removing The Existing Mongery Fittings Fixtures Locking Arrangement And Handling Over The Same To T.M.C All Complete As Directed , Providing Wood Work With 1St Class C.P. Teak Wood In Frames For Doors Windows, Ventilators, Air-Condition Frames, Clear Story Window, False Ceiling And Partitions Etc.Wrought Framed And Fixed In Position Including Applying One Coat Of Approved Wood Primer To The Exposed Surfaces And Tow Coats Of Bitumastic Paint To The Surface Of Wood In Contact With Masonry / Concrete Etc.Complete. In Frames Of Doors, Windows, Ventilators And Clear Storey Windows Etc. Fixed With M.S Hold Fast Of Size 40X3mmx150mm Long Bend To Shape And Embeded In Cement Concrete 1:2:4. , Providing And Fixingapproved Quality Machine Pressed Phenol Formal Dehy De Bonded Commercial / Marine Ply Wood Of Approved Size And Fixing The Same With Necessary Nails / Screws / Adhesive In Partition Cupboard Shelves / Ktichen / Cabinets / Flush Doors Etc. At All Floors And Locations In Quantities As Required At Site In Following Thickness Including 6 Mm Thick T.W.Lipping Patti At All Exposed Edges With Nails / Screws / Hardwares / Adhesive Wastage In Cutting, Transportation Etc. Complete All.Commercial Ply19mm Thick Ply , Providing And Fixing 1.0Mm Thick Laminate Of Required Colour Over Existing Surfaces Along With The Adhesive All As Required Specification Design Etc. Complete As Specified. 1.00 Mm Thick , Providing And Fixing Cabinet Made Up Of 19 Mm. Commercial Ply For Top, Bottom, Sides And Shelves And 6Mm Commercial Ply For Back Side.Door Shutter Made Up Of 19Mm Thick Commercial Ply And Outer Surfaces And Top Of Shelves For Open Type Cabine Should Be Laminated With 1.0Mm Thick Plastic Laminate Sheet Of Required Colour Including All Brass Fittings Such As Hinges, Tower Bolts, Ball Catches, Stopper, Handle, Knobs As Per Shown In Drawing Etc.And All Exposed Edges Lipping With 6Mm Laminate Finishthick T.W.Lipping Patti.Locking Arrangement Withmultipurpose Lock Etc. All Inside Areas Shall Be .80Mm Thick Approved Colour Laminate Etc. With Inner Side 0.8Mm Thick Laminatewith Shutter , Providing Making And Supplying Computer Table Made Out Fo 19Mm Commercial Ply For Table Top, Mounted On The Vertical Side Fo 19Mm Commercial Ply And Cabinet Made Out Of 19Mm Commercial Ply For Sides, Shelves And Shutters Making Concealed Monitor Arrangement By Providing 8Mm Thick Clear Glass On Table Top Of Required Size With Edge Polishasshown In Drawing Drawer And Wooden Key Board Drawer With Heavy Sliding Channels, Withhandle For Shutter, Cable Manager Drawers All Edges Shall Be Lipped With 6Mm Thick T.W. Lipping Patti. All Exposed Faces Should Be 1.0Mm Thick Laminate And Non Laminated Area Should Be French Poll-Shed Including Cost Of Other Materials Labour Etc. As Per Drawing.Computer Table With All Inner Surface With 0.8 Mm Thick Laminate , Providing And Fixing Tiled False Ceiling Of Specified Materials Of Size 595X595 Mm In True Horizontal Level, Suspended On Inter Locking Metal Grid Of Hot Dipped Galvanized Steel Sections ( Galvanized @ 120 Grams / Sqm, Both Side Inclusive ) Consisting Of Main T Runner With Suitably Spaced Joints To Get Required Length And Of Size 24X38 Mm Made From 0.30 Mm Thick ( Minimum ) Sheet, Spaced At 1200 Mm Center To Center And Cross T Of Size 24X25 Mm Made Of 0.30 Mm Thick ( Minimum ) Sheet, 1200 Mm Long Spaced Between Main T At 600 Mm Center To Center To Form A Grid Of 1200X600 Mm And Secondary Cross T Of Length 600 Mm And Size 24X25 Mm Made Of 0.30 Mm Thick ( Minimum ) Sheet To Be Interlocked At Middle Of The 1200X600 Mm Panel To Form Grids Of 600X600 Mm And Wall Angle Of Size 24X24x0.3 Mm And Laying False Ceiling Tiles Of Approved Texture In The Grid Including, Required Cutting / Making, Opening For Services Like Diffusers, Grills, Light Fittings, Fixtures, Smoke Detectors Etc. Main T Runners To Be Suspended From Ceiling Using Gi Slotted Cleats Of Size 27 X 37 X 25 X1.6 Mm Fixed To Ceiling With 12.5 Mm Dia And 50 Mm Long Dash Fasteners, 4 Mm Gi Adjustable Rods With Galvanised Butterfly Level Clips Of Size 85 X 30 X 0.8 Mm Spaced At 1200 Mm Center To Center Along Main T, Bottom Exposed Width Of 24 Mm Of All T-Sections Shall Be Pre-Painted With Polyester Paint, All Complete For All Heights As Per Specifications, Drawings.Gi Metal Ceiling Lay In Plain Tegular Edge Global White Color Tiles Of Size 595X595 Mm, And 0.5 Mm Thick Made Of G I Sheet Having Galvanizing Of 100 Gms / Sqm ( Both Sides Inclusive ) And Electro Statically Polyester Powder Coated Of Thickness 60 Microns ( Minimum ) , Including Factory Painted After Bending. , Providing Fixing Door Frame And Shutter Side Hung To Consist Of Partly Glazed Partly Panneled / Fully Panneled / Fully Glazed With 5.5Mm Thick Glass Sheet And Quality Plain Or Frosted Of Bajri Glass Fixed With Two Way Pvc Lining / Rubber Gasket To Ensure Notes Tightness And No Rattaling And Panneling With 12Mm Thick Nova Pan Or Ancholam Finished On Both Side As Required Using Extruded Alumimium Section Forshutter Frame24254545mm Satin Finish Anodized Including P / F Push-Pull Plates Handles And Heavy Duty Fittings Like Tower Bolts, Motice Lock With Keys Hinges Of 5 Inch Or 6 Inchas Per Requirement Hydraulic Door Closer / Floor Spring Of Suitable Capacity Etc Complete.With Powder Coated , Painting Work Providing & Applying One / Two Coats Of Primer Two Coats Of Paint As Mentioned Below First Quality Paint To The Required Colour Scheme And As Per Manufacturers Instructions / Specificationsto The Walls, Beams, Columns, Ceilings, Partitions, Doors Etc. Including Removing Existing Paints , Nails , Screws , Battens Etc. And Thoroughly Scrapping The Surface With Sand Papers Filling Up Crevices And Levelling With Putty To Obtain Smooth Surface Ie. Complete Surface Preparation Etc. Complete As Directed To The Entire Satisfaction Of Engineer In-Charge. , With Two Coats Of Primer And Two Coats Ofpaint , Using Luster Paint , Using Synthetic Enamel Paint ( Oil Paint ) , Providing And Applying Three Coats Of White Wash To Ceiling Etc. Including Removing Existing Nails , Screws , Battens Etc. Andthoroughly Scrapping The Surface With Sand Papers, Filling Up The Crevices And Levelling With Putty If Necessary Adding, Required Quantity Of Adhisive To Obtain Good Finish To Surface Complete As Directed. , Civil Work Breaking:Dismantling Carefully The Existing Damaged Cracked Serviceable Tiles / Slabs / Clay Tiles / Marble Slab / Granite Slab / Kota Stone / Tandur Stone / Shahabad Stone And All Types Of Flooring In Flooring Etc. Including Removing The 20Mm Thick Bedding Of Cement Mortar Stone Grit Or Brick Bat Coba Etc. At All Floors & Levels Including Disposing / Taking Away The Debris Outside The Premises & Disposing As Per The Guidlines Of Statutory Authoritised. ) , Granite Tiles:Providing & Laying 8 To 10Mm Thickgranite Tile Of Size 300Mm X 600Mmfor Flooring / Dado / Skirting Laid Over A Bedding Of C.M. 1:335Mm Thick In True Plain Line & Level Curing. Finishing The Joints Etc. Complete.In Flooring & In Dado / Skirting , Electricalsworks , Point Wiring :- Point Wiring For Light / Fan / Bell With Isi Mark 3 X 1.5 Sq.Mm ( P+N+E ) . Frls Pvc Insulated Copper Conductor Ofmake In Surface / Recessed Heavy Class Pvc Casing Capping / Conduit With Modular Switch - Ceiling Rose / Batten Holder / Slanting Holder Boxes Etc. With Circuit Labling / Marking / Ferruling Complete. , Primary Point Upto 4 Mtrs Length , Primary Point Length 4 Mtrs To 7 Mtrs , Primary Point Length7 Mtrs To 10 Mtrs , Secondary Point Extending From Primary Point Upto 4 M , Dismantling:- Carrying Out Assigned Jobsof Dismantling The Existing Light, Fan, Bell, Independent Plug Point Wiring Of All Types With Accessories And Cable / Switchgear , Supply & Installation Of Power Point ( Inclusive Of 2No.Of 15 Amp Switch Socket, Back Box, Face Plate & Wiring, Accesories Etc ) , Supply & Installation Of Power Point ( Inclusive Of 1 No.Of 15 Amp Switch Socket, Back Box, Face Plate & Wiring, Accesories Etc ) , Telephone Point :- Supplying And Instllation Of Telephone Point Inclusive Of Telephone Instrument, Telephone Socket With Back Box , Plate, Laying Two Pair0.5 Mm Gauge Unarmoured Telephone Wire D.O.T Approved, Make Through Conduit / Casing Caping. , Supplying And Laying Of 2 Core Audio Speaker Cable Throughconduit / Casing Caping / Cable Tray. , Sub Mainsmains :- Providing Heavy Duty Pvc Casing-Caping / Conduit, Supplying And Erecting Mains With Copper Conductor Pvc Insulated Frls Of 1100 V Ac Grade Wire With Circuit Labling / Marking / Ferruling Complete. , 2 X 1.5 Sq Mm -+ 1.5Sqmm Earth Wire , 2 X 2.5 Sq Mm -+ 1.5Sqmm Earth Wire , 2 X 4 Sq Mm -+ 2.5 Sqmm Earth Wire , Light Fixturessupply Of Led Fixtures - Surface / Suspended / Recessed Mounted Luminaires , Led Light Fixture Duraslim 15 Watt, Round6500k, , Led Light Fixture Full Glow 2Ft X 2Ft 6500K , Distribution Boards Supply, Installation, Testing & Commissioning Dbs , Spn Db With Metal Door, 12 Way, Ip 43, Inclusive Of Required Rating Mcb, Rcbo , Tpn Db With Metal Door, 8 Way, Ip 43, Inclusive Of Required Rating Mcb, Rcbo , Hvac Works , Hvac Works ( Low Side ) Fan Coils Units ( Ceiling Suspended Type / High Wall ) Supply, Installation, Testing And Commissioning Of Gi Powder Coated Horizantal Ceiling Suspended / High Wall Fan Coil Units Complete With Fan, 3 Speed Motor, 3 Row Deep Cooling Coil, 5 Mm External Static, Filters , Copper Connection, Canvass Connection ( If Required ) , Supporting Arrangement, Electrical Wiring Etc. The Complete Fan Coil Unit Shall Be In Line With The Standard Specification. The Capacity Of Fan Coil Units Shall Be As Follows. Proper Supporting System For Fcu To Be Provided & Will Be In Contractors Scope. 800 Cfm ( 2 Tr ) , Hvac Works ( Low Side ) :-Supply & Installation Of 2 Wayvalve , Hvac Works ( Low Side ) :-Supply & Installation Of Digital Thermostat Including All Accessaries , Mountings, Wiring Between Thermostat & Unit, Terminations Etc. , Supply, Installation Testing And Commissioning Of The Following Ball Valves Without Strainer Duly Insulated As Per Specifications And Drawings. It Shall Be Bronze Forged Body Construction With Chrome Plated Bronze Ball And Handle Of Stainless Steel Constructions. 25 Mm Dia , Supply, Installation Testing And Commissioning Of The Following Ball Valves With Strainer Duly Insulated As Per Specifications And Drawings. It Shall Be Bronze Forged Body Construction With Chrome Plated Bronze Ball And Handle Of Stainless Steel Constructions. 25 Mm Dia , Hvac Works ( Low Side ) :Supplying, Laying, Fixing, Testing And Commissioning Of Following Thickness Closed Cell Elastrometric Nitrile Rubber Of Class O Applied By Suiatable Adhesive, As Per Specifications And As Required Complete In All Respect-32Mm, Insulation Work Involve Removing Of Old Insulation On Chilled Water Pipeline And Installing New Insulation. , Hvac Works ( Low Side ) :-Providing And Fixing In Position The Following Upvc Heavy Class Cut To Required Length And Installed With Screw Joints Including The Necessary Fittings, Supporting Arrangements Like Clamps Etc. ( Bends, Tees, Unions, Sockets Etc ) Duly Insulated With Class O 6 Mm Thick Nitrile Rubber Insulation As Per Specifications. 25 Mm Dia , Hvac Works ( Low Side ) Supply, Installation, Balancing And Commissioning Offabricatedat Site Gss Sheet Metal Rectangular / Round Ducting Complete With Neoprene Rubber Gaskets, Elbows, Splitter Dampers, Vanes, Hangers, Supports Etc. As Per Approved Drawings And Specifications Of .63Mm Thickness Complete As Required. , Hvac Works ( Low Side ) Supplying, Installing Of External Thermal Insulation On Ducts Of Al Faced / Closed Cell Nitrile Rubber Insulation With Anti Microbial Properties With Duct Insulation With Density 40-55 Kg / Cum Complete As Per Specifications. •Thermal Conductivity Of Insulation Material Shall Not Exceed 0.035 W / ( M.K ) & R Value As Mentioned In Ecbc -2008 At Mean Temperature Of 24 Degree C As Per Astm C518. . Class-O Insulation With Aluminum Foil. • Moisture Diffusion Resistance Factor Or ‘?’ Value Of Insulation Material Shall Be Minimum 7, 000 Without Any External Barrier As Per En 13469. • The Insulation Material Shall Have Fire Performance Such That It Passes Class 1 As Per Bs476 Part 7 For Surface Spread Of Flame And Also Passes Fire Propagation Requirement As Per Bs476 Part 6 To Meet The Class ‘O’ Fire Category. 25 Mm Thick. , Hvac Works ( Low Side ) Supplying, Fixing Testing Commissioning Of Supply Air Diffusers Of Powder Coated Aluminium With Aluminium Volume Control Dampers With Anti Smudge Ring & Removable Core. , Hvac Works ( Low Side ) Supply, Installation, Testing & Commissioning Of Thermal Insulated Flexible Duct Of Following Sizes Duly Supported At Regular Interval As Per Site Requirement Etc. Complete As Required As Per Specifications.-300 Mm Dia , Hvac Works ( Low Side ) Supplying, Fixing Testing Commissioning Of Return Air Diffusers Of Powder Coated Aluminium Without Aluminium Volume Control Dampers With Anti Smudge Ring & Removable Core. , Hvac Works ( Low Side ) Supply, Installation, Testing And Commissioning Of Gi Volume Control Duct Damper Complete With Neoprene Rubber Gaskets, Nuts, Bolts, Screws Linkages, Flanges Etc, As Per Specifications , Dismantling, Removing Of Oldflexible Ducting , Pipelne, Insulation, Fcu ( 3Nos ) , Griil, Diffuser Etc Loading, Unloading, Lifting Shifting, Etc And Disposing The Same Outside Tmh Premises With Proper Housekeeping Complete In All Respect , Networking Supply, Installation, Testing And Commissioning Of Lan Cable Room No. Hbb-B-002-4 Nos. Of Network Points, Room No.-Hbb- B-003-2 Nos. Of Network Points. Total Networks Points. = 6 Nos. , Turnkey Works For Site Preparation Of Gmc, Shillong , Civil Shielding Works , Complete Dismantling Works Inside Bunker And Console Room, Of Plain Cement Concrete, Flooring, Brick Work, False Ceiling To Any Depth And Width, At All Levels Below & Above Ground Level Of Any Shape, Removal Of Debris, Disposing The Same Away From The Site, Loading And Unloading, Making The Surface Good Etc. Complete. Rate Shall Include For Dismantling Of Plain Cement Concrete / Brick Work By Manually / Mechanical Means With Necessary Tools And Plants, Scaffolding, Water And Power Charges, Cleaning The Surface, Preparation Of Surface Etc. Rate Shall Include For Stacking The Serviceable Materials And Disposing The Unserviceable Materials / Debris Away From The Site Premises By Mechanical Means Including Loading, Unloading, Clearing The Site Etc. Complete, As Directed. ( Measurement Is Done For Floor Area Only ) Demolishen Of The Walls Are As Per Approved Drawings , Providing And Casting In Situ Cement Concrete M-25 ( Concrete Density 2.35 Gms / Cc ) Of Trap / Granite / Quartzite / Gneiss Metal For R.C.C. Walls As Per Detailed Designs And Drawings Or As Directed Including Centering, Formwork, Cover Blocks Compacting And Roughening If Special Finish Is To Be Provided And Curing Complete. ( Excluding Reinforcement ) . With Fully Automatic Micro Processor Based Plc With Scada Enabled Reversible Drum Type Concrete Mixer. With Natural Sand. For Concrete Shielding And Bunker Door Wall As Per Aerb Approved Drawing , Providing And Applying Integral Crystalline Slurry Of Hydrophilic Innature For Waterproofing Treatment To The Rcc Structures Like Retainingwalls Of The Basement, Water Tanks, Roof Slabs, Podiums, Reservior, Sewage & Water Treatment Plant, Tunnels / Subway And Bridge Decketc., Prepared By Mixing In The Ratio Of 5 : 2 ( 5 Parts Integral Crystalline Slurry : 2 Parts Water ) For Vertical Surfaces And 3 : 1 ( 3 Parts Integralcrystalline Slurry : 1 Part Water ) For Horizontal Surfaces And Applyingthe Same From Negative ( Internal ) Side With The Help Of Synthetic Fiberbrush. For Bunker And Console Area , Civil Interior & Furniture Works , 50Mm Thick Cement Concrete Flooring Finished With 3Mm Thick Vinyl Flooring Location: Ups Room , 600Mmx 600Mm Vitrified Tiles With 100Mm Matching Tile Skirting. Providing And Laying Approved Quality, Colour, Design And Shade Fully Homogeneous 600 X 600 Mm ( Thickness To Be Specified By The Manufacturer ) Vitrified Tile Flooring ( Marbonite Or Granamite, Confirming To Is Code 15622 With Water Absorption Less Than 0.08% ) Flooring In Pattern As Detailed In Drawing Or As Directed By The Institute And Grouted With Matching Colour Approved Quality Readymade Grout, Curing, Cleaning Etc To Required Line Level Etc. All Complete At All Leads, Lifts And Heights To The Entire Satisfaction Of The Institute. Providing And Fixing 2-3Mm Thick Pop Protection Over Polythene Covering Sheet To Flooring Areas Till Handed Over And Cleaning, Etc All Complete As Per Drawings & Specification. ( Linac Room And Console Room ) , Two Coats Of Plastic Emulsion Paint Over 2 Coats Of Wall Putty Including Primer. Location: ( Ups Room And Outside Shielding Wall ) , Providing And Laying High Quality And Density Type Vitrified Wall Tile Of 1200 Mm Height In Radiation Therapy Room And The Control Room, Laid On 20Mm Thick Base Of Cement Mortar 1:3 ( 1 Cement : 3 Coarse Sand ) Or As Per The Appropriate Mortar Rquired To Hold The Wall Tiles Together, In All Shapes & Patterns Including Grouting The Joints With White Cement Mixed With Matching Pigments Etc. Complete As Per Direction Of Engineer-In-Charge Upto False Ceiling Level. Location: ( Linac And Control Console Room ) , Pest And Rodent Control From Pci Location: Linac Room, Control Console And Ups Room , Acoustical Tile For Ceiling With Light Weight Insulating Material Of High Quality Supported On Grid Or Finished Seamless With Support Above Ceiling. To Be Finished With White Paint Or Powder Coated With White Paint, If Metallic. The False Ceiling Panels Should Be Of Reputed Brands. Location: Linac Room, Control Console And Ups Room , Constructing Cable Trenches 300Mm Wide And 300Mm Deep As Per The Drawings , Preparing And Fixing Openable Covers Of Vitrified Tiles Fixed In The With Ability To Sustain A Load Of 200Kgs To Be Placed On The Trenches 300 Mm Wide, All Works Complete , Furniture , Revolving Chairs Height Adjustable, Medium-Back With Hand-Rest , Skylight , Wall-Mounted Storage Cupboards Within Linac Room; To Store: Dosimetry & Qa Items, Linac Accessories. ( Location: Treatment Room ) . Size: 2M Wide X 1.2M High X 0.4M Deep ( 19Mm Thick Marine Grade Ply ) , 40Mm Thick Plywood Door With Teak Wood Frame, Including All Accessories. Size 2M X 2.2M , Wooden Tables For Workstations. Size: 3 M Wide, 0.6 M Deep And 0.8 M High ( 16Mm Thick Marine Grade Ply ) For: Console , Wooden Tables For Workstations. Size: 4 M Wide, 0.6 M Deep And 0.8 M High ( 16Mm Thick Marine Grade Ply ) For: Tps , Plumbing Works , Supply & Installation And Commissioning Of Chiller Inlet & Outlet Equipment Flange & Union , Supply & Installation And Commissioning Of Pressure Gauge , Supply & Installation And Commissioning Of Thermometer , Supply & Installation And Commissioning Of Auto Air Vent , Supply & Installation And Commissioning Of Drain Valve , Supply & Installation And Commissioning Of Chiller Water Copper Piping 15 / 8 18 Gauge With Insulation 19Mm Thick , Supply & Installation Of Chiller Water Pipe Nylon With Wire Mesh Hss Slive Flexible 40Mm With Insulation 13Mm Thick , Supply & Installation And Commissioning Of Ball Valves 40 Mm , Supply & Installation And Commissioning Of Y Strainer 40 Mm , Supply & Refilling Of Dm Water , Supply & Installation And Commissioning Of Water Panel With 2 Nos Pressure Gauge And 5 Nos Valve, 2 Nos Thermometer , Hvac Works , Ductable A / C Units Along With Low Side Works ( Up To 50 Running Meters ) For Complete Installation & Commissioning Of Ac. Supply , Installation , Testing & Commissioning Of Aircooled Ductable Split Air Conditioner With Ceiling Suspended Idu And All Standard Fitting, Gss Sheet Metal Duct ( Insulation Using Resin Bounded Glass Wool With 7 Micron Aluminium Foil ) For Air Distribution 22 / 24 G, Idu Ss Drain Pan As Per Specification Complete With Suitable Capacity Drive Motor , Aircooled Condensor With All Accessories , Hermetically Sealed Scroll Compressor, Electronic Microprocessor Pendant Controller With Digital Display, First Charge Refrigerant Gas, Vibration Isolator Pads, Structural Support For Fixing Idu / Odu, Safety Devices Including Thermal Protector, Pressure Release Valve , Overload Relay Single Phase Preventer Etc, Power Wiring And Control Cabling ( Indoor To Outdoor ) , Thermostat Wiring, High-Low Pressure Cut Out Suitable For 3 Phase 440V Supply Etc Complete As Required. ( Warranty - 3 Years ) For Bunker And Console 5.5 Tr Working And 5.5Tr Stand-By , Split Units With Required Copper Piping And Drainage Outlet Lines ( For Ups Room 2Tr Working And 2Tr Stand-By ) With Auto-Timer Switch , 2-Litre Capacity Dehumidifier ( For Bunker - 2, Console - 1 ) , Electrical Works , Main Lt Panel Supply, Erection, Testing And Commisioining Of Cubicle Type Free Standing, Dust And Vermin Proof, Busbar Chambers, Shell Made Of 14Swg Crca Sheet, Doors Made Of 16Swg Crca Sheet With Powder Coating, Compartmentalised, Modular Type Ip 42 Protection, With Support Clamps And Angles Frames As Required As Per The Site Condition. Main Distribution Panel Consisting Of The Following. Incomer : 250A 3P Mccb With Rotary Handle Mechanism - 1No With Necessory Interlocking Arrangement Out Goings : 100A Tpn Mccb With Rotary Mechanism - 2 Nos. 63A Tpn Mccb With Rotary Mechanism - 3 Nos. 40A Tpn Mccb With Rotary Mechanism - 1 Nos. Incoming And Outgoing Cables Shall Be Of Top Or Bottom Entry Only. , Ups Output Panel Board Supply, Erection, Testing And Commisioining Of Cubicle Type Free Standing, Dust And Vermin Proof, Busbar Chambers, Shell Made Of 14Swg Crca Sheet, Doors Made Of 16Swg Crca Sheet With Powder Coating, Compartmentalised, Modular Type Ip 42 Protection, With Support Clamps And Angles Frames As Required As Per The Site Condition. Ups Output Panel Consisting Of The Following. Incomer : 100A 3P Mccb With Rotary Handle Mechanism - 1No Out Goings : 100A Tpn Mccb With Rotary Mechanism - 1 Nos. 40A Tpn Mccb With Rotary Mechanism - 2 Nos. Incoming And Outgoing Cables Shall Be Of Top Or Bottom Entry Only. , Distribution Boards Supply, Erection, Testing And Commisioining The Following Mcb Dbdouble Door Type, Ip 42 Powder Coated Comprising Of Fixed Flush With The Wall. The Cost Of Providing Adoptor Box Above The Db Shell Also Be Included , Power & Lighting Dbs 6 Way Etpn Mcb Db, All Mcbs Shall Be Of C Curve Type Only Meant For Lighting Application I / C -63 Amps Fp Mcb - 1 No O / G- 6 / 10 / 16 / 25Asp Mcb-18 Nos Including All Interconnections. , Ups Dbs 4 Way Etpn Mcb Db, All Mcbs Shall Be Of C Curve Type Only Meant For Ups Power Application I / C -40Amps Fp Mcb - 1 No O / G - 10 / 16Asp Mcb - 12 Nos Including All Interconnections. , Supply, Installation, Testing Andcommissioning 100A 4P Mcb With Water Proof Enclosure Including Earthing And All Other Required Accessories As Per Site Conditions.For A / C & Chiller , Supply, Installation, Testing Andcommissioning 100A Mccb With Ms Enclosure Including Earthing And All Other Required Accessories As Per Site Conditions. For Ups Incoming & Outgoing , L.T.Cables Supply, Laying, Testing And Commisioining Of 1100V Pvc Insulated Xlpe And Sheathed Armoured Copper / Aluminium Conductor Cables Laid Overms Supports / Cable Racks / Fixing Of Walls Including Clamping The Cable To The Support In All Approved Manner As All , 4C 4 Sq.Mm Cu. Ar. Cable Ups Db Incoming , 4C 10 Sq.Mm Cu. Ar. Cable For Pdb & Hvac Input Cable , 4C 16 Sq.Mm Cu. Ar. Cable For Chillerinput Cable , 4Run 25 Sq.Mm Copper Flexible Cable Machine Incomming & Outgoing Wiring , 4Run 25 Sq.Mm Copper Flexible Cable Ups Incomming & Outgoing Wiring , 1Run 25 Sq.Mm Copper Flexible Cable For Earth Cable , 4 Core 50Sq.Mm Copper Ar. Cable For Upsin & Out Going Power Cable , Cable Termination Supply, Erection, Testing And Commisioining For The Following Sizes Of 1100V Pvc Insulated Cu / Al. Conductor Cables Including Providing Single Compression Type Cable Gland Copper Sockets For Copper Cables, Crimping Lugs, Insulation Tape Including Gland , 4C 4 Sq.Mm Cu. Ar. Cable , 4C 10 Sq.Mm Cu. Ar. Cable , 4C 16 Sq.Mm Cu. Ar. Cable , 4Run 25 Sq.Mm Cu. Flexi. Cable , 1Run 25 Sq.Mm Cu. Flexi. Cable , 4 Core 50Sq.Mm Al. Ar. Cable , Submains Ups & Raw Power Circuts , Supply & Laying Of 2R 2.5Sqmm 1R 1.5 Sq.Mmpvc Insulated Frls Multistrand Copper Wire With 25Mm Dia Frpvc Conduit With All Accessories As Required As Per Site Conditions. ( Lighting & Raw Power Circuit Mains ) , Supply & Laying Of 2R 2.5Sqmm 1R 1.5 Sq.Mmpvc Insulated Frls Multistrand Copper Wire With 25Mm Dia Frpvc Conduit With All Accessories As Required As Per Site Conditions. ( Ups Circuit ) , Supply & Laying Of 2R 4Sqmm 1R 2.5 Sq.Mmpvc Insulated Frls Multistrand Copper Wire With 25Mm Dia Frpvc Conduit With All Accessories As Required As Per Site Conditions. ( Split A / C / Power Socket Circuit ) , Supply & Laying Of2 Run 1.5Sqmm Pvc Insulated Multistrand Copper Wire With 20Mm Dia Pvc Conduit With All Accessories For Emergency Push Button Wiring. , Supply & Laying Of3 Run 1.5Sqmm Pvc Insulated Multistrand Copper Wire With 25Mm Dia Pvc Conduit With All Accessories For Lmo Switch Wiring. , Supply & Laying Of8 Run 1.5Sqmm Pvc Insulated Multistrand Copper Wire With 25Mm Dia Pvc Conduit With All Accessories For Warning Lamp Wiring. , Supply & Laying Of12 Run 1.5Sqmm Pvc Insulated Multistrand Copper Wire With 25Mm Dia Pvc Conduit With All Accessories For Chiller Remote Panel Wiring. , Point Wiring Supply, Installation, Testing & Commisioning Of 3R1.5Sqmm Pvc Insulated Fr Copper Wire With Frpvc Conduit Along With Modular6a One Wayswitch With Moulded Front Plate Gi Anodised Enclosure And Other Associated Accessories As Required As Per The Site Condition , Primary Point , Dimmer Light Point With Dimmer , Sockets , Supply, Installation, Testing & Commissioning Of 1Nos 6A Socket And 1No 6A Switch And With Moulded Frontplate Gianodised Enclosure And Other Associated Accessories In The Work Station As Required As Per The Site Conditions. Bunker, Consol Room & Tps Room ( Raw Power ) , Supply, Installation, Testing & Commissioning Of 1No 6 / 13A Socket And 1No 6A Switch And With Moulded Frontplate Gianodised Enclosure And Other Associated Accessories In The Work Station As Required As Per The Site Conditions. Bunker, Consol Room & Tps Room ( Ups Power ) , Supply, Installation, Testing & Commissioning Of 1 No 16A Switched Socket With Moulded Frontplate Gianodised Enclosureand Other Associated Accessories As Per The Site Conditions. ( With Indicator ) , Installation Of Light Fittings , Supply, Erection, Testing And Commisioining Of 600Mm X 600Mm 36W Led Light Fittingalong With Electronic Ballasts With All Accessories And Interconnection , Supply, Erection, Testing And Commisioining Of 6 X 6 18W Led Light Fittingalong With Electronic Ballasts With All Accessories And Interconnection , Supply, Erection, Testing And Commisioining Of Single12 V, 15W Led Fitting ( Or ) 230V, 60Wrecessed Fixed Type Halogen Fitting With Copper Ballast, Lamps All Accessories And Interconnection ( Dimmer Light ) , Supply, Erection, Testing And Commisioining Of Led Strip Light , Data, Voice & Network ( Consile Room & Tps Room ) , Supply, Laying, Testing And Commissioning Of Cat - 6 Utpcable With Fr Pvc Conduit And All Accessories As Required. ( Voice And Data Cable ) , Supply, Fixing, Testing And Commissioning Of Infermation Outlet For Cat-6 Utp Cable Quader Front Plate With Back Box And All Accessories As Required. , Supply, Fixing, Testing And Commissioning Oftelephone Outletfront Plate With Back Box And All Accessories As Required. , Supply, Fixing, Testing And Commissioning Of 6U Communication Rack , Supply & Fixing Of 10 / 100 / 1000 Mbps 24Port T Switch With 24 Port Patch Panel , Supply Of 1 Mtr Pach Card , Earthing , Supply & Laying Of 8 Swg Bare Cu. Wire , Supply And Installation Of 12 Way Earth Bus With All Accessories As Required. , Supply, Installation, Testing & Commisioning Of 10 Feet Long 600 X 600 X 3Mm Copper Plate Or Chemical Earth Pit For Machine And Ups Netural And Body Earth , Miscellaneous , Supply & Laying Of20mm Pvc Hose , Supply & Laying Of25mm Pvc Hose , Supply, Fixing Of 105 X 50 Mm Cms Tray For Control Room , Warning Lamp Em Off Switch & Lmo Switch , Supply & Fixing Of Emergency Stop Switch And System On Switch With Base Box , Supply And Fixing Of Magnetic Door Switch , Supply, Erection, Testing And Commisioining Of Led Warning Lamp For Red, Green & Yellow . , Supply, , Erection, Testing And Commissioning Of Last Man Out Control Unit, Last Man Out Switch With Indicator, Buzzer And External Wiring Kit ( 1.0 Sq.Mm Cu. Wire & Pipes ) , Fire Alarm System , Supply, Fixing, Testing & Commissioning Of 2 Zone Conventional Fire Alarm Panel With Complete Set. , Supply, Fixing, Testing & Commissioning Of Conventionalsmoke Detectors With Base , Supply, Erection, Testing & Commissioning Of Conventional Manual Call Point. , Supply, Erection, Testing & Commissioning Of Conventional Hooter / Sounders , Supply And Laying Of 2 Core 1.5 Sqmm Copper Armoured Cable , Carbon-Di- Oxide Type Fire Extinguisher Of 4.5 Kgs. Capacity, Co2 Gas Filled In Brand New Seamless Cylinder With Powder Coated Finish, Made Out Of Manganese Steel, With Wheel Type Valve, Discharge Nozzle, Bend & Horn, Signages Etc. Complete, , Cc Tv , Supply, Fixing, Testing & Commissioning Of Hd Ir Ccd 1 / 3” Color Camera. ( Doom Or Bullet Modal Camera ) , Supply, Fixing, Testing & Commissioning Of Hd Mini Speed Dome Ir Camera. With 10 To 15X Zoom, Auto Iris Lens, Rs485 Control Ptz Camera , Supply, Fixing, Testing & Commissioning Of 4 Chenal Hd Dvr , Supply, Fixing, Testing & Commissioning Of Ptz Keyboard With Joystick , Supply, Fixing, Testing & Commissioning Of 24” Led Tv , Supply, Fixing, Testing & Commissioning Of 12V Dc Power Supply For Camera , Supply And Laying Of 3+1 Rg 58 Cctv Cable , Tack / Tack Back System , Supply, Fixing, Testing & Commissioning Of Tack / Tack Back Systems Comprises Of Console With Mike ( Inbled Amp. ) Ceiling Speaker Or Wall Mount Speaker - 1No. , Supply And Laying Of Two Core Screened Cable , Audio System For Playing Soft Music Inside The Treatment Room, Control Console, Patient Waiting Area Also To Be Supplied. , Turnkey Works For Site Preparation Of Dr. B. Borooah Cancer Institrute, Guwhati , A ) Civil Works , Demolishing Rcc Work Including Stacking Of Steel Bars And Disposal Of Unserviceable Material As Directed For All Levels , Dismantling And Removing The Existing Door And Window Frame ( Chowkath ) Both Wooden And Steel Of Different Sizes Without Damaging The Walls And Removing The Frame And Necessary Repairs To The Edges Of The Walls As Directed For All Levels. ( Ii ) Area Of Door / Window Above 3.00 M2 , Demolishing Cc Floors Of Various Thickness Including Top Layer And Base Course And Disposal Of Debris As Directed For All Levels. , Providing And Laying Plain / Reinforced Cement Croncrete Works Cement, Coarse Sand & 20Mm Down Graded Stone Aggregate Including Dewatering If Necessary, And Curing Complete But Excluding Cost Of Form Work And Reinforcement For Reinforced Cement Concrete Work ( Form Work And Reinforcement Will Be Measured And Paid Separately ) ( I ) Using Mixer Machine ( A ) In Substructure Up To Plinth Level P ) Using Admixture, Plasticiser Etc For Air Entraining, Water Reducing Purposes Including Addition Of Agent For Changing Normal Setting Time Of Concrete As Required. B ) M20 Grade Concrete Or Prop. 1:1.5:3 , ( B ) In Super Structure From Plinth Level Up To 1St Floor Level.P ) Using Admixture, Plasticiser Etc For Air Entraining, Water Reducing Purposes Including Addition Of Agent For Changing Normal Setting Time Of Concrete As Required. B ) M20 Grade Concrete Or Prop. 1:1.5:3 , Providing Form Work Of 12Mm Thick Plywood Board So As To Give A Rough Finish Including Centering, Shattering, Strutting And Propping Etc., Height Of Propping And Centering Below Supporting Floor To Ceiling Not Exceeding 4.0M And Removal Of The Same For In Situ Reinforced Concrete And Plain Concrete Work In: Flat Surfaces Such As Soffits Of Suspended Floors, Roofs, Landings, Cantelever Slabs, Chajjas, Balconies And The Like. ( B ) Floors Etc. Above 200Mm In Thickness. , Supplying, Fitting And Fixing In Position Reinforcement Bars Conforming To Relevant I.S. Code For R.C.C. Work / R.B. Walling Including Straightening, Cleaning, Cutting And Bending To Proper Shapes And Length As Per Details, Supplying And Binding With 20G Annealed Black Wire And Placing In Position With Proper Blocks, Supports, Chairs, Spacers Etc. Complete. ( No Extra Measurement For Lap, Hook, Chair, Anchor Etc. Will Be Entertained In The Measurement As They Are Included In The Rate ) ( Upto 1St Floor Level ) A ) From Primary Producer ( I ) Tmt Corrosion Resistant Steel ( Crs ) Reiforcement Bar , Plain Cement Concrete Works With Coarse Aggregate Of Sizes 13Mm To 32Mm In Foundation Bed For Footing Steps, Walls, Brick Works Etc. As Directed And Specified Including Dewatering If Necessary, And Curing Complete ( Shuttering Where Necessary Shall Be Measured And Paid Separately ) . ( A ) In Prop 1Cement: 3 Sand :6 Coarse Aggregate By Volume , 20 Mm Thick Cement Plaster In Two Coats On Single Or Half Brickwalls For Interior Plastering Up To 1St Floor Level Including Arises, Internal Rounded Angles, Chamfers And / Or Rounded Angles Not Exceeding 80Mm In Girth And Finished Even And Smooth Including Curing Complete As Directed. B ) On Fair Side ( Backing Coat 10 Mm And Finishing Coat 10Mm Thick ) A ) In Cement Mortar 1:3 , Providing Polished Granite Slab Of Approved Quality, Size, Shape And Thickness Not Less Than 18 Mm On Floors, Skirtings, Treads And Risers Of Steps Over Cement Mortar Bed 15 Mm Thick In Prop. 1:3 ( 1 Cement : 3 Coarse Sand ) Including Cutting Where Necessary Finished With Flush Pointing With Fix-A-Tile ) / White Cement Slurry Mixed With Approved Pigment To Match The Shade Of Granite Slab, Complete At All Levels As Specified And Directed. ( Cement Plastering To Be Measured And Paid Separately ) . ( Coloured Pigment Should Be In Conformity With Colour Of Slab And As Approved And Directed By The Department ) . ( Iii ) Deluxe Quality ( I ) With Fix-A-Tile , Providing Vitrified Floor Tiles Of Approved Quality Of Specified Size, Shape And Thickness Not Less Than 18Mm On Floors, Skirtings, Risers And Treads Of Steps Over 15 Mm Thick Base Ofcement Mortar In Prop. 1:3 ( 1 Cement : 3 Coarse Sand ) Including Cutting Where Necessary Finished With Flush Pointing With Fix-A-Tilewhite Cement Slurry Mixed With Approved Pigment To Match Shade Of Tiles, Mixed With Approved Pigment To Match The Shade Of The Tiles, Complete At All Levels As Specified And Directed. ( Coloured Pigment Should Be In Conformity With Colour Of Tiles And As Approved And Directed By The Department ) C ) Delux Range Ii ) Of Size 1200Mmx1600mm And Above , Providing Polished Vitrified Wall Tiles Of Approved Quality, Size, Shape And Thickness Not Less Than 8Mm On Walls And Skirtings Over Cement Mortar Bed 10 Mm Thick In Prop. 1:3 ( 1 Cement : 3 Coarse Sand ) Including Cutting Where Necessary Finished With Flush Pointing With Fix-A-Tile / White Cement Slurry Mixed With Approved Pigment To Match Shade Of Tilesc Complete At All Levels As Specified And Directed. ( Coloured Pigment Should Be In Conformity With Colour Of Tiles And As Approved And Directed By The Department ) . Iv ) Of Size300mmx900mm And Above , Supplying Fitting And Fixing Of Upvc Partition Wall 5 Mm Frosted Glass , Supplying Fitting And Fixing Of Upvc Double Leaf Door 5 Mm Frosted Glass , Supplying Fitting And Fixing Of Upvc Sliding Door Door 5 Mm Frosted Glass , Supplying Fitting And Fixing Of Upvcsliding Window 5 Mm Frosted Glass , Providing Wood Work In Frame ( Chowkaths ) Of Doors, Windows, Clerestory Windows And Other Similar Works Wrought, Framed And Fixed In Position In Contact With C.C Or Brick Masonry Wall Including Supplying, Fitting And Fixing With M.S. Hold Fast ( 40Mmx3mmx250mm ) As Per Design Embeded In Cement Concrete Block In Proportion 1:2:4 And With Two Coats Of Kiricide Oiling To The Timber Faces In Contact With C.C And Masonry As Directed And Specified. ( A ) With Sal Wood , Providing And Fixing Flush Door Shutters Solid Core Construction With Frame Of 1St Class Hard Wood With Cross Band And Face Veneered Ply Wood Face Panels Conforming To Relevent I.S Code Including Oxidised Iron Butt Hinges ( 100Mm X 75Mm X 3.5Mm ) 6 Nos With Necessary Wood Screws. A ) Decorative Type Face Panel And Block Board Core. ( Iii ) 30 Mm Thick . , Supplying, Fitting, Fixing And Painting Where Necessary ( One Coat Primer And Two Coats Of Paint ) Suspended Ceiling Which Includes G.I. Perimeter Channels Of Size 0.55Mm Thick ( Having One Flange Of 20Mm And Another Flange Of 30Mm And A Web Of 27Mm ) Along With Perimeter Of Ceiling, Screw Fixed To Brick Wall / Partition With The Help Of Nylon Sleeves And Screws, At 610Mm C / C. Then Suspending G.I. Intermediate Channels Of Size 45Mm ( 0.9Mm Thick With Twoequal Flanges Of15mm Each ) From The Soffit At 1220Mm C / C With Ceiling Angle Of Width 25Mmx10mmx0.55Mm Thick Fixed To Soffit With G.I.Cleat And Steel Expansion Fasteners. Ceiling Section Of 0.55Mm Thickness Having Knurled Web Of 51.5Mm And Two Equal Flanges Of 26Mm Each With Lips Of 10.5Mm Are Then Fixed To The Intermediate Channel With The Help Of Connecting Clip And In Direction Perpendicular To The Intermediate Channel At 298Mm C / C. Then 12.5Mm Thick Square Edge Fulltone / Sundance / Cratone / Louvertone / Textured. Gypboard Panels Of Size 595Mmx595mm ( Conforming To Is:2095-1982 ) Is Then Screw Fixed To Ceiling Section With 25Mm Long Drywall Screws At 290Mm C / C. Screw Fixing Is Done Mechanically Either With Screw Driver Or Drilling Machine With Suitable Attachment. Finally, The Boards Are To Be Jointed And Finished So As To Have A Flush Look Which Includes Filling And Finishing The Tapered And Square Edges Of The Boards With Jointing Compound, Joint Paper Tape And Two Coats Of Drywall Topcoat Suitable For Gypboard Complete At All Levels As Specified And Directed. ( For Light Fittings, Grill Diffusers Etc. Cut Out To Be Made With The Frame Of Perimeter Channel Supported Suitably And Measured And Paid Separately As And Where Necessary ) . ( Glass Wool To Be Measured And Paid Separately ) . M / F Frame Work With Acoustic Type Slit Gypboard ( Louvertone ) Tiles ( Nrc Value 0.72 With 50Mm Glass Wool Mat Backing ) 12.5Mm Thick. , Providing Surface Preparation For Walls, Celling Etc.Using Average 1.50 Mm Thick Plaster Of Paris Including Clearing, Rubbing With Sand Paper, Filling Gaps, Depression Etc. Where Necessary, With Chalk Powder And And Plaster Of Paris Paste, Making The Surface Even And Smooth Completeat All Levels As Specified And Directed. , Wall Painting ( Two Coats ) With Plastic Emulsion Paint On New Surface To Give An Even Shade After Throughly Brushing The Surfaces Free From Mortar Droppings And Other Foreign Matter And Sand Papered Smooth. ( A ) .Plastic Emulsion Paint , Extra Over Item No 13.4.7 Above For Every Subsequent Coat Of Wall Painting With Plastic Emulsion Paint. ( A ) .Plastic Emulsion Paint , Water Proofing Of Chajjas, Roof Slabs, Terraces, Sunken Slabs, Septic Tank, Oh Tank, Raft Slab In Basement, Walls Etc. ( B ) Using Polymer Based Cement Mortar. , Supplying Fitting And Fixing Of Sky View , Providing, Fitting, Hoisting And Fixing Of Roof Trusses Fabricated Out Ofcombination Of Anytwo Or All Of The Following Sections ( I ) Square Section ( Ii ) Rectangular Hollow Section Of Specification Rsh / Shs And ( Iii ) M.S. Circular Hlollow Section Of Grade 210 Including Purlins, Bottom Runners And Providing M.S. Cleat, M.S. Angle Base Plank, Bolts And Nuts With Red Oxide Primer Including Fitting Bottom Runner And Cleat Etc. For Fixing Ceiling Joist As Per Design Complete As Directed As Per Specifications. A ) Using Rhs / Shs Of Grade 310 Conforming To Relevant I.S. Code 4923 : 1997 , Providing Pre Painted Galvanized Ironsheetroofing ( Ppgi ) At All Levels Including Fitting And Fixing With Self Drilling, Self Tapping Screws Complete. ( Roof Trusses, Purlins Etc. To Be Measured And Paid Separately. ) As Directed By The Departement ( V ) 0.80 Mm Thick , Earth / Sand Filling In Plinth In Layers Not More Than 150Mm Thick Including Necessary Carriage, Watering, Ramming Etc. Complete As Directed And Specified Including Payment Of Land Compensation, Forest Royalty, Sales Tax And Other Duties And Taxes As May Be Necessary. ( B ) With Hill Sand Obtained By Truck Carriage Loading And Unloading, And Carriage To The Site Of Work. , Providing Soling In Foundation And Under Floorwith Stone / Best Quality Picked Jhama Brick, Sand Packed And Laid To Level And In Panel After Preparing The Subgrade As Directed Including All Labourand Materials And If Necessary Dewatering, Complete. ( A ) .Brick On Flat Soling. , 230Mm Thick Brick Wall In Cement Morter With 1St Class Brick Including Racking Out Joints And Curing Complete As Directed In Structure ( Ii ) In Superstructure Above Plinth Level Up To 1St Floor Level. ( A ) . In Proportion 1:3. ( 1 Cement:3 Sand ) , Supplying, Fitting And Fixing Chain Link Fencing Of 10 S.W.G, G.I. Wire 50Mm X50mm Mesh Fitted To M.S Angle Iron Post At 2000Mm Apart Of Specification Detailed Below Including Supplying, Fitting And Fixing Hooks, Eye Bolts With Nuts, Staples And Bolts Including Three Horizontal Lines Of G.I Wire 10 S.W.G At Top, Middle And Bottom And With One Vertical Line To Each Fencing Post For Keeping The Fencing Tight And Erect Complete, Including One Coat Of Primer Painting To M.S Angle Iron Post In P.C.C Base Etc. With Following. A ) Corner And End Posts With M.S Angle Of Size 50Mmx50mmx 5Mm And Length Not Less Than 1800Mm Only Duly Slotted And Bottom Torqued With Two Numbers As Stay Posts.. , Supply, Installation, Fixing Of Dry Chemical Powder Fire Extinguisher Confirming To Is: 2171 With Isi Mark And Co2 Cartridge Will Be Confirming To Is: 4947 With Isi Mark, Powder Will Be Confirming To Is: 4308 With Isi Mark ( 5 Kg ) , Wall Panelling With Ply And Mica Pesting , Finishingold / New Wall With Water Proofing Weathercoat Smooth Anti-Fungal Premium Textured Exterior Finish Ofrequired Shadeafter Clering And Clearing The Surfaces Etc.Including Scaffolding Complete As Directed At Alllevels ( Two Coats ) . , B ) External Electrification Works , Supplying Including Installation, Commissioning Of Vermin And Dust Proof Totally Enclosed Cubical Indoor Type Floor / Wall Mounting Compartmentalize Panel Board Of Size 0.95M X 1.30Mx 0.40M Made Of 16 Swg1.66 M Thick C.R. Sheet And40mm X 40Mm X 5Mm Size Angle Having 4 No Legs At The Bottom Complete Painting With 2 Coats Of Red Oxide Metal Primer And 2 Coats Of Enamel Paint. The Panel Board Is To Be Erected In 1 : 3 : 6 Pcc Foundation Including Brick Soling / Grouting Etc. Complete Neatly Wiring Done With Provision For One No 400A 4Pole Mccb Or Switch Fuse Unit As Incomer And Provision For 4Nos Dp Or Tpn Out Going As Specified And Directed By The Deptt. Confirming To Ip 43 Protection Comprising Of The Following Electrical Items: 1. 40Mm X 5Mm 4 Strip Copper Bus - Bar 1.20 M Length Each I20mm X 3Mm 4 Strip Copper Bus-Bar 0.5M Each 4 Sets 2. Digital 3 Phase Voltmeter Accuracy Class 0.5- 1 No 3. Digital 3 Phase Ammeter Accuracy Class 0.5- 1 No 4. Pilot Lamp With Integral Ckt Led 110- 230 V ( Red, Yellow, & Blue - 3 No 5. Voltmeter & Ammeter Selector Switch- 2 No 6. 2 A Slide Fuse Unit - 3Nos ( Incoming & Outgoing Switch Gear Of Reqd. Rating Will Be Measured And Paid Separately ) , Supply And Laying Of Following Size Pvc / Xlpe Insulated And Pvc Sheathed 1.1 Kv Gsolid Aluminium Conductor Up To 10 Sq Mm Balance Stranded Conductor, Xlpe Insulated, Cores Laid Up, Pvc Tape Inner Sheathed, Armour ( Aluminium For Single Core Up To 70 Sq Mm Balance Aluminium Strip, Galvanised For Cables Up To 2X10 Sq Mm.3X10 Sq Mm, 4X6 Sq Mm Balance All Galvanised Steel Strip ) , Extruded Pvc Type St2 Sheathed, 650 / 1100V Grade As Per Is 7908 ( Part 1 ) 1988 Armoured U.G. Cableu.G. Cable Laid In Ground / Partially In Air ( As Required For Termination Over Groundincluding Excavation Of Cable Trench Up To Depth Of 75Cm, Refilling, Protective Brick Covering, Sand Cushioning Etc Complete Handling Of Surplus Spoil, Debris Etto Proper Place As Specified And Directed By The Deptt.. 3 & 1 / 2 Core A2xfy 240.00 Sq.Mm.3 & 1 / 2 Core Armoured U.G. Cable Note:From Main Distribution Panel To Machine Panel , Supply And Laying Of Following Size Pvc / Xlpe Insulated And Pvc Sheathed 1.1 Kv Gsolid Aluminium Conductor Up To 10 Sq Mm Balance Stranded Conductor, Xlpe Insulated, Cores Laid Up, Pvc Tape Inner Sheathed, Armour ( Aluminium For Single Core Up To 70 Sq Mm Balance Aluminium Strip, Galvanised For Cables Up To 2X10 Sq Mm.3X10 Sq Mm, 4X6 Sq Mm Balance All Galvanised Steel Strip ) , Extruded Pvc Type St2 Sheathed, 650 / 1100V Grade As Per Is 7908 ( Part 1 ) 1988 Armoured U.G. Cableu.G. Cable Laid In Ground / Partially In Air ( As Required For Termination Over Groundincluding Excavation Of Cable Trench Up To Depth Of 75Cm, Refilling, Protective Brick Covering, Sand Cushioning Etc Complete Handling Of Surplus Spoil, Debris Etto Proper Place As Specified And Directed By The Deptt. 3 & 1 / 2 Core A2xfy 185.00 Sq.Mm.3 & 1 / 2 Core Armoured U.G. Cable Note:From Panel To Ups And Ups To Machine Control Panel , Supply, Installation & Testing Of Copper Plate Earth Station With600 Mmx600 Mmx3 Mm Copper Earth Plate Withnecessary 40 Mm Dia. G.I. Medium Duty Watering Pipewith G.I. Fittings Such As Socket, Tee, Elbow, Nipple And 50 Mmx40 Mm G.I. Reducing Socket For Funnel Including Locking Arrangement With 300 Mmx300 Mmx6 Mm C.I. Hinged Cover Plate Complete With Digging Of Earth Pit, Construction Of Brick Chamber And Plastering Of Both Inner & Outer Surface Of Wall As Specified And Directed By The Deptt . Note:For Machine, Chiller And Ups. , Extra For Using Salt ( 5 Kand Charcoal ( 96 Kin G.I. / Copper Plate Earth Station Pit To Provide Low Impedance Ground In Location Of High Soil Resistivity As And When Required And Specified By The Deptt . , Supply, Fitting & Fixing 20 Mmx3 Mm Copper Strips Drawn On Vertically Or Horizontally On Building Wall / Parapet Wall In Surface System Complete With Supply Of Brassnuts & Bolts, Screws Etc Including Riveting, Soldering And Making Connection As Approved By The Deptt. ) With Earth Electrode Copper Strips And Lightning Arrestor Etc. As Specified And Directed By The Deptt. , Supply And Laying Of Following Size Pvc / Xlpe Insulated And Pvc Sheathed 1.1 Kv Gsolid Aluminium Conductor Up To 10 Sq Mm Balance Stranded Conductor, Xlpe Insulated, Cores Laid Up, Pvc Tape Inner Sheathed, Armour ( Aluminium For Single Core Up To 70 Sq Mm Balance Aluminium Strip, Galvanised For Cables Up To 2X10 Sq Mm.3X10 Sq Mm, 4X6 Sq Mm Balance All Galvanised Steel Strip ) , Extruded Pvc Type St2 Sheathed, 650 / 1100V Grade As Per Is 7908 ( Part 1 ) 1988 Armoured U.G. Cableu.G. Cable Laid In Ground / Partially In Air ( As Required For Termination Over Groundincluding Excavation Of Cable Trench Up To Depth Of 75Cm, Refilling, Protective Brick Covering, Sand Cushioning Etc Complete Handling Of Surplus Spoil, Debris Etto Proper Place As Specified And Directed By The Deptt. 3 & 1 / 2 Core A2xfy 400.00 Sq.Mm.3 & 1 / 2 Core Armoured U.G. Cable , C ) Internal Electrification Works , Wiring For Circuit Wiring With P.V.C. Insulated Single Core Unsheathed Industrial ( Multistrand ) Cable Fr Conforming To Is-694: 1990 With Flexible Bright Annealed Electrolytic Copper Conductor For Voltage Grade Up To 1100 Volts In Surface / Recessedpvcconduit Wiring System. With 2 X 1.5 Sq. Mm. Cable In 20 Mm Dia. 2Mm Thick / Heavy Rigid Pvc Is: 9537 Part - Iiiconduit. Note: For Door Interlock, Fault Ceiling Light, Laser, Cctv, Public Adress System, Ceiling Fan, Emergency Switch , 2.7.1Wiring For Drawing Sub-Main Line With P.V.C. Insulated Single Core Unsheathed Industrial ( Multistrand ) Cable Fr Conforming To Is-694: 1990 With Flexible Bright Annealed Electrolytic Copper Conductor For Voltage Grade Up To 1100 Volts Pvc Conduit Including Earth Continuity In Surface / Recessed 20 Mm. Dia. 2Mm Thick / Heavy Isi Marked Is: 9537 Part - Iii Rigid Pvc Conduit Wiring System. With 2 X 2.5 Sq. Mm. + Earth Continuity With 1X1.5 Sq. Mm. In 20 Mm. Dia. 2Mm Thick / Heavy Rigid Pvc Is: 9537 Part - Iiiconduit Note:For 6A And 16A Power Points , 2.7.2Wiring For Drawing Sub-Main Line With P.V.C. Insulated Single Core Unsheathed Industrial ( Multistrand ) Cable Fr Conforming To Is-694: 1990 With Flexible Bright Annealed Electrolytic Copper Conductor For Voltage Grade Up To 1100 Voltspvc Conduitincluding Earth Continuity In Surface / Recessed 20 Mm. Dia. 2Mm Thick / Heavy Isi Marked Is: 9537 Part - Iii Rigid Pvc Conduit Wiring System. With 2 X 4 Sq. Mm. + Earth Continuity With 1X2.5 Sq. Mm. Cable In 20 Mm. Dia. 2Mm Thick / Heavy Rigid Pvc Is: 9537 Part - Iiiconduit. Note: For Air-Conditioner , Wiring For Drawing Sub-Main Line With P.V.C. Insulated Single Core Unsheathed Industrial ( Multistrand ) Cable Fr Conforming To Is-694: 1990 With Flexible Bright Annealed Electrolytic Copper Conductor For Voltage Grade Up To 1100 Voltspvc Conduit Including Earth Continuity In Surface / Recessed 20 Mm. Dia. 2Mm Thick / Heavy Isi Marked Is: 9537 Part - Iii Rigid Pvc Conduit Wiring System. With 2 X 10 Sq. Mm. + Earth Continuity With 1X 6 Sq. Mm. Cable In 25 Mm. Dia. 2Mm Thick / Heavy Rigid Pvc Is: 9537 Part - Iiiconduit. , Sb. 8.28Supplying With Fitting Fixing Of 6 Amp One Way Modular Clip In Switch, Including Making Necessary Connection As Per Direction Of Department. , Supplying Including Installation Of Socket Outlet 6 / 16 Amps 3 / 5 Pin Combine Shuttered Complete , Including Making Necessary Connection As Per Direction Of Department. , Supplying With Fitting Fixing Of 10 / 16 Amp One Way Modular Clip In Switch, Including Making Necessary Connection As Per Direction Of Department. , Supplying Including And Fixing Of Following Moulded Pvc Boxes For In Surface System Complete As Per Direction Of Department. 8 Module Surface Moulded Pvc Boxes. , Supplying Including Fitting Fixing Of Following Front Plate Of Suitable Colour As Per Direction Of Department. 8 Module , Supplying Including And Fixing Of Following Moulded Pvc Boxes In Surface System Complete As Per Direction Of Department. 12 Module Horizontal Surface Moulded Pvc Boxes , Supplying Including Fitting Fixing Of Followingfront Plate Of Suitable Colour As Per Direction Of Department. 12 Module , Supplying With Installation Testing And Commissioning Of Hi -- Wall 4 Star Rating Non Ducted Split Typeair Conditioner Of The Following Capacity With Cordless Remote Complete Withindoor And Outdoor Unit, Copper Pipeand Electrical Connection As Approved By The Deptt. ) Up To 5 M Between The Room Unit And Out Door Unit As Directed By The Department. 2 Ton Capacity R410 , Supplying With Fitting And Fixingvoltage Stabilizer Of The Following Specification Complete Including Making Necessary Connection As Approved, Specified And Directed By The Deptt. 5.0 Kva Automatic Input 120-280 V Out Put 200-240 V , Supplying With Fitting And Fixing Of Angle Iron Framing Made 50 Mmx50 Mmx5 Mm Size Angle Iron For Accommodation Of 1.00 Ton To 2.00 Ton Window / Split Type A.C. Machine , Supplying With Fitting And Fixing Of Single Phase Modular A.C Starter Switch Of The Following Specification Complete Including Making Necessary Connection As Specified And Directed By The Deptt. , Supplying Including Fitting Fixing Of Followinga.C. Ceiling Fan Complete With All Accessories Like Down Rod, Canopy Etc. Of Following Sweeps With Making Necessary Connection As Approved By The Deptt. ) As Required Complete And As Directed By The Department [ Without Regulator ] . Premium Model1400 Mm Sweep. , Supplying With Fitting And Fixing Of 120 Watt Electronic Modular Step Speed Control 2 - Module Type Including Making Necessary Connection As Per Direction Of Department. 120 Watt Electronic Modular Step Speed Control2 - Module Type , Supplying With Fitting And Fixing Panel Mounting Open Execution 35 / 36Ka 415V 50Hz 3P Mccb ( Ics=Icu, Adjustable Ir Setting 0.7 ) Without Enclosure ) Of The Following Capacity Complete With Making Necessary Connection As Approved, Specified And Directed By The Deptt. 35 / 36 Ka 415V 50 Hz 3P Mccb 400A , Supplying With Fitting And Fixing Panel Mounting Open Execution 25 Ka 415V 50Hz 3P Mccb ( Ics=Icu, Adjustable Ir Setting 0.7 ) Without Enclosure Of The Following Capacity Complete With Making Necessary Connection As Approved By The Deptt. As Specified And Directed By The Deptt. 25 Ka 415V 50 Hz 3P Mccb 125A , Supplying With Fitting And Fixing 4P 10 Ka 240 / 415V 50Hz Mcb Of The Following Capacity Complete With Making Necessary Connection As Approved, Specified And Directed By The Deptt. C Series 100A , Supplying With Fitting And Fixing 4P 10 Ka 240 / 415V 50Hz Mcb Of The Following Capacity Complete With Making Necessary Connection As Approved, Specified And Directed By The Deptt. C Series 63A , Supplying With Fitting And Fixing Single Pole 10 Ka 240 / 415V 50Hz Mcb Of The Following Capacity Complete With Making Necessary Connection As Approved, Specified And Directed By The Deptt.C Series 6 To 32A , Supplying With Fitting And Fixing Single Pole 10 Ka 240 / 415V 50Hz Mcb Of The Following Capacity Complete With Making Necessary Connection As Approved, Specified And Directed By The Deptt.B Series 6 To 32A , Cc Camera , Public Adress System , View Box , Supplying With Fitting And Fixing Of 12Watt, Round Led Ceiling Light With Frame , Supplying Including Fitting Fixing Of Followinga.C. Exhaust Fan In The Existing Hole On The Wall Of Following Sweeps With Making Necessary Connection As Approved By The Deptt. ) As Required Complete And As Directed By The Department. Heavy Duty 450 Mm Sweep 900 Rpm Single Phase , D ) Furniture Works , Suppying And Installation Of Coloured Tv 22 Flat Led Wall Mountingas Directed By The Department. , Supplying Fitting And Fixing Of Furniture Rack, Table, Store Almirah, Revolving Chair Etc. As Required. , A ) Computer Chair ( 6 Nos For Control Console & 6 Nos. For Tps Room ) , B ) Master Table For Use In Computer In Control Room Made Of Best Quality Water Proof Green Ply 18Mm Thick Finishing With Sunmika Size ( 10 X 3X2.5 ) ( 1 No For Control Console & 1 No. For Tps Room ) , C ) Wall Mounting Manual Shelf Control Room Made Of Best Quality Water Proof Green Ply 18Mm Thick Finishing With Sunmika Size ( 6X2x16 ) , D ) Shelf Inside The Labunkermade Of Best Quality Water Proof Green Ply 18Mm Thick Finishing With Sunmika Size ( 8 X 6X2 ) , E ) Sypplying Of Decorative & Comfortable 3-Seater Patient Waiting Chairmust Be Approved By The Department. , Cat ( B ) - Buy Back Items , Buy-Back ( Ie Minus ) Amount Of Old Linear Accelerator ( Tomotherapy ) At Actrec Kharghar , Buy-Back ( Ie Minus ) Amount Of Old Linear Accelerator ( Tomotherapy ) At Tmh Mumbai

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 06-Jun-2022 1CORRIGENDUM Date 13-06-2022
2 09-Jun-2022 2EXTENSION OF DUE DATE Date 20-06-2022
3 17-Jun-2022 3RD CORRIGENDUM FOR PREBID MINUTES, MODIFICATION, CLARIFICATION, ADDITIONS, RETAINMENT OF TECHNICAL SPECS, TURNKEY COMPONENTS, TENDER TERMS AND CONDITIONS, EXISTING LAYOUT PLANS FOR REFERENCE PURPOSE AND EXTENSION OF DUE DATE Date 12-07-2022
4 08-Jul-2022 Due Date Extension Date 01-08-2022
5 28-Jul-2022 Due date extended Date 08-08-2022
6 28-Jul-2022 Technical Specification modified Technical Bid 08-08-2022

Key Value

Document Fees
Refer document
EMD
INR 500000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work:ACTREC/PUR/2022-2023/E-TENDER/10 Supply, Installation, Testing and Commissioning of Linear Accelerator - Ring Gantry - 5 Nos. along with required Turnkey Works. To be installed at following 4 Centers i. ACTREC, Kharghar - 2 No., ii. TMH, Mumbai - 1 No., iii. BBCI, Guwahati, Assam - 1 No. and iv. Civil Hospital, Shillong, Meghalaya- 1 No.
Sl. No. Item Description
1Cat (A) -Supply, Installation, Testing and Commissioning of Linear Accelerator - Ring Gantry - 5 Nos along with required Turnkey Works.
2Supply, Installation, Testing and Commissioning of Linear Accelerator - Ring Gantry at ACTREC, Kharghar, Maharashtra as per tendered technical specifications
3Supply, Installation, Testing and Commissioning of Linear Accelerator - Ring Gantry at TMH, Mumbai, Maharashtraas per tendered technical specifications
4Supply, Installation, Testing and Commissioning of Linear Accelerator - Ring Gantry at BBCI, Guwahati, Assam as per tendered technical specifications
5Supply, Installation, Testing and Commissioning of Linear Accelerator - Ring Gantry at Civil Hospital, Shillong, Meghalaya as per tendered technical specifications
6TURNKEY WORKS AT ACTREC
7CIVIL MODIFICATION & INTERIOR WORKS
8Architectural & Structural Audit & Design consultancy: Appointment of reputed, Govt registered Architectural, Structural designer having mre than 10 years of experiencedto render interior & structural design consultancy for improvemetn and strucutral rehabilitation work as per AERB"s recommendation and Interior works matching the existing design, considering the following scope of work. Study of available Structural Audit Reports of the referred bunker Study of the existing building drawings, structural system and history of repairs Visual inspection the bunkers externally and internally Tapping exercise with the use of hammer Assessment of all structural elements (slabs, beams, columns, RC walls) Conducting necessary Non-Destructive Tests on concrete of existing Bunkers Ultra sonic pulse velocity - 15 Nos. points / bunker Re-bound hammer - min 15 Nos. points / bunker Conducting necessary Partial - Destructive Tests on concrete of existing Bunkers Core Cut - 1 No. points / bunker Preparation separate Structural Audit Reports Certifying feasibility of proposedstructural changes at the existing bunker (AERB drawings) Analysis & Design of structural elements for accommodating proposed structural changes at the existing bunker (AERB drawings) considering the items mentioned in the BOQ. Preparing GA/Schematic structural drawings for proposed revisions Getting Client’s approval on complete set of GA/Schematic drawings Sharing Design, Analysis and GA/Schematic drawings to Clint Appointed Structural designer for vetting and incorporating suggested recomendationa and implementing the same before issuing the GFC drawings. Preparing Working drawings (Structural) for proposed revisions Nominal changes to accommodate in the drawing, if any, as per client’s requirement Visiting site to inspect the execution work. Total visits - 3 Nos. Issuing stability certificate only after completion of work to our full satisfaction.
9Preparatory Civil
10Preparation of existing RCC wall or brick wall surface, by scrapping, existing finish / Paint cleaning the exposed concrete surface to remove any fungus, loosely particles, scales, by a stiff wire brush, clean by water wash the entire surface, exposed the damaged concrete surface with the help of small chisel and hammer, including collecting, stacking the debris at the site.
11Carefully removing or chiseling, existing plaster of thickness up to 20 mm from the damaged surface with the help of small chisel and hammer weighing not more than 5 pound, includingcollecting, stacking & carting away the debris from the site wherever required as directed by site incharge
12Removing existing flooring & skirting tiles, along with backing and bedding mortar, clean the surface, lifting & shifting debris to ground floor & carting away the same out of premises etc. complete.
13Breaking & removingexisting RCC wall by mechanical cutter without disturbing the adjacent structure, or any other concretemembers including cutting ofreinforcement bymeans of chisel &hammervery carefully,properplatform to collect the debris , lowering down & carting away the debris etc. complete.(30 MM THK)
14Demolishing the existing brick wall along with plaster bymeans of chisel &hammervery carefully,properplatform to collect the debris , lowering down & carting away the debris etc. complete.
15Brick wall 230 mm thick
16Brick wall 115 mm thick
17Carefully excavating in any kind of soil, in existing building in or out sides, including necessary shoring/propping if required and including carting away the debris including re-making the surface in good as same as existing as directed. Including dewatering and necessary back filling complete
18Dismantling of existing wooden/aluminium doors and handing over to the client as directed by PM.
19Labor charges for shifting the furniture remove all the cupboards and shift the same as directed to facilitate the work.
20Dismantling existing terrace water proofing including AAP membrane, cleaning the roof top free from dust and dirt with mechanical wire brush make it receive new concrete, shifing of debries from terrace to ground and carting away out of ACTREC campus complete as directed and instructed.
21Construction Civil
22Leveling and filling of earth below foundation and plinth level with quarry dust mixed with 5% cement (by volume) for the depth of 150 mm. After initial fill of 75 mm thick, pour water with required compacting, watering make the sub soil in good condition, pour water to dampen the dry mix enough to cake form. Similarly fill second layer of 75 mm. Pour water with required compacting after each stage of layer to make the mix damp enough to become solid form
23Providing and laying P.C.C. M15 (1:2:4) concrete in foundation as leveling course 150 mm thick including necessary form work, batching, mixing, placing, consolidating etc. complete including wet curing for specified time period.
24Supplying, Providing and placing in position RMC M25 Reinforced cement concrete with 20mm downgraded aggregates for walls of accelerator and maze rooms of thickness ranging from 300mm to 600 mm at all levels including vibrating, curing, providing construction joints, leaving cut-outs/ pockets for placing of inserts/ embedment, etc., complete, including cost of providing steel form work with plywood lining for all shapes (including scaffolding, centering, etc.), but excluding the cost of providing reinforcement all as per specifications.Include precautions to control heat of hydration and obtaining a homogeneous compact concrete. All exposed concrete surface to be of form finish complete as directed and instructed.
25For foundations
26For RCC Shielding
27For terrace shieling
28Providing and fixing high density (7.75gm/cc) steel plate to the existing concrete surface using holdfast and hot press technique. Also, the footing required to carry weight of steel plate would be included as per approved design by the consultant.
29Supply &fabricating and fixing reinforcement for RCC work with high yield strength ribbed cold twisted tor steel of variousdiametersand all lengths of grade Fe 415 / Fe 500 conforming to BIS specification including cutting, bending, fabricating, welding, wastage and placing in position according to drawings and binding the reinforcement with the use of 16 gauge galvanized binding wire of double fold and providing precast cement cover blocks for main reinforcements to ensure specified cover according to relevant IS code.The measurements will be in accordance with IS code 1200.
30Supplying,Drilling/Cleaning hole and injecting chemical laced heavy duty stainless steel anchor fasteners widely used in strucutral reahabilitation works to support re-bars and strenth enough to support additional concrete throug mechnical drilling into exisitng concrete surface. The application to be designed separately for Rebars as Simply Supported,Moment or Splice Connection as per Indian or European standard or relevant tested and accepted rebar guidelines. rebars. of 20 mm dia 200-300mm depth. The appointed strucutral designer should submit the detailed design analysis adopted, complete as directed and instructed.
31Providing and doing brick work with locally available good bricks of class designation 50, in required thickness of walls, in CM 1: 4, including adding polymer admixtureat 500ml per bag of cement, racking the joints, cleaning, carting away the wastages and curing
32For 230 mm thick
33For 115 mm thick
34Providign & Constructing Solid Cement concrete block of M-10 grade of required thickness in CM 1:6 with scafolding, labour work at all heights and levels including wastage, scafolding etc omplete as directed and instructed.
35Providing and doing pressure groiuting with waterproofing compound or structural reapiring compund as per manufacturers specfication as directed by the Structral consultant, withinsertion of pvc nozzles with drilling holes at regulaer intervals on exisit g RCC walls, beams, roof slabs etc complete as directed and instructed. (cosnidered for exsitng RCC walls which are developed cracks.)
36Providing & applying plaster at an average thickness of 12 to 15 mm in exact line & level in the proportion of 1 : 4 cement and sand mortar by manual mixing, with addition of waterproofing chemical @ 150 ml and Harbourite 12 mm fine fibrillated 100% virgin polypropylene fibers @ 150 gm per bag of cement including curing for at least 7 days, carting away a debris, cleaning (Note: Waterproof Plaster considered in Server Room only)
37Filling sunken portion of roof with brick bat mixed with CM 1:6 and complete as directed and instructed
38Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer in- Charge : With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
39Miscellaneous Civil
40Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.
41Supplying, providing and Laying vitrified tiled floor, wall on cement screed using 600 x 600 mm vitrified tiles. Total thickness of screed and tiles to be 30 mm. including lying 125mm high skirting all round. Laid area of wall, floor and skirting measured and paid
42Wall Tiling (1.8 mtr height) -
43Floor Tiling-
44Providing and fixing floor cover with quick access to sub-floor utilities Galvanized Steel Chequer Plate for Cabling modular factory finished widely for cabel laying to withstand heacy traffic movemetn of heavy matirials thelid has been designed to withstand for heavy loading, all lids are galvanized to prevent corrosion, with the larger lids having substantial underbracing to give the required strength, complete as directed and instructed.
45Providing and applying Pest and rodent control for the required in all respect including guarantee for the 18 months
46Providing & layi g approved shade minimum 18mm thick Granite slab in flooring, window cills etc over cement morter of 1:4 in wastage, labour. Complete as directed and instructed.
47Provide and fixing wall paneling up to the ceiling height in Radiation therapy processing room, passage and the control room, using 18/12mm thick high quality plywood paneling with 4mm thick veneer finished, cut to shape and size and fixed to wall in straight line including all supports, screws etc complete as per direction of Engineer-in-Charge.
48P/f Trap door in false ceiling with ACP panel in shutter and frame fixed ovwr 50x50x2 mm thick aluminumhollow swction with epoxy sealant as per manufacturer specification suspended from ceiling with suitable MS supporting system as per site condition, including p/f 32mm thick insulation on trap door complete as directed and instructed.
49Painting
50Providing and applying oil based internal paint as per the manufacturers specification to the interior surface of masonry walls,underside of roof slabs in UPS room ,control room , passages, of approved colour and shade with minimum two coats of paint. Item to include preparing the surface with necessary approved fillers, making good by touch up etc. to give the desired finish , all complete. Rate to include cost of the tools, tackles, labour, equipment, etc.(above Wall Tiling)
51Providing and applying exteriorpaint widly used to mactch exisitng colour schemewaterproofing paint, scrap and clean the surface, applyprimer as base coat, over the primer coat apply two coats or more paint approved color as per manufacturers sepecification all inclusive of labour, scafolding, safety precautions etc complete as directed and instructed.
52Providing & applyingenamel paint to wooden or steel doors,scrapping, cleaningthe surface, washingandfillingthe crevices with approved paste/putty as filling sealant & applying the paint with one metal primer base coat, two top coats or more over the primer as per manufacturers specification, including, labour, scafolding, safety precaution etc complete as directed nd instruted.
53Furniture
54Providing and fixing 5"W x 7"H, 38 mm thick, double leaf doors in solid hard wood core (phenyl Formaldehyde bonded) flush shutters both faces commercial ply including Ist class C.P.T.W. lippings all around, lock plate and complete hardware, finished with both sides 1.0 mm thk. Laminate as per specifications with grooves and clear / frosted glass as per design/detail complete in all aspects with necessary heacy duty hardware fixtures to mactch exisitng hardware fixtures already installed to maintain unifarmity as standerdization as per per the furniture drawing complete as directed and instructed.
55Repairing and alterations to existing wooden doors, by changing SS hinges, SS fittings and shutters to be 40mm thick, flush type with teak veneers on both sides open type. Inclusive of fixing heavy duty automatic door a closure, two doors handles per shutter concealed night latch locking device, etc. complete.
56Floor-mounted storage cupboards within Bhabhatron room; to store: accessories. (Location: Tomotherapy Room Passage) Size: 200 cm wide x 250 cm high x 60 cm deep (19mm thick commercial Grade Ply)
57Open type cabinetwith Shelves with 18 mm thick high quality plywood laminated with 0.9mm thick melamine laminates on both side of approved colour and make with 1 numbers of open type shelves 210cmx200X50cm size with 6 horizontal and 3 vertical partitions inside the therapy room with partitions for immobilization devices, electron applicator and cutouts. Type and utility should match with the existing work station. Provide necessary drawer-2 nos and shutter-2 nos as per the requirement from the Radiation physics division. Edges should be finished by machine press. All finishes and quality to be instructed by the engineering - in – charge.
58Providing and supplying officers chair with net back revolving type.The contractor shall furnish one year warranty. Economically designed and mat finish.
59Changing Room Partition (3"X4")
60ELECTRIVAL & LV WORKS
61Main Distribution LT PanelSupply, Erection, Testing and Commisioining of cubicle type free standing, dust and vermin proof, busbar chambers, shell made of 14SWG CRCA sheet, doors made of 16SWG CRCA sheet with powder coating, Compartmentalised, modular type IP 42 Protection, with support clamps and angles frames as required as per the site condition. MAIN DISTRIBUTION PANEL consisting of the following. Incomer : 1 no 250A TP 25KA MCCB + Neutral link with built-in adjustable O/L, S/C & E/F. MCCB with rotary handle mechanism. Outgoings : 1no 125A TP MCCB with rotory handile machanism for UPS,1no 100A TP MCCB with rotory handile machanism for Chiller,1 no. 125 A TPN MCCB for HVAC & 1 no 63A 25KA TPN MCB with mechanism for HVAC Unit. Busbar : Busbar rating shall be 1.2 sqmmper amphere formain bus bars with aluminium .Incoming and outgoing cables shall be Top of bottom entry only.
62UPS Output Panel BoardSupply, Erection, Testing and Commisioining of cubicle type free standing, dust and vermin proof, busbar chambers, shell made of 14SWG CRCA sheet, doors made of 16SWG CRCA sheet with powder coating, Compartmentalised, modular type IP 42 Protection, with support clamps and angles frames as required as per the site condition. UPS Output Panel consisting of the following. Incomer : 1No 125A TP 25K MCCB + Neutral link with built in adjustable O/L, S/C & E/F MCCB with rotary handle mechanism Outgoings : 1nos. 100A 25KA TP MCCB with rotary handle mechanism, & 3nos. 40A TPN MCB for DB Busbar : Busbar rating shall be 1.2 sqmmper amphere formain bus bars with aluminium . Incoming and outgoing cables shall be Top of bottom entry only.
63Electrical Wiring & Cabling
64DISTRIBUTION BOARDS Supply, Erection, Testing and Commissioning the following MCB DBDouble door type, IP 42 powder coated comprising of fixed flush with the wall. The cost of providing adaptor box above the DB shell also be includedDISTRIBUTION BOX 8 WAY 7Segment MCB DBI / C -63 AMP FP MCB - 1 NoO / G -63 AMP DP MCB -3 Nos O / G - 10/16A SP MCB - 18 Nos Including all interconnections and other accessories etc as reqd
65Supply, Installation, Testing andCommissioning 100A TPN MCCB with water proof enclosure including earthing and all other required accessories as per site conditions. For near Chiller
66Supply, Installation, Testing and Commissioning 63A TPN MCB with MS enclosure including earthing and all other required accessories as per site conditions for AC Outdoor Unit
67LT Cables Supply, Laying, Testing and Commissioning of 1100V PVC insulated XLPE and sheathed Armoured Copper / Aluminium Conductor cables laid overMS supports / Cable racks /fixing of walls including clamping the cable to the support in all approved manner as all
684R 50sq.mm Copper flexible cable Truebeam UPS Incoming & Outgoing
694R 25 sq.mm Copper flexible cable for UPS input & output and machine
701C 25 sq.mm Copper flexible cable for Earth
714C 16 sq.mm Copper flexible Cable for Chiller
724C 10 sq.mm Copper flexible Cable for AC
734C 6 sq.mm Copper flexible cable for DB
7412C 0.75sqmm Copper flexible Cable with PVC conduit for Chiller to control panel at console room & Warning Light
751C 6sq.mm Copper flexible cable for DB Earthing
76Cable TerminationsSupply, Erection, Testing and Commissioning for the following sizes of 1100V PVC insulated Cu / Al. conductor cables including providing single compression type cable gland copper sockets for copper cables, crimping lugs, insulation tape including gland
774R 50 sq.mm Copper flexible cable
784C 25 sq.mm Copper Flexible cable
791C 25 sq.mm Copper Flexible cable
804C 16 sq.mm Copper Flexible Cable
814C 10 sq.mm Copper Flexible Cable
824C 6 sq.mm Copper Flexible Cable
83Submain UPS and Raw Power Circuits
84Supply & Laying of 2R 2.5sqmm 1R 2.5PVC insulated FRLS multistrand copper wire with 25mm dia FRPVC conduit with all accessories as required as per site conditions.
85Supply & Laying of4 Run 1.5sqmm PVC insulated multistrand copper wire with 20mm dia PVC conduit with all accessories for Emergency push button wiring.
86Point Wiring Supply, Installation, Testing & Commissioning of 3R 1.5sqmm PVC insulated FRLS copper wire with FRPVC conduit along with Modular6A one wayswitch with moulded front plate GI anodised enclosure and other associated accessories as required as per the site.
87PRIMARY POINT
88SECONDARY POINT
89Dimmer light point With Dimmer
90Sockets
91Supply, Installation, Testing & Commissioning of 1no13A socket and 1no 6A switch and with moulded frontplate GIanodised enclosure and other associated accessories in the work station as required as per the site conditions. (UPS Power)
92Supply, Installation, Testing & Commissioning of 1no 6/16A socket and 1no switch and with moulded frontplate GIanodised enclosure and other associated accessories in the work station as required as per the site conditions.
93Installation of Light Fittings
94Supply,Erection, Testing and Commissioning of 2" X 2"LED 36 watts recessed mounting fitting with all accessories and interconnecting with 3 R 1.5 sqmm PVC insulated FRLS copper wire manufactured, used widely across campus to match exsitng pattern and design as standerdization complete as directed nd instructed.
95Supply,Erection, Testing and Commissioning ofLED 18 watts recessed mounting down light fitting with all accessories and interconnecting with 3 R 1.5 sqmm PVC insulated FRLS copper wire manufactured, used widely across campus to match exsitng pattern and design as standerdization complete as directed nd instructed
96Supply,Erection, Testing and Commissioning of single3W Recessed fixed type LED fitting with Electronics ballast and all accessories and interconnecting with 3 core 1.5 sqmm PVC insulated FRLScopper wire and fixing the same in the Ceiling.
97Data, Voice & Network
98Supply,Laying, Testing and Commissioning of Cat - 6 UTPCable with FR PVC conduit and all accessories as required.
99Supply,Fixing, Testing and Commissioning of Information Outlet for Cat-6 UTP cable quader front plate with Back box and all accessories as required.
100Supply,Fixing, Testing and Commissioning ofTelephone Outletfront plate with Back box and all accessories as required.
101Supply,Fixing, Testing and Commissioning of 4U Communication Rack
102Supply,Fixing, Testing and Commissioning of 6U Communication Rack
103Supply & Fixing of 24port Patch panel and 10/100/1000 mbps Base T Switch with 24 port patch panel
104Supply,Fixing, Testing and Commissioning of CAT-6 Telephone cable .
105Supply & Fixing of 24port Patch panel and 10/100/1000 mbps Base T Switch with 24 port patch panel
106Earthing
107Supply and Installation of 4 way earth bus with accessories as required
108Supply, Installation, Testing & Commissioning of Copper Earthing with 600x600x3mm Copper Plate and 25x6mm Copper flat bar confirmingIS:3043 with the provision for watering & inspection chamber.
109Perforeated Type GI Cable Tray
110Supplying, fabricating, erecting and connecting the following 1.6mm thickness GI perforated type cable trays with necessary supports, tees, elbows, bends,bolts and nuts and any other associated accessories to complete the job.-150mm (wide) X 50mm (collar height)
111Supply & Fixing of 50 mm PVC Pipe for CC TV, IRM and speaker cable pulling
112Warning Light Supplyfixing Testing & Commissioning of Warning Light, LED Green, Yellow, Red, + Power Supply .
113Emergency Stop Switch Supplyfixing Testing & Commissioning of Emergency Switch,3 No. NO, Element With Box
114Supply Fixing & Commissioning Of LMO Switch Indicator &Buzzer, SS Plate with all accessories
115Supply, Laying, Testing and Commissioning of 1100V PVC insulated XLPE and sheathed Armoured Copper / Aluminium Conductor cables laid overMS supports / Cable racks /fixing of walls including clamping the cable to the support in all approved manner as all
1164C 10 sq.mm Copper flexible Cable for AC
1171C 6sq.mm Copper flexible cable for DB Earthing
118Supply, Installation, Testing and Commissioning 63A TPN MCB with MS enclosure including earthing and all other required accessories as per site conditions for AC Outdoor Unit
119Supply Testing & Commissioning Of Panasonic Make Telephone Instument With Caller Id
120CCTV The camera should be compitable with exisitng CCTV system as standerdization, sample must be got approved before supply in bulk.
12116 channel DVR FUL HD
122HD outdoor bullet camera
123HD dome camera
124WD Hard Disk (DVR)1TB
125MONITER ( 19.5inch)
126CAMERA POWER SUPPLY(10amp)
127SDMI Cable (3 meter)
128BNC conector
129DC pin conector
130Wire 3+1 (heavy wire) per/meter
131Junction box for camera
132Tack/ Tack Back System
133Supply, Fixing, Testing & Commissioning of Tack/ Tack Back Systems comprises of console with Mike ( inbled amp.) Ceiling Speaker or Wall mount Speaker - 1 no.
134Supply and laying of two core screened cable
135Audio system for playing soft music inside the treatment room, control console, patient waiting area also to be supplid.
136SUPPLY TESTING COMMISSIONING OF TOKEN DISPLAY SYSTEM
137Firefighting Works -All devises should be compitable with exisitng system as standerdization, sample must be got approved before supply in bulk. Supply, installation, testing & commissioning:
138Smoke Detectors Bunker - 8 Nos; Maze - 2 Nos; UPS - 2 Nos.
139Response indicator.
140Manual call bell
141Hooter
142Cu. Ar. 1.5 Sq.mm. cable
143Fire Extinguisher - 5kg Bunker - 4 Nos; UPS - 1 No.
144HVAC WORKS
145Supply,Installation,TestingandCommissioningofAircooledscroll chilling machines having actual capacity of 38.4 TR at chilled water inlet/ outlet temperature of 12.0 deg. C / 7 deg. C having evaporator fouling factorof0.000018m2.k/w suitable for operation on refrigerant R- 407C or eco friendly gascomprising the following complete as required. Chiller capacity should not less than 38.4TR(Followingsafetyfactorwillinbuiltwithchillerunit-SPPR, Under/Over load protection, Phase reverse protection, HP/LP trip signal interlocking, Auto/Manual Test mode facility/ Run time equalization for multiple compressor, Password access for authorized handling, PT-100 RTD sensor for chiller unit, Interlocking for chilled water flow swtich) 135KW(38.4TR)
146AIR HANDLING UNITS Supply,Installation,Testingandcommissioningoffactorybuiltfloor mounted-doubleskintypehorizontal/verticalairhandlingunits made of43+2mm thick panels consisting ofpreplasticizedG.I. casing of thickness 0.8 mm outside layer and 0.8 mm plane GI at inside layer with CFC-FREE P.U. insulation of density 42(+5%) kg/m3 factory injectedbetweenthem byinjectionmouldingmachine,completewith DIDWbackwardcurvedcentrifugalfanwithVFDStarterDriven, suitablefor50mm WGstaticpressure,coilsectionwithaluminium blue finned copper tubes (tubes thickness not less than 0.41mm) cooling coil of 6 row deep, filter section with 50mm thick washable synthetic type air pre filters,belt drive package with TEFC drive motor suitable to operate at 415 ± 10% volts, 50Hz, 3 Phase AC supply, motor should be compatible with VFD, drain connections, stainless steel (18G) drain pan, necessary vibration isolation pads & accessories:and piping as per the norms duly insulated with requires thick nitrile rubber. AHU starterpanelshouldhaveVFDandVFDbypassoption,should have PLC based control and PLC bypass control for manual mode. Panel should provide with heater control. Note:- Temp and RH sensor to be included with control wiring. noadditional cost will be given for the same. 30.5 TR -12200CFM-50mm TSP (1 working +1 standby motor)
147Supply, Installation, Testing and commissioningof FCU 2 TR
148Supply, Installation, Testing and commissioningof Primary Pump-102USGPM-15m head.
149Supply, Installation, Testing and commissioningof Expansion Tank (100 LTR) with Air separator, air vent and pressure maintaining pumping unit.
150Supply, installation, testing and commissioning of chilled water MS pipe with supports,hardware etc.
15180 mm dia with 32mm nitrile insulation with 26G Al cladding
15225 mm dia with 19mm nitrile Insulation with 26G AL cladding
153PVC drain pipe having pressure holding of 8kg/cm2Drain piping complete with all accessories with 9mm Nitrile Rubber Insulation with supports
15432mm dia
15525mm dia
156Supply, Installation, Testing and commissioningof Valves & Guages as follows with 32mm nitrile insulation for CHW line:
157Butterfly valve
15880mm dia
15925mm dia
160Y-strainer
16180mmdia
16225mm dia
163Flexible connection80mmdia
164NRV valve80mmdia
1653-way valve
16680mm dia
16725mm dia
168Ball valve 25mm dia
169Airvent with Ball valve
170Temperature Gauge
171Pressure Gauge
172SITC of GI SHEET METAL RECTANGULAR DUCT with support, hangers, rods, frames, anchor fastners, etc.
17324 gauge
17422 gauge
175Supplying & Erecting Accoustic insulation Lining on the Ducts having 15mm thick Open Cell Nitrile Rubber Armasound to reduce noise
176Supplying & Erecting Thermal insulation on the Ducts having 19 mm closed cell nitrile rubber. Exposed duct should cover with 26G Al cladding
177SITC of Canvass connection for AHU machines
178SITC of Control Cabling in between for FCU and AHUunits
179SITC of Fire Damper
180SITC of Fire Actuator
181SITC of Supply/Return Air Grill with VCD
182Supply, installation and commissioning of duct strip heaters with thyristor control of necessary capacity made of SS strip (finned/finless tubular type) complete with RH sensor, industrial grade heating elements, protection against overheating, on/trip status, air flow switch, grounding terminals, terminals for power & control, intermediate control wiring for integration etc. for full automation working to achieve RH level of 40-60% non-condensing in the Treatment Room. (Rating/capacity considered to be specified by the bidder)
183Dismantling of existing HVAC systems - AHU, piping,valves ,ducting / copper piping / drain piping / units / hi wall split unit all complete as per instruction as nad directed by OIC-ES
184supply and fabrication of MS structure include one coat primer and one coat enamal paint.
185Dismantling & re-installing exisitng AC chiller plant including its roofing at terrace including disconnection of chilled water MS pipe lines, extending same till new location, with required insulation and necessarru hardware as directed and instructructed.
186TURNKEY WORKS AT TMH Mumbai
187CIVIL WORKS :-
188Labour charge only for removing and re-fixing available door shutter with necessary modification including cutting the existing shutter providing leeping patti all around the shutter if required including removing and refixingavailbale old hinges, mortice lock, tower bolts ect. fixing aligning the door shutter in proper plumb and level etc. complete allOnly fixing available door shutter with necessary repairing
189Removing existing false ceiling of any material and any size with all necessary allied works, removing out debris out of TMH premises
190Labour charges only for carefully removing and taking out existing wooden partitions (partly glazed, partly panneled or fully panneled with shutters glazing etc. at all floor levels and locations including removing the existing mongery fittings fixtures locking arrangement and handling over the same to T.M.C all complete as directed
191Providing wood work with 1st Class C.P. teak wood in frames for doors windows, ventilators, Air-condition frames, clear story window, false ceiling and partitions etc.wrought framed and fixed in position including applying one coat of approved wood primer to the exposed surfaces and tow coats of bitumastic paint to the surface of wood in contact with masonry/concrete etc.complete. In frames of doors, windows, ventilators and clear storey windows etc. fixed with M.S hold fast of size 40x3mmx150mm long bend to shape and embeded in cement concrete 1:2:4.
192Providing and fixingapproved quality machine pressed phenol formal dehy de bonded commercial/marine ply wood of approved size and fixing the same with necessary nails/screws/adhesive in partition cupboard shelves/ktichen/cabinets/flush doors etc. at all floors and locations in quantities as required at site in following thickness including 6 mm thick T.W.lipping patti at all exposed edges with nails/screws/hardwares/adhesive wastage in cutting, transportation etc. complete all.Commercial ply19mm thick ply
193Providing and fixing 1.0mm thick laminate of required colour over existing surfaces along with the adhesive all as required specification design etc. complete as specified. 1.00 mm thick
194Providing and fixing cabinet made up of 19 mm. Commercial ply for top, bottom, sides and shelves and 6mm commercial ply for back side.Door shutter made up of 19mm thick commercial ply and outer surfaces and top of shelves for open type cabine should be laminated with 1.0mm thick plastic laminate sheet of required colour including all brass fittings such as hinges, tower bolts, ball catches, stopper, handle, knobs as per shown in drawing etc.and all exposed edges lipping with 6mm laminate finishThick T.W.lipping patti.locking arrangement withmultipurpose lock etc. All inside areas shall be .80mm thick approved colour laminate etc. With inner side 0.8mm thick laminateWith shutter
195Providing making and supplying computer table made out fo 19mm commercial ply for table top, mounted on the vertical side fo 19mm commercial ply and cabinet made out of 19mm commercial ply for sides, shelves and shutters making concealed monitor arrangement by providing 8mm thick clear glass on table top of required size with edge polishasshown in drawing drawer and wooden key board drawer with heavy sliding channels, withhandle for shutter,cable manager drawers all edges shall be lipped with 6mm thick T.W. lipping patti. All exposed faces should be 1.0mm thick laminate and non laminated area should be french poll-shed including cost of other materials labour etc. as per drawing.Computer table with all inner surface with 0.8 mm thick laminate
196Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings.GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending.
197Providing fixing door frame and shutter side hung to consist of partly glazed partly panneled/ fully panneled/ fully glazed with 5.5mm thick glass sheet and quality plain or frosted of bajri glass fixed with two way PVC lining/rubber gasket to ensure notes tightness and no rattaling and panneling with 12mm thick nova pan or Ancholam finished on both side as required using extruded alumimium section forshutter frame24254545mm satin finish anodized including P/F push-pull plates handles and heavy duty fittings like tower bolts, Motice lock with keys hinges of 5 inch or 6 inchas per requirement hydraulic door closer/ floor spring of suitable capacity etc complete.With powder coated
198PAINTING WORK Providing & applying one / two coats of primer two coats of paint as mentioned below First quality Paint to the required colour scheme and as per manufacturers instructions / specificationsto the walls, beams, columns, ceilings, partitions, doors etc. including removing existing paints , nails , screws , battens etc. and thoroughly scrapping the surface with sand papers filling up crevices and levelling with putty to obtain smooth surface ie. complete surface preparation etc. complete as directed to the entire satisfaction of Engineer In-charge.
199With two coats of primer and two coats ofpaint
200Using Luster paint
201Using synthetic enamel paint (Oil Paint)
202Providing and applying three coats of White wash to ceiling etc. including removing existing nails , screws , battens etc. andthoroughly scrapping the surface with sand papers, filling up the crevices and levelling with putty if necessary adding, required quantity of adhisive to obtain good finish to surface complete as directed.
203CIVIL WORK BREAKING:Dismantling carefully the existing damaged cracked serviceable tiles / slabs / clay tiles / marble slab / granite slab / Kota stone/ tandur stone / shahabad stone and all types of flooring in flooring etc. including removing the 20mm thick bedding of cement mortar stone grit or brick bat coba etc. at all floors & levels including disposing / taking away the debris outside the premises & disposing as per the guidlines of statutory authoritised. )
204GRANITE TILES:Providing & laying 8 to 10mm thickgranite tile of size 300mm x 600mmfor flooring / dado / skirting laid over a bedding of C.M. 1:335mm thick in true plain line & level curing. Finishing the joints etc. complete.In flooring & In dado / skirting
205ELECTRICALSWORKS
206POINT WIRING :- Point wiring for light/fan/bell with ISI mark 3 x 1.5 sq.mm (P+N+E). FRLS PVC insulated copper conductor ofmake in surface/ recessed heavy class pvc casing capping/conduit with Modular switch - ceiling rose/batten holder/slanting holder Boxes etc. with circuit labling/marking/ferruling complete.
207Primary point upto 4 mtrs length
208Primary point length 4 mtrs to 7 mtrs
209Primary point length7 mtrs to 10 mtrs
210Secondary point Extending from Primary point upto 4 m
211DISMANTLING:- Carrying out assigned jobsof dismantling the existing light, fan, bell, independent plug point wiring of all types with accessories and cable /switchgear
212Supply & installation of Power point (inclusive of 2No.of 15 Amp switch socket, back box, face plate & wiring,accesories etc)
213Supply & installation of Power point (inclusive of 1 No.of 15 Amp switch socket, back box, face plate & wiring,accesories etc)
214Telephone Point :- Supplying and instllation of telephone point inclusive of Telephone instrument, Telephone socket with back box ,plate, laying two pair0.5 mm gauge unarmoured telephone wire D.O.T approved, make through conduit/casing caping.
215Supplying and laying of 2 core audio speaker cable throughconduit/casing caping/cable tray.
216SUB MAINSMains :- Providing Heavy duty PVC casing-caping/conduit, Supplying and erecting mains with copper conductor PVC insulated FRLS of 1100 V AC grade wire with circuit labling/marking/ferruling complete.
2172 x 1.5 sq mm -+ 1.5sqmm Earth wire
2182 x 2.5 sq mm -+ 1.5sqmm Earth wire
2192 x 4 sq mm -+ 2.5 sqmm Earth wire
220LIGHT FixturesSupply of LED fixtures - Surface /Suspended / Recessed Mounted luminaires
221LED Light fixture Duraslim 15 watt, Round6500K,
222LED Light Fixture Full Glow 2FT X 2FT 6500K
223Distribution Boards Supply, installation, testing & commissioning DBs
224SPN DB with Metal door, 12 way,IP 43, inclusive of required rating MCB,RCBO
225TPN DB with Metal door, 8 way,IP 43, inclusive of required rating MCB,RCBO
226HVAC WORKS
227HVAC WORKS (LOW SIDE) FAN COILS UNITS (CEILING SUSPENDED TYPE/HIGH WALL) Supply, installation, testing and commissioning of GI powder coated horizantal ceiling suspended/High Wall fan coil units complete with fan, 3 speed motor, 3 row deep cooling coil, 5 mm external static, filters , copper connection, Canvass Connection (If required), supporting arrangement, electrical wiring etc. The complete fan coil unit shall be in line with the standard specification. The capacity of fan coil units shall be as follows. Proper supporting system for FCU to be provided & will be in contractor"s scope. 800 CFM (2 TR)
228HVAC WORKS (LOW SIDE):-Supply & Installation of 2 Wayvalve
229HVAC WORKS (LOW SIDE):-Supply & Installation of Digital Thermostat including all accessaries ,mountings,wiring between thermostat & unit, terminations etc.
230Supply,Installation Testing and Commissioning of the following Ball Valves without strainer duly insulated as per specifications and drawings. It shall be bronze forged body construction with chrome plated bronze ball and handle of stainless steel constructions. 25 mm dia
231Supply,Installation Testing and Commissioning of the following Ball Valves with Strainer duly insulated as per specifications and drawings. It shall be bronze forged body construction with chrome plated bronze ball and handle of stainless steel constructions. 25 mm dia
232HVAC WORKS (LOW SIDE):Supplying, laying, fixing, testing and commissioning of following thickness closed cell elastrometric nitrile rubber of class "O" applied by suiatable adhesive, as per specifications and as required complete in all respect-32mm,Insulation work involve removing of old insulation on chilled water pipeline and installing new insulation.
233HVAC WORKS (LOW SIDE):-Providing and fixing in position the following UPVC Heavy class cut to required length and installed with screw joints including the necessary fittings, supporting arrangements like clamps etc. (bends, tees, unions, sockets etc) duly insulated with class "O" 6 mm thick nitrile rubber insulation as per specifications. 25 mm dia
234HVAC WORKS(LOW SIDE) Supply, installation, balancing and commissioning offabricatedat site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of .63mm thickness complete as required.
235HVAC WORKS (LOW SIDE)Supplying, installing of external thermal insulation on ducts of AL faced/closed cell nitrile rubber Insulation with anti microbial properties with duct insulation with density 40-55 Kg/ Cum complete as per specifications. •Thermal conductivity of insulation material shall not exceed 0.035 W/(m.K) & R value as mentioned in ECBC -2008 at mean temperature of 24 degree C as per ASTM C518. . Class-O Insulation with Aluminum foil. • Moisture Diffusion Resistance Factor or ‘µ’ value of insulation material shall be minimum 7,000 without any external barrier as per EN 13469. • The insulation material shall have fire performance such that it passes Class 1 as per BS476 Part 7 for surface spread of flame and also passes Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire category. 25 mm thick.
236HVAC WORKS (LOW SIDE) Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
237HVAC WORKS (LOW SIDE) Supply, installation, testing & commissioning of thermal insulated flexible duct of following sizes duly supported at regular interval as per site requirement etc. complete as required as per specifications.-300 mm dia
238HVAC WORKS (LOW SIDE) Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without aluminium volume control dampers with anti smudge ring & removable core.
239HVAC WORKS (LOW SIDE) Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications
240Dismantling,removing of oldFlexible Ducting ,pipelne,insulation,FCU(3Nos),Griil,Diffuser etc loading,Unloading,Lifting shifting,etc and disposing the same outside TMH Premises with proper housekeeping complete in all respect
241Networking Supply, Installation,Testing and Commissioning of LAN cable Room no. HBB-B-002-4 nos. of network points, Room no.-HBB- B-003-2 nos. of network points. Total networks points. = 6 nos.
242TURNKEY WORKS FOR SITE PREPARATION OF GMC, Shillong
243CIVIL SHIELDING WORKS
244Complete Dismantling Works inside Bunker and Console Room, of Plain Cement Concrete, Flooring, Brick work, False Ceiling to any depth and width, at all levels below & above Ground Level of any shape, removal of debris, disposing the same away from the site, loading and unloading, making the surface good etc. complete. Rate shall include for dismantling of Plain Cement Concrete / Brick work by manually / mechanical means with necessary tools and plants, scaffolding, water and power charges, cleaning the surface, preparation of surface etc. Rate shall include for stacking the serviceable materials and disposing the unserviceable materials/debris away from the site premises by mechanical means including loading, unloading, clearing the site etc. complete, as directed. (Measurement is done for Floor area only) Demolishen of the walls are as per approved drawings
245Providing and casting in situ cement concrete M-25 (Concrete Density 2.35 gms/cc) of trap / granite /quartzite/ gneiss metal for R.C.C. Walls as per detailed designs and drawings or as directed including centering, formwork, cover blocks compacting and roughening if special finish is to be provided and curing complete. (Excluding reinforcement). With fully automatic micro processor based PLC with SCADA enabled reversible drum type concrete mixer. With natural sand. For Concrete Shielding and Bunker door wall as per AERB approved drawing
246Providing and applying integral crystalline slurry of hydrophilic innature for waterproofing treatment to the RCC structures like retainingwalls of the basement, water tanks, roof slabs, podiums, reservior,sewage & water treatment plant, tunnels / subway and bridge decketc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integralcrystalline slurry : 1 part water) for horizontal surfaces and applyingthe same from negative (internal) side with the help of synthetic fiberbrush. For Bunker and console area
247CIVIL INTERIOR & FURNITURE WORKS
24850mm thick Cement Concrete Flooring finished with 3mm thick Vinyl Flooring Location: UPS Room
249600mmx 600mm Vitrified tiles with 100mm matching tile skirting. Providing and laying approved quality, colour, design and shade fully homogeneous 600 x 600 mm (thickness to be specified by the manufacturer)Vitrified tile flooring (Marbonite or Granamite, confirming to IS code 15622 with water absorption less than 0.08%)flooring in pattern as detailed in drawing or as directed by the institute and grouted with matching colour approved quality readymade grout, curing, cleaning etc to required line level etc. all complete at all leads, lifts and heights to the entire satisfaction of the institute. Providing and fixing 2-3mm thick POP protection over polythene covering sheet to flooring areas till handed over and cleaning, etc all complete as per drawings & Specification. (LINAC Room and Console Room)
250Two coats of Plastic Emulsion Paint over 2 coats of wall putty including primer. Location: (UPS Room and Outside Shielding Wall)
251Providing and laying high quality and density type vitrified wall tile of 1200 mm height in Radiation therapy room and the control room, laid on 20mm thick base of cement mortar 1:3 (1 cement : 3 coarse sand) or as per the appropriate mortar rquired to hold the wall tiles together, in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge upto False Ceiling level. Location: (LINAC and Control Console Room)
252Pest and Rodent Control from PCI Location: LINAC Room, Control Console and UPS Room
253Acoustical tile for ceiling with light weight insulating material of high quality supported on grid or finished seamless with support above ceiling. To be finished with white paint or powder coated with white paint, if metallic. The false ceiling panels should be of reputed brands. Location: LINAC Room, Control Console and UPS Room
254Constructing cable trenches 300mm wide and 300mm deep as per the drawings
255Preparing and fixing openable covers of vitrified tiles fixed in the with ability to sustain a load of 200kgs to be placed on the trenches 300 mm wide, all works complete
256Furniture
257Revolving chairs height adjustable, medium-back with hand-rest
258Skylight
259Wall-mounted storage cupboards within LINAC room; to store: Dosimetry & QA Items, LINAC accessories. (Location: Treatment Room). Size: 2m wide x 1.2m high x 0.4m deep (19mm thick Marine Grade Ply)
26040mm Thick Plywood door with Teak wood frame, including all accessories. Size 2m X 2.2m
261Wooden Tables for Workstations. Size: 3 m wide, 0.6 m deep and 0.8 m high (16mm thick Marine Grade Ply) For: Console
262Wooden Tables for Workstations. Size: 4 m wide, 0.6 m deep and 0.8 m high (16mm thick Marine Grade Ply) For: TPS
263PLUMBING WORKS
264Supply & installation and commissioning of chiller inlet & outlet Equipment flange & union
265Supply & installation and commissioning of pressure gauge
266Supply & installation and commissioning of thermometer
267Supply & installation and commissioning of auto air vent
268Supply & installation and commissioning of Drain valve
269Supply & installation and commissioning of chiller water copper piping 15/8" 18 gauge with insulation 19mm thick
270Supply & installation of chiller water pipe nylon with wire mesh HSS slive flexible 40mm with insulation 13mm thick
271Supply & installation and commissioning of Ball valves 40 mm
272Supply & installation and commissioning of Y strainer 40 mm
273Supply & refilling of DM water
274Supply & installation and commissioning of Water panel with 2 nos pressure gauge and 5 nos valve, 2 nos thermometer
275HVAC WORKS
276Ductable A/C units along with Low side works (up to 50 running meters) for complete installation & commissioning of AC. Supply , installation ,testing & commissioning of aircooled ductable split air conditioner with ceiling suspended IDU and all standard fitting,GSS sheet metal duct(insulation using resin bounded glass wool with 7 micron aluminium foil) for air distribution 22/24 G, IDU SS drain pan as per specification complete with suitable capacity drive motor , aircooled condensor with all accessories ,hermetically sealed scroll compressor, electronic microprocessor pendant controller with digital display, first charge refrigerant gas, vibration isolator pads, structural support for fixing IDU/ODU, safety devices including thermal protector, pressure release valve ,overload relay single phase preventer etc, power wiring and control cabling(indoor to outdoor), thermostat wiring, high-low pressure cut out suitable for 3 phase 440V supply etc complete as required. (Warranty - 3 years) For Bunker and Console 5.5 TR working and 5.5TR stand-by
277Split Units with required Copper Piping and Drainage outlet lines (For UPS Room 2TR working and 2TR stand-by) with Auto-Timer switch
2782-Litre Capacity Dehumidifier (For Bunker - 2, Console - 1)
279ELECTRICAL WORKS
280MAIN LT PANEL Supply, Erection, Testing and Commisioining of cubicle type free standing, dust and vermin proof, busbar chambers, shell made of 14SWG CRCA sheet, doors made of 16SWG CRCA sheet with powder coating, Compartmentalised, modular type IP 42 Protection, with support clamps and angles frames as required as per the site condition. MAIN DISTRIBUTION PANEL consisting of the following. Incomer : 250A 3P MCCB with rotary handle mechanism - 1No with necessory interlocking arrangement Out Goings : 100A TPN MCCB with rotary mechanism - 2 Nos. 63A TPN MCCB with rotary mechanism - 3 Nos. 40A TPN MCCB with rotary mechanism - 1 Nos. Incoming and outgoing cables shall be of Top or bottom entry only.
281UPS Output Panel Board Supply, Erection, Testing and Commisioining of cubicle type free standing, dust and vermin proof, busbar chambers, shell made of 14SWG CRCA sheet, doors made of 16SWG CRCA sheet with powder coating, Compartmentalised, modular type IP 42 Protection, with support clamps and angles frames as required as per the site condition. UPS Output Panel consisting of the following. Incomer : 100A 3P MCCB with rotary handle mechanism - 1No Out Goings : 100A TPN MCCB with rotary mechanism - 1 Nos. 40A TPN MCCB with rotary mechanism - 2 Nos. Incoming and outgoing cables shall be of Top or bottom entry only.
282DISTRIBUTION BOARDS Supply, Erection, Testing and Commisioining the following MCB DBDouble door type, IP 42 powder coated comprising of fixed flush with the wall. The cost of providing adoptor box above the DB shell also be included
283Power & Lighting DB"s 6 WAY ETPN MCB DB, all MCBs shall be of C curve type only meant for Lighting application I / C -63 AMPS FP MCB - 1 No O / G- 6/10/16/25ASP MCB-18 Nos Including all interconnections.
284UPS DB"s 4 WAY ETPN MCB DB, all MCBs shall be of C curve type only meant for UPS Power application I / C -40AMPS FP MCB - 1 No O / G - 10/16ASP MCB - 12 Nos Including all interconnections.
285Supply, Installation, Testing andCommissioning 100A 4P MCB with water proof enclosure including earthing and all other required accessories as per site conditions.For A/C & Chiller
286Supply, Installation, Testing andCommissioning 100A MCCB with MS enclosure including earthing and all other required accessories as per site conditions. For UPS Incoming & Outgoing
287L.T.CABLES Supply, Laying, Testing and Commisioining of 1100V PVC insulated XLPE and sheathed Armoured Copper / Aluminium Conductor cables laid overMS supports / Cable racks /fixing of walls including clamping the cable to the support in all approved manner as all
2884C 4 sq.mm Cu. Ar. Cable UPS DB incoming
2894C 10 sq.mm Cu. Ar. Cable for PDB & HVAC input cable
2904C 16 sq.mm Cu. Ar. Cable for Chillerinput cable
2914Run 25 sq.mm Copper flexible cable Machine Incomming & outgoing wiring
2924Run 25 sq.mm Copper flexible cable UPS Incomming & outgoing wiring
2931Run 25 sq.mm Copper flexible cable for Earth cable
2944 Core 50sq.mm Copper Ar. Cable for UPSin & out going Power cable
295CABLE TERMINATION Supply, Erection, Testing and Commisioining for the following sizes of 1100V PVC insulated Cu / Al. conductor cables including providing single compression type cable gland copper sockets for copper cables, crimping lugs, insulation tape including gland
2964C 4 sq.mm Cu. Ar. cable
2974C 10 sq.mm Cu. Ar. cable
2984C 16 sq.mm Cu. Ar. cable
2994Run 25 sq.mm Cu. Flexi. cable
3001Run 25 sq.mm Cu. Flexi. cable
3014 Core 50sq.mm Al. Ar. cable
302SUBMAINS UPS & RAW POWER CIRCUTS
303Supply & Laying of 2R 2.5sqmm 1R 1.5 sq.mmPVC insulated FRLS multistrand copper wire with 25mm dia FRPVC conduit with all accessories as required as per site conditions.(lighting & Raw Power circuit mains)
304Supply & Laying of 2R 2.5sqmm 1R 1.5 sq.mmPVC insulated FRLS multistrand copper wire with 25mm dia FRPVC conduit with all accessories as required as per site conditions.(Ups Circuit)
305Supply & Laying of 2R 4sqmm 1R 2.5 sq.mmPVC insulated FRLS multistrand copper wire with 25mm dia FRPVC conduit with all accessories as required as per site conditions.(Split A/C / Power Socket Circuit)
306Supply & Laying of2 Run 1.5sqmm PVC insulated multistrand copper wire with 20mm dia PVC conduit with all accessories for Emergency push button wiring.
307Supply & Laying of3 Run 1.5sqmm PVC insulated multistrand copper wire with 25mm dia PVC conduit with all accessories for LMO switch wiring.
308Supply & Laying of8 Run 1.5sqmm PVC insulated multistrand copper wire with 25mm dia PVC conduit with all accessories for warning lamp wiring.
309Supply & Laying of12 Run 1.5sqmm PVC insulated multistrand copper wire with 25mm dia PVC conduit with all accessories for Chiller Remote panel wiring.
310POINT WIRING Supply, Installation, Testing & Commisioning of 3R1.5sqmm PVC insulated FR copper wire with FRPVC conduit along with Modular6A one wayswitch with moulded front plate GI anodised enclosure and other associated accessories as required as per the site condition
311PRIMARY POINT
312Dimmer light point With Dimmer
313SOCKETS
314Supply, Installation, Testing & Commissioning of 1nos 6A socket and 1no 6A switch and with moulded frontplate GIanodised enclosure and other associated accessories in the work station as required as per the site conditions. Bunker, Consol Room & TPS Room (Raw Power)
315Supply, Installation, Testing & Commissioning of 1no 6/13A socket and 1no 6A switch and with moulded frontplate GIanodised enclosure and other associated accessories in the work station as required as per the site conditions. Bunker, Consol Room & TPS Room (UPS Power)
316Supply, Installation, Testing & Commissioning of 1 no 16A switched socket with moulded frontplate GIanodised enclosureand other associated accessories as per the site conditions.( with indicator)
317INSTALLATION OF LIGHT FITTINGS
318Supply,Erection, Testing and Commisioining of 600mm x 600mm 36W LED light fittingalong with electronic ballasts with all accessories and interconnection
319Supply,Erection, Testing and Commisioining of 6" x 6" 18W LED light fittingalong with electronic ballasts with all accessories and interconnection
320Supply,Erection, Testing and Commisioining of single12 V,15W LED fitting(or) 230V, 60WRecessed fixed type halogen fitting with copper ballast, lamps all accessories and interconnection ( Dimmer Light )
321Supply,Erection, Testing and Commisioining of LED strip light
322DATA, VOICE & Network (Consile Room & TPS Room)
323Supply,Laying, Testing and Commissioning of Cat - 6 UTPCable with FR PVC conduit and all accessories as required. ( Voice and Data cable )
324Supply,Fixing, Testing and Commissioning of Infermation Outlet for Cat-6 UTP cable quader front plate with Back box and all accessories as required.
325Supply,Fixing, Testing and Commissioning ofTelephone Outletfront plate with Back box and all accessories as required.
326Supply,Fixing, Testing and Commissioning of 6U Communication Rack
327Supply & Fixing of 10/100/1000 mbps 24port T Switch with 24 port patch panel
328Supply of 1 mtr Pach card
329EARTHING
330Supply & Laying of 8 SWG bare Cu. Wire
331Supply and Installation of 12 way earth bus with all accessories as required.
332Supply, Installation, Testing & Commisioning of 10 Feet long 600 X 600 X 3mm copper plate or Chemical Earth Pit for Machine and UPS Netural and body earth
333MISCELLANEOUS
334Supply & Laying of20mm PVC hose
335Supply & Laying of25mm PVC hose
336Supply, Fixing of 105 X 50 mm CMS Tray for control room
337Warning Lamp EM OFF switch & LMO switch
338Supply & Fixing of Emergency Stop switch and system On switch with base box
339Supply and fixing of Magnetic Door switch
340Supply,Erection, Testing and Commisioining of LED Warning Lamp for Red, Green & Yellow .
341Supply, ,Erection, Testing and Commissioning of Last man out control unit, Last man out switch with indicator, buzzer and External wiring kit (1.0 sq.mm cu. Wire & pipes)
342Fire Alarm System
343Supply, Fixing, Testing & Commissioning of 2 Zone Conventional Fire Alarm Panel with complete set.
344Supply, Fixing, Testing & Commissioning of conventionalSmoke Detectors with base
345Supply, Erection, Testing & Commissioning of Conventional Manual Call Point.
346Supply, Erection, Testing & Commissioning of Conventional Hooter/ Sounders
347Supply and Laying of 2 core 1.5 sqmm Copper armoured cable
348Carbon-di- oxide type fire extinguisher of 4.5 kgs. Capacity, CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel, with wheel type valve, discharge nozzle, bend & horn, signages etc. complete,
349CC TV
350Supply, Fixing, Testing & Commissioning of HD IR CCD 1/3” color camera. (Doom or Bullet modal camera)
351Supply, Fixing, Testing & Commissioning of HD Mini Speed Dome IR Camera. with 10 to 15X Zoom, Auto iris lens, RS485 Control PTZ Camera
352Supply, Fixing, Testing & Commissioning of 4 Chenal HD DVR
353Supply, Fixing, Testing & Commissioning of PTZ keyboard with joystick
354Supply, Fixing, Testing & Commissioning of 24” LED TV
355Supply, Fixing, Testing & Commissioning of 12V DC power supply for camera
356Supply and laying of 3+1 RG 58 CCTV cable
357Tack/Tack Back System
358Supply, Fixing, Testing & Commissioning of Tack /Tack Back Systems comprises of Console with Mike (inbled amp.) Ceiling Speaker or Wall mount Speaker - 1no.
359Supply and laying of two core screened cable
360Audio system for playing soft music inside the treatment room, control console, patient waiting area also to be supplied.
361TURNKEY WORKS FOR SITE PREPARATION OF Dr. B. Borooah Cancer Institrute, Guwhati
362A)CIVIL WORKS
363Demolishing RCC work including stacking of steel bars and disposal of unserviceable material as directed for all levels
364Dismantling and removing the existing door and window frame (chowkath) both wooden and steel of different sizes without damaging the walls and removing the frame and necessary repairs to the edges of the walls as directed for all levels. (ii) Area of door/window above 3.00 m2
365Demolishing CC floors of various thickness including top layer and base course and disposal of debris as directed for all levels.
366Providing and laying plain/reinforced cement croncrete works cement, coarse sand & 20mm down graded stone aggregate including dewatering if necessary, and curing complete but excluding cost of form work and reinforcement for reinforced cement concrete work (form work and reinforcement will be measured and paid separately) (I) Using Mixer Machine (A) In substructure up to plinth level P) Using admixture, plasticiser etc for air entraining, water reducing purposes including addition of agent for changing normal setting time of concrete as required. b) M20 grade concrete or Prop. 1:1.5:3
367(B)In super structure from plinth level up to 1st floor level.P) Using admixture, plasticiser etc for air entraining, water reducing purposes including addition of agent for changing normal setting time of concrete as required. b) M20 grade concrete or Prop. 1:1.5:3
368Providing form work of 12mm thick Plywood Board so as to give a rough finish including centering, shattering, strutting and propping etc., height of propping and centering below supporting floor to ceiling not exceeding 4.0M and removal of the same for in situ reinforced concrete and plain concrete work in: Flat Surfaces such as soffits of suspended floors, roofs, landings, cantelever slabs, chajjas, balconies and the like. (b) Floors etc. above 200mm in thickness.
369Supplying, fitting and fixing in position reinforcement bars conforming to relevant I.S. Code for R.C.C. work/ R.B. walling including straightening, cleaning, cutting and bending to proper shapes and length as per details, supplying and binding with 20G annealed black wire and placing in position with proper blocks, supports, chairs, spacers etc. complete. (No extra measurement for lap, hook, chair, anchor etc. will be entertained in the measurement as they are included in the rate) (Upto 1st floor level) a) From Primary Producer (i) TMT Corrosion resistant steel (CRS) reiforcement bar
370Plain cement concrete works with coarse aggregate of sizes 13mm to 32mm in foundation bed for footing steps, walls, brick works etc. as directed and specified including dewatering if necessary, and curing complete (shuttering where necessary shall be measured and paid separately). (a) In prop 1cement: 3 sand :6 coarse aggregate by volume
37120 mm thick Cement plaster in two coats on single or half brickwalls for interior plastering up to 1st floor level including arises, internal rounded angles,chamfers and / or rounded angles not exceeding 80mm in girth and finished even and smooth including curing complete as directed. B) On fair side (backing coat 10 mm and finishing coat 10mm thick) a) In cement mortar 1:3
372Providing polished granite slab of approved quality, size, shape and thickness not less than 18 mm on floors, skirtings, treads and risers of steps over cement mortar bed 15 mm thick in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with Fix-A-Tile ) /white cement slurry mixed with approved pigment to match the shade of granite slab, complete at all levels as specified and directed. (Cement plastering to be measured and paid separately). (Coloured pigment should be in conformity with colour of slab and as approved and directed by the Department). (iii) Deluxe Quality (i) With Fix-A-Tile
373Providing VITRIFIED floor tiles of approved quality of specified size, shape and thickness not less than 18mm on floors, skirtings, risers and treads of steps over 15 mm thick base ofcement mortar in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with Fix-A-Tilewhite cement slurry mixed with approved pigment to match shade of tiles, mixed with approved pigment to match the shade of the tiles, complete at all levels as specified and directed.(Coloured pigment should be in conformity with colour of tiles and as approved and directed by the Department) c) Delux range ii) Of size 1200mmx1600mm and above
374Providing polished vitrified wall tiles of approved quality, size, shape and thickness not less than 8mm on walls and skirtings over cement mortar bed 10 mm thick in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with Fix-A-Tile/white cement slurry mixed with approved pigment to match shade of tilesc complete at all levels as specified and directed. (coloured pigment should be in conformity with colour of tiles and as approved and directed by the department). iv) Of size300mmx900mm and above
375Supplying fitting and fixing of UPVC partition wall 5 mm frosted glass
376Supplying fitting and fixing of UPVC double leaf door 5 mm frosted glass
377Supplying fitting and fixing of UPVC sliding door door 5 mm frosted glass
378Supplying fitting and fixing of UPVCsliding window 5 mm frosted glass
379Providing wood work in frame (chowkaths) of doors, windows, clerestory windows and other similar works wrought, framed and fixed in position in contact with C.C or brick masonry wall including supplying, fitting and fixing with M.S. hold fast (40mmx3mmx250mm) as per design embeded in cement concrete block in proportion 1:2:4 and with two coats of kiricide oiling to the timber faces in contact with C.C and masonry as directed and specified. (a)With sal wood
380Providing and fixing flush door shutters solid core construction with frame of 1st class hard wood with cross band and face veneered ply wood face panels conforming to relevent I.S code including oxidised iron butt hinges (100mm x 75mm x 3.5mm) 6 nos with necessary wood screws. a) Decorative type face panel and block board core. (iii) 30 mm thick .
381Supplying, fitting, fixing and painting where necessary (one coat primer and two coats of paint) suspended ceiling which includes G.I. perimeter channels of size 0.55mm thick (having one flange of 20mm and another flange of 30mm and a web of 27mm) along with perimeter of ceiling, screw fixed to brick wall/ partition with the help of nylon sleeves and screws, at 610mm c/c. Then suspending G.I. intermediate channels of size 45mm (0.9mm thick with twoequal flanges of15mm each) from the soffit at 1220mm c/c with ceiling angle of width 25mmx10mmx0.55mm thick fixed to soffit with G.I.cleat and steel expansion fasteners. Ceiling section of 0.55mm thickness having knurled web of 51.5mm and two equal flanges of 26mm each with lips of 10.5mm are then fixed to the intermediate channel with the help of connecting clip and in direction perpendicular to the intermediate channel at 298mm c/c. Then 12.5mm thick square edge Fulltone/ Sundance/ Cratone/ Louvertone/ Textured. Gypboard panels of size 595mmx595mm (conforming to IS:2095-1982) is then screw fixed to ceiling section with 25mm long drywall screws at 290mm c/c. Screw fixing is done mechanically either with screw driver or drilling machine with suitable attachment. Finally, the boards are to be jointed and finished so as to have a flush look which includes filling and finishing the tapered and square edges of the boards with jointing compound, joint paper tape and two coats of drywall topcoat suitable for Gypboard complete at all levels as specified and directed. (For light fittings, grill diffusers etc. cut out to be made with the frame of perimeter channel supported suitably and measured and paid separately as and where necessary). (Glass wool to be measured and paid separately). M/F Frame Work with Acoustic Type Slit Gypboard (Louvertone) Tiles (NRC value 0.72 with 50mm glass wool mat backing) 12.5mm thick.
382Providing surface preparation for walls, celling etc.using average 1.50 mm thick plaster of paris including clearing, rubbing with sand paper, filling gaps, depression etc. where necessary, with chalk powder and and plaster of paris paste, making the surface even and smooth completeat all levels as specified and directed.
383Wall painting (two coats) with Plastic emulsion paint on new surface to give an even shade after throughly brushing the surfaces free from mortar droppings and other foreign matter and sand papered smooth. (a).Plastic Emulsion Paint
384Extra over item no 13.4.7 above for every subsequent coat of wall painting with Plastic Emulsion Paint. (a).Plastic Emulsion Paint
385WATER PROOFING OF CHAJJAS, ROOF SLABS, TERRACES, SUNKEN SLABS, SEPTIC TANK,OH TANK, RAFT SLAB IN BASEMENT, WALLS ETC. (B)Using Polymer based cement mortar.
386Supplying fitting and fixing of SKY VIEW
387Providing, fitting, hoisting and fixing of roof trusses fabricated out ofcombination of anytwo or all of the following sections (i) Square section (ii) Rectangular Hollow section of specification RSH/SHS and (iii) M.S. circular hlollow section of Grade 210 including purlins, bottom runners and providing M.S. cleat, M.S. angle base plank, bolts and nuts with red oxide primer including fitting bottom runner and cleat etc. for fixing ceiling joist as per design complete as directed as per specifications. a) Using RHS/SHS of Grade 310 conforming to relevant I.S. code 4923 : 1997
388Providing Pre Painted Galvanized IronSheetRoofing (PPGI) at all levels including fitting and fixing with self drilling, self tapping screws complete. (Roof trusses, purlins etc. to be measured and paid separately.) as directed by the Departement (v) 0.80 mm thick
389Earth/ sand filling in plinth in layers not more than 150mm thick including necessary carriage, watering, ramming etc. complete as directed and specified including payment of land compensation, forest royalty, sales tax and other duties and taxes as may be necessary. (b) With hill sand obtained by truck carriage loading and unloading, and carriage to the site of work.
390Providing soling in foundation and under floorwith stone/ best quality picked jhama brick, sand packed and laid to level and in panel after preparing the subgrade as directed including all labourand materials and if necessary dewatering, complete. (a).Brick on flat soling.
391230mm thick brick wall in cement morter with 1st class brick including racking out joints and curing complete as directed in structure (II) In superstructure above plinth level up to 1st floor level. (a). In proportion 1:3.(1 cement:3 sand)
392Supplying, fitting and fixing chain link fencing of 10 S.W.G, G.I. Wire 50mm x50mm mesh fitted to M.S angle iron post at 2000mm apart of specification detailed below including supplying, fitting and fixing hooks, eye bolts with nuts, staples and bolts including three horizontal lines of G.I wire 10 S.W.G at top,middle and bottom and with one vertical line to each fencing post for keeping the fencing tight and erect complete, including one coat of primer painting to M.S angle iron post in P.C.C base etc. with following. a) Corner and end posts with M.S angle of size 50mmx50mmx 5mm and length not less than 1800mm only duly slotted and bottom torqued with two numbers as stay posts..
393Supply, Installation, Fixing of DRY CHEMICAL POWDER Fire Extinguisher confirming to IS: 2171 with ISI mark and CO2 cartridge will be confirming to IS: 4947 with ISI mark, Powder will be confirming to IS: 4308 with ISI Mark (5 KG)
394Wall panelling with ply and mica pesting
395Finishingold/ new wall with water proofing weathercoat smooth anti-fungal premium textured exterior finish ofrequired shadeafter clering and clearing the surfaces etc.including scaffolding complete as directed at alllevels (two coats).
396B) EXTERNAL ELECTRIFICATION WORKS
397Supplying including installation, commissioning of vermin and dust proof totally enclosed cubical indoor type floor/wall mounting compartmentalize panel board of size 0.95M X 1.30MX 0.40M made of 16 SWG1.66 m thick C.R. sheet and40mm X 40mm X 5mm size angle having 4 no legs at the bottom complete painting with 2 coats of Red Oxide metal primer and 2 coats of Enamel paint. The panel board is to be erected in 1 : 3 : 6 PCC foundation including brick soling / grouting etc. complete neatly Wiring done with provision for one no 400A 4pole MCCB or Switch Fuse Unit as incomer and provision for 4nos DP or TPN out going as specified and directed by the deptt. confirming to IP 43 protection comprising of the following electrical items: 1. 40mm X 5mm 4 strip copper Bus - Bar 1.20 M length each i20mm X 3mm 4 strip copper Bus-Bar 0.5M each 4 sets 2. Digital 3 Phase Voltmeter Accuracy class 0.5- 1 no 3. Digital 3 Phase Ammeter Accuracy class 0.5- 1 no 4. Pilot Lamp with integral ckt LED 110- 230 V (Red, Yellow,& Blue - 3 no 5. Voltmeter & Ammeter Selector Switch- 2 no 6. 2 A Slide fuse unit - 3nos (Incoming & Outgoing Switch Gear of reqd. rating will be measured and paid separately)
398Supply and laying of following size PVC/XLPE insulated and PVC sheathed 1.1 KV GSolid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour (Aluminium for single core up to 70 sq mm balance Aluminium strip, Galvanised for cables up to 2x10 sq mm.3x10 sq mm,4x6 sq mm balance all galvanised steel strip) , extruded PVC Type ST2 sheathed, 650/1100V grade as per IS 7908(Part 1)1988 armoured U.G. cableU.G. cable laid in ground/partially in air (as required for termination over groundincluding excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris etto proper place as specified and directed by the deptt.. 3 & 1/2 Core A2XFY 240.00 Sq.mm.3 & 1/2 Core armoured U.G. cable Note:From Main distribution panel to Machine panel
399Supply and laying of following size PVC/XLPE insulated and PVC sheathed 1.1 KV GSolid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour (Aluminium for single core up to 70 sq mm balance Aluminium strip, Galvanised for cables up to 2x10 sq mm.3x10 sq mm,4x6 sq mm balance all galvanised steel strip) , extruded PVC Type ST2 sheathed, 650/1100V grade as per IS 7908(Part 1)1988 armoured U.G. cableU.G. cable laid in ground/partially in air (as required for termination over groundincluding excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris etto proper place as specified and directed by the deptt. 3 & 1/2 Core A2XFY 185.00 Sq.mm.3 & 1/2 Core armoured U.G. cable Note:From panel to UPS and UPS to machine control panel
400Supply, installation & testing of Copper Plate earth station with600 mmx600 mmx3 mm copper earth plate withnecessary 40 mm dia. G.I. medium duty watering pipewith G.I. Fittings such as Socket, Tee, elbow, nipple and 50 mmx40 mm G.I. reducing socket for funnel including locking arrangement with 300 mmx300 mmx6 mm C.I. hinged cover plate complete with digging of earth pit, construction of brick chamber and plastering of both inner & outer surface of wall as specified and directed by the deptt . Note:For machine,Chiller and UPS.
401Extra for using salt (5 Kand Charcoal (96 Kin G.I./Copper plate Earth Station pit to provide low impedance ground in location of high soil resistivity as and when required and specified by the deptt .
402Supply, fitting & fixing 20 mmx3 mm Copper strips drawn on vertically or horizontally on building wall/parapet wall in surface system complete with supply of BrassNuts & Bolts, Screws etc including riveting, soldering and making connection as approved by the Deptt.)with earth electrode copper strips and Lightning Arrestor etc. as specified and directed by the deptt.
403Supply and laying of following size PVC/XLPE insulated and PVC sheathed 1.1 KV GSolid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour (Aluminium for single core up to 70 sq mm balance Aluminium strip, Galvanised for cables up to 2x10 sq mm.3x10 sq mm,4x6 sq mm balance all galvanised steel strip) , extruded PVC Type ST2 sheathed, 650/1100V grade as per IS 7908(Part 1)1988 armoured U.G. cableU.G. cable laid in ground/partially in air (as required for termination over groundincluding excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris etto proper place as specified and directed by the deptt. 3 & 1/2 Core A2XFY 400.00 Sq.mm.3 & 1/2 Core armoured U.G. cable
404C) INTERNAL ELECTRIFICATION WORKS
405Wiring for circuit wiring with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts in surface/ recessedPVCconduit wiring system. With 2 x 1.5 sq. mm. cable in 20 mm dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - IIIconduit. Note: For Door interlock,Fault ceiling light,Laser,CCTV,Public Adress System,Ceiling Fan,Emergency Switch
4062.7.1Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts PVC conduit including earth continuity in surface/ recessed 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit wiring system. With 2 x 2.5 sq. mm. + earth continuity with 1x1.5 sq. mm. in 20 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - IIIconduit Note:For 6A and 16A power points
4072.7.2Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 voltsPVC conduitincluding earth continuity in surface/ recessed 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit wiring system. With 2 x 4 sq. mm. + earth continuity with 1x2.5 sq. mm. cable in 20 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - IIIconduit. Note: For Air-Conditioner
408Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 voltsPVC conduit including earth continuity in surface/ recessed 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit wiring system. With 2 x 10 sq. mm. + earth continuity with 1x 6 sq. mm. cable in 25 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - IIIconduit.
409SB. 8.28Supplying with fitting fixing of 6 amp one way modular clip in switch,including making necessary connection as per direction of department.
410Supplying including installation of socket outlet 6/16 Amps 3/5 pin combine shuttered complete , including making necessary connection as per direction of department.
411Supplying with fitting fixing of 10/16 amp one way modular clip in switch,including making necessary connection as per direction of department.
412Supplying including and fixing of following Moulded PVC boxes for in surface system complete as per direction of department. 8 module surface Moulded PVC boxes.
413Supplying including fitting fixing of following front plate of suitable colour as per direction of department. 8 module
414Supplying including and fixing of following Moulded PVC boxes in surface system complete as per direction of department. 12 module horizontal surface Moulded PVC boxes
415Supplying including fitting fixing of followingfront plate of suitable colour as per direction of department. 12 module
416Supplying with installation testing and commissioning of Hi -- wall 4 STAR rating non ducted split typeair conditioner of the following capacity with cordless remote complete withindoor and outdoor unit, copper pipeand electrical connection as approved by the Deptt.)up to 5 m between the room unit and out door unit as directed by the department. 2 Ton capacity R410
417Supplying with fitting and fixingVoltage stabilizer of the following specification complete including making necessary connection as approved, specified and directed by the deptt. 5.0 KVA Automatic Input 120-280 V Out put 200-240 V
418Supplying with fitting and fixing of Angle iron framing made 50 MMx50 MMx5 MM size angle iron for accommodation of 1.00 Ton to 2.00 Ton Window/split type A.C. Machine
419Supplying with fitting and fixing of Single Phase Modular A.C Starter switch of the following specification complete including making necessary connection as specified and directed by the deptt.
420Supplying including fitting fixing of followingA.C. Ceiling fan complete with all accessories like down rod, canopy etc. of following sweeps with making necessary connection as approved by the Deptt.)as required complete and as directed by the Department [Without regulator]. Premium model1400 mm Sweep.
421Supplying with fitting and fixing of 120 watt electronic modular STEP speed control 2 - module type including making necessary connection as per direction of department. 120 watt electronic modular step speed control2 - module type
422Supplying with fitting and fixing panel mounting open execution 35/36KA 415V 50Hz 3P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure)of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 35/36 KA 415V 50 Hz 3P MCCB 400A
423Supplying with fitting and fixing panel mounting open execution 25 KA 415V 50Hz 3P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure of the following capacity complete with making necessary connection as approved by the Deptt. as specified and directed by the deptt. 25 KA 415V 50 Hz 3P MCCB 125A
424Supplying with fitting and fixing 4P 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series 100A
425Supplying with fitting and fixing 4P 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series 63A
426Supplying with fitting and fixing single Pole 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt.C Series 6 to 32A
427Supplying with fitting and fixing single Pole 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt.B Series 6 to 32A
428CC Camera
429Public Adress System
430View Box
431Supplying with fitting and fixing of 12Watt,round LED ceiling light with frame
432Supplying including fitting fixing of followingA.C. Exhaust fan in the existing hole on the wall of following sweeps with making necessary connection as approved by the Deptt.)as required complete and as directed by the Department. Heavy Duty 450 mm sweep 900 RPM Single phase
433D) FURNITURE WORKS
434Suppying and installation of coloured TV 22" flat LED wall mountingas directed by the Department.
435Supplying fitting and fixing of furniture Rack, table, store almirah, Revolving chair etc. as required.
436A) Computer Chair (6 nos for control console & 6 nos. for TPS room)
437B) Master table for use in computer in Control room made of best quality water proof green ply 18mm thick finishing with sunmika size (10" x 3"x2.5") (1 no for control console & 1 no. for TPS room)
438C) Wall mounting manual shelf Control room made of best quality water proof green ply 18mm thick finishing with sunmika size (6"x2"x16"")
439D) Shelf inside the LAbunkermade of best quality water proof green ply 18mm thick finishing with sunmika size (8" x 6"x2")
440E) Sypplying of Decorative & comfortable 3-seater patient waiting chairmust be approved by the Department.
441Cat (B) - Buy Back Items
442Buy-Back (ie minus)Amount of Old Linear Accelerator (Tomotherapy) at ACTREC Kharghar
443Buy-Back (ie minus) Amount of Old Linear Accelerator (Tomotherapy) at TMH Mumbai