Housing Urban and Rular Development Government Departments Closing in 0 days TDR #31968827

Supplying , Installation, Testing And Commissioning Of Fire Alram System At Circuit House Manali District Kullu Hp

Issued by Government Departments · Kullu, Himachal Pradesh
Tender Value
8 Lakhs
Estimated cost
Bid Submission
02 May 2022
0 days left
EMD
16050
Bank guarantee accepted
Document Fee
350
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Kullu → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Supplying , Installation, Testing And Commissioning Of Fire Alram System At Circuit House Manali District Kullu Hp

BOQ

Name of Work: Supplying,Installation, Testing & Commissioning of Fire Alarm System at Circuit House Manali District Kullu HP.
Sl. No. Item Description
1SITC of UL268 6th and 7th edition compliance and FM approved Intelligent Addressable multi-criteria detector (optical and thermal sensors) complete with standard base,facility to mount in different comprehensive environment, Tri-color detector-status LED with 360 ° view, microprocessor circuitry with error check; detector self-diagnostics and supervision programs,Rate-of-Rise Detection: 15°F / min. (8.3°C / min.) - Fixed: 135°F (57°C) , Field programmable as rate-of-rise or fixed temperature, Polarity insensitive, Superior EMI and RFI immunity, RoHS compliant. Detector shall have in-built isolator for better reliability, circuit integrity and advanced fault finding. Manufacturers not having in-built Isolator feature in detector shall consider Isolator base in place of standard base OR separate Isolator before and after every detector to comply the same without any extra cost. Make : Cerberus by Siemens/ Esser by Honeywell/Autronica
2SITC of UL Listed Sounder cum Strobe rated at 75 dBA @ 3m for Audible annunciation and 75cd flashintg at 1 Hz for visual indication. Make : Cerberus by Siemens/ Esser by Honeywell/Autronica
3SITC of UL listed and FM approved Intelligent addressable Class X type (Style 7), Manual Pull Station Single Action, Shock and Vibration Resistant, with built in dual isolator, polarity insensitive, Tri color LED for status (Green for Normal,Yellow for Faulty and RED for activation), T-45 Key Reset lockset for easy maintenance, Operating Temp and RH: 0-49degC and <=95%. MCP shall have in-built isolator for better reliability, circuit integrity and advanced fault finding. Manufacturers not having in-built Isolator feature shall provide separate Isolator before and after every MCP to comply the same without any extra cost. Make : Cerberus by Siemens/ Esser by Honeywell/Autronica
4SITC of UL listed and FM approved Intelligent addressable Class X type (Style 7), Control Module with built in dual isolator, polarity insensitive, Tri color LED for status (Green for Normal,Yellow for Faulty and RED for activation), Operating Temp and RH: 0-49degC and <=95%. Module shall have in-built isolator for better reliability, circuit integrity and advanced fault finding. Manufacturers not having in-built Isolator feature shall provide separate Isolator before and after every Module to comply the same without any extra cost. (For AHU & Staircase Pressurization Fans, Hooters / Sounders / Strobes etc.) Make : Cerberus by Siemens/ Esser by Honeywell/Autronica
5SITC of UL listed and FM approved Intelligent addressable Class X type (Style 7), Mini Monitor Module with built in dual isolator, polarity insensitive, Tri color LED for status (Green for Normal,Yellow for Faulty and RED for activation), Operating Temp and RH: 0-49degC and <=95%. Module shall have in-built isolator for better reliability, circuit integrity and advanced fault finding. Manufacturers not having in-built Isolator feature shall provide separate Isolator before and after every Module to comply the same without any extra cost. (For Sprinkler Flow Switches and door holders) Make : Cerberus by Siemens/ Esser by Honeywell/Autronica
6SITC ofUL 864 10th edition UL Listed and FM approvedAnalog addressable 2 Loop Fire Alarm Control Panel having the total panel capacity of 252 devices. The panel shall be able to give pin point location of all Fire /fault and Isolation conditions of addressable units via the address codes.The panel shall have the capacity of storing upto 10000 events. Further, the panel must be able to automatically switch ON /OFF respective control module whenever any alarm is triggered. The panel should have inbuilt common Alarm, Fault and monitored sounder output. The panel shall have a2”x4-3/4”Size VGA monochromoe LCD display and having maximum 320 (8 x 40) Characters in the display with optional 24 Zones LED indicators. The panel shall have a built in power supply of 170 Watts and battery charger. Battery charger shall be able to charge the system batteries of up to 33AH capacity. The Panel shall have the capacity of connecting additional 31 panels or Network terminals using network card, with redundancy in the network. The panel shall have the capacity of connecting maximum 16 Remote terminals /16 remote displays or combined by using 2 X RS 485 Card. Make : Cerberus by Siemens/ Esser by Honeywell/Autronica
7SITC ofUL Listed and FM approved Repeater Panel. The panel shall be able to give location ofall fire/fault and Isolation conditions of addressable units of main Fire Alarm panel via the address codes and also having remote-system-control capabilities.The panel shall have a2”x4-3/4”Size VGA monochrome LCD display andhaving maximum 320 (8 x 40) Characters in the display along with RS485 Module. Make : Cerberus by Siemens/ Esser by Honeywell/Autronica
8Supply and erection of PVC insulated two core FR copper conductor cable ISI marked in PVC pipe recess/surface complete in all respect i) 2 core x 1.5 sq. mmMake - Finolex / Polycab /Hawells
9Supply and erection of PVC pipe 25mm dia ISI marked (Medium) recessed in wall / ceiling etc. including the cost of PVC bends , inspection boxes , iron hooks and cement concrete etc. complete in all respect upto the entire satisfaction of Engineer-in-charge of work. Make: BEC/Diplast /Polyplast
10Supply,Installation,Testingandcommissioning of IEC 60849 Approved Glow Type EXIT/Stair /Emergency Exit Sign Board as finalized by EngineerIn Charge,onbothsideshowing marking (running man, Arrow and Exit) and hangedwiththeceilingwithchainand fastener completetheworkuptotheentiresatisfactionof Engineer In Charge. Make: PES /HEINRICH/ OMEX/ COOPER/Agni/Falcon
11Supply,installation ,testing and commissioning ofwall mounted 6 watt speaker as required complete in all respect. Make: JBL/Honelywell/Ahuja
12Supply, Installation & comm. Of 120 W Power Amplifier as required complete in all respect. Make: Honeywell, Ahuja, JBL
13Supply, installation ,testing and commissioning of 6 zone controller /paging control unit as required compelete in all respect.Make: Honeywell, Ahuja, JBL.

AI Tender Summary

OUR REF NO 31968827
AUTHORITY Government Departments
TENDER VALUE 8 Lakhs
LAST DATE 02-05-2022
Authority
Authority Name Public Works Department
Work Description Supplying , Installation, Testing And Commissioning Of Fire Alram System At Circuit House Manali District Kullu Hp
Basic Detail
Tender No PW/MED/TA/NIT/ e-notice/21-22-144-154 dt 16.04.22
Bidding Type Tender
Location
City Kullu
State Himachal Pradesh
Key Dates
Publish Date 25 Apr 2022
Submission Date 02 May 2022
Open Date 02 May 2022
Finance
Tender Value 8 Lakhs
Tender Fee 350
EMD 16050
Exemption Not Available
Document List
1aa4dd20-f26d-4d31-aaa3-c3b3c6944e6b.html
biddocument.pdf
BOQ_90557.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Apr 25, 2022
11:30 IST

Tender Published

Tender notice published.

Completed
May 02, 2022
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
May 02, 2022

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

1aa4dd20-f26d-4d31-aaa3-c3b3c6944e6b.html

pdf

biddocument.pdf

xls

BOQ_90557.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender