Military Engineer Services-MES has published Day To Day Ht Lt Complaint For Electric Distribution Network And Allied Works Of Alpha Power House And Allenby Line Power House In Sector C Under Ge Utility Ambala Cantt. Submission Date for this Tender is 19-05-2022. Power Distribution Work Tenders in ambala Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

31927421
Corrigendum : Day To Day Ht Lt Complaint For Electric Distribution Network And Allied Works Of Alpha Power House And Allenby Line Power House In Sector C Under Ge Utility Ambala Cantt
Open Tender
Indian
Haryana
ambala
19-05-2022

Tender Details

Day To Day Ht Lt Complaint For Electric Distribution Network And Allied Works Of Alpha Power House And Allenby Line Power House In Sector C Under Ge Utility Ambala Cantt

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 26-Apr-2022 AMENDMENT TO TENDER PAGE Other 12-05-2022
2 26-Apr-2022 AMENDMENT TO BOQ BOQ 12-05-2022
3 12-May-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 19-05-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 106980.0 /-
Tender Value
INR 35.66 Lakhs /-

BOQ Items

Name of Work: DAY TO DAY HT/LT COMPLAINT FOR ELECTRIC DISTRIBUTION NETWORK AND ALLIED WORKS OF ALPHA POWER HOUSE AND ALLENBY LINE POWER HOUSE IN SECTOR "C" UNDER GE (U) AMBALA CANTT.
Sl. No. Item Description
1Labour only for attending complaint under Alpha Power House of HT electric distribution networkUG /OH in day to day maintenance by attendng daily complaints including Sunday and other holidays for round the clockand making the same serviceable in all respects alongwith replacement of any major part but including small length of cable (not more than 20 mtr), adhesive tape and other connected minor accessories shall also include to visual inspection of OH lines, Earth Resistance of transformer, switch gear GODO etc.Qouted rate also include excavation offaulty cable are making seviceable with accessories like joints, Fuze wire for GOD`s Note ‘A’ :- (i)Cost of materials for laying of cablesstrecthing of OH conductor, burnt out joints, fuse wires, insulator andjumper will be measured and paid separately under relevant items as Material & Labour. (ii) All T&P required for electrification work shall be provided by contractor at own arrangements to the trades mans & helpers. (iii) Contractor will supply following well experienced and well conversant manpower against these items during round the clock (03 shifts)Electrician -01 Nos & Helper -02 Nosat a time for attending HT distribution complaint all working days including Sunday & all Holidays. (iv) Contractor will provide well experienced and well conversant of one person for lodging the HT/LT complaint in complaint cell of each power houseduring workinghours from 0900hrs to 1700hrs on all working days including Sunday & all Holidays.
2Labour only for attending complaint under Allenby Line Power House of HT electric distribution networkUG /OH in day to day maintenance by attendng daily complaints including Sunday and other holidays for round the clockand making the same serviceable in all respects alongwith replacement of any major part but including small length of cable (not more than 20 mtr), adhesive tape and other connected minor accessories shall also include to visual inspection of OH lines, Earth Resistance of transformer, switch gear GODO etc.Qouted rate also include excavation offaulty cable are making seviceable with accessories like joints, Fuze wire for GOD`s Note ‘A’ :- (i)Cost of materials for laying of cablesstrecthing of OH conductor, burnt out joints, fuse wires, insulator andjumper will be measured and paid separately under relevant items as Material & Labour. (ii) All T&P required for electrification work shall be provided by contractor at own arrangements to the trades mans & helpers . (iii) Contractor will supply following well experienced and well conversant manpower against these items during round the clock (03 shifts)Electrician -01 Nos & Helper -02 Nosat a time for attending HT distribution complaint all working days including Sunday & all Holidays. (iv) Contractor will provide well experienced and well conversant of one person for lodging the complaint in complaint cell of each power houseduring workinghours from 0900hrs to 1700hrs on all working days including Sunday & all Holidays.
3Labour only for attending complaint under Alpha Power House of LT electric distribution networkUG /OH ofall nature likeNo light, faulty insulator, broken conductor& cable fault , burnt out MCCB`s, MCBs, isolators, switch fuses,service cables etc upto DB in buildings/OTM in Sector `C`area complete all as specified and as directed by Engineer-in-Charge.Cost of aluminium lugssaddle of any size for fixing of cables on walls, for finishing work and all fixing accessories required for rectifying the complaintsitems are included in the ratequoted by contractor. Note ‘A’ :- (i)Cost of materials for laying of cablesstrecthing of OH conductor, burnt out MCBs, MCCB`s will be measured and paid separately under relevant items as Material & Labour. (ii) All T&P required for electrification work shall be provided by contractor at own arrangements to the trades mans & helpers . (iii) Contractor will supply following well experienced and well conversant manpower against these items during round the clock (03 shifts)Electrician -01 Nos & Helper -02 Nosat a time for attending LT distribution complaint all working days including Sunday & all Holidays.
4Labour only for attending complaintAllenby Line Power House of LT electric distribution networkUG /OH ofall nature likeNo light, faulty insulator, broken conductor& cable fault , burnt out MCCB`s, MCBs, isolators, switch fuses,service cables etc upto DB in buildings/OTM in Sector `C`area complete all as specified and as directed by Engineer-in-Charge.Cost of aluminium lugssaddle of any size for fixing of cables on walls, for finishing work and all fixing accessories required for rectifying the complaintsitems are included in the ratequoted by contractor. Note ‘A’ :- (i)Cost of materials for laying of cablesstrecthing of OH conductor, burnt out MCBs, MCCB`s will be measured and paid separately under relevant items as Material & Labour. (ii) All T&P required for electrification work shall be provided by contractor at own arrangements to the trades mans & helpers. (iii) Contractor will supply following well experienced and well conversant manpower against these items during round the clock (03 shifts)Electrician -01 Nos & Helper -02 Nosat a time for attending LT distribution complaint all working days including Sunday & all Holidays. Note for items No 01 to 04 :- (i)The contractor may have to provided additional resources as per the direction of Engr-in-Charge for speedy disposal of complaints as andwhen required.Penal recovery at the rate of Rs 500/- per complaint per hour will be levied from the contractor in case of late attending of complaint after reasonable time or 2 hours whichever is more as decided by Engr-in-Chage / GE (ii)The scope of work cover all complaints received from above concern power houses will be lodged/docketed/attended/completed.The completion will be rendered on complaint register as well as on docket. Nature of fault may occurs given below :-
5Blown out fuses
6Faulty Insulator
7Loose GOD male & female contact
8Fault cable joint
9O/H conductor broken
10Broken jumpers
11Tightening of stay
12Stretching of broken loose fault conductor and binding on insulators up to 3 span
13Contractor will provide all the tools such as HT/LT meggar, Insulation Tester, Wrench, Rope, Bamboo ladder, search light and other tools and will maintain them in working condition all the time.
14Tightening of service connection as preventive maintenance
15Proper Uniform shall be provided by the contractor for pers employed on duty as desired by Engr-in-Charge.
16Tracing fault manually in LT/HT electric lines and underground cable network
17AC Complaints like connection / disconnecting
18Fault HT/LT switchgears
19Switching ON/OFF street lights at appropriate time as directed by JE/Engr-in-Charge.Penel recovery for Rs 100/- per day will be recovered if street light not put ON/OFF at appropriate time.
20The area covered under the above power house consists of HT/LT overhead lines. HT/LT underground cables, distribution transformers, HT/LT switch gears etc, including HT 11 KV incoming and numbers of outgoing HT feeders for the complete area.
21Any other electric complaint which is considered essential by the department.
22Confirmation on completion of any nature of major complaints will be intimated to JE concerned to the area or Engr-in-Charge immediately.
23Contractor will prepare the summary of complaints attended on monthly basis as per performa given by Engr-in-Charge.The summary will be submitted to Engr-in-Carge duly signed by JE and contractor at the end of month.
24The contractor will observe all labour laws as prevalent during the currency of work enacted by Central/State Deptt as well as Labour Commissioner Act.He shall also ensure, payment of minimum wages to the persons employed as per labour laws in vogue.
25Insurance, Education Qualification and experience cert for the personnel employed on duty shall be submitted to Engr-in-Charge before take over the installation.
26The contractor will provide the rain coats, gum boot and hand gloves in winter and summer season.
27Contractor will have no rights to object the work carrying out by other contractor at substation or HT/LT distribution system of the power house area under comprehensive maintenance. However necessary handing taking over the assets will be carried out between the agencies.
28Labour only for carry out visual inspection of transformer once in monthincluding minor maintenance like dusting, tightening of loose connection HT/LV Side and replacement of aluminium terminal and checking of transformer oil level, top up if required, checking of silca gel, heating/replacement of silca gel all as specified and as directed. T&P required for the job is deemed to be included in contract. The record of the same will be submitted in the performa as directed by Engr-in-Charge.
29Trimming of Tree branches falls into OH lines of HT/LT & minimum clearance of 3 Mtrfrom branches, proper shutdown will be taken and maintained in the register complete all as specified and as directed.
30Maintenance of sub Station including cleaning In /out of surroundings areas, zeroing of grass in two pole & four pole str ,loose filling of sands/pebbles as required,operations of GODs, Measuring of earth resistance of transformer,GODs ,LA & Switchgears ,Records of Earth resistance will be maintained Quarterly and signed by JE E/M & Engr-in-Charge all as specified and directed by Engr -in-Charge.
31Detecting of fault in cable HT/LT with fault locator equipment which is capable to supply as per cable of HT/LT (11 KV/430 Volts) serviceable to cable with Straight throughjoint of size 95-185 Sqmm. Notes (a) The HT fault which is detected through cable fault locator will only be paid under this item including transportation charges demed to be included in the quoted rate. (b)Charge of cable fault locator and DG set including transportation charge deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will lived Rs 500/ per hour. (d)Straight through joint , 95 to 185, sqm, Labour charges, excavation and making joint deemed to be including in quoted rate.
32Material & Labour indoor/outdoor end termination joint heat shrinkable 1100 Volts for XPLE cable of size 3.5/4.0 x 25-50 Sqmm.
33Material & Labour indoor/outdoor end termination joint heat shrinkable 1100 Volts for XPLE cable of size 3.5 x 70-120 Sqmm.
34Material & Labourindoor/outdoor end termination joint heat shrinkable 1100 Volts for XPLE cable of size 3.5 x 150-185 Sqmm.
35Material & Labour indoor/outdoor end termination joint heat shrinkable 1100 Volts for XPLE cable of size 3.50240-300 Sqmm.
36Material & Labour only straight through joint heat shrinkable 1100 Volts for XPLE cable of size 3.5/4 x 25-50 Sqmm.
37Material & Labour straight through joint heat shrinkable 1100 Volts for XPLE cable of size 3.5 x 70-120 Sqmm.
38Material & Labour straight through joint heat shrinkable 1100 Volts for XPLE cable of size 3.5 x 150-185 Sqmm.
39Material & Labour in replacement of old UNSV shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm complete all as specified and as directed.
40Material & Labour in replacement of old UNSV pintype insulator porcelain vitreous white or brown 1100 volts grade100 mm hight and 65 mm dia with GI spindle two washer and one GI nut.
41Material & Labour in replacement of aluminium conductor steel reinforced (ACSR).
42Material & Labour 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core.
43Material & Labour in replacement of MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type with thermal magnetic release complete all as specified and directed.
44Material & Labour in replacement MCCB TPN 250 Amps, 415 Volts, 40 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type.
45Material & Labour in replacement of MCCB TPN 160 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type.
46Supplyonly in replacementMCCB TPN 100 Amps, 415 Volts, 16/18 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type.
47Material & Labour aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 50 sqmm
48Material & Labour aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-185sqmm
49Material & Labour aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400 sqmm
50Suply only chemical (Round up) for remove unwanted vegitation/grass at various locations .
51Material & Labour straight through joint heat shrinkable 11 KV earthed system suitable for XLPE cable of size 3 x 70-120 Sqmm incl taking down old unsv HT joint complete all as directed by Engr-in-charge .
52Material & Labour straight through joint heat shrinkable 11 KV earthed system suitable for XLPE cable of size 3 x 150-240 Sqmm incl taking down old unsv HT joint complete all as directed by Engr-in-charge .
53Material & Labour cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPEcable 70-120 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as directed by Engr-in-charge .
54Material & Labour cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPEcable 150-240 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as directed by Engr-in-charge .
55Supply and fix in repair LT line separators 1100 V grade PVCspacer to separate LT conductor from each other 4 line as per IS complete all as specified and directed by Engr-in-Charge.
56Supply and fix in repair LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 5 line as per IS complete all as specified and directed by Engr-in-Charge.
57Re-stretching existing/retrievedACSR conductor on LT /HTpoleand binding conductor on insulator properly using new binding wire/jumper wire complete all as directed by Engr-in-Charge. Note : (i) Each Run of line conductor shall be measured & paid for separately.
58Material & Labour for in replacement of steel nuts, bolts, washers of any size required at siteas specified and directed by Engineer-in-Charge.
59M&Ldanger notice board/plate of 1.6mm thickmild steel sheet , vitreous enameled white with letters, figures , and conventional skull and bone in signalred colour and fixed with MS clamps bolts approved size ofr HT 25cmx20 cm.
60Supply only ofPVC self adhesive insulation tape ofSize .125mm x 25mm x 25 mtr long ISI marked all as specified and as directed.
61Supplyonly for loose filling in substations, under poles, under transformers of hard core broken to gauge not exc 63 mm broken stone/boulders incl leveling and spreading complete all as per direction of Engr-in-Charge.
62Anti climbing device, spikes type fabricated out of MS bars (round,square and flat) including nuts,bolts,washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed.
63M&L for providing plain cement concrete type C-2, 1:3:6 (using 40 mm graded crushed stone aggregate) as in coping, finished even and fair, including necessary from work all as directed.
64Material & Labour for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed inclusive of one primer coat, one under and one finishing coat of aluminium paint all as specified including taking down the old cross arms bracing complete all as directed.
65Supply only pouring new transformer oil as per IS : 335 (1993)for transformers installed at various site for topping up to achieve the di electric strength 60 KV at 4 mm gap, complete all as specified and as directed by Engr-in-Charge. Note : Transformer oil shall be brought at site in sealed container from the original manufacturer and shall be opened in front of Engr-in-charge, Container shall be deposited by the contractor to the deptt, which will be returned after completion of conract.
66Labour onlyin replacement of silica gel 4-6 mesh suitable for transformers breather andprotect VCBs, RMUs from moisture at 11 KV stations as per site requirement complete, all as specified and as directed.
67Note:-Amount of credit scheduleRs. 17455.00for retrieved materials as mentioned in Schedule of Credit attached in tender documents in pdf form which will be deducted offline while acceptance of tender.