Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 26-04-2022 | DATE EXTENSION | Date | 09-05-2022 |
| Sl. No. | Item Description |
| 1 | Maharashtra State Police HQ (DG Office)LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/M.H/SLD/T3A). |
| 2 | Cubical : Supplying and erecting GI sheet 1.6 mm (16 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and paintingwith one coat of red lead paint and 2 coats of enamel paint. |
| 3 | Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete as per specification no. CP-BB |
| 4 | Supplying, erecting & marking FPMCB 40A to 63A B series in provided distribution board as per specification no. SWSWR/MCB |
| 5 | Supplying, erecting & marking TPN MCB 6A to 32A, B series in provided distribution board as per specification no. SW-SWR/MCB |
| 6 | Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB |
| 7 | Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA forthree phase and neutral as per specification no. CP-SPD |
| 8 | Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON |
| 9 | Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 10 | Empty encloser for led driver : |
| 11 | Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 12 | Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 13 | Cable Tray : Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner. |
| 14 | Cable : |
| 15 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 16 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 17 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 18 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 19 | GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE |
| 20 | Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI |
| 21 | Exterior Luminaires : |
| 22 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 13° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 23 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 700 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 24 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 500 lumen (Tolerence ±15%), the power consumption should not be more than 10 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 25 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 900mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 26 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 20° x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 27 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 28 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 29 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 30 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 31 | Supply and erection of 4 meter high decorative pole of made in which pole pedstal should made of cast aluminium and pole should be GI in ribbed form. Thickness of the GI pole should be 3.2mm and aluminium pedstal thickness 6.5mm. Aluminum casted embalishments. Complete pole should be painted in PU paint and dark grey color. Base plate 300mm x 300mm x 10mm suitable to mount the pole on a concrete foundation. Pole must be connected to earthing. |
| 32 | Supply installation testing & commisioning of exterior rated posttop of system lumen output should not be less than 3500 lumen (Tolerence ±15%), the power consumption should not be more than 50 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen\"s Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage& Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass with impact resistance IK 08.LM80 |
| 33 | Supply installation testing & commisioning of customised decorative wall light as per detailed drawing no. LUC/PHQ/Wall-01 |
| 34 | Convocation Hall:LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/M.H/SLD/T3B). |
| 35 | Cubical : Supplying and erecting GI sheet 1.6 mm (16 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and paintingwith one coat of red lead paint and 2 coats of enamel paint. |
| 36 | Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete as per specification no. CP-BB |
| 37 | Supplying, erecting & marking FPMCB 40A to 63A B series in provided distribution board as per specification no. SWSWR/MCB |
| 38 | Supplying, erecting & marking TPN MCB 6A to 32A, B series in provided distribution board as per specification no. SW-SWR/MCB |
| 39 | Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB |
| 40 | Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA forthree phase and neutral as per specification no. CP-SPD |
| 41 | Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON |
| 42 | Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 43 | Empty encloser for led driver : |
| 44 | Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 45 | Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 46 | Cable Tray : Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner. |
| 47 | Cable : |
| 48 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 49 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 50 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 51 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 52 | GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE |
| 53 | Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI |
| 54 | Exterior Luminaires : |
| 55 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 56 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1200mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 40 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 57 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1100 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 16° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 58 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 10°x30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 59 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 10°x30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 60 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 61 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts per meter, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 62 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 700 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 63 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2500 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 64 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1200 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 65 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 66 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts per meter, 10° x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. IP65 driver boxes, leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 67 | Supply and erection of 4 meter high decorative pole of made in which pole pedstal should made of cast aluminium and pole should be GI in ribbed form. Thickness of the GI pole should be 3.2mm and aluminium pedstal thickness 6.5mm. Aluminum casted embalishments. Complete pole should be painted in PU paint and dark grey color. Base plate 300mm x 300mm x 10mm suitable to mount the pole on a concrete foundation. Pole must be connected to earthing. |
| 68 | Supply installation testing & commisioning of exterior rated posttop of system lumen output should not be less than 3500 lumen (Tolerence ±15%), the power consumption should not be more than 50 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen\"s Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage& Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass with impact resistance IK 08.LM80 |
| 69 | Elphine CollegeLT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/M.H/SLD/T3C). |
| 70 | Cubical : Supplying and erecting GI sheet 1.6 mm (16 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and paintingwith one coat of red lead paint and 2 coats of enamel paint. |
| 71 | Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete as per specification no. CP-BB |
| 72 | Supplying, erecting & marking FPMCB 40A to 63A B series in provided distribution board as per specification no. SWSWR/MCB |
| 73 | Supplying, erecting & marking TPN MCB 6A to 32A, B series in provided distribution board as per specification no. SW-SWR/MCB |
| 74 | Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB |
| 75 | Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA forthree phase and neutral as per specification no. CP-SPD |
| 76 | Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON |
| 77 | Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 78 | Empty encloser for led driver : |
| 79 | Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 80 | Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 |
| 81 | Cable Tray : Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner. |
| 82 | Cable : |
| 83 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 84 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 85 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 86 | Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 87 | GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE |
| 88 | Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI |
| 89 | Exterior Luminaires : |
| 90 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 91 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1200 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 92 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1200 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 93 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 20 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 94 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 20 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 95 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1200 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 96 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 600 lumen (Tolerence ±15%), the power consumption should not be more than 10 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 97 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen per meter (Tolerence ±15%), the power consumption should not be more than 10 watts per meter, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 98 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 99 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts per meter, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 100 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 700 lumen (Tolerence ±15%), the power consumption should not be more than 10 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 101 | Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should haveCRI>80, SDCM=4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant) |
| 102 | Supply and erection of 4 meter high decorative pole of made in which pole pedstal should made of cast aluminium and pole should be GI in ribbed form. Thickness of the GI pole should be 3.2mm and aluminium pedstal thickness 6.5mm. Aluminum casted embalishments. Complete pole should be painted in PU paint and dark grey color. Base plate 300mm x 300mm x 10mm suitable to mount the pole on a concrete foundation. Pole must be connected to earthing. |
| 103 | Supply installation testing & commisioning of exterior rated posttop of system lumen output should not be less than 3500 lumen (Tolerence ±15%), the power consumption should not be more than 50 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen\"s Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage& Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass08.LM80 |
| 104 | Maintaince charges for 1 yr |
| 105 | Maintaince charges for 2nd yr |
| 106 | Maintaince charges for 3rd yr |
| 107 | Maintaince charges for 4th yr |
| 108 | Maintaince charges for5th yr |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy