Repair & Maintenance Of E / M Water Supply Installation, Internal Electrification, Fans, Heating Appliances, Flame Proof Light Fittings, Flame Proof Wiring, Summer Cooling Appliances At Mahul & Sewri, Transformers, Ht Breakers, Ht Cables, Ht God, mankhurd-Maharashtra

Military Engineer Services-MES has published Repair & Maintenance Of E / M Water Supply Installation, Internal Electrification, Fans, Heating Appliances, Flame Proof Light Fittings, Flame Proof Wiring, Summer Cooling Appliances At Mahul & Sewri, Transformers, Ht Breakers, Ht Cables, Ht God. Submission Date for this Tender is 21-04-2022. Electrification Work Tenders in mankhurd Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

31807807
Corrigendum : Repair & Maintenance Of E / M Water Supply Installation, Internal Electrification, Fans, Heating Appliances, Flame Proof Light Fittings, Flame Proof Wiring, Summer Cooling Appliances At Mahul & Sewri, Transformers, Ht Breakers, Ht Cables, Ht God
Open Tender
Indian
Maharashtra
mankhurd
21-04-2022

Tender Details

Repair & Maintenance Of E / M Water Supply Installation, Internal Electrification, Fans, Heating Appliances, Flame Proof Light Fittings, Flame Proof Wiring, Summer Cooling Appliances At Mahul & Sewri, Transformers, Ht Breakers, Ht Cables, Ht God & Other Ht Equipments, Cleaning Of Oh & Ug Tanks And External Water Supply Pipe Lines And Comprehensive Repair / Maintenance Of Lt Panel, Lt Ug Cabl, Apfc Panel And Allied Works At Nrs At 31 Weu Thane, Manual Rescue And Operation Rescue Of New Ac Plant At Bldg P / 43, P / 44, P / 45, P / 47 ( Pbgm ) & P / 48 ( Mrp ) At Nadunder Ge ( Nw ) Mankhurd

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 14-Apr-2022 AMDT IN BOQ BOQ 21-04-2022

Key Value

Document Fees
INR 1000 /-
EMD
INR 215970.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: REPAIR & MAINTENANCE OF E/M WATER SUPPLY INSTALLATION, INTERNAL ELECTRIFICATION, FANS, HEATING APPLIANCES, FLAME PROOF LIGHT FITTINGS, FLAME PROOF WIRING, SUMMER COOLING APPLIANCES AT MAHUL & SEWRI, TRANSFORMERS, HT BREAKERS, HT CABLES, HT GOD & OTHER HT EQUIPMENTS, CLEANING OF OH & UG TANKS AND EXTERNAL WATER SUPPLY PIPE LINES AND COMPREHENSIVE REPAIR/MAINTENANCE OF LT PANEL, LT UG CABL, APFC PANEL AND ALLIED WORKS AT NRS AT 31 WEU THANE, MANUAL RESCUE AND OPERATION RESCUE OF NEW AC PLANT AT BLDG P/43, P/44, P/45, P/47 (PBGM) & P/48 (MRP) AT NADUNDER GE (NW) MANKHURD
Sl. No. Item Description
1M&L for cleaning underground / semi-underground sumps of 10,000 gallons capacity by draining out sludge from bottom blocking all inlet/outlet, removing alge-fungi growth from wall, floor, ceiling by wire brush/ water jet pressure machine, cleaning complete surface and dis-infecting with bleaching powder all as specified and directed.
2All as per item No 1 above but 20,000 gallons capacity.
3M & L for cleaning of over head reservoir 20,000 gallonsby draining out water,removing sludge, alge-fungigrowth from walls/floor, roof by rubbing with wire brush and disinfecting the reservoir with bleaching powder, draining out and making reservoir totally clean all as specified and directed.
4M & L for cleaning RCC / PVC Service Tanks upto 500 Ltrs capacity by draining out entire water, removing sludge, mud etc, cleaning the ceilings from spider webs, mud accumulations etc., with water jets etc., brushing / rubbing with wire / nylon brush / mop to remove all algae / fungal growth and moss etc. entirely from walls, floors, etc. washing clean with fresh water by using water jets and then again washing and treating with anti - bacterial agents, disinfectants and bleaching powder, as required at site and writing in paint approved font of size "Date of Cleaning" and "Capacity" of sumps in cleaning off the premises complete all as specified and directed by the Engineer-in-charge.
5-Ditto- all as per item No 4 above but 1,000 Ltrs capacity.
6-Ditto- all as per item No 4 above but 1001 Ltrs to 2,000 Ltrs capacity.
7-Ditto- all as per item No 4 above but2001 Ltrs to 5,000 Ltrs capacity.
8M & L for servicing ofCentrifugal pump set upto 20 HPby taking to workshop and opening end covers, greasing the bearings, replacing worn out nut, bolts, gasket, air release valve key, gland stuffing box male/ female set, Rubber bush and painting one coat ofsynthetic enamel paint, including writing/marking in 1" size letters SM & MES No and reinstalling in existing foundation complete with testing all as specified and directed by Engr-in-Charge. Note :-(i) Parts if required for pump shall be measured and paid separately here-in-after under another item as "supply only.
9All as per item No 8 above but Pump set 5 HP
10Supply only Ball bearing 6207 Make-SKF or eqivalant as approved by GE
11Supply only Ball bearing 6208 Make-SKF or eqivalant as approved by GE
12M&L for rewinding of electric motor 3 phase 50 Hz 415 volt for 15 HP capacity complete all as directed and specified. (a) Disconnecitng, dismantling existing burnt widning from motor and rewinding complete with super enamled copper winding wire of matching gauge including all insulation material such as PVC insulated sheet, cotton tape sleeves varnish etc., (b) Transporting electric motor including loading/ unloading upto wksp and back to site. (c) Re-installing the same at the orignal locaition with proper alignmenent connecting and testing onload. (d) Replacement 2 Nos ball bearing for each motor of existing size/model. Make- SKF/NBC/TATA. (e) Replacement of winding terminal plate with brass stus,/nut, bolt washer. NOTE: Quoted rates shall be deemed to include one year warranty formotors after rewinding and commissioning.
13-Ditto- all as per item No 12 above but Motor 5 HP Cap
14S&F cast iron covers, circular, for overhead PVC / RCC water storage tanks of any size, with MS strip / flat iron framework, with all necessary fixing and locking arrangements, nuts, bolts, washers, all as per BMC standards, with a shop coat of primer, including all necessary scaffolding / staging as required to cater at heights, taking out and disposing off old PVC covers, making any required addition / alteration to the tank for fixing of new CI covers, etc. complete all as specified, as directed by the Engineer-in-charge. (weight of tank cover not less than 10 KG). Make : As per sample
15M & L for preparation of old painted / unpainted surfaces of any description, including taking out of parts / components under painting (if required) from any position / location as listed hereinunder and applying one coat of epoxy paint (with colour code maintained as per relevant IS) including marking with flow directions (of approved colour) complete al as specified and as directed by the Engineer-In-Charge. (a) Induction motors 15 HP/20 HP - 03 Nos. (b) Filteration plant 10,000 GLNs/Sec - 01 No. (c) Electric motor 5 HP - 01 No. (d) Sluice valve 100 mm dia. - 03 Nos. (e) Sluice valve 80 mm dia. - 03 Nos. (f) Electric Panel Board - 02 Nos
16Supply only Calcium based granular disinfectant for drinking water treatment having 60% to 70% chlorine content in granular, sealed/ packed in 45 Kg drum.(Free from toxic constituent) all as required and directed by Engr-in-charge. Make- Purichlor/Declibac/potter & watts or other equivalent make.
17Supply, fixing, jointing and testing of 80 mm, CI Sluice Valve heavy duty PN 1.6 with iron wheel head jointing, coupling both ends for cast iron pipes including nuts, bolts, rubber gaskets etc including taking down old unserviceable sluice valves complete all as specified and directed . Make : Kirloskar / leader /Kartar/Racold
18-Ditto- all as per item No 17 above but 100 mm bore
19M & L in replacement of PVC Service Water Tank including tank nipple, bends, sockets complete all fitting required at site all including taking down the existing tanks as specified and directed by Engineer-in-Charge of 500 Ltrs capacity. Make : Sintex/Sharp/Rotex/Infra
20-Ditto- all as per item No 19 above but 1000 Ltrs capacity.
21-Ditto- all as per item No 19 above but 2000 Ltrs capacity.
22Taking up or down steel water tubing of upto 80 mm bore and connections including cleaning and setting a side for refixing, etc complete all as specified and directed by the engineer-in-charge.
23Supplying, laying, connecting and testing of GI tubing med gde of 25 mm dia with and including all fittings such as bends elbows, tees, short pieces, connectors, check nuts, diminishing pieces, caps and plugs, unions,etc fixed complete laid in trenches / along the walls / ceilings / floors / ducts / on pillar post all as specified and directed by Engineer-in-charge. Make: Jindal, TATA, Swastik,
24All as per item No 23 above but 40 mm dia.
25All as per item No 23 above but 65 mm dia.
26All as per item No 23 above but 80 mm dia.
27Taking up old CI/DI pipe of upto 100 mm bore and connections including cleaning and setting a side for refixing, etc complete all as specified and directed by the engineer-in-charge.
28M&L DI pipe 80 mm borewith spigot & socket ends centrifugally cast class K-7 in any length laid in trench including rubber joint (tyton joint) as required as directed by Engineer-in-charge. Make :
29-Ditto- all as per item No 28 above but 100 mm dia. Note for Item Ser No 26 to32 : Excavation, returning filling and shall be measured and paid separately under respectiveitem of schedule "A".
30Supply and fix in repair of Cable junction box IP 66/69 "weather proof" (with knockouts for cable entry) box of size 155 x 210 x 92 mm with connector/terminal, Din Rail, GI clamps made out of GI flat of size 25 mm X 3 mm channelincluding providing detachable GI 3 mm thick plate inside looping box as cable gland plate and including cable glands as required at size and making connections all as specified and directed by Engineer –in –Charge. Make - Hensel cat part No KF1616B /National/Sintax
31Supply and fix in repair of Cable junction box IP 66/69 "weather proof" (with knockouts for cable entry) box of size 130 x 180 x 77mm with connector/terminal, Din Rail, GI clamps made out of GI flat of size 25 mm X 3 mm channelincluding providing detachable GI 3 mm thick plate inside looping box as cable gland plate and including cable glands as required at size and making connections all as specified and directed by Engineer –in –Charge. Make - Hensel cat part No KF1010B /National/Sintax
32S& F in replacement of GI steel tubing medium grade 40 mm dia for laying in ground, along the pole in coping, road crossing etc for cabe protectionincluding necessary fittings , clamps for supports, etc all as directed by Engineer in charge.
33S& F in replacement of GI steel tubing medium grade 80 mm dia for laying in ground, along the pole in coping, road crossing etc for cabe protectionincluding necessary fittings , clamps for supports, etc all as directed by Engineer in charge.
34M & L for taking down of 400 Amp ATS having two incomingand one outgoing, including opening the cable ends and disconnecting the incoming and outgoing cables and removing the ATS, clening and servicing and reinstalling the ATS after carry out necessary repairs to the ATS main controler, PCB Card, cleaning and earthing all parts and reconnecting the cables all as specified and directed by the Engineer-in-charge.
35Supply & Fix 9 watts LED Bollard Garden light fittings with efficient high outputLED, Pressure die cast powder coated housing with PC diffuser , driver nuts, bolt, washers, base plate, foundation0.3 Meter x 0.3 Meter x 0.3Meter by PCC 1:2:4 type B-1 using 20 mm graded stone aggregates of size including excavation and earthwork, provision of pvc of size 40 mm dia in the PCC for cable entry , the Fitting Shall Conform to Cat No - PGR0301007 of Polycab or Equivalent from Bajaj/Crompton/Havells
36Supply and fix in replacementof Rectangular LED Flood Light 350 Watt with innovativethermal management, multiple optics and equipped with IP66 protectionflood light fittingsincluding drivers, pressure die cast aluminium housing,prewired complete. Make - Crompton Cat Part No -LSFO-350-CDL/60 / Havells/ Bajaj
37Supply and fixing post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection die cast aluminium spigot with spun aluminium top duly powder with PC diffuser & PMMA clear diffuser from outside with impact and corrosion resistant complete with driver and lamp complete. . Make - Havells/ Crompton /Bajaj
38Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection die cast aluminium spigot with spun aluminium top duly powder with PC diffuser & PMMA clear diffuser from outside with impact and corrosion resistant complete with driver and lamp complete. . Make - Havells/ Crompton /Bajaj
39S & F in repair/replacement of LED Driver 60 Watt Suitable for street light fitting, driver Shall Conform to Cat no X075C070V107FNY1BO of Crompton or Equivalent from Havells /Bajaj
40S & F in repair/replacement of LED Driver 30/35 Watts Suitable for street light fitting, driver Shall Conform to Cat no S0DQL1-54-700-40Wof Crompton or Equivalent from Havells /Bajaj
41Supply and fixing in replacement ofMCCB 400 Amps 36 KA, 3 Pole including lugs,nut, bolts. washers etc and dismentling of oldMCCB testing complete all as specified and directed by Engineer-in-Charge. Make : Havells/L&T/Legrand/Schneider
42-Ditto- all as per item ser No 41 above butMCCB 250 Amps 36 KA, 3 Pole Make : Havells/L&T/Legrand/Schneider
43-Ditto- all as per item ser No 41 above butMCCB 200 Amps 25 KA, 3 Pole Make - Havells/L&T/Legrand/Schneider
44-Ditto- all as per item ser No 41 above butMCCB 100 Amps 2 KA, 3 Pole Make - Havells/L&T/Legrand/Schneider
45M&L for straight through joint (HEAT SHRINKABLE TYPE KITS) for underground cable including joint kits and labour complete for making joints suitable for LT, XLPE/PILCA/PVC sheathed armoured heavy duty cable with aluminium conductor 3.5/4 core 25 to 50 Sqmm complete with testing till satisfaction of Engr-in-Charge.
46-Ditto- all as per item No 45 here-in-before but 2/4 core 6 to 16 Sqmm size -do-
47-Ditto- all as per item No 45 here-in-before but 3.5/4 core 70 to 95 Sqmm size -do-
48-Ditto- all as per item No 45 here-in-before but 3.5/4 core 120 to 185 Sqmm size -do-
49Supply& fixing in repairs of Chequered plate Fe 410-W(Gde-E- 250)A quality- for cable trenches, ladders including equal angle trench frames, including cutting as per requirement of site, square cut or notched (ordinary and counter sunk) forming holes, without any including providing handles
50Supply& fixing in repairs for mild steel work confirming to Fe-290, GdeE-165 in stairs/ladders including stringes, treades, landing, balusters, hand rails etc including applying two coat of paint over one coat of red oxide complete all as specified and directed.
51M&L for reinforced cement concretenominal mix M-20(using 20mm graded stone aggregate) for foundations, including rafts, footings, foundation beams, plinth beams, bases for column etc and mass concrete, complete all as specified and directed.(Note - Reinforcement and form work will be measured and paid separately).
52M & L for TMT bars of Fe-500 D grade conforming to IS: 1786, 10 mm dia & over, including cutting to length, bent to shape required, cranking, bending spirallyfor hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc, complete all as specified and directed.
53M & L for TMT bars of Fe-500 D grade conforming to IS: 1786, 8mm dia bars as in binders, spacers, strippusincluding cutting to length, bent to shape required, cranking, bending spirallyfor hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc, complete all as specified and directed.
54M & L for use and waste of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams , side and soffits (if any) of foundation and plinth beams and similar work, vertical or to batter, for rough finished surfaces of concrete, complete all as specified and directed.
55Dismantling old PCC Pole/ Steel Pole and Supply, Fixing and connection of hot dip galvanised octagonal poles of height 6 mtr with 130mm bottom A/F & 70mm top A/F made up of 3mm thick HT sheet along with base plate of size 200 x 200 x 12mm thick including 4 nos of M20 x 600 long J type foundation bolts and 1 mtr long hot dip galvanised single arm standard bracket, including MCB of 6 Amps, with connector 4 way to be provided as termination point complete all as specified and directed.
56Excavation in trenches not exceeding 1.50 m wide and n.exc 1.5 m in depth for foundation of poles, cable etc, not exc 10 sqm on plan and getting out in soft/loose soil including taking out brick protection etc complete all as specified and directed.
57Returning, filling in, including spreading, leveling, wateringand well ramming in layers not exc 25cm thick complete all as specified and directed.
58Removing excavated materials (soils) not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed.
59M & L for sand cushioning by spreading in trenches crushed stone by gently by punning down manually as in cable protection all as specified and as directed by Engineer -in-charge.
60Supply and laying un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified..
61Laying only un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid Note :- Serviceable cable cover obtained from Ser Item No 10 to 14 shall be reused.
62Dismentling of PCC foundation / pole coping from ground level all as per specified.
63M & L for PCC 1:2:4, type B-1, (using 20mm graded stone aggregate) as in coping including necessary use & waste of form work complete all as specified and directed.
64M&L for locating of faults of LT under ground cable XLPE upto 400 Sqmm size by using computerised / primary current injection method including cutting and removing the faulty portion of the cable and jointing with suitable cable joint and testing after jointing all as required and directed at site. Notes:-(i) Excavation, earth work, sand cushioning, PCC coveretc will be measured and paid separately under relevant items of BOQ. (ii) Cable jointwill be measured and paid separately. (iii) Additional length of cable required at site for jointing will be measured and paid separately.
65Supply and Layingor fixing or passing through pipe, XLPE ISI marked insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 240 Sqmm 3.5 core including necessary connection and providing cable lugs as required includingdisconnection/taking down of existing cable all as specified.
66-Ditto- all as per item No 65 above here-in-before but 150 Sqmm 3.5 Core -do-
67-Ditto- all as per item No 65above here-in-before but 95 Sqmm 3.5 Core -do-
68-Ditto- all as per item No 65above here-in-before but 16 Sqmm 4 Core -do-
69-Ditto- all as per item No 65above here-in-before but 10 Sqmm 4 Core -do-
70M&L for Preparingsurfaces of steel tubular swaged pole LT with scraping out old paint by emmery paper, caustic soda complete and painting with two coats of aluminium paint and numbering of poles with white paint on black paint base and stripping with black paint (100 mm each stripe) 3 Nos at equal distance from bottom (above PCC coping) upto a height of 1200 mm complete.
71M&L for preparation of old painted surfaces of pre-stressed concrete pole upto 11/9 mtr long by scarping old paint and applying two coats of cement base paint including numbering of pole with black oil paint painting the base of the pole in alternate black and yellow stripes each 30 Cm apart up to 1.5mtr height all as directed by Engineer in Charge.
72Equipment and labour for servicing of ACB including drawing/taking out from LT Panel, cleaning the Contacts,checking the breaker accessories, replacing the burnt out control wiring, burnt fuse units, old unsversiable spring units for proper function and carrying out ratio testby applying primary injection all for LT ACB 630 Amps to 800 Amps and refixing the breaker in position and testing all as directed by Engineer in Chare at site Note : The Contractor shall brought all T & P and testing equipments.
73Supply and fix in repairs power factor controller relay 8 Stage RPM 8, 415 volts, 50 cycles suitable for manual / automatic operation with indication for each stage, power factor adjustment setting knob complete all as specified and directed.
74M & Lfor testing of APFC panel for proper functioning in manual & auto mode, including re-wiring theburnt outwires, replacing the wiring ducts/casing Capping, fuse units and cleaningand testing complete all as specified and directed.
75Supply and Fix in replacement of Contactor Three Pole 415 volts 25 Amps AC 3 Rating,Conforming to Type MNX 25 & Cat No - CS94110 of L & T or Equivalentt from Schnider Electric, ABB including add on Blocks suitable for driving POWER Capacitors, including making addition/Alternation to existing Wiring/circuit system
76All as per item No 78 above but Contactor Three Pole 415 volts 32 Amps AC 3 Rating Conforming to Type - MNX 32 & Cat no - CS94111 of L & T or equivalent from Schnider Electric, ABB/ C&S
77All as per item No 78 above but Contactor Three Pole 415 volts40Amps AC 3 RatingConforming to Type- MNX - 40 & Cat no - CS94190of L & T or equivalent from Schnider Electric/ABB/ C&S
78All as per item No 78 above but Contactor Three Pole 415 volts50 Amps AC 3 Rating Conforming to Type-MNX - 50 & Cat noST19001of L & T or equivalent from Schnider Electric/ABB/ C&S
79All as per item No 78 above but Contactor Three Pole 415 volts70 Amps AC 3 Rating Conforming to Type- MNX - 70 & Cat no - ST19002of L & T or equivalent from Schnider Electric/ABB/ C&S
80Supply and fixPower Capacitors of Rating 25 KVAR 415 Voltin repairs Naturally air cooled Double dielectric heavy duty, MPP type440 Volt 50 HZ Watt Less Power Capacitors wattage not more than 0.5 Watt per KVAR conforming to IS 13340 and 13341 ISI Marked all as specified.
81All as per item No 80 above but Power Capacitors of Rating 20 KVAR 415 Volt
82All as per item No 80 above but Power Capacitors of Rating 15 KVAR 415 Volt
83All as per item No 80 above but Power Capacitors of Rating 10 KVAR 415 Volt
84All as per item No 80 above but Power Capacitors of Rating 7.5 KVAR 415 Volt
85All as per item No 80 above but Power Capacitors of Rating 5 KVAR 415 Volt
86Supply and fix in repair add on Blocks suitable forPower contactors of range 25 Amps to 140 amps (MNX 25 to MNX 140 including making addition/Alternation to existing Wiring/circuit system all of Make- L&Tor equivalent from Schnider Electric/ABB/ C&S
87Maint/Cleaning ofSub stationsinside and out side area andremoving of creepers raised along with sub station including surface dressing around the sub station not less then 3 mtrfrom out side fencing and removing the all waste material from site and Chemical spray inside and out side area of Sub station. Note:- T & P will bearreanged by contractor
88Repair/Maintenance of LT Panel board by taking shut down, removing of carbon particles, rubbing of heated portion of bus bar and cleaning complete by means of CRC-226/Petrol, tightening of all joints in bus bar, checking of earthand neutral voltage and make a record, replacement of u/s nuts/bolts/washers including replacement of corroded glands, lugs/ thimbles and tightening them properly all as directed by Engineer-in-charge.
89Labour only for removing of creepers raised along with LT panels/feeder piller box etc surface dressing around the LT panels not less then 1.5 mtr in radius and removing the all waste material from site including suppling and spraying chemical for destruction of grass all as directed by Engineer-in-Charge.
90S & F in replacement of Voltmeter Digital type ,3 Phase Volts of size 96x96mm. Make : AE/L&T/Schenider
91S & F in replacement of Ammeter Digital type of 0-400 amps capacity of size96X96mm. Make : AE/L&T/Schenider
92S & F in replacement of Selector switch for voltmeter / Ammeter.
93S & F in replacement ofPhase indicating lamp neon type complete with holder assy RYB. Make : AE/L&T/Havells/Indoasian
94S & F in replacement CT coils of ratio 400/5 Amps, 15 VA class -1 as per IS- 2705/92. Make : AE/L&T/Havells/Indoasian
95M&L for cutting existing road/hard standing not exc 45x45 cm in wide & depth getting out excavated material for laying GI tube including returning filling & well rammaing wateringfinish suraface and provision of 10 cm concrete using PCC 1:3:6 type C2 from Top", including removal of surplase soil all as directed.
96M&L for taking down old unsv and supply & lay 3Core 1.5 Sq mm size multistranded FRLS copper conductor PVC unsheathed 650 / 1100 Volt Grade As per IS 694 with and including 20 mm dia PVC conduit and passing through PVC conduit with necessary saddle, clamps, bolts & nuts,all for interconnection of cable looping box to Street Light Fitting, Post Top Lantern etc all as Directed. Make :- POLYCAB / KEI / HAVELLS
97Dismantling and taking down the existing defective street light fitting/Garden lights/Building security light of any type and any capacity from steel tubular pole, opening the street light fitting, checking the serviceability of spare parts including replacement of defective parts such as electric drivers andLED 36/70 wattafter repairing including refixing on pole including connecting & testing complete all as directed by Engr-in-Charge. [Note:- Electronic drivers and LEDwill be measured and paid separately on respectiveitemof Sch "A"here-in-after].
98Supply and fix in replacement flood light fittingsin street light poles/Buildings the fitting shall be of LED type 170 Wattscomplete with and including drivers, pressure die cast aluminium housing,prewired complete. Make : Philips/Bajaj/Crompton/Benlo
99S&F in repair/replacement of building Security lightfitting 30 Watt made up of pressure die cast alluminium body with mid power LED as lighting sources and PC cover having Top opening seperate driver compartment with IP66 protection and impact resistance of IK07including fixing arrangements and taking down old rusted bracket fittings completeall as per directed by Engr- in – charge. Make : Philips/Bajaj/Crompton/Benlo
100M&Lin repairs for 24 Hrs240 V FM1 Quartz type Time switches astronomical type (Having longitude and latitude of Indian cities in memory) timer for controlling street lights contactors complete all as directed by Engr-in - Charge .Make legrand Cat No. 412780 or equivalent of Havells L&T/Indo Asian as approved by GE
101M&L for DI fittings of class K-12 such as bends , collars, caps, plugs, connecting pieces any typeupto 150 mm dia completeall as specified and directed.
102M & L for dismantiling the existing valve chamber of size 900 X 900 X 900 mm including necessary earth work in any type of soil, PCC foundation D-2 1:3:6 in base concrete, brick work in CM 1:6 with 10 mm thick plaster internally and 15 mm thick externally in CM 1:4, 6 mm thick MS cover with hinges and locking arrangement fixed to angle iron frame made-out of 40 X 40 X 6 mm MS angles complete with 2 coats of synthetic enamel paint over one coat of red oxide zinc chrome primer on all metal works including necessary excavation earth workall plastered surfaces of valve chambers complete all as specified and directed by Engr-in-Charge.
103M & L in replacement of run lead joint forCI Spigotand socket 80 mm bore pipes and fittingscomplete.
104-Ditto- all as per item No 103 above but 100 mm dia.
105M & L in replacement of rubber gasket joint of the size 80 mm size for CI flanged type pipe including nut, bolt, washer complete all as specified and directed .
106-Ditto- all as per item No 105 above but 100 mm dia.
107S & F in repairs Gun metal gate or globe valve 40 mm dia, confirming to IS-778, ISI marked, with iron wheel head screwed at both ends for iron pipes or ferrule and fixing including necessary fittings like unions, check nuts, etc. and any addition / alteration required for threading and fixing complete all as specified and as directed by the Engineer-In-Charge of the following diameters:
108-Ditto- all as per item No 107 above but 25 mm dia.
109Supply and fixing of cast iron flanged ends sluice valve suitable for 100 mm dia pipes conforming to IS - Class PN - 1.0 with MS nuts, bolts, washers etc, as approved including taking out/ dismantling old unserviceable one and testing complete all as specified and as directed.Make :- KIRLOSKAR/KARTAR/ LEADER/VENUS/Racold
110S & F in repairs float ball valve assembly 20 mm bore , high pressure grade, with polythene float, fly nuts, screwed to GI pipe or brass ferrule, CI fittings viz. nipples, check nuts, reducers, elbow, sockets, etc. fixed complete all as specified and as directed by the Engineer-in-charge for the following bores of pipes:
111-Ditto- all as per item No 110 above but 25 mm bore
112-Ditto- all as per item No 110 above but 40 mm bore
113Drilling and taping cast iron water mains (in position) for branch connections 15 mm bore of the internal dia including ferrule and required fittings all as specified and directed.
114-Ditto- all as per item No 113 above but 20 mm bore
115Taking up or down steel water tubing 15 mm bore and connections includingcleaning and re-fixing if found serviceable including all new fittings or removal unsv pipe to store.
116-Ditto- all as per item No 115 above but 20mm bore
117-Ditto- all as per item No 115 above but 25mm bore
118-Ditto- all as per item No 115 above but 40mm bore
119-Ditto- all as per item No 115 above but 50mm bore
120S & F fully automatic star delta starter suitable for 15 HP motor conforming to IS -13947-4 after taking down old unserviceable one. Make- Havells
121M & L for PCC 1:2:4, type B-1, (using 20mm graded stone aggregate) as in foundation for pump sets and blocksincluding necessary form work complete all as specified and directed.
122Supply and fix Mild steel type "C" Channel made of any angle iron of suitable size for pump foundation frame of any size suitable for site by welding including all necessary nuts, bolts, washer complete all as specified and as directed.
123Supply and fix in replacement ladder height 10 feet max, steps on every 01 feet made of angle iron of size 50x65x5 mm thickfor sump including taking down old rusted iron ladder complete all as specified and directed.
124M& L for attending day to day complaint of minor nature including replacement of fittings such aselbow,socket,tee etc and deposting the complaint slip in complaint cell after user signature complete as per directed by engineer in charge.
125M&L for provn of Earthing complete with M.S. galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the plate not less than 1.5M below normal GL, connected to Galvanized earth strip 32x6mm upto 7.5 mtr with protection pipe by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick reinforced with 6 mm dia bar, 3 Nos. both way, 40mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No. 3 of SSR Pt-I 2009 specification.
126S&F GI strip size 32 x 6 mmall as directed including welding brazing and taking down of old copper strips as required at site
127Supply and Fix in repairs Change Over TPN 400 Amps 415 Voltin open construction, panel mounted type with base plate for mounting in panel, including taking down of old Change over and reconnecting the cabes with proper glands. Make : L&T/Havells/Legrand/Stranded
128Supply & Fix in repair ACB 800 Amps, 4 Pole, 50 KA, Manual Draw out type, with Spring Charge Mechanism, over Load protection, Short Circuit Protection & earth Fault Protection, Metering Display including all necessary alteration required for fixing and testing complete all as specified and as directed. Make: Indo Asian /Havells/CG/Legrand/Stranded
129S & F foot valve of size 80 mm dia cast iron body, ball type, with flanged and drilled ends and synthetic rubber coated MS ball, conformimg to relevant IS, ISI marked, including all joints, gaskets, bolts and nuts, washers, including taking up/down old unserviceable valves from any position and any addition/alteration for fixing required complete all as specified and directed by the engineer in charge.Make : Kirloskar or equivalant or as approved by GE.
130Supply and Fixing industrial type pressure gause made out of SS 304 material, SS sipon shall be factory insulated with closed cell elastomeric insulation in tubing form, pressure gauses shall be factory fitted with a ball valve complete, all as specified and directed.
131Supply and fixing Gun Metal Air Release Valve of size 15mm bore, complete all as specified and directed.
132S & F in repairs Perforated Brass Threaded End cap size 15 mm dia for over flow pipe of water tank as per BMC standard including all fittings like GI Nipple, Bend, Elbow, Tee, Socket etc.
133Supply and fix cast iron water meter of size 100 mm class B flange type conforming to IS-2373 all as specified and as directed. size all as specified and as directed. Make : Kranti/Capston/ Dashmesh
134Dismantling unserviceable chemical dosing pump and replace with capacity of flow 10 LPM at max 5 Kg/cml pressure, 240 V, 50 Hz, complete with suction straner, pipe and dosing pipe including testing complete all as specified and directed. Make : Declibac Technologies pvt Ltd / Raclod / Milton Roy
135M & L MS coverin repair suitable for existing size with hinges and locking arrangement fixed to angle iron frame made-out of 40 X 40 X 6 mm MS angles with locking arrangement complete with 2 coats of synthetic enamel paint over one coat of red oxide zinc chrome primer on all metal works including necessary excavation earth workall plastered surfaces of chambers complete all as specified and directed by Engr-in-Charge.
136Manning & Operation of Central AC Plants [Installation consisting of AC plant with chilled water system 78 TRcapacity having 03 Nos compressors each of 39 TR capacity (02 Nos working at a time and 01 No. standby) with all connected equipments and machineries round the clock through out the monthin two shifts (including Sundays and Holidays) by employing one operator cumAC machenic per shift of eight hours including carrying out routine maintenance and upkeeping the Installation / AC Plants in operation condition complete in all respects as specified and directed :- Location : P-47,P-48 at NAD (Trombay): (i)1stshift-0600 hrs to 1400 hrs (ii)2nd shift - 1400 hrs to 2200 hrs
137Manning & Operation of Central AC Plants [Installation consisting of AC plant with chilled water system 22 TRcapacity having 03 Nos compressors each of 11 TR capacity (02 Nos working at a time and 01 No. standby) with all connected equipments and machineriesthrough out the monthin two shifts (including Sundays and Holidays) by employing one operator cumAC machenic per shift of eight hours including carrying out routine maintenance and upkeeping the Installation / AC Plants in operation condition complete in all respects as specified and directed :- Location-:P-43,P-44,P-45 at NAD(Trombay): (i)1stshift-0600 hrs to 1400 hrs (ii)2nd shift - 1400 hrs to 2200 hrs Notes for ITEM NOS 140 TO 141 :- Quoted rates shall also be deemed to include the following elements:- (i) To provide uniform, tools & plants, safety means like glove etc to the employees and also alternative employee (reliever) for Manning and Operation of AC Plants/Installation so that the other employees can avail the facility of weekly leave etc. (ii)To keep the AC Plant Room & allied area in clean and tidy condition during the operation period. (iii)To carryout the routine maintenance, minor repairs, oiling, greasing and to rectify the minor defects to keep the plants / Installation in serviceable condition all as directed by the GE and Engineer-in-Charge.However, the major repairs, replacements, overhauling, gas charging, topping-up oil etc are not included in the scope of the above items. (iv)To keep necessary documentation duly signed by all the concerned. (v) To hand over the entire plant in serviceable condition at the time of completion. (vi) Contractor shall submit the details ofpayment of wages forstaff employed through Aadhaar linked bank accounts for payment purpose.
138Filtration and dehydration of transformer oil using ON-LINEfiltartion plant to remove moistrure and carbon contents to achieve dielectric strength of oil not less than 50KV in 4mm gap,Oil samples of each transformer, OCB and OFS etc are to be tested before and after filtration test, results to be recorded on aprinted format and also painting the date of test on the equipment with synthetic enamel paint all as specified and directed and also including disconnecting the HT and LT cables and cleaning the bus bar surfaces and reconnecting the cables by providing copper washers, bolts, nuts etc all as specified and directed. Notes:-(i)Oil required for toppingup for filtration willbe measured and paid separately under respective item of BOQ . (ii)The quoted rates shall also be deemed to include for proper cleaning of the tank surfaces to make the same free from sludge etc. (iii)The qty of oil payable under this item shall be the net qty reused for filling after dehydration and filtration having dielectric strength not less than 50 KV in 4mm gap
139Filtration and Dehyderten ofoil of 11 KV CTPT by ON-LINE filtration plant to remove moisture and carbon contentents to acheive dielectric strength of oil not less than 50KV in 4mm gap and producing test result on records before and after filtration of each CTPT and also including servicing and painting the entire unit and reconnnecting the same all as specified and directed, Note - Oil required for toppingup for filtration willbe measured and paid separately under respective item of BOQ .
140Material and Labour for supply and filling of Transformer insulation oil as per IS 335-1993 having die electric strength minimum 50 KV in 4mm gap for topping up in transformer, OCB, OFS etc all as specified and directed, Make: SAVITA/POWER OIL/APAR.
141M&L for prepartion of old painted surfaces of transformer 100 to 315 KVA capacity, 11KV-22KV/433 Voltincluding removing of any oil spillage and applyIing two coats of anti corrosive paint of shade as per existing, complete all as specified and directed.
142M&L for prepartion of old painted surfaces of transformer 400 to 630 KVA capacity , 11KV-22KV/433 Voltincluding removing of any oil spillage etc and applying two coats of anti corrosive paint of shade as per existing, complete all as specified and directed.
143M & L for taking out unserviceable LT bushings with stud etc and replacing LT Bushings complete with and including copper/brass stud, rubber gasket, brass bolts, brass nuts, cable lugs etc for11 KV - 22 KV/0.433 KV transformer of rating upto 315 KVA, complete all as specified and directed.
144M & L for taking down/opening top cover of 11 KV - 22KV/0.433 KV transformer of rating upto 315 KVA, replacing the gasket of top cover and refixing the top cover, including testing, complete all as specified and directed.
145M & L for taking out unserviceable HT bushings with stud etc and replacing HT Bushings complete with and including copper/brass stud, rubber gasket, brass bolts, brass nuts, cable lugs etc for11 KV/0.433 KV transformer of rating upto 315 KVA, all as specified and directed.
146M & L for taking out unserviceable HT bushings with stud etc and replacing HT Bushings complete with and including copper/brass stud, rubber gasket, brass bolts, brass nuts, cable lugs etc for22 KV/0.433 KV transformer of rating upto 315 KVA, all as specified and directed.
147M & L for taking out unserviceable LT bushings with stud etc and replacing LT Bushings complete with and including copper/ brass stud, rubber gasket, brass bolts, brass nuts, cable lugs etc for11 KV /0.433 KV transformer of rating 400 to 630 KVA, all as specified and directed.
148M & L for taking down/opening top cover of 11 KV - 22KV/0.433 KV transformer of rating 400 to 630 KVA, replacing the gasket of top cover and refixing the top cover including testing, complete all as specified and directed.
149M & L for taking out unserviceable HT bushings with stud etc and replacing HT bushings complete with and including copper/ brass stud, rubber gasket, brass bolts, brass nuts, cable lugs etc for11 KV/0.433 KV transformer of rating 400 to 630 KVA, complete all as specified and directed.
150M&L for locating faults of HT under ground cable PILCA/XLPE 11 KV/22KVupto 300 Sqmm size by using computerised / primary current injection method including cutting and removing the faulty portion of the cable and jointing with suitable cable joint and testing after jointing all as required and directed at site. Notes:-(i) Excavation, earth work, sand cushioning, PCC coveretc will be measured and paid separately under relevant items of BOQ. (ii) Cable jointwill be measured and paid separately. (iii) Additional length of cable required at site for jointing will be measured and paid separately.
151M&L for High pot charges during locating faults of HT under ground cable all as directed by Engr -in- Charge
152M&L for heat shrink type straight through cablejointing kitsuitable for 3Core 50- 95 sqmm 11 KV earthed XLPE cable complete with and including jointing materials, accessories and thimbles etc, complete all as specified and directed.
153M&L for heat shrink type straight through cablejointing kitsuitable for 3 Core 120-185 Sqmm 11 KV earthed XLPE cable complete with and including jointing materials, accessories andthimbles etc, complete all as specified and directed.
154M&L for heat shrink type straight through cablejointing kitsuitable for 3 Core 120-240 Sqmm 22 KV earthed XLPE cable complete with and including jointing materials, accessores andthimbles etc, complete all as specified and directed.
155S & F in repairs indoor heat shrink type end termination cable jointing kit for 11 KV (Earthed) grade cable complete with and including jointing materials,accessories and thimbles etc suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 Sqmm, complete all as specified and directed.
156S & F in repairs indoor heat shrink type end termination cable jointing kit for 11 KV (Earthed) grade cable complete with and including jointing materials,accessories and thimbles etc suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 240Sqmm, complete all as specified and directed.
157S & F in repairs indoor Heat shrink typeend termination cable jointing kit for 22 KV (earthed) grade cable complete with and including jointing materials,accessories and thimbles etc suitable for 3 core XLPE armoured aluminium conductor cable of size 120Sqmm to 185 Sqmm, complete all as specified and directed.
158S & F in repairs out door heat shrink type end termination cable jointing kit for 22 KV (earthed) grade cable complete with and including jointing materials, accessories and thimbles etc suitable for 3 core XLPE armoured aluminium conductor cable of size 120Sqmm to 185 Sqmm, complete all as specified and directed.
159Taking out existing 11 KV/22 KV grade defective cable of any type and size from the trenches and from any other locations(including taking out of cable covers, pipes etc) complete all as directed. Note: Excavation and earth work shall be measured and paid for separtely.
160Supply, laying and testing in trenches, road crossing, through pipes, ducts etc, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cable (heavy duty ) with aluminium conductor, 11000 volts grade (earthed), cross sectional area 120 Sqmm X 3 core, complete all as specified and directed.
161Supply, laying and testing in trenches, road crossing, through pipes, ducts etc, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cable (heavy duty ) with aluminium conductor, 11000 volts grade (earthed), cross sectional area 185 Sqmm X 3 core, complete all as specified and directed.
162Supply, laying and testing in trenches, road crossing, through pipes, ducts etc, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cable (heavy duty ) with aluminium conductor, 22000 volts grade (earthed), cross sectional area 120 Sqmm X 3 core, complete all as specified and directed.
163Supply and laying unreinforced precast factory made concrete cable cover, class HV, Type -I, flat, size 300mmx 180mm x40mm, complete all as specified and directed.
164Supply & laying reinforced precast factory made concrete cable cover, class EHV, type -I with peak size 450mm x 230mm x 50mm complete all as specified and directed.
165Supply & fix in replacement Silica Gel Breather with silica gel for 11 KV to 22 KV Transformer of Rating upto 630 KVA, complete all as specified and directed.
166Overhaulingof HT OCB 11 KV, 400 Amps, 250 MVA of Make Crompton Greaves/MEI/GEC/ Alstom installed at various locations after taking shut down from department and opening both incoming and outgoing connections, dismantling complete Circuit Breaker after detaching oil tank and draining out oil in a separate container and cleaning of oil tank throughly and carrying out thefollowing repair work :- (i) Taking out complete parts of OCB separatelyviz. like ARC control pot assembly, jack ring , contact main, TULIP contact finger assembly, terminal bushing, moving contact block, fixed contact block, pick off spring assembly, moving ARC, Contact ARC, assembly of main moving contact, speed control device assembly etc and checking the same for its serviceability/ suitability for refixing, cleaningthe OCB externally and internally including all parts thoroughly as per standard practice (also cleaning the male female contacts with emery papers and insulator with CRS spray and applying petrolium jelly/grease to themoving parts), reassembling complete parts of OCBs including replacement of existing unserviceable parts /components all as approved and directed. (ii) Taking out complete parts of Truck & Hoist Assembly, after removing old greasechecking the same for its suitability/ serviceability and reassembling complete truck and hoist assembly after replacement of defective parts all as approved and directedincluding greasing and oiling the complete mechanism as per standard practice. (iii) Servicing of dependent/independent mechanism and spring charging mechanism including replacement of spares comprising of scope as under :- (a)Recommissioning including testing of HT OCB for overload setting and adjustment. (b) Recommissioningof complete Truck and Hoist assembly all as directed (iv) Checking/testing/servicing of tank assembly/barrier, solenoid machianism, trip unit assembly, BUS bar spout epoxy cast side entry cable base busing, arrangment with drawable type PT assembly of male female housing etc complete including repalcement of defective parts with new all as directed.
167(v)Over hauling of HT panel of each OCB including cleaning of bus bar chember, CT"s and painting all exposed surfaces with one coat of insulation paint of same colour and replacement of control fuses, replacement of panel heater and bus bar insulators all as directed and painting Alphbet/Numbers with bold letters upto 5 cm height with black colour. (vi)Checking/repairing the auxillary wiring. (vii)Testing of relays, CT & PT units and relay settings etc. NOTES:(i)Cost of all the materials, repairs and works as specified above as well as all the other elements(except followings) to make the OCB"s fully functional shall be deemed to be included in the quoted rates :- (a) Cost for supply only of the components/parts/spares catered for under item Nos 34 to 41 to the extentrequired and operated here-in-after. (b) Cost for filteration and dehydration of transformer oil to achieve the desired dielectric value as catered for under item No. 1.00 here-in-before. (c) Cost for provision ofadditional transformer oil for topping-up as catered for under item No. 3.00 here-in-before. (ii)The above OCB"s are located at :(a) SPDC (b) NAD COLONY (c)NAD DEPOT(d)Nausena Baugh(e) Mahul (f)CABS
168Supply onlyOCB Top plate insulator Bus Bar side with current carrying parts for 11 KV OCB,Make Crompton Greaves/MEI/GEC/Alstom, capacity 400 Amps, 250 MVA rating, complete all as specified and directed.
169Supply only spout insulator (Epoxy) for OCB Trolley complete with current carrying parts for 11 KV OCB, make Crompton Greaves/MEI/GEC/Alstom, capacity 400 Amps, 250 MVA rating, complete all as specified and directed.
170Supply onlydigital type Ampmeter with selector switch for 11 KV system for 11 KV OCB of make Crompton Greaves/MEI/GEC/Alstom, capacity 400 Amps, 250 MVA rating, complete all as specified and directed.
171Supply onlydigital type Voltmeter with selector switch for 11 KV system for 11 KV OCB of make Crompton Greaves/MEI/GEC/Alstom, capacity 400 Amps, 250 MVA rating, complete all as specified and directed.
172Supply only spare of Main Contact Male suitable for R, Y, B Phase for 11 KV OCB of make Crompton Greaves/MEI/GEC/ Alstom, capacity 400 Amps, 250 MVA rating, complete all as specified and directed.
173Supply only spare of Main Contact Female for R, Y, B Phase for 11 KV OCB of make Crompton Greaves/MEI/GEC/ Alstom, capacity 400 Amps, 250 MVA rating, complete all as specified and directed.
174Supply only 11 KV resin cast Single core single ratio Current transformer of ration 60/5Amps class C, 15 VA burden, including carrying out testing.
175Supply only PT 11 KV/110 V AC, 100 VA, suitable for existing PT of OCB/VCB.
176M & L for servicing (as described below) of indoor type, HT 11 KV, draw out type VCB of capacity 630 Amps, 350 MVA, MakeAREVA/ Kirloskar/ SIEMENS, Schneider:- a) Servicing, cleaning and inspectingof draw out type trolly mounted, Mannual spring charge ON-OFF mechanism and testing for proper functioning of braker for ON and OFF operation, servicing of male female contacts, greasing all the mechanical components and applying dry graphaite conductive sealent for contacts. b) Cleaning, inspecting and testingHT 11 KV Bus bar chamber, Checking of insulators at input and out put for any crack or damages, Checking of cable termination for all the three phases, Cleaning the copper bus bar, checking for proper insulation, tightening all the nuts, bolts of bus bar. c) Cleaning, inspecting and testing of electrical wiring system, Ammeter, voltmeter ,VAF meter,selector switch, all illuminated indicators for R Y B phase, DC supply healthy, spring charge, trip circuit healthy etc d) Cleaning, inspecting and testing for Over current relay, CT for Ammeter, PT for Voltmeter for display of voltage HT 11 KV e) Setting of earth fault relay and over current relay as per manufacturer"s recommendation and site requirement. Note:Cost of all the materials, components, repairs, elements as per above as well as other elements (except supply only of the components considerd under item Nos. 43 to 60 hereinafter to the extent required and operated) to make the VCB"s complete functional shall be deemed to be included in the quoted rate of the contractor.
177Supply onlyvacuum bottle type VG 2 of11 KV VCB trolley rating 350MVA, current rating 630Amps & Conforming to cat no MST10SG200300NA of Schnider or Equivalent from ABB/ SIEMENS
178Supply only Single phase Circuit Spout R, Y, B Phase Conforming to Cat no - MEP-39-32187 of Schnider Electric or Equivalent from ABB/SIEMENS
179Supply only Single phase Bus Bar Spout for R & B Phase Conforming to Cat no - MEP-39-32185 of Schnider Electric or Equivalent from ABB/SIEMENS
180Supply only Single phase Bus Bar Spout for Y Phase Conforming to Cat no - MEP-39-32186 of Schnider Electric or Equivalent from ABB/SIEMENS
181Supply only Copper Flexible connections 800 Amps Capacity suitable for VG2 VCB trolley, conforming to Cat no MCU39S4126302FNof Schnider or Equivalent fromABB/Siemens
182Supply only Closing coil operating on 30 Volt DC for VCB trolley conforming to Cat no ECO39SN134700FN of Schnider or Equivalent fromABB/Siemens
183Supply only Trip coil operating on 30 Volt DC for VCB trolley conforming to Cat no ECO39SN133900FN of Schnider or Equivalent fromABB/Siemens
184Supply only Silver plated copper Isolating contact flat type 800 Amps capacity, including mounting screws conforming to Cat no MVIK00190-01 of Schnider or Equivalent fromABB/Siemens
185Supply only Insulator for Bus Bar Support, Conforming to Cat no MEP-39-37399 of Schnider or equivalent from ABB/Siemens
186Supply only Drive beam conforming to cat no MSM39S0118600FN of Schnider or equivalent from ABB/Siemens
187Supply only buffer for opening spring, conformin to cat no MVIJ0098-01 of Schnider, or Equivalent from ABB/Siemens
188Supply only buffer for closing spring, conformin to cat no MVIJ0056-01 of Schnider, or Equivalent from ABB/Siemens
189Supply only Spring charging motor with gear box, the motor shall be operating on 110 V AC supply.conformin to cat no MVIJ00157-01 of Schnider, or Equivalent from ABB/Siemens
190Supply only local remote switch for vaccum circuit Breaker
191Supply only Indicator lamp ,30 Volts, pin type as per sample.
192Supply only Flange Tank Gasket suitable for existing size for OCB.
193Supply only Earth fault and Over current relay suitable for existing VCB.
194Supply only PT primary fuse for 11 KV, 3 Amp.
195M&L for dismantlingHT 22 KV SF6 braker Make - ABB, open thecable termination compartement, Dismantle the HTcable temination burnt spout insulator, copper termination rod,rubber bushings and CTs and replace with new spout insulator, rubber bushings, CTsandcopper cable termination rod, after replacing the above components, cleanthe splashes over compartment, servicing the entire braker,testing the braker standard parameters andset the Earth fault and over current relay all as per existing setting,after carryout above repairs, Megerring the braker for Phase to Phase and earthto phase, earth fault values with HT Megar, clean all thesplashes over compartment completely , clean all spout insulator , Rubber insulatoretc, complete all as specified and directed. Note : (a) Technician to be engaged for carrying out Maintenance Shall haveHT Licence (b) Prior Liaison shall be done with the supply agency for HT Power Shut Down.
196M&L for dismantlingHT 22 KV Fuse fromfuse compartment ofSF6 braker of Make - ABB,replacing with new fuse of rating IN- 16 Amps, U N -24 KV, 13 - 55 A, 11- 63 KA,including Cleaning thefuse compartment,complete fuse shall be of Cat No 1YMB531004M0003 of ABB Make. Note- a) Technician to be engaged carrying out Maintenance Shall haveHT Licence. (b) Prior Liaison shall be done with the supply agency for HT Power Shut Down.
197M & L for servicing IDMT relays (Two Nos over current and one No earth fault relays) fixed in 11 KV HT panels for primary and secondary injection and calibration of all the relays and setting the relay tripping timings in advance to match the outgoing load on the Incoming and outgoing feeders, complete all as specified and directed.
198Supply and fix in replacement of old unserviceable battery charging unit Input - 230 VAC and Out Put 30 V DC, Maximum 10 Amps Current Out Putfor charging of battery bank.
199Supply and fix in replacement battery back up unit including of 2 Volt, 100 AH VRLA battery - 15, interconnection link for connecting batteries to achive 30 Volt out put. Make of Battery shall be Exide, Amaron, Amco
200Material and labour for scrapping of old paint and applying two coats of Aluminium paint over a coat of Red oxide all for 22 KV two pole structure including GOD & operating rod
201M&L for earthing complete with copper earth plate electrode 600x 600x 3 mm buried directly in ground with top edge of the plate not less than 1.5 mtrs below normal ground level and connected to earth test point by means of copper Strip of size 20x3 mm all as specified and shown in electric plate No 3 of MES SSR Part-I including necessary excavation and earthwork, PCC chamber, CI cover, protection and watering pipe, funnel, mesh etc all as required at site and all as directed and including taking down of old earthing materials, complete all as specified and directed. Notes: (1). Cost for provision of 7.5 RM Copper strip and G I protection pipe 25mm bore, light grade sahll also deemed to be included in quoted rates. (2). Earth resistance of earth pit should be less than 0.5 Ohms. On testing, if the desired earth resistance is not obtained, the earthing will be redone at no extra cost.(3) Rate quoted by the tenderer shall also be deemed to include salt & Charcoal fillings upto & above 450 mm top of Copper plate.
202S&F copper strip of size 20 x 3.00mm including welding, brazing and taking down of old copper strip as required at site, complete all as specified and directed.
203Material and labour loose filling with graded coarse stone aggregate 40 mm for out type sub Stations not exceeding 15 Cm thick.
204Dismantling air break gang operated switches vertical/horizontal mounted incl insulators and operating mechanism for repair/replacement of broken/worn out components and insulators etc.
205Supply and fixing triple pole mechanically operated air break isolator (GOD), vertical mounting, rotating type, mounted on insulator and steel frame with operating mechanism worked from ground level complete in all respect such as gun metal moving contacts and spring loaded gun metal fixed jaws, knife copper jumper strip etc, suitable for 22000 Volts grade, 50 Hz, with 9 insulator of rating upto 200 Amps complete all as specified and as directed.
206S & F drop out fuse single pole mounted on insulator, 22000 Volts grade double pole steel frame of current rating 50 Amps including taking down existing DO fuse complete and removing from site complete all as specified and directed.
207Supply only brass terminal plate for mounting male contact of air break switch insulator including GI nuts and bolts washers etc as required complete
208Supply only male contact / female contact for air break switch
209Supply only post insulator for air break switch with metal part suitable for HT 22 KV conforming to IS-5572-1972
210Supply only Post insulator double stack for air break switch suitable for HT 22 KV
211Supply only DO insulator suitable for 22 KV with metal part conforming to IS-5572-1972.
212Supply only high conductivity copper wire mesh jumper 200 Amps rating for air break switch, 22 KV
213Supply only dropout fuses top/bottom contact
214M & L for Steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11m long) conforming to IS-2713 (Part-I & II) including painting of pole with two coats of aluminum paint over a coat of red oxide primer from top of the pole to 1.5m above the bottom of the pole and painting with two coats of black paint over a coat of red oxide primer upto 1.5m from bottom of the pole including numbering of poles as directed complete all as specified and directed.(Note: Excavation and earth work and PCC shall be measured and paid separately under respective item)
215M & L for PCC 1:4:8, type D-2, (using 40mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed.
216M & L for PCC 1:3:6, type C-2, (using 40mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and directed.
217M & L for PCC 1:2:4, type B-1, (using 20mm graded stone aggregate) as in coping including necessary use & waste of form work complete all as specified and directed.
218M & L for servicing (as described below) for outdoor type, HT 11 KV/433 Volt, Dry type Transformer of capacity upto 1000 KVA and carrying out thefollowing repair work :- (a) Servicing, cleaning, inspecting and testing for proper functioning of operation. (b) Servicing of de-hummidifying of core coils assly by hot air blower. (c) Cleaning of the coils of dust & other paricles. (d) Retightening of all the tie rods & core bolts. (e) Checking gaskets for the HT/LT insulators & Replacing the same. (f) Internal touch up for the enclosures & external touch up paint.
219Taking down copper/ aluminum point wiring (Light/Fan/Socket or power) complete including fixtures and fittings such as switches, ceiling roses, pendants, regulators, sockets light fitting etc.Removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces to walls floors etc.
220Taking down complete main switches/DBs with enclosure and its components of any size and capacity etc complete all as specified and directed.
221M & L for point wiring complete with proper colour coding using, 1100 Volts grade, 1.5 Sqmm, PVC insulated FRLS, unsheathed wire with multi stranded copper conductor confirming to IS-694, Part II, ISI marked drawnin and including PVC casing caping (minimum 25mm width) fixed on the surfaces of wall, ceiling etcwith all accessories, fittings, PVC junction boxes etc, sunk pressed steel boxes not less than 2 mm thick, 50 mm deep terminal boxes covered with 3mm thick plastic laminated sheet top cover fastended with chromium plated brass screws, also including 1.5 Sqmm, PVC insulated, FRLS, unsheathed, 1100 Volts multistranded copper conductor green colour as continuous earth wire connected to common earth dolly all as specified and directed for following items-:(a) one light point /fan/bell point controlled by one one way switch
222-ditto- all as per item No.220 above but for One 2pin/3 pin socket outlet 5 Amps on same board
223-ditto- all as per item No.220 above but for One 2pin/3 pin socket outlet 5 Amps on independent board
224M&L for point wiring using proper colour coding with 1100 Volts grade, 2.5 Sqmm PVC insulated, FRLS, unsheathed, wire confirming to IS-694, Part-II, ISI marked with multistranded copper conductordrawn in and including PVC casing caping (minimum 25mm in width)fixed on the surfaces with all accessories, fittings, PVC junction boxes etc, sunk pressed steel terminal boxes not less than 2 mm thick, 50 mm deep, covered with 3 mm thick plastic laminated sheet top cover fastened with chromium plated brass screws, also including 2.5 Sqmm, PVC insulated, FRLS, unsheathed, multistranded, copper conductor 1100 Volts grade, green color, continuous earth wire connected to common earth dolly for 15 Amps, 3 Pin, socket outlet independent, complete all as specified and directed.
225Supply & Fix Bell push, flush type, 5 Amp,230 Volts,complete all as specified and directed.
226S&F Switch Piano 5 Amps, 250 Volts, one way, flush type, complete all as specified and directed.
227S&F Switch Socket combination 2 in 1 , 5 Amps, flush type, 5 Pin, 240 Volts, complete all as specified and directed.
228S&F Switch Socket combination 2 in 1 , 5/15 Amps, flush type, 6 Pin, complete all as specified and directed.
229S&F ceiling rose three terminal, 230 Volts PVC / Polycarbonate body, complete all as specified and directed.
230S&F fan regulator, electronic stepped (5 step), 230 volts, 100 watt, flush type and connecting-up, complete all as specified and directed.
231Taking down carefully and refixing in position after repairs to existing flameproof LED lamp fitting including S & Fix in replacementunserviceable pin/ screw typeMLL lamp 60 watts all as directed and specified by Enginer in charge
232Taking down carefully and Refixing in position after repair to existingLED tube light fitting any watt any type, complete all as specified and directed
233S & F in repairs LED high bay fittngs of 120 Watts, IP 66 including providing hooks/clamps and steel counduit of suitable size as down rod for length up to 1.5 Meter including taking down rod unserviceable light fitting complete all as specified and directed by Engr-in - charge. Make of fitting shall be Cat part no-BJFL120W LED of Bajaj or equivanelt from Philips/Havells
234Supply and fix on roof / wall/purlins or on false ceiling with necessary fixing arrangement forCable PVC insulated armoured,PVC sheathered Stranded copper conductor1100 Volts grade 2.5 Sqmm 3 core for connecting the highbay light fittings from DB / switchboardincluding taking down old cable all as specifid and directed at site.
235S&F in Ultra bright glassLED tube rod 18/20 Watts, 230 Volts, with high efficencysuitable forT8 fitting with G13 lamp holder, the rod shall conform to Cat No CRYSTAL 1213T8DSTL 20 W LED 865 SGLASS of HAVELLSor equivalent from Philips/Crompton Bajaj .
236S&F indecorative box type fitting prewired Regal batten forLED light fitting 16/20 Watts, 230 volts, including PVC Mounting blocks - 2 Nos, including connecting up with 1.5 Sqmm White colour PVC insulated three core flexible multistranded copper conductor for connecting with ceiling rose. The fitting shall conform to Cat No REGALBATTENT8UPTO1X22WSSBSWH for Havells equivalent from Philips/Crompton Bajaj .
237Supply and fix in repairs SUPRA NEO-ILED Lights fittings 35 W wellglass in PDC Aluminium housing with finless design and exellent thermal management offering high durability and superior performance with energy saving and having efficacy of 110 Lm/W with provision of suitable fixing arrangement such as MS clamps,nut,bolts etc. Ingress protection of IP66 confirm to CAT No LWV12-35-(CDL) of crompton or equivalent from Philips/Bajaj as approved by the GE.
238S&F in Repairs Retro LED tube rod 8 Watts, 230 Volts, with high efficency PMMA diffuser, the rod shall conform to Cat No LTT8-8 of Crompton or equivalent from Philips/Bajaj.
239S&F in Repairs decorative box type fitting prewired Retro LED light fitting 8 Watts, 230 volts, including PVC Mounting blocks - 2 Nos, including connecting up with 1.5 Sqmm White colour PVC insulated three core flexible multistranded copper conductor for connecting with ceiling rose. The fitting shall conform to Cat No DMLN1LT8-8 of Crompton or equivalent from Philips/Bajaj.
240S&F in Repairs SKY LUX efficient LED (white)recessed 4x1 luminaire to enhance the delight of occupants with comfortable exprience through its classic design & glare free soft illuminations mounted direct/indirect architectural luminaire including connecting 1.5 Sqmm white colour suitable for false ceiling fixing arrangement all as specified and directed in EIC. The fitting shall conform to cat No BZRSLL 36W GZ1 WHof Bajaj or equivalent Philips/ Crompton.
241Taking down and refixing any type of DB and including cutting chases in wall, concealing DB in wall, making good the disturbed surfaces and making all connections, complet all as specified and directed
242S & F MCB DB, 12 way, SPN, double door, 240 Voltsand including cutting chases in wall, concealing DB in wall, making good the disturbed surfaces and making all connections, complete all as specified and directed. Note: Quoted rate shall also be deemed to include for provision of copper bus bar of 200 Amps rating.
243S & F MCB DB, 8 way, SPN, double door, 240 Voltsand including cutting chases in wall, concealing DB in wall, making good the disturbed surfaces and making all connections, complete all as specified and directed. Note: Quoted rate shall also be deemed to include for provision of copper bus bar of 200 Amps rating.
244S & F MCB DB, 4 way, SPN, double door, 240 Voltsand including cutting chases in wall, concealing DB in wall, making good the disturbed surfaces and making all connections, complete all as specified and directed. Note: Quoted rate shall also be deemed to include for provision of copper bus bar of 200 Amps rating.
245S & F MCB TPN 63 to 100 Amps, 240 / 415 Volts, 50 Hz, 10 KA Breaking capacity complete all as specified and directed.
246S & F MCB SPN 40Amps, 240 / 415 Volts, 50 Hz, 10 KA Breaking capacity complete all as specified and directed.
247S & F MCB, SP, 05 to 32 Amps, 240 Volts, 10 KA Breaking capacity, C-series, complete all as specified and directed.
248S & F MCB SPN 32 Amps, 240 / 415 Volts, 50 Hz, 10 KA Breaking capacity complete all as specified and directed.
249Disconnecting the electric connecting and screwing and taking down the unserviceable sub mainwiring and M&L for sub mainwiring with twosingle core4.0 Sqmm PVC insulated FRLS multistrandedflexible copperconductorcable 660/1100 volts grade downin throughnon metalicPVC casing capingwith and includingPVC insulated 4.0 Sqmsinglecore singlestrand copperconductoras continous earth wire in greencolour connected to commonearth dolly all as specified and as directed Note : 1. Two runs ofcable, one run of earth wire, one run of PVC casing capping will be measured and paid one unit.
250S& F in repair of GI steel tubing medium grade 40mm dia and length up to 1.5 meter bent to shape of offset angle upto 45degree for fixing of security /street light fittings including MS clamps made of 32mm x5mm flat iron, nuts , bolts, etc all as directed by Engineer in charge.
251Supply and fix in repair ofFRP looping box of size 155x210x92 mm with connector, MCB 6 Amps, Din Rail, GI clamps made out of GI flat of size 25mm X 3 mm channelincluding making connections all as specified and directed by Engineer -in -Charge confirm to Cat No KF 1616 B of Hansel or equivalent of sintex/Standared.
252supply & lay 3Core 1.5 Sq mm size multistranded copper conductor PVC unsheathed 650 / 1100 Volt Grade As per IS 694 with and including 20 mm dia PVC conduit and passing through PVC conduit with necessary saddle, clamps, bolts & nuts,all For interconnection of cable looping box to Street Light Fitting, Post Top Lantern etc including taking down existing cable & PVC ConduitAll as Directed.
253M&L for Multistranded Copper Conductor cable of3 Core 1.5 Sq mmsize drawn through steel tubular poles for interconnection of cable looping box to Street Light Fitting, Post Top Lantern etc taking down old unsv cable all as Directed.
254Supply and fix in repair street light/ building security lightfitting LED 60 watts Cat no - BRTFG 60W LED V3 of Bajaj orequivalent inHavells / Philips .with Pressure die casthousing wih toughened glass and individual LED"s with secondary optics& IP66 protection etc all as directed by Engineer in charge
255Taking down carefully ceiling fan, exhaust fan, wall / pedestal fan of any make and any sweep and dismantling of blades canopy down rod etc & remove to store for repair. & Refix the same including provision of3 core 1.5 sq mm copper flexiable cable from ceiling rose to connector of suitable length. Note:(i) The representative of the contrcator shall report to Engineer-in-charge/JE on daily basis to carry out repairs to fan and the defects should be rectified on the same day.
256M&L for Opening of body cleaning of slots, Rewinding of fan by super ennameled copper insulated wire as per existing gauge, varnishing, heating assembling and testing complete all as directed by Engineer-in-Charge. Note - Spares such as Bearing, Capacitor, Capacitor Clamp, Rubber insulator will be measured seperately under respective item of this schedule.
257-ditto-as per item No 255 but Ceiling fan 1200 / 1400 mm Sweep.
258-ditto-as per item No 255 but Exhaust Fan,Pedestal fan,wall fan, table fan 300/400 mm Sweep.
259-ditto-as per item No 255 but Exhaust Fan, Pedastal fan,wall fan,450/600 mm Sweep.
260Painting onlyof ceiling fan,exhaust fan,wall fan,pedestal fan for any size and type, scraping out of old paint filling of cavities with filler preparationof body and cleaning of dust etc Painting by Spray with first Quality Paintcomplete allas specified and directed.
261Overhauling of Ceiling Fan, Exhaust Fan, Wall Fan,Table fan,Pedestal Fan any Make & any Sweep including dismantling/opening of body, cleaning of body, oiling, greasing & reassembling complete, replacing of split pin, nut , bolts etc and testing Note : Spares shall be measured & paid respective item of this sch.
262Supply only spare parts to be incorporated for repairing fans in respective item of this schedule
263Capacitor up to 2.5 Mfd
264Capacitor Clamp with Connector As Par Sample
265Rubber Insulator sutiablefor any type ofCeiling Fan.
266Mild steel Down Rod 600 mm Long with Clamp nut bolts & split pin as per sample/ existingsize
267Mild steel Down Rod with Clamp nut bolts& split pin for 900 mm Long as per sample/ existingsize
268Ball bearing sutiable for any type of fans
269Gun Metal bush as per sample sutiable for any type of fans
270Mild steel shaft as per sample / existingsize for any fan
271Ceiling Fan Blade suitable for 1200/1400 mm sweep as per sample/ existingsize.
272M & L forFlame proof Light point wiring withFRLS PVCinsulated unsheathed 1100 Volts grade single core multistranded copper conductor cable 1.5 Sqmm drawn in and including Stove Enamlled steel conduitand accessories such as bend tee elbow(two way, three way,four way) junction box with cover fixed on wall / ceiling etc with neccessar fixing access complete for allas directed
273S&F in repair flame proof WP rotoy switch/Isolator 230 volt 10 A double pole ON / OFF with cable termination box in LM6, including anchor fasteners complete for allas directed
274Supply and fix in repairs flame proof LED Light fittings CIMFR certified LED flameproof wellness in die cast AI housing with heat resistance toughened glass GLAZE PROLED Lights fittings 30 W . Recommendation for gas/Vapour group of IIA and IIB and Zone 1 & 2 IP65 pretected confirm to CAT No FWL1315-30-CDL of crompton or equivalent from Philips/Bajaj as approved by the GE.
275Taking down carefully point wiring of any type & pattern (Light/Fan/Socket or power) including fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings of any type etcand making good disturbed surfaces of walls/ roof etc, complete all as specified and directed.
276M & L forpoint wiring with PVCinsulated FRLS unsheathed 1100 Volts grade single core multistranded copper conductorcable 1.5 Sqmm drawn in and including PVC casing-caping, fixed on wall / ceiling with all accessories, fittings, PVC junction boxes etc, with suitabe sunk pressed steel boxes for modular fittings not less than 1.6 mm thick, etc with necessary fixing accessories andearth continuity conductor cable of 1.5 Sqmm size connected to common earth and earth dolly including 1.6 mm thick pressedsteel terminal boxes concealed in wallall as specified for one light / fan / bellpoint controlled by one switch.
277-Ditto- all as per item No 263 here-in-before but for one 5A 2pin/3pin socket out let multipurpose on the same board with other switches.
278-Ditto- all as per item No 263 here-in-before but for one 5A 2pin/3pin switch socket out let multipurpose on independent Board.
279All as per item No. 271 above but wiring complete with 2.5Sqmm for 3 pin 15A socket multipurpose on independent board
280S&F modular type6A one way SP switch 1 moduleconfirming to IS: 3854-1997 with fingure proof terminal complete all as specified and directed.
281S&F modular type 2/3 pin combined shuttered type 6 Amps socket 2 module conforming to IS: 1293-2005 complete all as specified and directed.
282S&F modular type 2/3 pin combined shuttered typr 16 Amps socket 2 module conforming toIS: 1293-2005 complete all as specified and directed.
283S&F modular type16 A one way SP switch 1 module confirming to IS: 3854-1997 with finguer proof terminal complete all as specified and directed.
284S&Fmodular type 120W step fan regulator of 2 module size conformng to IS: 11037-1984 complete all as specified and directed.
285Supply & Fix Modular Bell push flush type 6 Amp, 1 module, 230 Volts complete all as specified and directed.
286S & F Modular Blank plate 1 module suitable for Modular switch boards all as specified and as directed
287S & F Modularcover plate 8 modules
288S & F Modularcover plate 4 modules
289S & F Modularcover plate 3 modules
290S & F Modularcover plate 6 modules
291S & F Modularcover plate 1 modules
292Material and labour for carrying out vaccum test, pressure test and detecting leakage rectifying the leak and charging the refrigerant (R-22) complete for Tower/split/window type A/C of any capacity Note : (i) Job includes dismentling equipment from any site, height and transporting to workshop if necessary and reinstalled in situ and testing (ii) Above Job to be guaranteed for minimum one year
293--ditto -- all as per item No 279but for water cooler of any capacity
294--ditto -- all a s per item no279 abovebut suitablefor refrigertor/ deep freezer of any capacity
295M & L for repairs to base/body/stand of water cooler of any capacity by cutting out rusted portion, replacing with new M.S sheet of existing gauge including finishing wall surface and painting complete body of water cooler of any capacity Noe :- Job includes dismantling equipment transporting to workshop and back included" re-installing in situ.
296Supply and fix in repairs chasis made out of 2mm thick MS sheet suitable for 1.5 TR/ 2.0 TRcapacity window type AC including dismantling accessories and re-installing on new chasis,painting complete body and required parts incld connection with new wiring etc all as directed
297Material and labour for servicing of A/C window type or split type A/C, tower ACof capacity1.5/2/2.5 TRincluding washing with sodash the cooling coil/condensor coil base body drying with air blowerchecking complete wiring testing and re-installing in situ and testing the unit.
298M & L for dismentling unserviceablecompressor from the window type AC, Split type A/C 1.5 TR/ 2.0 TR capacity from any location , supply and fix new hermatically sealed compressor unit , assembling, brazing pressure/vaccum testing initial oil charging, gas charging,reinstalling A/C in situ and connecting to electric supply and testingall as directed and specified. Make : Voltas/Carrier/Kirloskar /bluestar Note : (i)Job including removing A/C from any site/height/location (ii)Transporting A/C unit to repair workshop and back to site (iii) Loading/unloading etc
299--ditto -- all as per item 285 above but suitable for refrigerator 165 to 320 ltrs capacity
300--ditto -- all as per item 285 above but suitable for water cooler 40 t0 150 ltrs capacity
301--ditto -- all as per item 285 above but suitable for deep freezer of 200 to 500 ltrs capacity
302Supply and fix in repairAC fan motor for window/splittype A/C of 1.5/2 TR ,Tower AC 2.5 TRcapacity single phase 230 volt 50 HZ complete with fan blade/blower includingany addition/alteration to suit new fitting of motor.
303--ditto -- all as per item No. 289 but for Water cooler any capacity
304--ditto -- all as per item No. 289 but for deep freezer any capacity
305Supply and fix in repairRelay for A/C split/window type,Tower AC
306Supply and fix in repair Relay for WATER COOLER/DEEP FREEZER
307Supply and fix in repairThermostat for A/C 1.5 TR/2 TR,Tower AC
308-ditto- all as per item No 294 but for water cooler of any capacity
309Supply and fix in repair Air filtter for window type/split type AC, Tower AC as per sample
310Supply and fix in repairStarting capacitor 80-100 mfd 220 volt 50 HZ
311Supply and fixing in repairof Running capacitors ofcapacity 36 MFD220 volt50Hz complete all as specified and directed by Engr-in-Charge
312-ditto- all as per item No 298 but 6 MFD
313-ditto- all as per item No 298 but 4 MFD
314-ditto- all as per item No 298 but 45 MFD
315Supply and fix Starting capacitor of capacity 120 - 150 MFD for 2 TR, 2.5 TR capacity
316Supply and fix in repair 3 core 4 sqmm flexible cable PVC insulated sheathed copper 1100 volts grade.
317Supply and fix in repair 3 core 2.5 sqmm flexible cable PVC insulated sheathed copper 1100 volts grade.
318Supply and fix in repair earthed metal clad socket outlet with earthed plug top 20 Amps capacity with sheet metal enclosure and one 20 Amps MCB SP all as specified and directed.
319M & L for power point wiring with PVC insulated sheathed copper wire 4 Sqmm size 1100 volts grade IS-654 in and including PVC casing and capping with all accessories including one run of 2.5 Sqm earth lead wire all as directed and specified.
320Supply and fix in repair copper tube of size 6mm bore including brazing etc with rubberised insulation and tape suitable for supply pipes for air-conditioners complete all specifiedby Engineer -in-charge
321Supply and fix in repair copper tube of size 10 mm bore including brazing etc with rubberised insulation and tapesuitable for supply pipes for air-conditioners complete all specified by Engineer -in-charge.
322Supply and fix in repairs 8mm dia hand shut off valve
323Supply and fixing in repair and testing fan blade of motor for water cooler of 80/100/120/150 Ltrs capacity including removing old fan blade.
324Supply and fixing in repair and testing fan blade suitable for window type Air conditioner of 1.5 Ton/2 Ton capacity including removing old fan blade.
325Supply and fix in repairs front grill as per sample suitable for window type AC 1.5 TR/2 TR capacity.
326Supply and fixing in repair of blower drum suitable for window type Air concitioner of capacity 1.5Ton /2TON.
327Supply and fix in repair stainless steel tank of capacity 40 ltrs capacity water cooler of existing size shape
328All as per item No. 314 but 80 ltrs capacity
329-All as per item No. 314 but 120 ltrs capacity
330Supply and fix in repairwaste water tray suitable for single/double tap with waste hose.
331Supply and fix in repair PVC float valve wih PVC ball suitable for 15mm dia
332Supply and fix in repairs bibtap push type stainless steel 15mm dia
333Supply and fix in repairs gun metal gate valve with iron wheel head screwed both ends for iron pipe of size 20mm.
334Supply and fix in repairs gun metal gate valve with iron wheel head screwed both ends for iron pipe of size 15mm.
335Supply and fix in repairs remote sensor kit with Manual control pendent suitable for split type A/C,Tower AC1.5 TR to 2.5 TR capacity work on 230 volt SP 50 HZ
336Supply and fixbase tray suitable A/C 1.5/2 TR made out of 2mm thick of existing size and shape including painting one coat zine chromered oxide and two coats of synthetic enamelled paint
337Supply and fix in repairs ventury and blower drum suitable for A/C window type 1.5 TR/2 TR as per existing model, size, and shape
338Supply and fix in repairs condensor coils suitable for 1.5 TR to 2.5 TR capacity including dismentling old one brazing, testing, leakage rectification all as directed.
339Supply and fix in repairs cooling coil suitable for 1.5 TR to 2.5 TR A/C of existing model including taking out old defective coil, brazing work, brass charging to full pressure
340Supply and fix in repairs thermal over load relay 415 volts 66 - 110 Amps rating MMX R-4 model
341Supply and fix in repairs thermal over load relay 415 volts 32 - 50 Amps rating MMX R-4 model
342M&Lin repair for wall mounted powder coated MS bracket suitable for 1.5TR/2TR Split type AC, Towre AC 2.5 TR out door unit
343M&L for repair of rubberised insulation and tape for copper tubes of size 6mm/10mm.