Defence Statutory Bodies & Commissions/Committees Closing in 0 days TDR #31792987

Spl Repair/Replacement Of Lt Feeder Pillar Box, Mccb, Lt Ug Cable And Allied Items For Security Light/Streets Light At Mahar Area And Spl Repair/Replacement Of Window And Doors Of Bldg No 142 Of Engr Regt At Dipatoli Pocket Of Ranchi Mil Station Spl Repai

Issued by Statutory Bodies & Commissions/Committees · dipatoli, Jharkhand
Tender Value
30.39 Lakhs
Estimated cost
Bid Submission
23 Apr 2022
0 days left
EMD
60800
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
dipatoli → Jharkhand
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Spl Repair/Replacement Of Lt Feeder Pillar Box, Mccb, Lt Ug Cable And Allied Items For Security Light/Streets Light At Mahar Area And Spl Repair/Replacement Of Window And Doors Of Bldg No 142 Of Engr Regt At Dipatoli Pocket Of Ranchi Mil Station Spl Repair/Replacement Of Lt Feeder Pillar Box, Mccb, Lt Ug Cable And Allied Items For Security Light/Streets Light At Mahar Area And Spl Repair/Replacement Of Window And Doors Of Bldg No 142 Of Engr Regt At Dipatoli Pocket Of Ranchi Mil Station

BOQ

Name of Work:- SPL REPAIR/REPLACEMENT OF LT FEEDER PILLAR BOX, MCCB, LT UG CABLE AND ALLIED ITEMS FOR SECURITY LIGHT/STREETS LIGHT AT MAHAR AREA AND SPL REPAIR/REPLACEMENT OF WINDOW AND DOORS OF BLDG NO 142 OF ENGR REGT AT DIPATOLI POCKET OF RANCHI MIL STATION
Sl. No. Item Description
1Taking down cement plaster on brick/stone surface of wall built in cement mortar including racking out joints, hacking for key, scrubbing down with water etc complete all as specified and as directed
2Demolition ofBrick/stone works masonry, built in cement mortar or cement limemortar including all quoins, arches, pillars etc but excludingashlar facing, dressed stone work andpre-cast concrete articles complete all as specified and as directed
3M&L brick work using fly ash brick curved or straight on plan exc 6m mean radius, built in CM(1:4)complete all as specified and as directed
4M&L rendering on other than fair faces of brick work 15mm thick in CM 1:6 and to be finished smooth and even with out using extra cement for internal surfacecomplete all as specified and as directed
5S&F wire netting of galvanised steel wire 1.23mm dia and size of mesh 25 on crack of corners/wall/ceiling as required and as directed
6M&L rendering on other than fair faces of brick work 15mm thick in CM (1:4) and to be finished smooth and even with out using extra cementfor external surfacecomplete all as specified and as directed
7M&L for preparation of new plastered and applying two coats of exterior weather coat over one coat of alkali resistant priming plastered complete all as specified and as directed (Weather coat shall be of Asian paint, Apex ,ultima or equivalent as approved by GE)
8M&L for preparing newly plastered surfaces and applying two coats of distember oil emulsion white or tinted on walls and including average 3mm thick white wall care putty in two layer to achieve even and smooth surfacecomplete all as specified and as directed
9Complete removal of existing treatment and preparing the surface of walls/ceiling with Birla putty/JK Wall putty and applying two coat of oil bound distemper over a coat of chalk whiting primer complete all as specified and directed
10M&L for preparation of old surface of ceiling and applying two coats of white wash and all as specified and directed.
11M&l for complete removal of existing treatment on wall by brooming down with wire brushing etc andapplying two coats of exterior weather coat over one coat of cement base primer complete all as specified and as directed (Weather coat shall be of Asian paint, Apex ,ultima or equivalent as approved by GE)
12M&L for applying two coats of white wash on oldsurfaces of ceiling including preparation of newly plastered surfaces all as specified and directed.
13Taking down chowkhat with shutter (without taking off shutter from chowkhat/frame) not exceeding 1.5 Sqm each complete all as specified and as directed
14Ditto all as per item No 13but exceeding 1.5 Sqm but not exceeding 4 Sqm each complete all as specified and as directed
15S&F powder coated anodised aluminium window and ventilator shutters, sliding type, aluminium sections weighing 0.55 Kg/M including necessary joining cleats, glazing, clip, rubber packing, anodised aluminium snap beading, anodised aluminium fittings such as stopper, locking etc complete all as specified and directed
16S&F powder coated anodised aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc complete all as specified and directed.
17S&F powder coated alumunium glazed door shutters aluminium section weighing 0.55 Kg/m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 02 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified and directed.
18S&F GI mild steel wire cloth 0.56 nominal dia wire and average width aperture 1.18mm and fixed with pinned tack or galvanized staples complete all as specified and as directed
19M&L mild steel works as in framed work such as grills, gratings, etcwith ends of bars shoulderedand/or riveted or forged into spikes and similar works conforming to Fe-290, Gde-E165 etccomplete all as specified and as directed
20Preparation of new steel surface of any description any applying two coats of synthetic enamel paint under one coat of red oxide, over 10 cm in width or girth, not otherwise described
21M&L in applying two coats of synthetic enamel paintson old surfaces wooden over 10 cm width or girth including preparatinon of surfacescomplete all as specified and as directed
22M/L PCC 1:2:4 type B1 20mm grade aggregate as in padding, hold fasts/filling of chowkhats or similar work complete all as specified and as directed
23S & F Sheet glass, ordinary quality and glazing with oil putty in square n exc 0.5 sqm in each pane 4mm thick complete all as specified and as directed
24S & F Sheet glass, ordinary quality and glazing with oil putty in square n exc 0.5 sqm in each pane 5.50mm thick complete all as specified and as directed
25Supply only integral waterproofing compound
26Roundering to edges of stone slabs on edge such as in steps, cooking plateform and other similar situations.
27M&L Machine cut black Granite stone slab 20 mm thick (as in window cill) over 15mm thick (1:6) cement screedbase laid and jointed with greyement slurrymixed with pigment to match the shade of slab including rounding of edges,grinding and polishingcomplete all as specified and as directed
28Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish offi the premises.
29S&F as in repairsm harrison rails, anodised aluminium alloy chromium plated with fixing backets, stops, rollers etc.
30S&F 4 levers brass mortice lock vertical type, size 100mm and all as specified and directed.
31S&F Aluminium (extruded section) body door closer hydraulically regulated, designation No 1 universal type, suitable for door shutters of 851 to 1000mm in width and of weight between 61 to 80 Kg and fixed and all as specified and directed
32Taking loose/damaged concrete incl plaster of any description and in any position from RCC structure like beam,column,facia,chajjas and ceiling by carefully hummering with wooden mallets, chipping of concrete surfaces and cleaning of old concrete and rendering 10mm thickin CM (1:3) including throating,also necessary repairconcrete surfaces if any with cement concrete(1:2:4) Type B-0 using 12.5mm gradedaggregateincluding water proofing compound andnecessary scafolding as requiredfor single storey bldgscomplete all as specified and as directed.(Note steel measured separate and paid)
33Dismantling and taking down old unserviceable street light fitting/bldg security light fittings/High Mast Light fitting/Post top laltern of any capacity from upto 20 mtr height of pole /wall incl disconnecting the cable connections complete all as specified and directed.
34S & F Pressure die cast aluminum alloy housingLED street light fitting60Wattcomprises of pressure die cast Aluminium housing & having system efficiency 110 lumens/Watt i.e 6670 lumns,All LEDs should be highpower LEDs of 1W to 3W Only with moduler lens for batwin shape distribution of 30 degree & 60 degree,Input voltage working range is 140 Vac to 270 Vac,Brand name should be emoboised,Potted Driver is used with 4KV internal & external 5KV Potted surge protection,Short Circuit Protection,Open Circuit Protection,High & low voltage protection,fixture should withstand high & low voltage protection,fixture should withstand high voltage upto440 v for 8 hr,IP66 Protected,THD<10%,CRI>70CCT 5700+/-300K, PF>0.9, Driver efficiency>85%,LM79 report require from NABL Accediated lab all as directed by Engr-in-Charge. Make : Crompton cat part No. LSTP-72-CDL-M or equivalent inPanasonic/Philips.
35S & F Pressure die cast aluminum alloy housingLED street light fitting90Wattcomprises of pressure die cast Aluminium housing & having system efficiency 110 lumens/Watt i.e 6670 lumns,All LEDs should be highpower LEDs of 1W to 3W Only with moduler lens for batwin shape distribution of 30 degree & 60 degree,Input voltage working range is 140 Vac to 270 Vac,Brand name should be emoboised,Potted Driver is used with 4KV internal & external 5KV Potted surge protection,Short Circuit Protection,Open Circuit Protection,High & low voltage protection,fixture should withstand high & low voltage protection,fixture should withstand high voltage upto440 v for 8 hr,IP66 Protected,THD<10%,CRI>70CCT 5700+/-300K, PF>0.9, Driver efficiency>85%,LM79 report require from NABL Accediated lab all as directed by Engr-in-Charge. Make : Crompton cat part No. LSTP-90-CDL-M or equivalent in Panasonic /Philips.
36Supply & Fix LED flood light ftg 150 Watts , Incl Driver unit assy with surge protection,Short Circuit Protection,Open Circuit Protection,High & low voltage protection,fixture should withstand high & low voltage protection,fixture should withstand high voltage upto440 v for 8 hr,IP66 Protected,Make: Crompton Cat part No LFNL-150-CDL/60-M or equivalent in Panasonic /Philips.
37Taking down XLPE cable and high mast cablefrom any height of pole and removing the materials from site and making good thedisturbed surfacesetc complete all as specified and directed.
38Supply,laying,jointing,testing andcommissioningXLPE insulated,armoured,heavy duty, LT UG cable with aluminium conductor,1100 volts grade cross sectional area10 sqmm 4 core connectedwith aluminium lugsconnectedby cramping toolscomplete all as specified and directed.Note:- Excavation andearth work will be measured and paid separately.
39Supply,laying,jointing,testing andcommissioningXLPE insulated,armoured,heavy duty, LT UG cable with aluminium conductor,1100 volts grade cross sectional area16 sqmm 4 core connectedwith aluminium lugsconnectedby cramping toolscomplete all as specified and directed.Note:- Excavation andearth work will be measured and paid separately.
40All as per Srl items No.39here-in-beforebut of size 70 sqmm x 3.5 core
41All as per Srl items No.39here-in-beforebut of size 95 sqmm x 3.5 core
42Excavation in trenches in soft/loose soil n.exc 1.5 mtr wide and n.exc 1.5 mtr depth and getting out for taking out / laying of cable complete all as specified and directed.
43Supply and providing sand cushioning with dry clean sand 15 cm below cable and 8 cm above the cable complete all as specified and directed. Note : Punned thickness shall be measured for the purpose of payments.
44Supply and laying burnt bricks old size sub class-B laid in trenches for cable protection with length of brick perpendicular to length of cable complete all as specified and directed.
45Removing surplus excavated material not exc 50 mtrs and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
46Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed.
47Taking down outdoor type LT Panel with by disconnecting all connections very carefully of any size and capacity and complete all as specified and directed
48Supply and installationtesting andand commissioning outdoor LT panel totally enclosed weather and vermin proof, suitably ventilated, 440 Volts, 50HZ,AC supply,fully compartamentalised cubical type made out of 3 mm thick CRCA sheet steel for load bearing and2.0 mm thick non load bearing portions, protection ofenclosure IP-54 as per IS-2147 of 1962 complete with pretreatmentand powder coating of approvedcolour including suitable angleiron/flat iron frame work/ supports, excavation and earth work, PCC foundation etc, including the follwoing switchgear, suppliedfitted and connected internally complete with bus bar all as directed and specified :- (a)4 Nos copper bus bar of equal size of aluminium conductor with PVC coloured heat shrinkable type sleevescontiuous rating 800 Ampswith CTs, ammeter and volt meter with selector switches, set of LED type,indicating lamps R,Y,B on incoming side (b) MCCBTPN, 415 volt adjustable type, 630 Amps with breaking capacity 50 KA- 01 No (Incoming) (Make: L&T/Schnieder/siemens)(c) MCCB TPN 415 volt 250 Amps wirh breaking capacity 36 KA-02Nos(d) MCCB TPN 415 volt 200 Amps wirh breaking capacity 36 KA-02Nos (outgoing) (Make: L&T/Schnieder/siemens)(e) MCCB TPN 415 volt 160 Amps wirh breaking capacity 25 KA-02Nos (outgoing) (Make: L&T/Schnieder/siemens) (f) MCB TPN 63 Amps Outgoing -01 Nos
49Taking down MCCB by disconnecting all connections very carefully of any size and capacity and deposit to MES Store complete all as specified and directed
50Supply and fix in replacement MCCB TPN 415 volts with microprocessor based release50 Hz , 630 Amps with breaking capacity 50 KAcomplete all as specified and directed. Make : legrand/Schenider/siemens
51Supply and fix in replacement MCCB TPN 415 volts with thermal magnetic release 50 Hz500 Amps with breaking capacity 36 KAcomplete all as specified and directed. Make :legrand/Schenider/siemens
52Supply and fix in replacement MCCB 4 Pole 415 volts 350 Amps 50 Hz Adjustable type, with breaking capacity 36 KA complete all as specified and directed at site. Make : legrand cat no 4220 02 /Schenider/siemens
53Supply and fix in replacement MCCB TPN 415 volts 250 Amps 50 Hz Adjustable type, with breaking capacity 36 KA with breaking capacity 36 KAcomplete all as specified and directed.Make : legrand cat no 4202 39 /Schenider/siemens
54Supply and fix in replacement MCCB TPN 415 volts 160 Amps 50 Hz Adjustable type, with breaking capacity 36 KA with breaking capacity 36 KAcomplete all as specified and directed. Make : legrand cat no 4200 87 /Schenider/siemens
55M&L for PCC(1:3:6) type C1 using 20 mm graded stone aggaregate in kerbs/coping /bed plates and like including weathering slightly rounded or chamfered completewith necessary use and waste fo formwork complete all as specified and directed
56M &L for GI Earthing complete with GIearth plate electrode 60cm x 60cm x6 mm buried directly in ground verticvally to size of earth pit not less than 0.90x 0.90 x 2.25 mtr below ground level with top edge ofthe plate at a depth not less than 1.5 mtr below ground level, earth plate connected to galvanised earthstripof size 32 x 6 mm, 7.5 mtr long (Min) by means of brazing nuts, bolts, check nuts, & washers,testing of completion (drawn in earth strip protection pipe light gade GI of size 40 mm dia) by means brazing at both edges with vertical plane of electrode all as shown in plate No 3 of SSRPart - I filling with charcoal dust , and common salt,including necessary excavation and earth work in any type of soil ,perforated watering pipeof size 15 mm dia,funnel with wire mesh,earth strip protection pipe light grade PCC chamber 1:3:6 type C1 (for even finish on both the faces) and RCC cover 1:2:4 Type B1,450 x450 x50 mm thick with 6 mm dia CTD bars 150 mm c/c with 2 Nos of handles of 10 mm dia steel rod all as specified and directed and testing on completion and connected to equipment with lugs and screw nuts etc all as specified and directedNote :(i) 7.5 RM GI earth wire deemed to be included in quoted rates beyond 7.5 RM wire shall be measured and paid separately.(ii) Earth resistance of earth pit should be not more than 02 Ohms on testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.(iii) Rate quoted by the tenderer is deemed to included salt & Charcoal upto & above 450 mm (Min) top of GI Plate.
57S&F GI earth strip (32x6) mm strip with and including necessary clamps, nut bolts laid in ground complete all as specified and as directed.
58S&F steel work in tubular trusses including special shaped washer etc complete using ERW or induction butt welded tubes confirming to I.S. 1161-1998

AI Tender Summary

OUR REF NO 31792987
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 30.39 Lakhs
LAST DATE 23-04-2022
Authority
Authority Name Military Engineer Services
Work Description Spl Repair/Replacement Of Lt Feeder Pillar Box, Mccb, Lt Ug Cable And Allied Items For Security Light/Streets Light At Mahar Area And Spl Repair/Replacement Of Window And Doors Of Bldg No 142 Of Engr Regt At Dipatoli Pocket Of Ranchi Mil Station Spl Repair/Replacement Of Lt Feeder Pillar Box, Mccb, Lt Ug Cable And Allied Items For Security Light/Streets Light At Mahar Area And Spl Repair/Replacement Of Window And Doors Of Bldg No 142 Of Engr Regt At Dipatoli Pocket Of Ranchi Mil Station
Basic Detail
Tender No 8000/1779/E8
Bidding Type Tender
Location
City dipatoli
State Jharkhand
Key Dates
Publish Date 09 Apr 2022
Submission Date 23 Apr 2022
Open Date 25 Apr 2022
Finance
Tender Value 30.39 Lakhs
Tender Fee 500
EMD 60800
Exemption Not Available
Document List
Tendernotice_1.pdf
33c2e273-8979-44e4-8f74-1d668e761e3d.html
1779tenderdocuments2ndCall.pdf
BOQ_578472.xls

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Apr 09, 2022
11:30 IST

Tender Published

Tender notice published.

Completed
Apr 23, 2022
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Apr 25, 2022

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
pdf

Tendernotice_1.pdf

html

33c2e273-8979-44e4-8f74-1d668e761e3d.html

pdf

1779tenderdocuments2ndCall.pdf

xls

BOQ_578472.xls

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders