Repair / Maintenance Of Central Ac Plant, Annual Maintenance Contract And Maintenance Of Dg Sets, Amf Panel And Allied Works And Repair / Maint Of Summer Appliances And Other Connected Works In Zone A Area Under Ge ( I ) Rnd Delhi, delhi-Delhi

Military Engineer Services-MES has published Repair / Maintenance Of Central Ac Plant, Annual Maintenance Contract And Maintenance Of Dg Sets, Amf Panel And Allied Works And Repair / Maint Of Summer Appliances And Other Connected Works In Zone A Area Under Ge ( I ) Rnd Delhi. Submission Date for this Tender is 16-04-2022. Diesel Generators Tenders in delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

31644718
Corrigendum : Repair / Maintenance Of Central Ac Plant, Annual Maintenance Contract And Maintenance Of Dg Sets, Amf Panel And Allied Works And Repair / Maint Of Summer Appliances And Other Connected Works In Zone A Area Under Ge ( I ) Rnd Delhi
Open Tender
Indian
Delhi
delhi
16-04-2022

Tender Details

Repair / Maintenance Of Central Ac Plant, Annual Maintenance Contract And Maintenance Of Dg Sets, Amf Panel And Allied Works And Repair / Maint Of Summer Appliances And Other Connected Works In Zone A Area Under Ge ( I ) Rnd Delhi

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 09-Apr-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 16-04-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 98400.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : REPAIR/MAINT OF CENTRAL AC PLANT, AMC AND MAINT OF DG SETS, AMF PANEL AND ALLIED WORKS AND REPAIR/MAINT OF SUMMER APPLIANCES AND OTHER CONNECTED WORKS IN ZONE A AREA UNDER GE (I) R&D DELHI
Sl. No. Item Description
1M&L for overhauling of compressor of central AC plant of capacity 40 TR of make blue star model JS 43/44 including rewinding of compressor motor, grinding of crank shaft,connecting rod , greasing ,polishing, replacement of any unserviceable spares like connecting rod, piston,liner,piston rings, suction/discharge head, suction/discharge spring, main bush, oil pump assembly, oil filter, gasket, studs,nuts,bolts,thrust washer, oil pump, main bearingand repair of inner guide,wall plate,crank shaft complete with testing complete allas specified and directed.
2M&L for disconnecting, dismantling and strip opening of the existing air handling unit of any description and in any position and of capacity of 40TR for overhauling and servicing, including taking out existing shaft, blower drum, pulley and de-humidifier pump etc of air handling unit, checking thoroughly serviceability of the parts, fixing the serviceable parts in positiion, replacement of the defective/non functional/unserviceable parts/spares, reassembling, commissioning, fixing in position and testing of the air handling unit on full load for its smooth and trouble free operation complete all as specified and directed.
3M&L for repairingof cooling tower of central AC plant of 40TR including replacement of 7.5 HP Motor, FRP side pannels,PVC Fillsand jali and jointing , cleaning of cooling towerstuds,nuts,bolts and repair ofleakage etc if any complete with testing all as per satisfaction of Engineer-in-Charge complete all as per specified and as directed.
4S&Fin replacement ofAluminium fansix nos of blades suitable for 40 TR cooling tower complete all as specified and as directed.
5M&Lfor overhauling of pump and rewinding of electric mortor with super enameled copper winding wire of existing gauge of capacity 7.5 HP capacity by opening up and cleaning of all parts such as impeller , rotor, stator, fan cover, greasingmachine,work etc and reconnecting back and testing complete all as per specified and as directed.
6M&Lfor overhauling of pump and rewinding of electric motor with super enamelled copper winding wire of existing gauge of capacity05 HPby opening up and cleaning of all parts such as impeller, rotor, stator, fan cover, greasing machine work etc and reconnecting back and testing complete all as per specified and as directed.
7All as per item ser No. 06.00 above but 15 to 20 HP.
8M&L for descaling and cleaning of 40 TR condenser water cooled by circulating the diluted chemical HCL by forced feed method not less than 6.00 hrs duration by opening of the end covers of the condenser brushing the tubes thoroughly,re-fixing back the end cover of the condensers with 3mm thick rubber gasket and testing complete to maintaining desired discharged pressures for water cooled condenser complete all as specified and as directed.
9M&L for charging of Refrigerant R-22 complete including testing after completion in 60 TR AC plant and window / split AC upto 2 ton capacity complete all as specified anddirected.
10M&L for charging of Refrigerant R-410A complete including testing after completion in split AC upto 2 ton capacity complete all as specified anddirected.
11Supply & filling in replacement ofcompressors oil (Refrigeration lubricant)with testing complete all as specified anddirected.
12M&L for repair to leakage including brazing, Nitrogen Testing and recommissioning of 40 TR water cooledChiller complete all as specified and directed.
13Comprehensive Maintenance of Blue Star Make : Water Cooled 40 TR -02 Nos. (I) SCOPE OF WORK- AC Plant (a) Blue Star shall check and render preventive maintenance service to all the equipment every 3 months i.e., four times in a year during the currency of the contract. Blue Star will also attend/arrange to attend all normal break-downs if any, on call basis. Each service will include the following: (b). Checking the functioning of Condensor/Air Handling unit/Pumps/Controls and all such equipment covered under the contract. (c). Free replacing of defective/worn out parts with new or repaired parts for compressor/thermostat/ cut outs based on our assessment. (d). Repairing of equipment at site (e). Descaling of condensers/chemical cleaning of evaporator coils based on our assessment and working parameters of the plant. (f). Annual pumping-down and restarting as and when required. (g). Checking of Microprocessor control panel, control boards, transducers of packaged chillers/condensing unit for their correctness and replace if necessary. (h). Replacing of parts due to normal wear and tear.
14(II) EXCLUSIONS (a). Day to day maintenance and operation of the machine/plant (Except for operation contracts) or additional service during the year. These services shall be offered on chargeable basis. (b). Cleaning of equipment external (like drain piping) to the equipment. (c). Refillingrefrigerant gas and compressor oil. (d). Repairs and/or replacement of any spare or equipment due to ageing and damage due to external factors to the equipment. All requirements arising out of normal wear and tear and/or normal break-downs shall be covered under the contract as per the type of the contract. (e). Repairs or replacement of AHU coils and bottom trays. . (f) Repairs or replacement of water piping/gate valve/globe valve, modulating and mixing valve, make up water and expansion tank, insulation, ducting, sheet metal, outdoor condenser coils, refrigerant piping, back cover, front grille, dampers, grills, diffusers, false ceiling, microwave and HEPA filters, doors, locks, gasket, heating elements, auto defrost system, hinges, doorbell, light fixtures and bulbs. (g). Cooling tower structural, fills, louvers and air washer internals
15(h). Main electrical panel for the system with all components. (j). Repairs to or replacement of electrical installation like cabling, switch boards, isolators, panels, strip-heaters, ammeters, voltmeters and other such instruments external to the equipment. (k). Failure or deterioration of any equipment or parts due to atmospheric condition/corrosive atmosphere. (l). Providing unskilled labour. (m). Transportation of equipment. (n). Anything not specified within the Scope of Contract above. (o). Some of the above referred exclusion of supplies/services can be arranged by Blue Star at extra cost.
16M&L for B check general servicing by authorised rep of manufacturer of DG set of capacity 62.5 KVA, replacement of oil filter, fuel filter, air filter, by pass filter cleaning of radiator with chemical afterdraining out engine/ lubrication oil, coolant flushing and cleaning of oil chamberafter opening of tappet cover/ top cover tappet clearence setting with injector timing adjustment reaffixing of tappet/ top cover including replacement of tappet cover packing set, bonding and leak proof solution, oil pan/ chamber gasketat the servicing and other work comes under B Check service as mentioned in B Check by the manufacturer complete all as speciied and as directed. Note-Engine oil & Coolant will be paid separately under respective item.
17All as per ser item No 14 above but of capacity 100 KVA
18All as per ser item No 14 above but of capacity 250 KVA
19All as per ser item No 14 above but of capacity 320 KVA
20M&L for repair of self starter 12 V including rewinding of armature with super enamaled copper conductor wire of superier quality as per existing gauge, turn and pattern and replacement of bendex drive, carbon brush including services suitable for DG set 62.5 to 100 KVA complete all as specified and directed
21M&L for repair of self starter 24 V including rewinding of armature with super enamaled copper conductor wire of superier quality as per existing gauge, turn and pattern and replacement of bendex drive, carbon brush including services suitable for DG set upto 320 KVA complete all as specified and directed.
22S&F in replacement of automatic battery charger with auto cut OFF suitable for charging of 2X12V 180AH batteries complete with all required necessary wiring complete all as specified and directed.
23M&L for replacement of wiring complete to AMF panel for any capacity of DG set includinginterlock system of AMF panel with existing size of copper wiring including proper connection and testing complete all as specified and directed.
24S&F in replacement of self starter 24 V suitable for upto 320 KVA DG sets complete all as specified and directed.
25S&F in replacement of battery brass terminals heavy duty suitable for 12V 180 AH battery with minimum 2 RM Battery Lead of copper Cable single core complete all as directed.
26S&F in replacement ofrelay 24 V 8 pin type as per matching to existing and properly connection and testing after completion complete all as specified and directed.
27S&F in replacement ofengine starting relay suitable for DG set of capacity 62.5 KVA to 100 KVA as per matching to existing complete all as specified and directed.
28S&F in replacement ofengine starting relay suitable for DG set of capacity 250 to 320 KVA as per matching to existing complete all as specified and directed.
29S&F in replacement of Electronic timer suitable for AMF panel of DG setas per matching to exisitng, 230 V AC 50 Hz complete all as specified and directed.
30S&F in replcement of Voltmeter analog type for voltage range of (0-24V) as per matching to existing with all accessories and wiring complete all as specified and directed.
31S&F in replcement of Voltmeter analog type for voltage range of (0-500V) with all accessories and wiring all as specified and directed.
32S&F in replcement of Ammeter analog type for current range of (0-24Amps) as per matching to existing complete with all accessories and wiring complete all as specified and directed.
33S&F in replcement of Ammeter analog type for current range of (0-1000Amps) as per matching to existing with all accessories and wiring complete all as specified and directed.
34S&F in replecement of power contactor ML 6 suitable for AMF panel of DG sets a per matching to existing complete all as specified and directed.
35S&F in replecement of power contactor ML 4 suitable for AMF panel of DG sets a per matching to existing complete all as specified and directed.
36S&F in replecement of power contactor ML 3 suitable for AMF panel of DG sets a per matching to existing complete all as specified and directed.
37S&F in replecement of power contactor ML 2 suitable for AMF panel of DG sets a per matching to existing complete all as specified and directed.
38S&F in replacement of selector switch suitable for voltmeter and Ammeter complete all as specified and directed.
39S&F in replacement of under voltage relay suitable for DG set upto 320 KVA complete all as specified and directed.
40S&F in replacement of complete wiring with single core multistranded copper cable with flexible 20mm dia conduit for DG set of various capacities complete all as specified and directed.
41S&F in testing Electronic Governor Controller for 100 to 320 KVA DG Set including taking down old Governor Controller complete all as specified and directed.
42S&Fnew actuator for upto 320 KVA DG Set complete including taking down old unserviceable actuator complete all as specified and directed.
43M&L for charging of Refrigerant R-32 complete including testing after completion complete all as specified and directed.
44Opening the DG set of 100 to 250 KVA repair to any leakage in radiator, greasing of all movable parts & equipments and re-assembling the complete Parts and Testing completeand spare parts of the following shall be measured and paid under relevent items complete all as specified and as directed.
45S&F Piston ring and liner for 100 to 250 KVA DG Setas per existing make & OEM completeall as specified and directed.
46Supply only Head valve, Head Guide, Head sheet & Head seal for 100 to 250 KVA DG Setas per existing make & OEM complete all as specified and directed.
47Supply only Injector sleeves & Head gasket for 100 to 250 KVA DG Setas per existing make & OEM complete all as specified and directed.
48Supply only Packing Kit for 100 to 250KVA DG Setas per existing make & OEM complete all as specified and directed.
49M&L for repair of Head and fuel injector assembly complete for 100 to 250 KVA complete all as specified and directed.
50M&L for repair of Turbo assembly completefor 100 to 250 KVA complete all as specified and directed.
51Opening the DG set of 320 KVA , repair to any leakage in radiator, greasing of all movable parts & equipments including re-assembling the complete Parts and Testing completeand spare parts of the following shall be measured and paid under relevent items complete all as specified and as directed.
52S&F Piston ring and liner for 320 KVA DG Setas per existing make & OEM complete all as specified and directed.
53Supply only Head valve, Head Guide, Head sheet & Head seal for 320 KVA DG Setas per existing make & OEM complete all as specified and directed.
54Supply only Injector sleeves & Head gasket for 320 KVA DG Setas per existing make & OEM complete all as specified and directed.
55Supply only Packing Kit for 320 KVA DG Setas per existing make & OEM complete all as specified and directed.
56M&L for repair of Head and fuel injector assembly complete for 320 KVA complete all as specified and directed.
57M&L for repair of Turbo assembly completefor 320 KVA complete all as specified and directed.
58S&F in replacement of old unserviceable fan belt of existing size for DG Set of capacity 62.5 to 100 KVA complete all as specified and directed.
59S&F in replacement of old unserviceable fan belt of existing size for DG Set of capacity 250 to 320 KVA complete all as specified and directed.
60Supply and Cladding with glass/rock wool and aluminium sheets of exhaust manifoldforfor DG sets62.5 KVA includung removing of existing asbestos rope or any other type of insulation complete all as specified and directed.
61Supply and Cladding with glass/rock wool and aluminium sheets of exhaust manifoldforfor DG sets 100 KVA includung removing of existing asbestos rope or any other type of insulation complete all as specified and directed.
62Supply and Cladding with glass/rock wool and aluminium sheets of exhaust manifoldforfor DG sets 250 to 320 KVA includung removing of existing asbestos rope or any other type of insulation complete all as specified and directed.
63S&F in replacement fly wheel ring of DG Set of capacity upto 62.5 KVA complete all as specified and directed.
64S&F in replacement fly wheel ring of DG Set of capacity 250 to 320 KVA complete all as specified and directed.
65Draining out the diesel tank, cleaning/washing out the sludge and re-filling with diesel for the DG Set of capacity 62.5 to100 KVA complete all as specified and directed.
66Draining out the diesel tank, cleaning/washing out the sludge and re-filling with diesel for the DG Set of capacity 250KVA complete all as specified and directed.
67Draining out the diesel tank, cleaning/washing out the sludge and re-filling with diesel for the DG Set of capacity 320 KVA complete all as specified and directed.
68S&F in replacement of Changeover switch on load front operated 320 Amps 4 Pole 415 volt complete including properly connecting incoming and outgoing cable andtesting after completion complete all as specified and directed.
69M&L for Repairingtoradiator of 62.5 to 100 KVA DG set ,arresting leakage if any by welding/brazing and refixing the same for(Necessary coolant and distrilled water required will be measured and paid seperately) complete all as specified and directed.
70Repair toradiator of 250 to 320 KVA DG set,arresting leakage if any by welding/brazing and refixing the same for(Necessary coolant and distilled water required will be measured and paid seperately) complete all as specified and directed.
71Removing and replacing the old unserviceable lead acid battery of size 12 Volt, 180 AH of reputed make including charging complete all as specified as directed
72Removing old U/Sinsulating material asbestos rope and fixing of newof existing size and shapecompleteall as specified anddirected.
73M&L for Spray painting of diesel generating set of capacity 62.5 to 100 KVA with with accostic enclosure/ open type one coat of synthetic enamel paint body colour shall be apple green,black for foundation base frame, red for all guards for completeall as specified anddirected.
74M&L for Spray painting of diesel generating set of capacity 250 KVA with accostic enclosure one coat of synthetic enamel paint, body colour shall be apple green,black for foundation base frame, red for all guards for complete all as specified and directed.
75M&L for Spray painting of diesel generating set of capacity 320 KVA with accostic enclosure one coat of synthetic enamel paint, body colour shall be apple green,black for foundation base frame, red for all guards for complete all as specified directed.
76M&L for PCC (1:2:4) type B1 using 20 mm graded stone aggregate for foundation of pole complete all as specified and directed.
77S&F in replacement of3 Pole MCCB,630Amp, 36 KA with microprosseor release and Adjustable overload setting , 50 Hz, 415 V complete all as specified and directed.
78S&F in repair MCCB 125Amps 3 Pole breaking capacity 35KA complete all as specified and as directed.
79All as per item ser No. 64.00 above but 100 Amp 3 Pole 25 KA.
80All as per item ser No 64 above but of capacity 250A 3 Pole 25 KA.
81All as per item No 64 above but of capacity 200A 25 KA
82S&F in repair MCCB 630 Amps 4 Pole breaking capacity 50KA complete all as specified and as directed.
83S&F in repair MCCB 400 Amps 4 Pole breaking capacity 36KA complete all as specified and as directed.
84S&F in repair MCCB 250 Amps 4 Pole breaking capacity 36KA complete all as specified and as directed.
85Material and Labour for earthing complete with Steel earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not less than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same.GI plate connected with galvanised iron strip of 25x4 mmby means of Copper nuts, bolts and washers.Strip shall be laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following complete all as specified and shown in electrical plate No 3 of SSR Part-I & testing on completion :- (a)GI strip of size 25mm x 4mm. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit.(GI Funnel should properly be tightened on GI watering pipe and embeded in PCC earth pit with open top suitable for watering of earth pits) (c)Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 including RCC pit cover 50mm thick 1:2:4 type B1 reinforced with 8mm dia mild steel TMT bar 75mm centre to centre with 2 Nos MS handles of 12mm dia mild steel TMT bars suitable for carrying of pit cover.
86M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 25x4 mm galvanised iron strip complete all as specified and directed.
87Supply and laying 50 mm dia GI pipe light grade in replecement of old unserviceable including GI fittings laid in trenches or under road crossingfor protection of UG cable complete all as specified and directed.
88Supply and laying 80 mm dia GI pipe light grade in replecement of old unserceable including GI fittings laid in trenches or under road crossingfor protection of UG cable complete all as specified and directed.
89M&L for boring of holes under road, pavement, hard standing by trenchless techonology using ultra sound technique/mannually/mechanically and necessary machine including supply and laying of 100mm diaGI pipe light grade including making necessaryexcavation upto 1.5 mtr deep on both side of road for making holes and inserting 100mm dia GI Pipe complete all as specified and directed.
90S&F in repair ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 800 Amps complete all as specified and directed.
91S&F in repair ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 1000 Amps complete all as specified and directed.
92S&F in repairall the accessories includingGI Butterfly Valve 150mm diaincluding the application of nitrile rubber insulatioin over the valves complete all as specified and directed.
93All as per item ser No. 78 00 above but 100 mm dia.
94S&F in repair including installation of V belt of size A60 complete all as specified and directed.
95S&F in repair including installation of V belt of size A65 complete all as specified and directed.
96S&F in repair including installation of V belt of size A85 complete all as specified and directed.
97S&F in repair water pressure gauge along with stop cock and fixing arrangement suitable for water pressure 0-16/20 kg/sq cm complete all as specified and directed.
98S&F in repair industarial type thermometer of range 0-50 degree centigrade for AC plant as per sample complete all as specified and directed.
99S&F in repair suction pressure gauge suitable for suction pressure 0-250 PSI complete all as specified and directed.
100S&F in repair discharge pressure gauge suitable for discharge pressure 0-500 PSI complete all as specified and directed.
101S&F in repair timer electronic type adjustable time(6 to 60 Seconds) complete including connection & testing complete all as specified and directed.
102S&F in repair power contactor of MNX - 70complete all as specified and directed.
103S&F in repair power contactor of MNX - 25complete all as specified and directed.
104S&F in repair 3 phase preventer/phase sequence for line complete all as specified and directed.
105S&F in repair of LP switch suitable for central/package AC plant 40TR suitable for as per site requiremet complete all as specified and as directed.
106S&F in repair of HP switch suitable for central/package AC plant 40TR suitable for as per site requirement complete all as specified and directed.
107S&F in repair of refrigerantcopper pipe 6mm 0.64 thickwall complete all as specified and directed.
108S&F in repair of refrigerantcopper pipe 12 mm 0.64 mm thick wall complete all as specified anddirected.
109S&F in repair of refrigerant copper pipe 5/8" (15.88mm) thick including foam insulation for copper tube wall complete all as specified and directed.
110S&F in repair of refrigerantcopper pipe 3/8" (9.52mm) thick including foam insulation for copper tube wall complete all as specified anddirected.
111Taking down of existing unserviceable micropressor magnum controller and M& L charges forinstallation of Microprocessor Magnum Controller alongwith Software, installation and controlling arrangement including thimbles control wire etc complete suitable for 40TR AC Plantcompleteall as specified anddirected.
112S&F in repair including installation, testing andcommissioning of auto air vent valve of 15 mm diacompleteall as specified anddirected.
113S&F in repair PVC Drain pipe20mm complete all as specified and directed.
114M&L forcutting of GI/CI piping work 100/150mm dia inlet/outletincluding plumbing work and Welding work as required to prevent leakage completeall as specified anddirected.
115M&L for Repair to alternator of DG Set of capacity 100 KVA complete including rewinding & replacement of connected items such as bearing, sleeves Nut bolts, coupling etc complete all as specified anddirected
116M&L for Repair to alternator of DG Set of capacity 320 KVA complete including rewinding & replacement of connected items such as bearing, sleeves Nut bolts, coupling etc complete all as specified anddirected
117Auto Main Failure (AMF) panel made out of 2 mm CRCA sheet in Door type, powder coated of conforming to IS 8623 totally enclosed dust and vermin proof with front and rear openings of 415 Volts, 3 Phase, 4 Wire, AC 50 Hz having aluminium bus bar capacity required to carry current at 110% load of 320 KVA DG Set with three phase and half neutral colour coded, prewired with copper flexible cable of size 4 Sqmm all as specified with the following accessories, control cable from Gen Set to AMF panel & finishing complete with 7 tank process for powder coating in approved shade, having IP-42 degree of protection with hinged lockable doors, dust and vermin proof CPRI approved IP-54 duly painted with epoxy based powder coated paint complete all as specified and directed:-
118(i) Micro processor based MCCB 3 Pole of suitable capacity as recommended by OEM, Manual draw out type with electrical contractor 500 Amps 4 pole for alternator (DG supply and Main Supply) -02 Nos. (ii) All controls indicators and standard fittings as follows: (a) Digital type Ammeter meter with in built selector switch of suitable capacity with CTs- 1 set. (b) Digital-type Voltmeter meter with in built selector switch of suitable capacity- 1 Set. (c) Multifunctional digital meter fro KWH, KVA, KW Amps, Volts, frequency, power factor etc. -1 No.
119(iii) Functions:- (a) Supply failure timer and restroration - 1 No. (b) 3 impulse automatic engine Start/Stop logic. (iv) Announceation with indicators LED lamps for (a) Protective over loading relay- 1 No. (b) Low buld oil pressure, high water temperature, Engine over speed, battery low voltage, under voltage- 1 No., Earth fault relay- 1 No. (v) Controls (a) Load on indicators. (b) Load off indicators. (c) Engine start push button. (d) Engine stop push button. (e) Fault except/reset push button. (vi) Battery charging SMPS unit within auto built manual : (a) DC Volt meter. (b) DC Ammeter. (c) Charger rate selector switch.
120S&F in replacement of Pressure booster Pump with motor 0.5 HP Head Range 06 to 24 Meter complete all as specified and directed.
121S&F in replacement of Sine wave Invertor 1000 VA240Volts including connection complete all as specified and directed.
122Supply and laying in replacement of GI pipe medium grade in replacement of 100mm dia laid in trenches for protection of UG cable complete all as specified and directed.
123S&F earth pit chamber alongwith cover of Polymer, FRP Pit Cover of heavy high grade polypropelene for high stress and starin level of size 225x300x195 mm complete all as specified and directed.
124S&F ACP retro sign board of size 1.5x1.1 Meter using retro reflective high intensity prismatic reflective sheeting. The back ground of board is Blue Colour with white border and writing letter, numbers white colour mentioning the DG Set sub-station Details and Single line Schematic diagram of substation. Retro sign board shall be pasted on 3 mm thick ACP sheet. The board shall be fixed on Wall including fixing of fastners, nuts, bolts, washer etc complete all as specified and directed.
125Supply, installing, testing and commissioning Approx size 1500mmx1200mmx550mm factory fabricated and tested LT outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated electrolytic Aluminium bus bars TPN of capacity 800 Amps on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof,made out of3.15 mm thick CRCA mild steel sheet and mild steel & Mounting Channel frame work made out of MS angle iron 75X40 mm duly coated with zinc metal coating, front opening type . A clear space of 450 mm to be kept from floor level for switchgear compartment & control wiring with Copper conductor FRLSH cable of adequate size but not less than 2.5 sqmm complete all as specified and directed.
126BUS BAR CHAMBER:- (a) 800 Amps 3 Strips & 1 Neutral Strip 800 Amps, Aluminium , E-91 grade with colour coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER:- (i) Digital Multi Function Meter with LED display for measurement of Voltage, current, frequency, Power Factor, 96 X 96 mm, 3 Phase - 01 Set. (ii)C.T"s of capacity 250/5 A Cl 1.0 - 01 Set. ( Set of 3) (iii) LED Phase Indicator. ( Set of three ). (iv) Protection MCB 6 A SP C Series- 1 Set. ( Set of 3) INCOMING SUPPLY :- (i) MCCB 315 Amps,breaking capacity 35 KA 4P- 01 No(ii) Changeover Switch 320 Amps FrontOn load Operated. (iii) Digital Time switches astronomical programmable current capacity 16 Amp.- 1 No. OUTGOING SUPPLY :- (i)MCCB 160 Amps4 Pole 25KA, 415 volts,= 02 Nos., (ii) MCCB 100 Amps 4 Pole 415 Volts= 02 Nos. (iii)MCB SPN 40 Amps C Curve - 06 Nos.
127Note :- (i) The quoted rates shall deemed to be included the earth work & civil work platform for panel of 15cm thick PCC 1:2:4 type B2 in foundation, brick (sub class "B") work shall be in CM 1:6 15 mm rendering in CM 1:6 in exposed surface and 100mm PCC 1:3:6 type C1 using 20mm graded stone aggregate as in padding on top and grouting legs of panels. The platform shall be 450mm heigh or as per OEM drawing /recommendation. (ii) The line plan diagram with showing all accossories shall be get approved from GE (I) before order to the manufacturer.
128Supply and fixing chain link Ms Galvanized fencing, any size or type complete including taking down old unserviceable complete all as specified and directed.
129M&L MS chequred plate of suitable size for cable duct cover 6mm thick and earth pit cover including cutting, welding, rivetting etc complete all as specified and directed.
130S&Frolled section framed work as in doors or gates of angle or other section with gusset plates, rails braces, and angle post for fencing etc complete drilled for fixing of steel sheeting or other covering, Doors etc to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fitting (exclusive of steel sheeting or other covering, running rails and guides) and hanging also fastening and fixing complete all as specified and directed.
131M&L mild steel in flat, round or square bars, in available in length Fe 410-w (Gde-E-250)sqality-A of 6mm to 8mm complete all as specified and directed.
132M&L for Preparation of newly steel surfaces of any description, over 10cm in width or girth, not otherwise described and applying two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and as directed.
133S&F in replacement of PVC flooring 1.5mm thick including properly fixing with required adhesive complete all as specified and directed.
134S&F in replacement of Acoustic enclosure suitable for 320 KVA DG Set complete including proper fixing arrangementEnclosure is free standing floor mounted factory built and madular in construction to facilitate easy assembly at work site and will be drop over housing type. It well consist of acoustically treated panel housed in sheet steel will provide easy access for maintenance, repairs and operation. The enclosure is custom built to suit conditions, with the following features:-
135(i) Custom built product for various equipments, with ensure the optimum performance without duration. (ii) Rugged in construction maintenance free and modular designs which facilitate easy at site. (iii) 16 SWG (1.6mm) thick CRCA Sheets to be used for endosure panel to ensure longer life against weathering action. High quality acoustic insulation materials to be used as per IS 8183 for maximum sound obsorption. Acoustic layers are supported by oerforated sheets. (iv) sheet metal components of the enclosure should undergo various stages of surface treatment prior to painting which leads to be better life of the enclosure against weathering action. (v) Special paint treatment with pure polyester powder/epoxy to be provided for better weather resistance.
136(vi) Well designed ventilation system to be provided to pump up the heat in the chamber efficiently. (vii) For effective acoustic/weather sealing a special type weather sealing gaskets, new frame rubber gaskets to used. (viii) Working space is to be provided around the equipment for easy maintenance/repairs. (ix) Necessary cot out provision for entry and exist of fuel lines cable to be incorporated in the enclosure as per the requirement. (x) A see through transparent window (glass or acrylic) in front of engine panel to provide for monitoring the operation. (xi) Ducting if required, bellows, mechanical hardware like locks, hinges fasteners etc to be provided. (xii) Deliverables As per manufacturer Design 75 DBA; @lmtr at 75% load under free field conditions. The temp inside the enclosure will be within as per manufacturers recommendations above ambient temp as per IS: 8528 part 10 as per approved CPCB II norms.
137(xiii) The enclosure should be provided with bulk head light fitting for inside illumination. (xiv) The battaries should be placed inside the enclosure beside the DG Set on a suitable insulated plaeform. (xv) The DG Set should be provided with external Emergency stop push button. (xvi) The accoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Genset Green. The base frame should be painted with epoxy based black shade. (xvii) Acoustic insulation. Insulated Rock Wool fire retarded/non igniting and noise reduction type, properly clamped shall be provided on all doors, roof and sides to absorb noise. (xviii) Door locks and Door Hinges. Special designed stainless steel Door Locks and doors hinges ensuring for smooth operation and long life. (xix) Residential Silencer. Absorption type non-resistance Residential Silencer insulated from inside with glass wool shall be provided to suppress exhaust noise from the engine.
138M & L for Servicing of the window AC 1.5/2 ton capacity of any make, including oiling/greasing the blower motor, cleaning the evaporator condenser coils externally to remove the dust, replacement of defective thimbles etc and re-fixing the air conditioner at its original position by the experienced refrigeration mechanic complete all as specified and as directed. Note:- (i) Any u/s items need to be replaced/gas charging etc shall be replaced & paid seperately under respective items. (ii) The cost of dismantling, taking out window AC 1.5/2.0 ton from window and shifting to location where directed for proper washing and servicing and refixing the same shall be deemed to be included in item rate quoted.
139All as per item ser No. 117 above but for split type AC/Inverter type AC 1.5/2.0 ton
140All as per item ser No. 117 above but cassete AC of capacity 4.1TR.
141M&Lin replacement Fan Motor of AC (Window/ Split Type) 1.5 TR Capacityof approved Make and required Size to suit existing AC including taking out the unservice-able Fan Motor from the AC, complete all as specified and as directed.
142All as per Item ser No. 120 above but AC(Window/Split Type). 2.0 TR Capacity complete all as specified and directed.
143M&L Rewinding Fan Motor of AC 1.5/2.00 TR Capacity, (Window/Split Type) of any Make with Super Enameled Copper Wire of appropriate Gauge and Quantity including taking out burnt Winding, complete all as specified and as directed.
144M&L in replacement Air circular BlowerFan Motor ofAC (Split Type), 1.5 TR/2.0/3.00TR Capacity including taking out unser-viceableAir circular BlowerFan Motor complete all as specified and as directed.
145M&Lin replacement Air Filter suitable of AC (Window type) 1.5 TR/2.0 TR Capacity including taking out unserviceable Air Filterfrom AC complete all as specified and as directed.
146M&Lin replacement Air Filtersuitable of AC (Split type)1.5 TR/2.0 TR Capacityincluding taking out unserviceableAir Filtercomplete all as specified and as directed.
147M&Lin replacementCapacitorRunning 36 mfd – 45 mfd suitable for new/star rated for AC (Window/Split Type)1.5 TR/2.0 TR Capacity and of any make includingtaking out unserviceableCapacitor from ACcomplete all as specified and as directed.
148M&L in replacement Capacitor Starting80 mfd – 120 mfd suitable for old ones AC(Window/Split Type)1.5 TR/2.0 TR Capacity and of any make including taking out unserviceableCapacitorfrom ACcomplete all as specified and as directed.
149M&L in replacement Fan MotorBlades AC (Window/Split type)1.5/2.0 TR capacity including taking out unserviceable Blades of FanMotor from AC complete all as specified and as directed.
150M&L in replacement Fan MotorCapacitor 4 mfd of suitable for new/star ratedAC (Window/Split Type) 1.5/2.0TR capacity including taking our unserviceable Fan motor capacitor from ACcomplete all as specified and as directed.
151M&L Fan Motor in replacementCapacitor 6 mfd suitable for old ones AC (Window/Split Type) 1.5/2.0TR capacity including taking our unserviceable Fan motor capacitor from ACcomplete all as specified and as directed.
152M&Lin replacement Front Plastic Grill (as per Sample) of AC (Window type)1.5 TR/2.0 TR Capacity including taking out unserviceable Front Plastic Grill from ACall as per existing and complete all as specified and as directed.
153M&L in replacement Front Plastic Grillfor inner unit (asper Sample) of AC (Splittype)1.5 TR/2.0 TR Capacity including taking out unserviceable Front Plastic Grill from AC all as per existing complete all as specified and as directed.
154M&L in replacement Runner for air blower motor of AC(split type)AC 1.5/2.00TR capacity (As per sample or as per site requirement)including Runner of Air Blower Motor from ACall as per existing complete all as specified and as directed.
155M&L in replacement Selector Switch of AC (Window/Split Type)1.5 TR/2.0 TR Capacity including taking out unserviceable Selector Switch from ACcomplete all as specified and as directed.
156M&L in replacement Selector Switch Knob of AC(Window/ Split Type)1.5 TR/2.0/3.00 TR Capacity including taking out unserviceable Selector Switch Knob from ACcomplete all as specified and as directed.
157M&L in replacement Starting Relay of AC(Window/Split Type) 1.5 TR/2.0/3.00TR Capacityincluding taking out unser-viceable Starting Relay from ACcomplete all as specified and as directed.
158M&L in replacement Strainer with Capillary Tube of ACWindow/ Split Type) 1.5 /2.0TR Capacity (including taking out unserviceable Strainer with Capillary Tubefrom ACcomplete all as specified and as directed.
159M&Lin replacement Thermostat Switch of AC(Window/Split Type) 1.5 TR/2.0 TR Capacityincluding taking out unserviceable Thermostat Switch from ACcomplete all as specified and as directed.
160S&F in replacement cooling coil suitable forwindow type room AC 1.5/2 TR including taking out unserviceable cooling coilof capacity 1.5/2 TR.as per sample complete all as specified and directed.
161S&F in replacementCondensing coil suitable forwindow type AC 1.5/ 2 ton including taking out unserviceable Condensing coil of capacity 1.5/2 ton complete all as specified and directed.
162S&F in replacement Condensing coil suitable for split type AC including taking out unserviceable Condensing coil of capacity 2 ton complete all as specified and directed.
163S&F in replacement cooling coil suitable for split type ACincluding taking out unserviceable cooling coilup to capacity 2 ton omplete all as specified and directed.
164S&F in replacement Indoor unit suitable for 1.5 TR split type ACincluding taking out unserviceable Indoor unitcomplete all as specified and directed.
165S&F in replacement outdoor unit suitable for 1.5 TR splittype AC without compressor including taking out old unserviceable outdoor unitcomplete all as specified and directed.
166S&F in replacement Indoor unit suitable for up to 2 TR split type ACincluding taking out old unserviceable Indoor unitcomplete all as specified and directed.
167S&F in replacement outdoor unit suitable for up to 2 TR splittype AC without compressor including taking out unserviceable outdoor unitcomplete all as specified and directed.
168S&F in replacement of Hermitacally sealed compressor for split/ window type AC capacity 1.5 Ton complete all as specified and directed.
169All as per ser item No. 147 above but of split/ window type AC capacity 2.0 Ton.
170Taking down/up defective AC 1.5 TR Capacity (Window/Split Type), Transportation from MES Store Yard/Site to Workshop and Back including re-fixing /re-installing after taking out defective/burnt Com-pressor Sealed Unit and providing new Compressor Rotary/ Reciprocating as per site requirment of same Capacity from Authorised Dealer including Flushing of Condenser and Charging with required quantity of appropriate Refrigerant Gas R22/R410 includingre-connection of Electric Connections, functioning AC complete in all respect and Testing, complete all as specified and as directed.
171All as per Item ser No. 149 above but AC 2.0 TR Capacity (Window/Split Type) complete all as specified and directed.
172M&L in replacement PCB with remote for windowtype AC up to 2 Ton capacityincluding taking out unserviceable PCB complete all as specified and directed .
173M&L in replacement PCB with remotefor Split type AC 2/3(1.5x2) Ton capacityincluding taking out unserviceable PCB complete all as specified and directed .
174M&L in replacement PCB & motherboard with remotecomplete setforInverter Split type AC up to 2 Ton capacityincluding taking out unserviceable PCB complete all as specified and directed .
175M&L in replacement Remoteof AC ( Window/Split Type) 1.5/2.0 TR capacity(As per sample or as per site requirement)complete all as specified and as directed.
176S&F in replacement wiring kit suitable for 1.5 to 2.0 ton capacity AC including taking out unserviceable wiring kit complete all as specified and directed.
177S&F in replacement gas charging pin valve including taking out unserviceablepin valve complete all as specified and directed.
178Taking out window type AC complete unit from any height/ any floor up to fourstorey buildingand shifting to another locationin the sameor other building in the complex including refixing of the unitcomplete all as specified and directed.
179Taking out split type AC complete indoor and outdoor unit from any height/ any floor up to fourstorey buildingbyincluding pumping down the gas into thecompressor by controlling the suction and discharge valves , disconnecting the suction and dischagre copper piping and shifting to another locatiionin the sameor other building in the complex including refixing of the unit complete all as specified and directed.
180Supply and charging the gas refrigerant R22 (including refrigerant) of window type AC upto 2 ton capacityincluding testing after application of nitrogen gas pressure to find out any leakage, brazing and stopping of all leakage detected, re-application of nitorgen pressure to ensure leak proof gas circulator system flushing out the nitrogengas complete all as specified and directed.
181All as per item ser No. 159 above but R- 410 for split type AC up to 2 TR capacity omplete all as specified and directed.
182All same as per item serNo 159 above but R410 cassatte type AC 4 TR capacity omplete all as specified and directed.
183All same as per item ser No 159 above but R-32 Refg upto 02 Ton AC.
184S&F in replacement of casing of window type AC including company fitted condensing & cooling coil including PCB except compressor complete all as specified and directed.
185M&L for replacement of split valve ¼” for split AC up to 2.00 ton capacity complete all as specified and directed.
186All as per item ser item No. 164 above but 1/2"
187S&F in replacement compressor shut off valve 3/8" for split AC up to 2.00 ton capacity complete all as specified and directed.
188S&F in replacement compressor shut off valve 5/8" for split ACup to 2.00 toncapacity complete all as specified and directed.
189S&F in replacement PVC conduit 20mm dia medium grade including all clamps & accessories and connecting the condensate pipe of ACs to this conduit for proper drainout of condensate water from ACs upto 5 (five) storey blds complete all as specified and directed.
190S&F in replacement PVC conduit 25mm dia medium grade including all clamps & accessories and connecting the condensate pipe of ACs to this conduit for proper drainout of condensate water from ACs upto 5 (five) storey bldgs complete all as specified and directed.
191S&F in replacement Hermatically Sealed compressor for 40/80 Ltrs capacity water cooler including bracing the suction and discharge lines complete all specified and directed.
192S&F in replacement Hermatically Sealed compressor for 60/120 Ltrs capacity water cooler including bracing the suction and discharge lines complete all as specified and directed.
193S&F in replacement metal plug top 3 pole and earth, 20 Amps, 240 volts suitalbe for sheet metal enclousers complete all as specified and directed.
194S&F in repalcement metal enclosures with clad socket & plug top 3 pole and earth, including of MCB SP 25 Amps 240 voltscomplete all as specified and directed.
195S&F in replacement of PVC insulated flexible copper conductor 3 core 1100 volts grade of size 2.50 Sqmm complete all as specified and directed.
196S&F in replacement of PVC insulated flexible copper conductor cable 1100 volts grade, 3 core of size 1.5 Sqmm complete all as specified and directed.
197M&L in replacement for submain wiring with 2 run 4.00 Sqmm cable PVC insulated copper conductor multi - stranded as per FRLS cable drawn throughconduit pvc 20mm dia medium duty with all accessories including 4.0 Sqmm single strand copper conductor cable PVC insulated unsheathed for earth continuity connected to common earth dolly and complete all as specified and directed.
198S&F in replacement AC stand suitable for wall mountedout door AC unit up to capacity of 2 ton, necessary 40x40x6mm angle iron including fixing arrangements like welding, fabrication and nuts & bolts etc upto six stories building complete allas specified and as directed.
199S&F in replacement floor mountedAC stand suitable for out door AC unit up to 2 ton capacity,necessary 40x40x6mm angle iron including fixing arrangements like welding, fabrication and nuts & bolts etc upto six stories building complete allas specified and as directed.
200Taking down Defective Water Cooler 40/80 litres Capacity, Transportation from MES Store Yard/Site to Workshop and back including re-fixing /reinstall -ing, Testing, connecting the same after replace-ment of defective/burnt Compressor Selected Unit with new Compressor from Authorised Dealer including Flushing of Condenser and Charging with required quantity of appropriate Refrigerant Gas complete all as specified and as directed.
201M&L for servicing of water coolerof any capacity including cleaning of water cooler from inside and outside with potassium permanaganates, servicing of cooling coil, fan, motor, condensor, fan blades and its connected water and refrigerant fittings complete all as specified and directed.
202Supply and charging the gas in the water cooler of any make and capacity up to 150 ltr capacity including testing and detecting leakage if any with nitrogen gas and vaccum the system after rectification of all leakages complete all as specified and directed.
203S&F in replacement thermostat switch suitalbe for water cooler of any make & size complete all as specified and directed.
204S&F in replacement starting relay/over load relay suitable for water cooler of any make & size complete all as specified and directed.
205S&F in replacement defective push cock 15 mm bore chromium plated heavy duty suitable for water cooler of any make and capacity complete all as specified and directed.
206M&L for preparation of old painted surfacesof water cooler by removing old deteriorated paint, making surfaces smooth and applying two coats of synthetic enamel paint over a coat of red oxide primer by spray painting complete all as specified and directed..
207S&F in replacement fan motor ISI marked suitable for water cooler as per existing capacity upto 150 ltrs of any make complete all as specified and directed.
208S&F in replacement of condenser fan of any make suitable for water cooler upto 150 ltrs capacity complete all as specified and directed.
209S&F in replacement 15 mm dia PVC connection of length upto 600mm with PTMT nuts on both ends complete all as specified and directed.
210S&F in replacement water collection tray made of CGI sheet 2 mm thick suitable for window AC upto 2 Ton capacity complete all as specified and directed.
211S&F in replacement steel/aluminium waste water tray suitable for water cooler upto 150 ltrs capacitycomplete all as specifed and directed.
212M&L for servicing of desert cooler of any size including cleaning of desert cooler from inside & outside repair/replacement of defective/unserviceable parts, greasing of fan kit, motor, water pump and connected accessories complete all as specified and directed. Note : Unserviceable parts requires for replacement shall be measured and paid separately as supply only under respective items of this schedule.
213M&L for painting ofdesert cooler capacity upto 4000 Cfm with two coats of approved synthetic enamel paint inside & outside including fan/fan blade/brackets after scrapping the rust,peal of paint and preparation of surface complete all as specified and directed Note : The rates are inclusive of taking down coolerfrom any height, removal to workshop for painiting and refixing in position after painting.
214S&F in replacement of desert cooler sub mersiblewater pump complete with electric motor single phase 230 volts 50Hz including lead, connecting & testing as per sample complete all as specified and directed.
215S&F in replacementdesert cooler fan motor,copper wound suitable for upto 450mm sweep SP 230 volts 50HZ including legs, rubber bush nuts/bolts for fixing of fan motorwith connection & testing complete all as specified and directed.
216S&F in repalcement of commercial ply wood BWP 4mm thick ISI marked for desert cooler of any size to close the opening between desert cooler grill and window complete all as specified and directed.
217S&F in replacement plug top 3 pin 5 Amps complete all as specified and directed.
218S&F in replacement plug top 3 pin 15 Amps complete all as specified and directed.
219S&F in replacement motor capacitor 2.5/3.15/4 mfd complete all as specified and directed.
220S&F in replacement front grill made of MS complete with air guide vanes suitable for desert cooler of capacity 4000 Cfm complete all as specified and directed.
221S&F in replacement of body without side panels made out of galvanised iron sheets of 22 gauge for bottom tank & 20 gauge for top cover of desert cooler body duly painted with 2 coat of synthetic enameled paint over one coat of red oxide primer complete with fixing of all spare complete all as specified and directed.
222S&F in replacement of side panels of desert cooler body of 22 gauge of existing size & shape duly painted with 2 coat of synthetic enameled paint over one coat of red oxide primer complete with fixing complete all as specified and directed.
223S&F in replacement of float valve assembly with PTMTferrule 15 mm dia and PVC ball valve suitable for water cooler up to 150 ltrs capacity and desert cooler upto 4000 Cfm complete all as specified and directed.
224S&F in replacment new wood wool pad,(Khus Khus) set of threecovered by GI wire mesh suitable for desert cooler including taking out the old unserviceable existing pad complete all as specifed & directed
225M&L for replacement of aluminium multi wing Fan blade, best qualityas per existing type and size suitable for of desert cooler complete all as specifed and directed
226Taking down ceiling fan/exhaust/pedestal/table/air circulating fan of any size or make by disconnection eletric connection and removing from site for overhauling/ engraving of MES No of fans and fixing the same ineixsting position or as directed by engineer-in-charge with eletric connection and testing complete all as specified and directed
227M & L for overhauling of ceiling fan/pedestal/exhaust/table/aircirculating fan of any size or make opening the fan motor, overhauling by removing dust from field coils including varnishing of field coils and greasing from motor with superior qauality grease for smooth running inlcuding cleaning and washing the blades and assembling of fan motor and refixing at the same place complete all as specified and directed.
228M & L for removing of burnt out winding wire from ceiling fan of any make of size 1200/1400 mm sweep including cleaning of slots etc and rewinding with super enameled copper winding wire as per existing size/gauge including insulating material and varnishing complete all as specified and directed.
229All as peritem ser No. 207 above but for exhaust fans of size 225 mm sweep to 380 mm sweep
230All as peritem ser No. 207 above but for exhaust fan of size 450 mm sweep
231All as peritem ser No. 207 above but for table fan/wall mounted of 400 mm sweep
232M&L for replacement of ceiling fan regulator five step 60/120 watt electronic type AC 230/240 Volts suitable for 1200/1400 mm sweep complete with all fixing accessories including necessary electric connection complete all as specified and directed.
233S&F in replacement voltage stabilizer 4 KVA suitable for window/split type AC of capacity upto 1.5 TR working on AC 240 V,50Hz single phase completeall as specified and as directed.
234S&F in replacement voltage stabilizer 5 KVA suitable for window/split type AC of capacity upto 2 TR working on AC 240 V,50Hz single phase complete all as specified and as directed.
235S&F in replacement Pedestal fan 450mm sweep working on AC 240 V,50Hz, single phase complete all as specified and as directed.
236S&F in replacement exhaust fan PVC body 250mm sweep working on AC 240 V,50Hz, single phase complete all as specified and as directed.
237M&L for taking down of geyser of capacity 25 ltrs after dissconnecting the water and electric connections etc and replace the new stainless steel tank with assembly to make the geyser fully functional and refixing the same at its orignal position complete all as specified and directed.
238All as per ser item No. 216 above but capacity 50 ltrs
239S&F in replacement of Heating element triangle/round type as per existing of capacity 1.5KW of Hot appliances complete all as specified and directed.
240All as per ser item No. 218 above but capacity 2KW
241S&F in replacement of thermostatas per existing of capacity 25/50 ltrs of Hot appliances complete all as specified and directed.
242S&F in replacement of shut off valve as per existing of capacity 25/50 ltrs of Hot appliances complete all as specified and directed.
243M&L for taking out the diffective PCB & mother board with remotecomplete set from "inverter split type AC upto 2 Toncapacity and repair the deffective PCB with mother board and remote and fixed the same in its original position complete all as specified and directed.
244S&F in replacement of Thermo insulation glass wool as per existing of capacity 25/50 ltrs of Hot appliances complete all as specified and directed. .
245S&F in replacement of water connection CPfor inlet & outlet (Hot & Cold) as per existing of capacity 25/50 ltrs of Hot appliances complete all as specified and directed.
246S&F in repair of switch pianotype 5 ASP one way complete all as specified and directed.
247S&F in repair socket outlet 5 pin5 Aflush type complete all as specified and directed.
248S&F in repair Switch socket combination 2 in 1, 3 pin, 5 and 15 amp flush type universal complete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail