| 1 | SCHEDULE \"A\"SEC-I (PART-I) (BUILDING WORK) |
| 2 | M&L for treating thetop surface offilled earth at the rate of 5.0 ltr of emulsion per sqm. |
| 3 | M&L for PCC 1:4:8 type D-2 (40mm graded agg) as in foundation filling & mass concrete all as specified and directed. |
| 4 | M&L for RCC M-25 Design Mix as inchajjascomplete all as specifiedand directed. |
| 5 | Used and wast of form work to chullah hoods, chajjas, trough, and similaritems including edges all as specified and directed by Engr-in-charge. |
| 6 | M&L for preparation of new wall surfaces with using 3 to 5mm thick wall care puty and applying two coats ext.grade wheather paint all as specifiedand directed. |
| 7 | SCHEDULE \"A\"SEC-I (PART-II) (BUILDING WORK INCLUDING INTERNAL SERVICES) |
| 8 | Demolition of reinforced cement concrete of any escription and in any position complete all as specified. |
| 9 | Taking down cement plaster on brick ,stone wall,etc, including racking out joints, hacking for key, scrubbing down with water etcall as specified. |
| 10 | Taking down of chowkhat or frame (without taking off shutter from frame) nexc 1.50 Sqm and including builder hardwarefitting complete all as specified. |
| 11 | S&F of manuallysliding , hermetically sealing type of door of size 1500x2100mm or of any size as required having PUF / high density particleboard cores, high pressure laminated face on both sides, viewing window300x300mm and for smooth effortless sliding, the door runs on nylon wheels within an aluminium extrusion track all as specified and directed. The door are to be made high density particle board core with stainless steel 0.5 mm thick facing both side and run on Nylon wheels in a track made from aluminium extrusion, fixed firmly to the wall. The door frame shall be made or reinforced plaster board panels faced with the same llaminates as the doors and shall be edged with and aluminium extrusion and concealed fixing. The Track and wheel design shall be as sutch that during the last 50mm at travel on the closing cycle the door moves in 3 direction to from a seal against the floor at the bottom and against the frame on both sides and on the top. |
| 12 | S&F of micro processor based electronic automation for door controlling the direction, the acceleration and speed of the door with a low noise level pluse generator motor it includes a photo cell for user\"s safety and a set of sensor and foot switches/ operation allas specified and directed.Note: The automation to be used to item No 67 for making it functional automatically. |
| 13 | S&F of 2 Bay scrub sink made out of 304 graded brushed finished stainless steel, 1.6mm thick, 1800mm length, width 510mm, height 1370mm with photoelectric sensors-2Nos, thermo static mixture valves-1 No, Solenoid valves-2Nos with foot operated switch-2Nos spouts-2Nos for foam supply all as specified and directed. |
| 14 | S&F of 3 Bay scrub sink made out of 304 graded brushed finished stainless steel, 1.6mm thick, 2100 mm length, width 510mm, height 1370mm with photo electric sensors-3Nos, thermo static mixture valves-1No, solenoid valves-3Nos with foot operated switch-3 Nos spouts-3Nos for foam supply all as specified and directed. |
| 15 | SCHEDULE \"A\"SEC-II (PART-I) REFRIGERATION & AIR CONDITIONING (To be priced and quoted by tenderer) |
| 16 | PIPING WORK |
| 17 | SITCof Valves/ Strainers for following diacomplete with all accessories with thermal insulation complete all as specified for Chilled Water Piping. |
| 18 | Y- Strainers made of cast carbon steel |
| 19 | 40 mm dia |
| 20 | SITCof Valves/ Strainers complete with all accessories with thermal insulation complete all as specified for Hot Water Piping but except Valves/ Strainers. |
| 21 | Butterfly valves made out of gun metal or forged brass but except buttterfly Valve. Note: Butterfly valves for BOQ Item Nos 22.01 & 22.02 shall only be issued nder Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 22 | 50 mm |
| 23 | 40 mm |
| 24 | Balancing Valve made out of gun metal of following dia:- |
| 25 | 25 mm |
| 26 | Y-strainer made out of cast carbon steel of following dia:- |
| 27 | 25 mm |
| 28 | Temperature gauge graduated both in degree C & degree F suitable rang fitted with fixing arrangement with adopter all as specified but except Temperature gauge.Note:Temperature gauge shall only be issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 29 | Pressure gauge dial type graduated both in kg/cm2 and PSI fitted with U Tube adopter and socket in water pipe. |
| 30 | All as per item No 24.00 here in before but except Pressure gauge.Note: Pressure gauge. shall only be issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 31 | SITC of 3 way modulating valves for AHU complete with linkage modulating actuator with all accessories complete in all respect as specified. |
| 32 | 25 mm dia |
| 33 | All as per item No 26.00 here in before but except 3 way modulating valves.Note: 3 way modulating valves for BOQ Item No 27.01 shall only be issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 34 | 40 mm dia |
| 35 | SITC of stand alone TRH sensors digital / analoge along with temperature and humidity controller duly interlocked as specified but except TRH sensors. Note:TRH sensors shall only be issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 36 | AIR FLOW MANAGEMENT STATION FOR OT AHU (8 Nos) |
| 37 | Motorised assembly for AFM Station with application programmable controller for enabling stable pressure control; shall be able to control air handler drive in tune to filter condition & maintain desired volume flow rate; shall communicates on pLAN network; differential pressure sensor; & necessary step down transformer from 220 V includingall necessary control wiring for working the same. |
| 38 | Supplying, fabricating, installing and testing of sheet metal ducts of following thicknesses including necessary supports, flexible hangers with isolators, nut bolts, gasket, splitter dampers and vanes, volume control dampers etc. complete as per specification in accordance with the approved shop drawings and required by the specifications. |
| 39 | GSS Ducting :SMACNA |
| 40 | Maximum Gauge Joint TypeBracing |
| 41 | Duct Size Spacing |
| 42 | 751 -1000 mm24(4 BoltNil |
| 43 | TDC (E)) |
| 44 | 1001 -1200 mm22 (4 Bolt Nil |
| 45 | TDC (H)) |
| 46 | INSULATION |
| 47 | Providing & fixingof external thermal insulation of ducts with approved sample of Nitrile Rubber prelaminated with aluminium foil complete asper specifications. |
| 48 | 32 mm thick insulation withMechanicalprotection over insulation with fiber glass cloth & UV paint (for exposedduct) but except insulation material. Note:Insulation Material shall only be issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 49 | Acoustic Lining in The Supply/Return Ducts |
| 50 | Supplying, installing & testing of acoustic lining within supply and return air ducts as per the specifications. All ducts shown cross hatched on the approved shop drawings shall be provided with acoustic lining of Nitrile Rubber open cell foam .• The density of the same shall be within 140-180 Kg/m3 & thermal conductivity not exceeding 0.050 W/m.K.• The material should withstand maximum surface temperature of +85C and minimum surface temperature of -20C &should conform to Class 1 rating. |
| 51 | 20 mm thick acoustic lining for ducts other than OTs. |
| 52 | Supply, Install, DOP testing and commissioning of modular type unidirectional Laminar air flow system for Operation Theatres assembled and sealed in factory comprising of plenum & holding structure complying to ISO 5 to ISO 6, made out of MS Sheet with epoxy coated paint/stainless steel having minimum thickness of 2mm protected with oven baked RAL 9010 epoxy coating both inside and outside and sealed with 100% leak proof gasket in accordance with ISO EN 14644-3. Air tightness of casing shall be in accordance with class B of EN-1866-1998. Class L1 (M) of PREN 1886-2003. Calss \"C\" of PREN 12237-2003 and ISO-EN14644-3. One test connector accessible from the operating theater shall be provided to measure loss of pressure and take test Aerosol samples. Provision for filtter mounting shall be with rotating clamps. Removable \"Screentek\" screens of monofilament polyster fabric in individual clip-on frames for projection of HEPA filters against exposure to blood splash shall be provided. Mini Pleat HEPA Filters(as per UL 900 fire rating) in Aluminum frame flange type , filter media consisting of Micro Fibre Glass (imported) protected with Aluminum mesh on both sides having efficiency better than 99.97% down to 0.3 microns particle size with I.P.D< 15 mm WG, F.P.D>= 50 WG for the following .Contractor to quote forof one of the following three makes with respective specifications mentioned against each make at (a), (b) & (c ) below :- |
| 53 | For OTs size of Plenum 1815mm (L) x 2415mm (W) x 400mm (h) fitted with 6 Nos mini pleat HEPA Filters 580mm x 860mm x 66mm and 02 Nos 560mm x 560mm x 66mm but except plenum 1815mm (L) x 2415mm (W) x 400mm (h) fitted with 6 Nos mini pleat HEPA Filters 580mm x 860mm x 66mm and 02 Nos 560mm x 560mm x 66mmMake :- CAMFIL, Equivalent AMERICAN AIR FILTERS/FRUDENBERG.Note :- DOP SITE TESTING OF HEPA FILTERS :-(a) Testing will be done with the help of photometer and smoke generator.(b) Room validation will be done with particle counter.(c) Velocity of outlet of HEPA filters shall be done with velocity meter.Compressed air and all other materials for testing shall be arranged by the contractor.Contractor shall visit the site befor quoting the above items and quote accordingly.Note:Plenum 1815mm (L) x 2415mm (W) x 400mm (h)with 6 Nos mini pleat HEPA Filters 580mm x 860mm x 66mm and 02 Nos 560mm x 560mm x 66mm shall only be issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 54 | SCHEDULE \"A\" SEC-II(PART-II) HVAC ELECTRICAL PANNELS (To be priced and quoted by tenderer) |
| 55 | Cabling: |
| 56 | Supplying, Laying, testing & commissioning of the following sizes ofAl. Conductor, XLPE insulated,armoured cables of 1.1KV grade on the surface of wall, cable trays or buried in trenches all as specified in SSR part -1. complete withfixing hardware etc. as required |
| 57 | 4C x 4 Sq.mm cable |
| 58 | Cable Tray: |
| 59 | Supply & installation of perforated GI tray made out of 2mm thick sheet, suspended from ceiling & fixing on wall / column etc. as required including GI hangers & supports & fastners etc. as required (Cable tray layouts with supporting arrangements to be approved by Project Manager/Consultants. |
| 60 | 100 mm(W) x 40 mm (D) |
| 61 | G.I. Earthing Strip/Wire: |
| 62 | Supply, installation, testing and commissioning of followingsizes ofG.I.strip/wireclampedto walls,cable trays,busducts, cablesin recess or surfaceetc for equipment/ System / Lightning protectionearthing completeas required including interconnectionbetween lengthatjoints, allfixing accessoriessaddles, clamps etc.andother fixing hardware material as required for proper installation. |
| 63 | 32 x 6 mm strip |
| 64 | All as per item No 49.01 here in before but except 32 x 6 mm strip.Note: 32 x 6 mm strip shall only be issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 65 | Earthing complete with galvanized steel earth plate electrod each 60cmx60cmx6mm thick burried directly in ground (earth pit not less that 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level and having alternate level of charcoal and salt connected to GI strip of size 32mm x 6mm upto the eqpt all as shown in electrical plate No 5 connected to earth test point, with watering pipe of GI light grade 20mm dia, virnless funnel, PCC pit cover all as specified and directed but except earth plates. Note: Earth plates shall only be issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. |
| 66 | SCHEDULE \"A\" SEC-III INTERNAL ELECTRIFICATION (To be priced and quoted by tenderer) |
| 67 | Recess mounted IP-54 protcol non-hygroscopic peripheral lights 2 x36 W having fluroescent lamp and dimmable analogue bilast (LED BASED)but except Recess mounted IP-54 protcol non-hygroscopic peripheral lights. Note: Recess mounted IP-54 protcol non-hygroscopic peripheral lights shall only issued under Sch \"B\".Remainingconnected accessoriesas per CA provision shall be done by contractor and rate of the same shall deemed to be included in quoted rate. . |
| 68 | Note for items to be issued under Schedule \"B\":Contractor shall visit the site before quoting of tender,for check the servicablity of items to be issued under Schedule \"B\".If, it is found that items are requires any type of repair/ replacement of any part or in full or servcing or any other chemical treatment for proper functioning of system through OEM, hence rates quoted by the tenderer shall deemed to be inclusive of this aspact wheather he has visited the site or not and no further claim shall be admissinble on this account. |
| 69 | SCHEDULE \"A\" SEC-IV - RECTIFICATION/REPLACEMENT OF DEFECTIVE ITEMS ALREADY EXECUTEDE AT SITE UNDER CA NO CEDZ-35 OF 2015-16 (To be priced and quoted by tenderer) |
| 70 | 3 - WAY gun metal valve |
| 71 | Repair/ replacement to 3 way modulating valves for AHU complete with linkage modulating actuator with all accessories complete in all respect as specified. |
| 72 | 65mm dia |
| 73 | 50 mm dia |
| 74 | 40 mm dia |
| 75 | 3 - WAY VALVES |
| 76 | Repair/ replacement to 3 way modulating valves for AHU complete with linkage modulating actuator with all accessories complete in all respect as specified. |
| 77 | 50 mm dia |
| 78 | 40 mm dia |
| 79 | 32 mm dia |
| 80 | 25 mm dia |
| 81 | Repair/ replacement to stand alone TRH sensors digital / analoge along with temperature and humidity controller duly interlocked as specified. |
| 82 | CHILLED & HOT WATER COIL AHU |
| 83 | (a) S&F suitable VFD - 02 Nos alongwith control wiring and calibration for 3000 CFM Backward curve airofoil Blower With 125 mm static pressure, 0.56 Sq.M. Coil Area, 8 row deep cooling coiland 4 row hot water coil & 2700CFM with 20mm static Forward Curved Exhaust Air Fan In same AHU Section. |
| 84 | (b) S&F suitable VFD - 02 Nos alongwith control wiring and calibration for 3200CFM Backward curve airofoil Blower With 125 mm static pressure, 0.59 Sq.M. Coil Area, 8 row deep cooling coil and 4 row hot water coil.& 2800 CFM with 20mm Forward Curved Exhaust Air Fan In same AHU Section |
| 85 | (c)S&F suitable VFD - 01 No alongwith control wiring and calibration for3000 CFM Backward curve airofoil Blower With 125 mm static pressure, 0.56 Sq.M. Coil Area, 8 rowdeep cooling coiland 2 row hot water coil |
| 86 | (d) S&F suitable VFD - 01 No alongwith control wiring and calibration for 3200 CFM Backward air flow blower with 125mm static pressure 0.56 Sqmtr coil area, 8 row deep cooling coil and 2 row hot water coil. |
| 87 | DX & HOT WATER COIL AHU |
| 88 | S&F suitable VFD - 02 Nos alongwith control wiring and calibration for 3500CFM Backward curve airofoil Blower With 125 mm static pressure, 0.65 Sq.M. Coil Area, 4 row deep DX- Cooling coil and 4 row hot water coil & 3000CFM Forward Curved Exhaust Air Fan In same AHU Section to be connecting with existing Dx Plant |
| 89 | S&F suitable VFD - 02 Nos alongwith control wiring and calibration for 3000CFM Backward curve airofoil Blower With 125 mm static pressure, 0.56 Sq.M. Coil Area, 4 row deep DX- Cooling coil and 4 row hot water coil & 2700CFM Forward Curved Exhaust Air Fan In same AHU Section to be connecting with existing Dx Plant |
| 90 | PAN HUMIDIFIER |
| 91 | Repair/ replacement to horizontal type PanHumidifier complete with suitable size of PVC water tank pump sprey nozzle piping and electrical accessories |
| 92 | AIR FLOW MANAGEMENT STATION FOR OT AHU (8 Nos) |
| 93 | Repair/ replacement to AFM Station made out of heavy gauge extruded alluminium of 1.5 mm nominal thickness consists of low leakage extruded alluminium volume control damper; Rapid Average Pitot tube; Air Flow Straightner (Honey-Comb patterned). |
| 94 | Repair/ replacement to Motorised assembly for AFM Station with application programmable controller for enabling stable pressure control; shall be able to control air handler drive in tune to filter condition & maintain desired volume flow rate; shall communicates on pLAN network; differential pressure sensor; & necessary step down transformer from 220 V includingall necessary control wiring for working the same. |
| 95 | Repair/ replacement, DOP testing and commissioning of modular type unidirectional Laminar air flow system for Operation Theatres assembled and sealed in factory comprising of plenum & holding structure complying to ISO 5 to ISO 6, made out of MS Sheet with epoxy coated paint/stainless steel having minimum thickness of 2mm protected with oven baked RAL 9010 epoxy coating both inside and outside and sealed with 100% leak proof gasket in accordance with ISO EN 14644-3. Air tightness of casing shall be in accordance with class B of EN-1866-1998. Class L1 (M) of PREN 1886-2003. Calss \"C\" of PREN 12237-2003 and ISO-EN14644-3. One test connector accessible from the operating theater shall be provided to measure loss of pressure and take test Aerosol samples. Provision for filtter mounting shall be with rotating clamps. Removable \"Screentek\" screens of monofilament polyster fabric in individual clip-on frames for projection of HEPA filters against exposure to blood splash shall be provided. Mini Pleat HEPA Filters(as per UL 900 fire rating) in Aluminum frame flange type , filter media consisting of Micro Fibre Glass (imported) protected with Aluminum mesh on both sides having efficiency better than 99.97% down to 0.3 microns particle size with I.P.D< 15 mm WG, F.P.D>= 50 WG for the following .Contractor to quote forof one of the following three makes with respective specifications mentioned against each make at (a), (b) & (c ) below:- |
| 96 | S&F 6 Nos mini pleat HEPA Filters 580mm x 860mm x 66mm and 02 Nos 560mm x 560mm x 66mm for OTs size of Plenum 1815mm (L) x 2415mm (W) x 400mm (h).Make :- CAMFIL, Equivalent AMERICAN AIR FILTERS/FRUDENBERG.Note :- DOP SITE TESTING OF HEPA FILTERS :-(a) Testing will be done with the help of photometer and smoke generator.(b) Room validation will be done with particle counter.(c) Velocity of outlet of HEPA filters shall be done with velocity meter.Compressed air and all other materials for testing shall be arranged by the contractor.Contractor shall visit the site befor quoting the above items and quote accordingly. (Note For Item No 72.00 & 72.01: -Only Hepa Filters shall be supplied and fixed & DOP Test at site shall be carried out is to be provided by the contractor as per directions of Engineerin-Charge/GE) |
| 97 | Note for Srl Item Nos 53.00 to 72.01: - Contractor shall visit the site before quoting of tender,for check the servicablity of items to be repair/replaced andif found that items provided at site needs any type of repair/ replacement of any part or in full or servcing or any other chemical treatment for proper functioning of system through OEM.Rates quoted by the tenderer shall deemed to be inclusive of this aspact wheather he has visited the site or not and no further claim shall be admissinble on this account. |