Repair, Maintenance Of Dg Set, Amf Panels, Switch Gears And Connected Works At Airforce Station Thanjavur, thanjavur-Tamil Nadu

Military Engineer Services-MES has published Repair, Maintenance Of Dg Set, Amf Panels, Switch Gears And Connected Works At Airforce Station Thanjavur. Submission Date for this Tender is 25-04-2022. Switch Gear Tenders in thanjavur Tamil Nadu. Bidders can get complete Tender details and download the document.




Tender Notice

31620484
Corrigendum : Repair, Maintenance Of Dg Set, Amf Panels, Switch Gears And Connected Works At Airforce Station Thanjavur
Open Tender
Indian
Tamil Nadu
thanjavur
25-04-2022

Tender Details

Repair, Maintenance Of Dg Set, Amf Panels, Switch Gears And Connected Works At Airforce Station Thanjavur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-Apr-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 25-04-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 40000.0 /-
Tender Value
INR 20 Lakhs /-

BOQ Items

Name of Work: REPAIR,MAINTENANCE OF DG SET,AMF PANELS,SWITCH GEARS AND CONNECTED WORKS AT AIRFORCE STATION THANJAVUR.
Sl. No. Item Description
1Carrying out"B"- check to 320 KVA generator set of Kirloskar make once in a period six months or 250 hrs of run whichever is earlier by authorized / OEM including replacement ofEngine oil, oil filter fuel filter "O" ring,tappet valve adjustment replacing the tappet gasket water leakage rectification and testing commissioningrecommended by OEM for smooth running, complete all as directed by the Engineer-in-Charge. Notes : (i) Engine oil, fuel filter and oil filter shall be measured and paid separately under relevant items.
2All as per item No. 1 above but for 250 KVA DG set of Kirloskar make.
3All as per item No. 1 above but for 125 KVA DG set of Kirloskar/Cummins make.
4All as per item No. 1 above but for 100 KVA DG set of Kirloskar/Cummins make.
5All as per item No. 1 above but for 82.5 KVA DG set of Kirloskar make.
6All as per item No. 1 above but for 62.5 KVA DG set of Kirloskar make.
7All as per item No. 1 above but for 45 KVA DG set of Kirloskar make.
8All as per item No. 1 above but for 40 KVA DG set of Kirloskar make.
9All as per item No. 1 above but for 30 KVA DG set of Kirloskar make.
10All as per item No. 1 above but for 15/20 KVA DG set of Kirloskar make.
11All as per item No. 1 above but for 7.5 KVA DG set of Kirloskar make.
12Dismantling and taking out blocked / choked radiator assembly including dismantling of rubber hose, fan bladeand V belt etc feeding the high pressure air mixed with water alternatively and applying cleaning chemical on the surfaces of radiator and cleaning thoroughly, brazing work for leakage and refixing the same in position complete all as specified.
13Dismantling and taking out self starter assembly suitable for 125 KVA to 250 KVA DG Set and replacement of wornout spare parts like field coil, armature assembly, solenoid assembly, carbon brush, carbon brush assembly, clutch plate assembly and bushes including servicing and refixing to engine complete all as specified.
14Dismantling and taking out self starter assembly suitable for 62.5 KVA to 100 KVA DG Set and replacement of wornout spare parts like field coil, armature assembly, solenoid assembly, carbon brush, carbon brush assembly, clutch plate assembly and bushes including servicing and refixing to engine complete all as specified.
15Dismantling and taking out self starter assembly suitable for 20 KVA to 45 KVA DG Set and replacement of wornout spare parts like field coil, armature assembly, solenoid assembly, carbon brush, carbon brush assembly, clutch plate assembly and bushes including servicing and refixing to engine complete all as specified.
16Dismantling and taking out battery charging alternater assembly suitable for 125 KVA to 250 KVA DG Set and replacement of wornout spare parts like field coil, rotor assembly, carbon brush, rectifier assembly and bushes etc including servicingand refixing complete all as specified.
17Dismantling and taking out battery charging alternater assembly suitable for 62.5 KVA to 100 KVA DG Set and replacement of wornout spare parts like field coil, rotor assembly, carbon brush, rectifier assembly and bushes etc including servicingand refixing complete all as specified.
18Dismantling and taking out battery charging alternater assembly suitable for 20 KVA to 45 KVADG Set and replacement of wornout spare parts like field coil, rotor assembly, carbon brush, rectifier assembly and bushes etc including servicingand refixing complete all as specified.
19Dismantling and taking out fuel injector pump assembly suitable for 125 KVA to 250 KVA DG Set and complete overhauling of FIP including replacement of unserviceable parts like rebuild overhauling kit, rebuild seal kit, fuel injector "O" rings, OEM gaskets, spring gasket injector, valve bearing etc complete all as specified.
20Dismantling and taking out fuel injector pump assembly suitable for 62.5 KVA to 100 KVA DG Set and complete overhauling of FIP including replacement of unserviceable parts like rebuild overhauling kit, rebuild seal kit, fuel injector "O" rings, OEM gaskets, spring gasket injector, valve bearing etc complete all as specified.
21Dismantling and taking out fuel injector pump assembly suitable for 20 KVA to 45 KVA DG Set and complete overhauling of FIP including replacement of unserviceable parts like rebuild overhauling kit, rebuild seal kit, fuel injector "O" rings, OEM gaskets, spring gasket injector, valve bearing etc complete all as specified.
22Supply and fix in replacement Self starter assembly12 Volt suitable for 82.5 KVA to 125 KVA DG Set complete all as Specified.
23Supply and fix in replacement Self starter assembly12 Volt suitable for 30 KVA to 62.5 KVA DG Set complete all as Specified.
24Supply and fix in replacement Banded cogged belt (2JAX51-LP-1326) cat part No - 06.032.03.0.00 complete all as specified.
25Supply and fix in replacement V Belt (A-47) 1227 length cat part No - 04.140.01.0.00 complete all as specified.
26Supply and fix in replacement Fuel pipe (7.5, 14x14B, 700 PB) cat part No - 34.151.04.0.00 complete all as specified.
27Supply and fix in replacement Fuel pipe (9.5I.D x 4000L) cat part No - 06.610.03.0.00 complete all as specified.
28Supply and fix in replacement Leak off pipe 1000mm long cat part No - 48.112.01.0.00 complete all as specified.
29Supply and fix in replacement Silencer assembly cat part No - 48.318.10.0.00 complete all as specified.
30Supply and fix in replacement Rubber hose for air intake cat part No - 48.464.02.0.00 complete all as specified.
31Supply and pouring KOEL care super genuine oil Cat part No - 82.050.10.0.20complete all as specified.
32Supply and pouring KOEL care Genuine coolant premix Cat part No - 82.020.35.1.01 complete all as specified.
33Supply and fixing in replacement 1.1 litre fuel filter kit cat part No - 48.040.01.0.00 complete all as specified.
34Supply and fixing in replacementLub oil filter element cat part No - 06.040.01.0.00 complete all as specified.
35Supply and fixing in replacementair filter element suitable for up to 45 KVA DG Set complete all as specified.
36Supply and fixing in replacementair filter element suitable for up to 62.5 KVA to 82.5 KVA DG Set complete all as specified.
37Supply and fixing in replacementair filter element suitable for up to 100 KVA to 125 KVA DG Set complete all as specified.
38Supply and fixing in replacementair filter element suitable for up to 250 KVA DG Set complete all as specified.
39Supply and fix in replacement stop solenoid 12V 10 amps single coil 75mm dia cat part No - 02.477.01.0.00 complete all as specified.
40Supply and fix in replacement stop solenoid 24V 10 amps single coil complete all as specified.
41Supply and fix in replacement generator control unit KG541 level-0 cat part No - D8.048.07.0.00 complete all as specified.
42Supply and fix in replacement generator control unit KG934 level-1 cat part No - 2H.894.06.0.00 complete all as specified.
43Supply and fix in replacement generator control unit KG545 level-2 cat part No - DV0.901.13.0.00 complete all as specified.
44Supply and fix in replacement exhaust fan (450mm) with connector cat part No -D8.079.26.0.00 complete all as specified.
45Supply and fix in replacementKirloskar green AVR for alternator suitable up to 45 KVA DG Set complete all as specified.
46Supply and fix in replacementKirloskar green AVR for alternator suitable for 62.5 KVA to 125 KVA DG Set complete all as specified.
47Supply and fix in replacementKirloskar green AVR for alternator suitable for 250 KVA DG Set complete all as specified.
48Supply and fix in replacement 4-20mA lube oil pressure sensor gems make 3100 series cat part No - Dvo.812.11.0.00 complete all as specified.
49Supply and fix in replacement Fuel level sensor height 225mm cat part No- DV0.802.15.0.00 complete all as specified.
50Supply and fix in replacement Expantion bellow assembly 3" cat part No - 06.602.10.0.00 complete all as specified.
51Supply and fix in replacement Thermostat element (74 Deg) WTIL No.DEV358 cat part No - 39.040.09.0.00
52Supply and fix in replacement Nozzele leak off pipe cat part No - 06.819.20.0.00 complete all as specified.
53Supply and fix in replacement electronic battery charger 12 volt DC 10 amps NHP make cat part No 02.872.18.0.00 complete all as specified.
54Supply and fix in replacement electronic battery charger 24 volt DC 10 amps NHP make cat part No 6H.849.09.0.00 complete all as specified.
55Dismantling of existing defective Alternator any capacity any makefrom the foundation, disconnecting the electric connection, coupling pulley, and taking out to work shop cutting down and removing existing burnt out copper windings, cleaning of slots and rewinding with super enamelled solidcopper conductor ( winding wire) complete including varnishing, drying, ovening, overhauling, greasing and fixing in the same position, making necessary electric connection and testing of Alternator complete all as specified.
56Supply and fix in replacement ATS (automatic transfer switch) 4 pole (TPN) with enclosure with complete protection 100 amps 415 volts 50 HZ AC supply including mounting arrengement and disconnecting / connecting electrically with existing cableincluding matching with existing generator safety unit complete all as per Havells cat part No IHYFCDE100.
57Battery 12V,180 AH mainteance free (replacement warranty period not less than 3 years) complete all as specified.
58Battery 12V, 90 AH mainteance free( replacement warranty period not less than 3 years)complete all as specified
59Supply OnlyBattery Lead 0.5 mtr long.
60Supply OnlyBattery terminal as per sample
61Supply and fix in replacement Voltmeter, digital typewith built inselector switch including control wiring with 1.5 Sqmm copper conductor cable complete on AMF Panel, LT Panel complete all as specified.
62Supply and Fix in replacement Ammeter,Digital typewith built in selector switch including control wiring with 1.5 Sqmm copper conductor cable complete on AMF Panel, LT Panel complete all as specified.
63Supply and Fix in replacementIndicating lamps 240V LED type for indication ofRYB Phases complete all as specified.
64Material and labour for Servicing /maint /repair ofAMF panel by checking and replacing defective relays, timers, single phase preventer,panel control wiring with suitable size power contactor in AMFpanelcomplete all as specified Note:- relays, timers, contactors single phasing preventor will be measured and paid for separately under relevent items.
65Supply and fix in replacement KRB relay card 8 way 20 pin (PCB = relay card - 8 ATS - 12 V DC) cat part No 03.218.13.0.00 complete all as specified.
66Supply and fix ion replacement ATS relay card 8 way 20 pin (PCB = relay card - 8 KRB - 12 V DC) cat part No 03.218.14.0.00 complete all as specified.
67Supply and fix in replacement Contactor relay Unit of suitableDG Set 24 Volt DC complete all as specified.
68Supply and fix in replacementContactor relay 9/8 pin with base12 Volt DC complete all as specified.
69Supply and fix in replacementtimer relay ,relay assembly 220 Volt, 6 Terminals complete all as specified.
70Supply and fix in replacement HBC fuse link 40 to 160 amps complete all as specified.
71Supply and fix in replacement DN open type fuse bases fixed type 100 to 160 amps complete all as specified.
72Supply and fix in replacement 400 amps 3.pole power contactor suitable for 250 KVA DG Set AMF panel complete all as specified.
73Supply and fix in replacement 250 amps 3 pole power contactor suitable for 125 KVA DG Set AMF panel complete all as specified.
74Supply and fix in replacement 200 amps 3 pole power contactor suitable for 82.5 KVA to 100 KVA DG Set AMF panel complete all as specified.
75Supply and fix in replacement 95 amps 3 pole power contactor suitable for 30 KVA to 62.5 KVA DG Set AMF panel complete all as specified.
76Supply and fix in replacement single phasing preventor (VMR) complete all as specified.
77Supply and fix in replacement left / right hand lock with catcher complete all as specified.
78Supply, Laying, jointing & testingin trenches or passing through pipe, 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor of cross sectional area 95 sqmm 3.5 core with all fixing & connecting accessories including taking down old unserviceable cable complete all as specified. Make: Havell’s / Polycab / Finolex)
79Excavation in trenches in soft/loose soil not exc. 1.5 metre wide and not exc. 1.5 metre in depth and getting out for taking up / layingunder ground electric cable or for pole etc complete all as specified and as directed. Note :- Mechanical excavation is not allowed in this Stn only manual excavation allowed.
80Returning and filling in two parts (i) using riddled soil obtain from excavated soil upto depth of 30 cm (8 cm below cable and remaining above cable) for cushioning of cable and (ii) refilling the trench of remaining depth with normal excavated soil all as specified and directed. Note:- Excavated soil shall be riddled by using sieve to separate composite partricles etc as per IS 1255 1983 and refilling in trenches as in cable cushioning.
81Removing surplus soils to a distance not exceeding 50 mtr and depositing where directed at a level not exc. 1.5 mtr above the starting point all complete as specified and as directed.
82Sub class "B" old size bricks, laid flat dry with width of the bricks laid to the axis of the cablecomplete all as specified.
Disclaimer :