| 1 | Excavating in trenches not exceeding 1.5m wide and not exceeding1.5m in depth/width for laying under ground cable/foundations and getting out in soft/loose soil complete all as specified and as directed. Note: During excavation, no mechanical excavator is permitted to use at site, |
| 2 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and as directed. |
| 3 | Removing of surplus excavating material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed. |
| 4 | M&L for sand cushioning for protection of LT under ground cable with screen wash sand and punning to proper required cover complete all as specified and as directed. |
| 5 | M&L brick protection with old size sub class ‘B’brick for PVC under ground cable protection in trench with width equal to length of brick, laid dry and flat joining each other with gap between adjacent brick not exceeding 10mm over LT under ground cable complete all as specified and as directed. |
| 6 | Laying only old brick for PVC under ground cable protection in trenches with width equal to length of brick laid dry and flat joining each other with gap between adjacent brick not exceeding 10mm over LT under ground cable complete all as specified and as directed.Note : Old serviceable retrived during taking out bricks shall re-use. |
| 7 | M&L excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for making foundation or any other works in hard/dense soil including removing excavated materials not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the staring point complete all as specified and as directed. |
| 8 | M&L for cement concrete (1:3:6) type C-2 (using 40mm graded stone aggregate) as in foundations, filling and mass concrete, etc complete all as specified and as directed. |
| 9 | M&L forPCC (1:3:6) type C-1 (using 20mm graded stone aggregate) as in foundation or any other works complete all as specified and as directed. Note: Form work if so required for PCC works are deemed to be inclusive with quoted rate. |
| 10 | M&L for rendering 10mm thick in CM (1:6) on fair faces of brick works or concrete surfaces complete all as specified and as directed. |
| 11 | M&L for dismantling of ACSR or AAC conductors of any sizes or types etc. complete, setting aside for taking credit complete all as specified and asdirected. |
| 12 | M&L for dismantling of cross arms of M.S.channels or angle sections, etc. complete and depositing to MES Store Yard for re-use the serviceable steel sections complete all as specified and as directed. |
| 13 | M&L for dismantling of insulators of any type and sizes and depositing to MES Store Yard for re-use the serviceable insulators complete all as specified and as directed. |
| 14 | M&L for dismantling of earth wire or copper conductor, service feeder or distributor span of any type and sizes and depositing to MES Store Yard for re-use the serviceable conductors complete all as specified and as directed. |
| 15 | M&L for taking out of old bricks of any sizes or types for replacement of old unserviceable cable with new bricks complete all as specified and as directed. |
| 16 | M&L for taking out of old unserviceable cable of any sizes or types for replacement with new cable complete all as specified and as directed. |
| 17 | M&L for relaying of heavy duty LT under ground cable of any sizes and types in pipe/trench /cable duct/fixed on wall by proper size shaped GI clamps with nuts, bolts, etc. and making good the disturbed surfaces by cement mortar/paint to match with the existing surface complete all as specified and as directed. |
| 18 | M&L for connection to Feeder Pillar Box, DB or any other indicatated location by heavy duty round wire armoured LT under ground cable of size 120 Sq.mm, 3.5 Core, 1100 volt grade, HR PVC insulated, HR PVC inner and outer sheathed, multi stranded aluminium cable conforms to IS 7098 (Part-I) 1988 with latest ammendments inpipe/trench/cable duct/fixed on wall by proper size shaped GI clamps with nuts, bolts, etc. and making good the disturbed surfaces by cement mortar/paint to match with the existing surfaces complete all as specified and as directed. |
| 19 | All as per Serial item No. 18 here-in-before butcable of size 95 Sq.mm, 3.5 Core, 1100 volt grade. |
| 20 | All as per Serial item No. 18 here-in-before butcable of size 70 Sq.mm, 3.5 Core, 1100 volt grade. |
| 21 | All as per Serial item No. 18 here-in-before butcable of size 35 Sq.mm, 3.5 Core, 1100 volt grade. |
| 22 | All as per Serial item No. 18 here-in-before butcable of size 25 Sq.mm, 3.5 Core, 1100 volt grade. |
| 23 | All as per Serial item No. 18 here-in-before butcable of size 16 Sq.mm, 4 Core, 1100 volt grade. |
| 24 | All as per Serial item No. 18 here-in-before butcable of size 10 Sq.mm, 4 Core, 1100 volt grade. |
| 25 | All as per Serial item No. 18 here-in-before butcable of size 10 Sq.mm, 2 Core, 1100 volt grade. |
| 26 | Supply and use of corrosion inhibiting compound during fixing the cable end in aluminium reducer terminals or any other specified location complete all as specified and as directed. |
| 27 | M&L for boring of holes under road, pavement, hard standing, etc. by trenchless technology using ultra sounding techinque and necessary machine for insertion of pipes, suitable for 50mm to 80mm dia GI pipes complete all as specified and as directed. |
| 28 | M&L for 80mm bore GI pipe, light grade, with all fittings, laid in trenches/wall/pole through MS flat iron of size 25X3mm, including nuts, bolts & washers, etc. of proper sizes for cable protection complete all as specified and as directed. |
| 29 | All as per Serial item No. 28 here-in-before but 50mm bore. |
| 30 | All as per Serial item No. 28 here-in-before but 40mm bore |
| 31 | Taking down old unserviceable/corroded LT feeder pillar box/busbar chamber/DBs of any size or type after disconnection of all electrical connections complete for replacement with new one complete all as specified and as directed. |
| 32 | Supply, install, testing and commissioning of LT feeder pillar box, IP-54 type of size 1300mm x 800mm x 500mm, out door type, made out of 3.15mm thick CRCA sheet supported and fixed on structural frame, factory made incubicle shaped, roof canopy type, with special type of heavy duty stainless steel door hinges and totally enclosed dust proof and vermin prooffront and back opening with locking arrangements and duly fixed on ground by PCC foundation in PCC (1:2:4) type B-1 (using 20mm graded stone aggregate) of size 700mm x 300mm x 600mm on the adjacent pairs of leg and net cementing the same. The feeder pillar box shall have enamelled danger notice plate of 1.6mm thick, duly painted with two coats of enamel paint over a coat of red oxide primer (internally & externally) on the surface complete all as specified and directed with the provision/comprising of the following electrical equipments/items:- |
| 33 | Make : LT Feedere Pillar Box shall be of make L&T/Milestone/C&S Electric Ltd/Scheider/Indo Asian/Unitec or CPRI type tested and certified approval.Note : (i) The locking arrangement of fixing pad lock on the front door with 1 No 7 levers Pad Lock (Type Nav-Tal, 6 levers, 3 Keys of make- Godrej. (ii)Legs of the feeder pillar shall not be less than 600mm length. |
| 34 | INCOMING/OUT GOING : (i) Aluminium bus bar 4 strips (covered with PVC insulated sleeves) 600 Amps capacity, 60-70 cm long including connection, etc. - 01 Set(ii) MCCB 250 Amps, 415 volts, Adjustable Thermal Magnetic Trip Unit, Ics = 100%Icu,4 pole, 25 kA breaking capacity.= 01 Nos.(Incoming to FP Box)(iii) MCCB 250 Amps, 415 Volts, Adjustable Thermal Magnetic Trip Unit, Ics=100%Icu, 4 pole, 25 kA breaking capacity with incoming and outgoing spreader sets - 01 Nos.(Outgoing to another FP Box)Note :The connection between the MCCB and bus bar shall be done by aluminium bar or cable of suitable rating with nut, bolts & washers and quoted rate shall be nclusive. |
| 35 | OUT GOING (i) MCB SP 40 to 63 Amps, 415 volts, 50 HZ, 10 kA breaking capacity (DIN rail mounted) Type ‘C’ Characteristic = 06 Nos(ii) MCB SPN, 20 to 32 Amps, 240 Volts, 50 HZ, 10 kA breaking capacity (DIN rail mounted) Type ‘C’ Characteristic - 2 Nos Note : (i) All cables in the feeder pillar box should be properly glanded and thimbled. (ii) Cable Lugs or thimble for connection to UG cable shall be measured and paid separately. |
| 36 | M&L for fixing the aluminium terminal in cable end (through corrosion inhibiting compound) of cable size 95 sq.mm complete all as specified and as directed. Note: Corrosion inhibiting compound which shall be used during crimping of terminal shall be measured and paid separately. |
| 37 | All as per Serial item No. 33 here-in-before cable size 70 sq.mm |
| 38 | All as per Serial item No. 33 here-in-before but cable size 50 sq.mm |
| 39 | All as per Serial item No. 33 here-in-before but cable size 35 sq.mm. |
| 40 | All as per Serial item No. 33 here-in-before but cable size 25 sq.mm. |
| 41 | All as per Serial item No. 33 here-in-before but cable size 16 sq.mm. |
| 42 | All as per Serial item No. 33 here-in-before but cable size 10 sq.mm. |
| 43 | M&L for fixing the cable junction boxes of size 225 x 295 x 122mm with terminals for 35 sq.mm, 3.5 core, 1100 volt cable, IP 66/69, weather proof, outdoor installation type with threaded cable glands and pole mounting brackets, etc. complete all as specified and as directed. |
| 44 | M&L for fixing the cable junction boxes of size 205 x 255 x 112mm with terminals for 10 - 25 sq.mm, 4.0/3.5 core, 1100 volt cable, IP 66/69, weather proof, outdoor installation type with threaded cable glands and pole mounting brackets, etc complete all as specified and as directed. |
| 45 | M&L for making two nos hole (one at top portion of the pole and one at bottom portion of the pole) for throughing 1.5 sq.mm, 3 single core, 1100 volt cable with in steel tubular swaged pole of type SP 31/ 55 through drill or other required T&P complete all as specified and as directed. |
| 46 | M&L for 3 single core PVC insulated multi stranded copper conductorcable 1.5 sq.mm 1100 volt unarmoured for connection from loop /junction box to street lights/security lights,etc. complete all as specified and as directed. |
| 47 | M&L for triming the tree branches of girth 10 to 20cm, falling/touching the HT/LT overhead line in various area ofAF Station Borjhar with skilled labours and cutting tools and disposed the branches to a distance not exceeding 50m from starting point complete all as specified and as directed. |
| 48 | All as per Serial item No. 44 here-in-before but girth 20 to 30cm |
| 49 | M&L for painting of RCC pole, 7.5m approx above ground level with two coats of sky blue anti algal or fungal paint (second coat of paint to be carried out one day later after the first coat), over a coat of primer on plaster/cement surfaces of 2m from the ground level and two coats of white colour anti algal or fungal paint (second coat of paint to be carried out one day later afterthe first coat) over and including one coat primer on plaster/ cement surfaces of any description including preparation of old painted surfaces and steel bracket to be painted with two coats of aluminium paint (second coat of paint to be carried out one day later afterthe first coat), over and incuding one coat of red oxide primer complete all as specified and as directed. |
| 50 | M&L for painting of steel tubular swaged poles, 7.5m approx above ground level including brackets, clamps, etc. with two coats of sky blue enamel paint (second coat of paint to be carried out one day later after the first coat) over and including a coat of red oxide primer on steel surfaces of 2m from the ground level and two coats of aluminium paint (second coat of paint to be carried out one day later after the first coat) over and including one coat of red oxide primer on steel surfaces of any description including preparation of old painted surfaces complete all as specified and as directed. |
| 51 | M&L for painting of RCC poles, 10.5m approx above ground level with two coats of sky blue anti algal or fungal paint (second coat of paint to be carried out one day later after the first coat), over and including one coat primer on plaster/ cement surfaces of 2m from the ground level and two coats of white colour anti algal or fungal paint (second coat of paint to be carried out one day later afterthe first coat) over and including one coat of primer on plaster/cement surfaces of any description including preparation of old painted surfaces and steel bracket to be painted with two coat of aluminium paint (second coat of paint to be carried out one day later afterthe first coat) over and including one coat of red oxide primer complete all as specified and as directed. . |
| 52 | M&L for painting of steel tubular swaged pole, 10.5m approx above ground level including angles, clamps, etc. with two coats of sky blue enamel paint (second coat of paint to be carried out one day later afterthe first coat), over and including one coat of red oxide primer on steel surfaces of 2m from the ground level and two coats of aluminium paint (second coat of paint to be carried out one day later after the first coat) over and including one coat of red oxide primer on steel surfaces of any description including preparation of old painted surfaces complete all as specified and as directed. |
| 53 | S&F LED street light luminaries with aesthetically designed IP-66, pressure die cast aluminium housing and toughned flat glass with wattage90 W ± 5%, 230V, 50 Hz, current < 0.414, power factor > 0.95, Ithd <10%, system efficacy 100 lumen/W, with lumen maintenance 50000 Hrs @ L70 for LED, LED should be LM 80 certified, peanut lens for batwing 135/ 85° light distribution with surge protection kV including taking out old unserviceable one complete all as specified and as directed. Make : Orient, Type LSFS-090-C or equivalent model from make Havells/Philips/Bajaj |
| 54 | M&L for hot dip galvanised (as perBS EN ISO 1461 1991) brackets of 40mm dia GI pipe, medium grade, 1.5m long for fixing LED type street light luminaires, fixing it to pole through MS Clamps, nuts, bolts & washers, etc including taking down old unserviceable one complete all as specified and as directed. Note : Any welding works related to brackets shall be carried out at the factory premises of the manufacturers |
| 55 | M&L for taking down and refixing LED street/ flood light luminaries after replacement of unserviceable LED outdoor driver with new one of any type or capacity or any other specified works complete all as specified and as directed. Note::Driver will be measured and paid separately. |
| 56 | Supply only LED outdoor drivers for 120 W, 230 volt LED outdoor street light luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 57 | Supply only LED outdoor drivers for 90 W, 230 volt LED outdoor streetlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 58 | Supply only LED outdoor drivers for 60 W, 230 volt LED outdoor streetlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 59 | Supply only LED outdoor drivers for 30 W, 230 volt LED outdoor streetlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 60 | Supply only LED outdoor drivers for 160 W, 230 volt LED outdoor floodlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 61 | Supply only LED outdoor drivers for 120 W, 230 volt LED outdoor floodlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |