| 1 | Excavating in trenches not exceeding 1.5m wide and not exceeding1.5m in depth/width for laying under ground cable/foundations and getting out in soft/loose soil complete all as specified and as directed. Note: During excavation, no mechanical excavator is permitted to use at site, |
| 2 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and as directed. |
| 3 | Removing of surplus excavating material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed. |
| 4 | M&L for sand cushioning for protection of LT under ground cable with screen wash sand and punning to proper required cover complete all as specified and as directed. |
| 5 | M&L brick protection with old size sub class ‘B’brick for PVC under ground cable protection in trench with width equal to length of brick, laid dry and flat joining each other with gap between adjacent brick not exceeding 10mm over LT under ground cable complete all as specified and as directed. |
| 6 | Laying only old brick for PVC under ground cable protection in trenches with width equal to length of brick laid dry and flat joining each other with gap between adjacent brick not exceeding 10mm over LT under ground cable complete all as specified and as directed.Note : Old serviceable retrived during taking out bricks shall re-use. |
| 7 | M&L excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for making foundation or any other works in hard/dense soil including removing excavated materials not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the staring point complete all as specified and as directed. |
| 8 | M&L for cement concrete (1:3:6) type C-2 (using 40mm graded stone aggregate) as in foundations, filling and mass concrete, etc complete all as specified and as directed. |
| 9 | M&L forPCC (1:3:6) type C-1 (using 20mm graded stone aggregate) as in foundation or any other works complete all as specified and as directed. Note: Form work if so required for PCC works are deemed to be inclusive with quoted rate. |
| 10 | M&L for rendering 10mm thick in CM (1:6) on fair faces of brick works or concrete surfaces complete all as specified and as directed. |
| 11 | M&L for dismantling of ACSR or AAC conductors of any sizes or types etc. complete, setting aside for taking credit complete all as specified and asdirected. |
| 12 | M&L for dismantling of cross arms of M.S.channels or angle sections, etc. complete and depositing to MES Store Yard for re-use the serviceable steel sections complete all as specified and as directed. |
| 13 | M&L for dismantling of insulators of any type and sizes and depositing to MES Store Yard for re-use the serviceable insulators complete all as specified and as directed. |
| 14 | M&L for dismantling of earth wire or copper conductor, service feeder or distributor span of any type and sizes and depositing to MES Store Yard for re-use the serviceable conductors complete all as specified and as directed. |
| 15 | M&L for taking out of old bricks of any sizes or types for replacement of old unserviceable cable with new bricks complete all as specified and as directed. |
| 16 | M&L for taking out of old unserviceable cable of any sizes or types for replacement with new cable complete all as specified and as directed. |
| 17 | M&L for relaying of heavy duty LT under ground cable of any sizes and types in pipe/trench /cable duct/fixed on wall by proper size shaped GI clamps with nuts, bolts, etc. and making good the disturbed surfaces by cement mortar/paint to match with the existing surface complete all as specified and as directed. |
| 18 | M&L for connection to Feeder Pillar Box, DB or any other indicatated location by heavy duty round wire armoured LT under ground cable of size 120 Sq.mm, 3.5 Core, 1100 volt grade, HR PVC insulated, HR PVC inner and outer sheathed, multi stranded aluminium cable conforms to IS 7098 (Part-I) 1988 with latest ammendments inpipe/trench/cable duct/fixed on wall by proper size shaped GI clamps with nuts, bolts, etc. and making good the disturbed surfaces by cement mortar/paint to match with the existing surfaces complete all as specified and as directed. |
| 19 | All as per Serial item No. 18 here-in-before butcable of size 95 Sq.mm, 3.5 Core, 1100 volt grade. |
| 20 | All as per Serial item No. 18 here-in-before butcable of size 70 Sq.mm, 3.5 Core, 1100 volt grade. |
| 21 | All as per Serial item No. 18 here-in-before butcable of size 35 Sq.mm, 3.5 Core, 1100 volt grade. |
| 22 | All as per Serial item No. 18 here-in-before butcable of size 25 Sq.mm, 3.5 Core, 1100 volt grade. |
| 23 | All as per Serial item No. 18 here-in-before butcable of size 16 Sq.mm, 4 Core, 1100 volt grade. |
| 24 | All as per Serial item No. 18 here-in-before butcable of size 10 Sq.mm, 4 Core, 1100 volt grade. |
| 25 | All as per Serial item No. 18 here-in-before butcable of size 10 Sq.mm, 2 Core, 1100 volt grade. |
| 26 | Supply & use of corrosion inhibiting compound during fixing the cable end in aluminium reducer terminals or any other specified location complete all as specified and as directed. |
| 27 | M&L for boring of holes under road, pavement, hard standing, etc. by trenchless technology using ultra sounding techinque and necessary machine for insertion of pipes, suitable for 50mm to 80mm dia GI pipes complete all as specified and as directed. |
| 28 | M&L for 80mm bore GI pipe, light grade, with all fittings, laid in trenches/wall/pole through MS flat iron of size 25X3mm, including nuts, bolts & washers, etc. of proper sizes for cable protection complete all as specified and as directed. |
| 29 | All as per Serial item No. 28 here-in-before but 50mm bore. |
| 30 | All as per Serial item No. 28 here-in-before but 40mm bore |
| 31 | Taking down old unserviceable/corroded LT feeder pillar box/busbar chamber/DBs of any size or type after disconnection of all electrical connections complete for replacement with new one complete all as specified and as directed. |
| 32 | Supply, install, testing and commissioning of LT feeder pillar box, IP-54 type of size 1300mm x 800mm x 500mm, out door type, made out of 3.15mm thick CRCA sheet supported and fixed on structural frame, factory made incubicle shaped, roof canopy type, with special type of heavy duty stainless steel door hinges and totally enclosed dust proof and vermin prooffront and back opening with locking arrangements and duly fixed on ground by PCC foundation in PCC (1:2:4) type B-1 (using 20mm graded stone aggregate) of size 700mm x 300mm x 600mm on the adjacent pairs of leg and net cementing the same. The feeder pillar box shall have enamelled danger notice plate of 1.6mm thick, duly painted with two coats of enamel paint over a coat of red oxide primer (internally & externally) on the surface complete all as specified and directed with the provision/comprising of the following electrical equipments/items:- |
| 33 | Make : LT Feedere Pillar Box shall be of make L&T/Milestone/C&S Electric Ltd/Scheider/Indo Asian/Unitec or CPRI type tested and certified approval.Note : (i) The locking arrangement of fixing pad lock on the front door with 1 No 7 levers Pad Lock (Type Nav-Tal, 6 levers, 3 Keys of make- Godrej. (ii)Legs of the feeder pillar shall not be less than 600mm length. |
| 34 | INCOMING/OUT GOING : (i) Aluminium bus bar 4 strips (covered with PVC insulated sleeves) 600 Amps capacity, 60-70 cm long including connection, etc. - 01 Set(ii) MCCB 250 Amps, 415 volts, Adjustable Thermal Magnetic Trip Unit, Ics = 100%Icu,4 pole, 25 kA breaking capacity.= 01 Nos.(Incoming to FP Box)(iii) MCCB 250 Amps, 415 Volts, Adjustable Thermal Magnetic Trip Unit, Ics=100%Icu, 4 pole, 25 kA breaking capacity with incoming and outgoing spreader sets - 01 Nos.(Outgoing to another FP Box)Note :The connection between the MCCB and bus bar shall be done by aluminium bar or cable of suitable rating with nut, bolts & washers and quoted rate shall be nclusive. |
| 35 | OUT GOING (i) MCB SP 40 to 63 Amps, 415 volts, 50 HZ, 10 kA breaking capacity (DIN rail mounted) Type ‘C’ Characteristic = 06 Nos(ii) MCB SPN, 20 to 32 Amps, 240 Volts, 50 HZ, 10 kA breaking capacity (DIN rail mounted) Type ‘C’ Characteristic - 2 Nos Note : (i) All cables in the feeder pillar box should be properly glanded and thimbled. (ii) Cable Lugs or thimble for connection to UG cable shall be measured and paid separately. |
| 36 | M&L for fixing the aluminium terminal in cable end (through corrosion inhibiting compound) of cable size 95 sq.mm complete all as specified and as directed. Note: Corrosion inhibiting compound which shall be used during crimping of terminal shall be measured and paid separately. |
| 37 | All as per Serial item No. 33 here-in-before cable size 70 sq.mm |
| 38 | All as per Serial item No. 33 here-in-before but cable size 50 sq.mm |
| 39 | All as per Serial item No. 33 here-in-before but cable size 35 sq.mm. |
| 40 | All as per Serial item No. 33 here-in-before but cable size 25 sq.mm. |
| 41 | All as per Serial item No. 33 here-in-before but cable size 16 sq.mm. |
| 42 | All as per Serial item No. 33 here-in-before but cable size 10 sq.mm. |
| 43 | M&L for fixing the cable junction boxes of size 225 x 295 x 122mm with terminals for 35 sq.mm, 3.5 core, 1100 volt cable, IP 66/69, weather proof, outdoor installation type with threaded cable glands and pole mounting brackets, etc. complete all as specified and as directed. |
| 44 | M&L for fixing the cable junction boxes of size 205 x 255 x 112mm with terminals for 10 - 25 sq.mm, 4.0/3.5 core, 1100 volt cable, IP 66/69, weather proof, outdoor installation type with threaded cable glands and pole mounting brackets, etc complete all as specified and as directed. |
| 45 | M&L for making two nos hole (one at top portion of the pole and one at bottom portion of the pole) for throughing 1.5 sq.mm, 3 single core, 1100 volt cable with in steel tubular swaged pole of type SP 31/ 55 through drill or other required T&P complete all as specified and as directed. |
| 46 | M&L for 3 single core PVC insulated multi stranded copper conductorcable 1.5 sq.mm 1100 volt unarmoured for connection from loop /junction box to street lights/security lights,etc. complete all as specified and as directed. |
| 47 | M&L for triming the tree branches of girth 10 to 20cm, falling/touching the HT/LT overhead line in various area ofAF Station Borjhar with skilled labours and cutting tools and disposed the branches to a distance not exceeding 50m from starting point complete all as specified and as directed. |
| 48 | All as per Serial item No. 44 here-in-before but girth 20 to 30cm |
| 49 | M&L for painting of RCC pole, 7.5m approx above ground level with two coats of sky blue anti algal or fungal paint (second coat of paint to be carried out one day later after the first coat), over a coat of primer on plaster/cement surfaces of 2m from the ground level and two coats of white colour anti algal or fungal paint (second coat of paint to be carried out one day later afterthe first coat) over and including one coat primer on plaster/ cement surfaces of any description including preparation of old painted surfaces and steel bracket to be painted with two coats of aluminium paint (second coat of paint to be carried out one day later afterthe first coat), over and incuding one coat of red oxide primer complete all as specified and as directed. Note:- Anti Fungal/ Algal Paint to be of Apex of Asian Paint or Weather Coat of Berger or equivalent to Dulux/ Nerolac. |
| 50 | M&L for painting of steel tubular swaged poles, 7.5m approx above ground level including brackets, clamps, etc. with two coats of sky blue enamel paint (second coat of paint to be carried out one day later after the first coat) over and including a coat of red oxide primer on steel surfaces of 2m from the ground level and two coats of aluminium paint (second coat of paint to be carried out one day later after the first coat) over and including one coat of red oxide primer on steel surfaces of any description including preparation of old painted surfaces complete all as specified and as directed. |
| 51 | M&L for painting of RCC poles, 10.5m approx above ground level with two coats of sky blue anti algal or fungal paint (second coat of paint to be carried out one day later after the first coat), over and including one coat primer on plaster/ cement surfaces of 2m from the ground level and two coats of white colour anti algal or fungal paint (second coat of paint to be carried out one day later afterthe first coat) over and including one coat of primer on plaster/cement surfaces of any description including preparation of old painted surfaces and steel bracket to be painted with two coat of aluminium paint (second coat of paint to be carried out one day later afterthe first coat) over and including one coat of red oxide primer complete all as specified and as directed. Note:- Anti Fungal/ Algal Paint to be of Apex of Asian Paint or Weather Coat of Berger or equivalent to Dulux/ Nerolac. |
| 52 | M&L for painting of steel tubular swaged pole, 10.5m approx above ground level including angles, clamps, etc. with two coats of sky blue enamel paint (second coat of paint to be carried out one day later afterthe first coat), over and including one coat of red oxide primer on steel surfaces of 2m from the ground level and two coats of aluminium paint (second coat of paint to be carried out one day later after the first coat) over and including one coat of red oxide primer on steel surfaces of any description including preparation of old painted surfaces complete all as specified and as directed. |
| 53 | S&F LED street light luminaries with aesthetically designed IP-66, pressure die cast aluminium housing and toughned flat glass with wattage90 W ± 5%, 230V, 50 Hz, current < 0.414, power factor > 0.95, Ithd <10%, system efficacy 100 lumen/W, with lumen maintenance 50000 Hrs @ L70 for LED, LED should be LM 80 certified, peanut lens for batwing 135/ 85° light distribution with surge protection kV including taking out old unserviceable one complete all as specified and as directed. Make : Orient, Type LSFS-090-C or equivalent model from make Havells/Philips/Bajaj |
| 54 | M&L for hot dip galvanised (as perBS EN ISO 1461 1991) brackets of 40mm dia GI pipe, medium grade, 1.5m long for fixing LED type street light luminaires, fixing it to pole through MS Clamps, nuts, bolts & washers, etc including taking down old unserviceable one complete all as specified and as directed. Note : Any welding works related to brackets shall be carried out at the factory premises of the manufacturersMake- NTL/ Nezone/ Jindal/ Tata |
| 55 | M&L for taking down and refixing LED street/ flood light luminaries after replacement of unserviceable LED outdoor driver with new one of any type or capacity or any other specified works complete all as specified and as directed. Note::Driver will be measured and paid separately. |
| 56 | Supply only LED outdoor drivers for 120 W, 230 volt LED outdoor street light luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 57 | Supply only LED outdoor drivers for 90 W, 230 volt LED outdoor streetlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 58 | Supply only LED outdoor drivers for 60 W, 230 volt LED outdoor streetlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 59 | Supply only LED outdoor drivers for 30 W, 230 volt LED outdoor streetlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 60 | Supply only LED outdoor drivers for 160 W, 230 volt LED outdoor floodlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 61 | Supply only LED outdoor drivers for 120 W, 230 volt LED outdoor floodlight luminaires complete all as specified and as directed.Note: Manufacturer of unserviceable LED luminaires are Surya Roshni Ltd, Bajaj and Havells |
| 62 | S&F as in replacement of decorative post top lantern for 360 degree indirect light with IP-65 protection, resistant to impact and corrosion, glare free and better uniformity complete of wattage 40 watt complete with and including fixing of MS pipe of lenght 10 to 15cm with welding in existing pipe (as per site required) and connecting to electrical connection complete all as specified and as directed. |
| 63 | S&F as in replacement of HOT moulded (FRP) jucntion box for street light pole with locking arrangementt with IP-65 protection of size 140 x 140 x 95mm (inside dimension) with 2 Nos cable connector of suitable amp rating mounting on din rail complete with 01 No32 Amps MCB SP fixed over din rail and fixed on wall with 04 Nos screws of suitable size complete all as specified and as directed.Make : Sintex and/or any approved make by MES organisation. Note : Quoted rate shall be all inclusive for MCB SP and cable connector mounting of din rail. |
| 64 | S&F LED street light fitting pressure die cast aluminium housing with heat resistant toughened glass and IP-66 protection luminaries of capacity 72 watt including taking down old unserviceable one complete all as specified and as directed.Make : Crompton/Surya/Phillips/Bajaj |
| 65 | All as per Serial item No. 61 here-in-before but 120 watt. |
| 66 | S&F LED floodlight fitting pressure die cast aluminium housing with heat resistant toughened glass & IP-66 protection luminaries of capacity 50 watt including taking down old unserviceable onecomplete all as specified and as directed.Make: Crompton/Bajaj/Surya Roshni Ltd/Havells |
| 67 | S&F HOT moulded (FRP) jucntion box for street light pole with locking arrangementt with IP-65 protection of size 300 x 200 x 105mm (inside dimension) with 4 Nos aluminium bus bar strips of suitable rating upto 63 Amps capacity mounting on DMC insulators (08 Nos) with nuts and bolts complete with 01 No. 32 Amps MCB SP fixed over din rail andone bracket & nuts and bolts of suitable size to fix with pole complete all as specified and as directed.Make : Sintex and/or any approved make by MES organisation.Note : (i) Each aluminium busbar having 4 to 5 holes for connection of cable with nuts and bolts etc. (ii)Quoted rate shall be all inclusive for MCB SP and clamp with nuts & bolts, etc. |
| 68 | S&F 1100 volts PVC insulated and PVC round sheathed multicore bright annealed bare copper conductor, heavy duty, flexible cable confirming to IS-694 : 2010 of size 1 sq.mm 3 core including taking down old one complete all as specified and as directed. |
| 69 | Taking out/down unserviceable 1.1 KV, LT UG cable from existing trenches/duct/Poles of any cross sectional areaincluding disconnecting, bricks, GI pipe, etc. of any descriptions,segregation of serviceable materials viz brick cover, GI pipes, UG cables, etc. and tracing the location of fault and keeping in safe custody for re-use complete all as directed NOTE : (i) Necessary excavation and earth work shall be measured and paid for separately.(ii) Serviceable cable covers, cables and GI pipes shall be kept aside for re-use. |
| 70 | Relaying of old LT cable, XLPE insulated with aluminium conductor of size from 10 to 120sq.mm, 2/3.5/4 core, 1100 volts grade complete all as specified and as directed.Note : (i) Seviceable LT cable obatined from Serial item No. 72 above shall re-use. |
| 71 | Supply and laying LT underground cable XLPE insulated and sheathed armoured cable, 1100 volts, 10 Sq.mm, 2 core aluminium conductor in trenches/poles and connecting with all accessories lugs & glands, etc. complete all as specified and as directed. |
| 72 | All as per Serial item No. 74 here-in-before but 16Sq.mm, 4 Core cable. |
| 73 | All as per Serial item No.74 here-in-before but 25Sq.mm,3.5 Core. |
| 74 | All as per item No.16 above but of cable 50Sqmm3.5 Core complete all as specified and directed. |
| 75 | All as per Serial item No.74 here-in-before but 95Sq.mm, 3.5 Core. |
| 76 | All as per Serial item No.74 here-in-before but 120Sq.mm,3.5 Core. |
| 77 | S&F on load change over switch 4 pole, 415 volt, 50 Hz in sheet steel enclosure of capacity 63 amps, front operated, confirming to IEC-947-3 complete all as specified and as directed. |
| 78 | S&F on load change over switch 4 pole, 415 volt, 50 Hz of capacity 63 Amps, open execution front operated, confirming to IEC-947-3 complete all as specified and as directed. |
| 79 | S&F off load change over switch 4 pole, 415 volt, 50 Hz of capacity 63 Amps, in sheet metal enclosure, powder coated, wheather proof, side handle operated confirming to IS-13947 (Pt-3) 1993 complete all as specified and as directed. |
| 80 | Supply, installation, commissioning and testing of LT panel board, 3 phase 4 wire system outdoor type, factory made, supported with MS angle iron frame of size 50 x 50 x 6mm, dust and vermin proof cubical type interlocking arrangement (IP- 65 protection) fabricated with 3.15mm CRCA sheet with Anti corrosion coating and finally polyester powder coated of finite green fully compartment with providing with suitable size of coated aluminium busbar strip complete all as specified and as directed comprising with the followings:- |
| 81 | (A) INCOMING(i) MCCB 100 AMPS 4 pole, 415 Vollts, 25 kA -01 No. |
| 82 | (B) OUT GOING(i)MCCB 32 Amps, 4 pole, 415 volts, 18 kA - 01 No(ii) MCCB 16-20 Amps 4 pole, 415 volt, 18 kA -03 Nos(iii) MCB DP 63 Amps, 240 volt, 10 kA, \"B\" curve -03 Nos(iv) Digital type Amp Meter 0-400 Amps- 01 No(v) Digital type volt Meter 0 - 500 volts - 01 No(vi) Indicating lamps (RYB) - 01 Set of 3(vii) Insulated Aluminium bus bar rating 300 Amps 3 phase neutral - 01 Set(viii) Chamber for incoming & outgoing cable(ix) One spare space for MCCB |
| 83 | M&L for shifting of LT panel of any make and any size from existing location including dismantiling of existing PCC platform with electrical connection and relocated it with elecrical connection and necessary foundation with PCC (1:3:6) type C-2 (using 40mm graded stone aggregate) and replacement of unserviceable MCCBs/Change over switches, etc complete all as specified and as directed.Note :Payment of MCCBs/Change Over switch shall be paid separately. |
| 84 | S&F including connection and testing of MCCB, 4 pole, 415 volts, breaking capacity 25 kA of rating 63 Amps in replacement complete all as specified and as directed. |
| 85 | S&F includingconnection and testing MCCB, 4 pole, 415 volts, breaking capacity 25 kA of rating 100 Amps in replacement complete all as specified and as directed. |
| 86 | M&L for earthing complete with galvanised steel earth plate electrode of size 600 x 600x 6mm burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edged of the plate not less than 1.5m below normal ground level, connected to galavanised iron earth lead by means of bolt, nut, check nut and washer of galavanised iron strip of size 25 x 4mm as earthing lead as shown in Electrical Plate No 4 of SSR Part-I connected to earthing test point/LT panel all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, earth pit in PCC (1:3:6) type C-1 (using 20mm graded stone aggreate), funnel, 20mm dia GI pipe, medium grade water pipe, 50mm dia GI pipe, light grade as earth lead protection pipe, CI frame and cover, wire, copper lugs, wire mesh, charcoal or coke and common salt in alterative layer all around the earth electrode compacted thickness 15cm including excavation and earth work pit cover including disposal of surplus soil to a distance not excessding 50m complete testing on completion complete all as specified and as directed. |