Internal Electrification Of 07 ( Seven ) No Science Laboratories At Different Schools Under R.D. Kalacherra Sub-Division During The Year 2021-22. Internal Electrification
Tender Value
3.88 Lakhs
Estimated cost
Bid Submission
07 Mar 2022
0 days left
EMD
7778
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
North Tripura → Tripura
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Internal Electrification Of 07 ( Seven ) No Science Laboratories At Different Schools Under R.D. Kalacherra Sub-Division During The Year 2021-22. Internal Electrification
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvcinsulated copper conductor cable (FR) in pvc casing and capping completewith surface modular switch board with cover plate and modular switchincluding connection etc as required.Short Point :- |
| 2 | Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvcinsulated copper conductor cable (FR) in pvc casing and capping completewith surface modular switch board with cover plate and modular switchincluding connection etc as required.Medium Point :- |
| 3 | Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvcinsulated copper conductor cable (FR) in pvc casing and capping completewith surface modular switch board with cover plate and modular switchincluding connection etc as required.Long Point :- |
| 4 | Providing and fixing of 3 pin 6/10 amps plug point with modular type6/10 amps switch and socket including connection with 2x1.5 sq. mmPVC insulated Copper conductor cable (FR) on surface modular switchboard, earthing the 3rd pin etc. as required. |
| 5 | Providing and fixing of 3/6 pin 16/20 amps plug point with modular type 16/20 amps switch and socket including connection with 2x2.5 sq. mm PVC insulated Copper conductor cable(FR) on surface modular switch board, earthing the 3rd pin etc. as required. |
| 6 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick i/c accessories and providing masonry enclosure with CI cover plate Size 12\"x 12\" having locking arrangement, along with 20 mm dia (medium gauge) watering pipe including CC work etc as required:- |
| 7 | Wiring for Circuit/Sub-main wiring with the following sizes PVC insulated copper conductor cable (FR) in PVC casing capping etc. as required:- 2 X 1.5 sq mm |
| 8 | Wiring for Circuit/Sub-main wiring with the following sizes PVC insulated copper conductor cable (FR) in PVC casing capping etc. as required:- 2 X 2.5 sq mm |
| 9 | Wiring for Circuit/Sub-main wiring with the following sizes PVC insulated copper conductor cable (FR) in PVC casing capping etc. as required:- 2 X 4 sq mm |
| 10 | Extra for using salt (12 kg) and charcoal (96kg) for pipe earth electrode as required. |
| 11 | Proving and fixing / drawing of 4.06 mm dia (8 SWG) G.I. wire on surface or in existing G.I/ PVC/ Polythene pipe for loop earthing as required. |
| 12 | Supplying and drawing 4 sq. mm copper conductor wire along with other |
| 13 | Providng and laying 15mm dia(medium gauge) G.I. pipe for drawing of 4.06mm (8SWG) dia G.I./ Copper wire for earth connection from earth |
| 14 | Supplying & fixing of 1200 mm sweep white color AC ceiling fan capacitor type double ball bearing complete with 300 mm down rod,canopies,shackles, 3nos blades, including wiring the down rod with 2x1.5 sqmm PVC insulated copper conductor cable(FR) conforming to IS 374 (1979), BEE 5 star. |
| 15 | Supplying and fixing of the following switch disconnector fuse unit(main switch)made of sheet steel enclosure with all accessories including drilling holes on the board/MS clamp including necessay connection etc. as required. |
| 16 | Supplying and fixing of powder coated sheet steel enclosure on surface/recess, suitable for 240/415 volts MCB/Isolator/RCCB (SP/SPN/DP/TP/TPN/FP) complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connection as required. 4 way MCB DB (double door):- |
| 17 | Supplying & fixing of 10 KA breaking capacity, B/C curve MCB of following ratings in the existing MCB DB including connection as required:- 6 to 32 amps SP MCB:- |
| 18 | Supply & fixing of G.I. pipe (medium gauge) bracket fabricated at suitable angle for fixing of outdoor light on wall/ RCC base with necessary MS clamp, nut, bolt etc as required:- 40 mm dia |
| 19 | Supplying & fixing of electronic 5 step fan regulator in existing switch board including necessary connection etc as required:- |
| 20 | Supplying and fixing of following outdoor LED luminaries in powder coated die cast housing complete with heat resisatnt tempered glass/diffuser including necessary connection etc. as required:- |
| 21 | Supplying and fixing of following accessories for LED luminaries including necessary connection etc. as required:-20 watt LED tube light :- |
| 22 | Supplying and fixing of following accessories for LED luminaries including necessary connection etc. as required:- 12 watt LED retrofit lamp with polycarbonate body and aluminium heatsink :- |
AI Tender Summary
Tender Timeline
Feb 24, 2022
11:30 IST
Tender Published
Tender notice published.
CompletedMar 07, 2022
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedMar 07, 2022
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender