Design, Engineering, Procurement, Construction Of Abd-1 Substation And All Associated Infrastructure & Interior Works Including Operation And Maintenance Of Entire Facility For Three Years And Trail Run In Satna, Madhya Pradesh.- 1 33Kv Bay Exten, satna-Madhya Pradesh

Smart City Development Limited has published Design, Engineering, Procurement, Construction Of Abd-1 Substation And All Associated Infrastructure & Interior Works Including Operation And Maintenance Of Entire Facility For Three Years And Trail Run In Satna, Madhya Pradesh.- 1 33Kv Bay Exten. Submission Date for this Tender is 16-03-2022. Substation Tenders in satna Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

31208486
Corrigendum : Design, Engineering, Procurement, Construction Of Abd-1 Substation And All Associated Infrastructure & Interior Works Including Operation And Maintenance Of Entire Facility For Three Years And Trail Run In Satna, Madhya Pradesh.- 1 33Kv Bay Exten
Open Tender
Indian
Madhya Pradesh
satna
16-03-2022

Tender Details

Design, Engineering, Procurement, Construction Of Abd-1 Substation And All Associated Infrastructure & Interior Works Including Operation And Maintenance Of Entire Facility For Three Years And Trail Run In Satna, Madhya Pradesh.- 1 33Kv Bay Extension In The Source Substation With Feeder Protection 2 33 Kv Vcb, Outdoor Porcelain Cladtype With Complete Structure And Accessories 3 33 Kv Cts ( Out Door Oil Filled Type ) 300-150 / 5 Amps 4 33 Kv Control & Relay Panel With Scada Compatiblefor Feeder Protection ( For 1 Feeder ) 5 33 Kv Isolator 600 A. ( Turn & Twist Type ) 6 33 Kv / 110 V 3P4w Ct / Pt Ratio 400-200 / 5 Amp. Outdoor Oil Immersed Type 7 Copper Control Cable 12 Core, 2.5 Sqmm Pvc Unarmored 8 Copper Control Cable 4 Core, 2.5 Sqmm Pvc Unarmoured 9 Shield Cable From Control Pannel To Rtu Panel ( 17 Core*1.5Sqmm ) 10 Structures And Bus-Bar Arrangements 11 H- Beam 9 Meter 152 X 152 Mm 37.1 Kg / Meter = 333.9 Kg.For 33Kv Gantry Structure 12 Clamp Suitablefor 152 X 152 Mm., 37.1 Kg. / Mtr 13 Mtr. Long H-Beam ( Each Weight 3.2 Kg ) 13 Strain Plat ( Is Ms Flat 65X8x250mm ) 0.65 Kg Each 14 Acsrpanther Conductor 0.20 Sq. Inch ( 200 Sq.Mm Al.Eq. ) 15 33 Kv, 10 Kn Pincomposite Polymer Insulator, Frp Dia 33.5Mm 16 33 Kv Top Clamps 75X75x6 Mm Angle ( Each Weight 3.58 Kg ) 17 33 Kv , 45 Kn 16Mm Frp With 25Mm Per Kv Creepage Disc Polymer Long Rod Type T&C Insulator ( For 33Kv Side ) 18 33 Kv Composite Polymer Strain Set With Hard Ware Suitable For Panther Conductor ( For 33Kv Side ) 19 33 Kv , 45 Kn 16Mm Frp With 25Mm Per Kv Creepage Disc Polymer Long Rod Type T&C Insulator ( For 11Kv Side ) 20 Stone Block / Pre Cast Block For Base Pedding 450X450x75mm 21 Concreting ( 1:3:6 ) Of H-Beam @ 0.65Cmt.Per Pole Including Muffing 22 Other Miscellaneous Items 23 Concreting ( 1:3:6 ) Of Vcb Structures 3.5 Cmt Per Vcb & Pole @0.45 Cmt. Per Structure 24 Concreting ( 1:3:6 ) Of Isolator Support Structure @ 0.1 Cmt. Per Structure 25 R.S.Joist 175X85mm-9 Mtr. Long For Yard Lightening 26 Pvc Cable 2 Corearmoured 2.5 Sqmm Aluminium Conductor 27 Pvc Cable 4 Corearmoured 16 Sqmm Aluminium Conductor 28 M S Bolt With Nut16x250 Mm 29 M S Bolt With Nut 16X200 Mm 30 M S Bolt With Nut 16X165 Mm 31 M S Bolt With Nut16x140 Mm 32 M S Bolt With Nut16x90 Mm 33 M S Bolt With Nut16x40 Mm 34 Red-Oxide Paint 35 Aluminum Paint 36 Danger Board Enameled 33 Kv 37 For 33Kv Underground Cable From Abd-1 Substation To Each Project Area ( Aac & Lake Nectar ) 38 33 Kv3x300 Sq Mm Xlpe Cable With Inner Side Shall Be Waterproofing With Insulation Of Individual Core And Outer Side Of Cable Shall Be Stretch Resistance. 39 Termination Kit For 33 Kv Grade Xlpe Cable For 3 Core 300 Sq Mm ( 3 X 240-400 Sq. Mm. ) 40 Heat Shrinkable Cable ( Straight Through ) Jointing Kit With Lugs For 33 Kv Grade Xlpe Cable For 3 Core 300 Sq Mm 41 Supplying And Installing Double Wall Corrugated Pipes ( Dwc ) Of Hdpe ( Is 14930 Part Ii -Marked ) For Cable Laid Underground With Necessary Material And At Required Depth Upto 90Cm. Below Road / Ground Surface, Including Excavation, Back Filling With Excavated Material, Ramming And Making The Surface Good.210.00Mm Outside Dia. 42 Supply Of Approved Type Cable Cover Flag Stone 200Mm Width & 32Mm To 50Mm Thick Of Required Length Inclusive Of Transport As Required. 43 Laying Of One Number 3 Core H.T Armoured / Unarmoured Power Cable 33Kv Grade Of Size Not Exceeding 300 Sq. Mm In The Existing Rcc / Hume / Stoneware / G.I. Pipe / Surface In Existing Trench As Required. 44 33 / 11 Kv Transformers 45 33 / 11 Kv Power Transformer , Oftc Type5000 Kva Loss ( 4 Kw + 23 Kw ) , With Off Load Tap Changer, 3 Ph, 50 Hz, Onan, Cu Wound, Outdoor Conventional Type Power Transformer Along With Transformer Oil, Buchholtz Relay, Breather, Oti & Wti, Marshalling Box, Conservator Tank, Oil Level Indicator, Valves, 2 Sets Of 50X8 Mm Gs Neutral Earthing Strips { ( With Braided Conductor On Bushing End ) , Isolating Link, Isolation With Insulators } , Vent Explosion Plug, Control Wiring Between Sensing Equipment And Marshalling Box, Cable Supporting Tray On The Body Of Transformer, Transformer Wheels, Cable Junction Box Lv / Hv Bushing Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Work. 46 Ptr Foundation 47 Scada Compatible Winding Temp. Indicator 48 Scada Compatible Oil Temp. Indicator 49 33 Kvla Polymer Type Gapless / Metal Oxide Substation Type 50 11 Kvla Polymer Type Gapless / Metal Oxide 9 Kv , 10 Kasubstation Type 51 Remote Terminal Unit ( Rtu ) Including Software For 2 No. Power Transformer 52 11 Kv1500 Kvar Auto Switch Indoor Capacitor Bank Including Associated Equipments Such As 11 Kv Vacuum Circuit Breaker, Control Panel, 11 Kv Outdoor Current Transformer With Adequate Metering & Protection Class Of Service, Bus & Equipment Isolators With Earth Switch, Matching Rvt, Suitable Gapless Lightening Arrestors, Necessary Cables For Successful Commissioning Complete 53 For 33Kv Underground Cable From Abd-1 Substation To Each Project Area ( Aac & Lake Nectar ) 54 33 Kv3x300 Sq Mm Xlpe Cable With Inner Side Shall Be Waterproofing With Insulation Of Individual Core And Outer Side Of Cable Shall Be Stretch Resistance. 55 Termination Kit For 33 Kv Grade Xlpe Cable For 3 Core 300 Sq Mm ( 3 X 240-400 Sq. Mm. ) 56 Heat Shrinkable Cable ( Straight Through ) Jointing Kit With Lugs For 33 Kv Grade Xlpe Cable For 3 Core 300 Sq Mm 57 Supplying And Installing Double Wall Corrugated Pipes ( Dwc ) Of Hdpe ( Is 14930 Part Ii -Marked ) For Cable Laid Underground With Necessary Material And At Required Depth Upto 90Cm. Below Road / Ground Surface, Including Excavation, Back Filling With Excavated Material, Ramming And Making The Surface Good.210.00Mm Outside Dia. 58 Supply Of Approved Type Cable Cover Flag Stone 200Mm Width & 32Mm To 50Mm Thick Of Required Length Inclusive Of Transport As Required. 59 Laying Of One Number 3 Core H.T Armoured / Unarmoured Power Cable 33Kv Grade Of Size Not Exceeding 300 Sq. Mm In The Existing Rcc / Hume / Stoneware / G.I. Pipe / Surface In Existing Trench As Required. 60 For 11Kv Underground Cable From Abd-1 Substation To Each Project Area ( Indoor Sports Complex ) 61 3 Core Xlpe Cable 11 Kv Grade, High-Tension Xlpe Cable, 3 Core 300 Sq.Mm Armoured Al. Conductorsupply Of Approved High-Tension Xlpe Cable ( Conforming Is-7098 / Ii / 85 ) As Per Isi Standard 3 Core Armoured With Alu. Solid / Stranded Conductor Isi Marked As Required 62 Termination Kit 11 Kv Xlpe Cable O.D. Termination, 3 X 240-400 Sq. Mm 63 Heat Shrinkable Jointing Kit 11 Kv Xlpe Cable Straight Joint, 3 X 240-300 Sq. Mm. 64 Supply Of Approved Type Cable Cover Flag Stone 200Mm Width & 32Mm To 50Mm Thick Of Required Length Inclusive Of Transport As Required. 65 Laying Of One Number 3 Core H.T Armoured / Unarmoured Power Cable Of Grade Exceeding 1.1Kv But Not Exceeding 11Kv Of Size Not Exceeding 300 Sq. Mm In The Existing Rcc / Hume / Stoneware / G.I. Pipe / Surface In Existing Trench As Required. 66 For 415V Underground Cable From Project Lake Nectar To Project Synthesis. 67 Supply Of Xlpe Insulated Power Cable ( Conforming Is-7098 Part-I ) 1100 Volt Grade, 1 Core / 2 Core / 3½ Core / 4 Core Isi Marked With Alu. Stranded / Solid Conductor4cx300 Armoured 68 1.1 Kv Xlpe / Hd Cable End Termination ( 185-300 Sq. Mm. 3½ / 4 Core ) 69 1.1 Kv Xlpe / Hd Cable Straight Through Jointing Kit, 300-400 Sq. Mm. 3½ / 4Core 70 Supply Of Approved Type Cable Cover Flag Stone 200Mm Width & 32Mm To 50Mm Thick Of Required Length Inclusive Of Transport As Required. 71 Laying Of One Number 3 Core H.T Armoured / Unarmoured Power Cable Of Grade Exceeding 1.1Kv But Not Exceeding 11Kv Of Size Not Exceeding 300 Sq. Mm In The Existing Rcc / Hume / Stoneware / G.I. Pipe / Surface In Existing Trench As Required. 72 Dp Structures For Receiving 33 Kv Incoming At 33Kv Substation 73 H-Beams 152 X 152 Mm., 37.1 Kg. / Mtr.-11 Mtr. Long = 408.1 Kg 74 Dc.Cross Arms 8`Centre To Centre 100X50x6 Mm Channel ( Each Weight-56.32 Kg ) 75 Clamp Suitablefor 152 X 152 Mm., 37.1 Kg. / Mtr 13 Mtr. Long H-Beam ( Each Weight 3.2 Kg ) 76 Horizonatal & Cross Bracing 8 Centre ( Wt Of Eachx-Bracing-64.29 Kg 77 Back Clamp Suitable For H-Beam ( Ms Flat 65X8 Mm ) -Each Weight 1.92 Kg 78 33 Kv ( 45Kn ) Composite Polymer Disc Insulators 79 33 Kv Strain Hardware ( T&C Type ) Fittings 80 33 Kv, 10 Kn Pincomposite Polymer Insulator, Frp Dia 33.5Mm 81 Stay Set 20 Mm 82 Staywire 7 / 4.00 Mm. ( 7 / 8 Swg ) 83 Clamp Suitablefor 152 X 152 Mm., 37.1 Kg. / Mtr H-Beam ( Each Weight 3.2 Kg ) 84 Stone Block / Pre Cast Block For Base Pedding 450X450x75mm 85 Concreting ( 1:3:6 ) Of H-Beam @ 0.70 Cmt.Per Pole Including Base Pedding 86 Concreting Of Stay ( 20 Mm / 25 Mm ) @ 0.3 Cmt. Per Stay 87 Earthing Coil Of 115 Turns Of 50 Mm.Dia And 2.5 Mtr Lead Of 4.0 Mm G.I Wire 88 33Kv Switchgear:33 Kvair Insulated Switchgearindoor Type, Extensible Type & Scada Compatible - As Per Iec 62271-200 With Following Features, Compartmentalized Modular Typesuitable For 36Kv 1250A Copper Busbar With Short Circuit Rating Of 31.5Ka For 3 Sec. 89 Incomer:1. 36Kv 1250A Copper Busbar With Short Circuit Rating Of 31.5Ka For 3 Secwith Motor Operated Spring Charging Mechanism, Control Circuit Suitable For Local And Remote Operation.The Breakers Shall Be Trip Free And Shall Have Anti Pumping Feature.2.The 33Kv Ht Panel Shall Be Internally Arc Tested For 31.5Ka For 1 Sec Duration A-Flr.Necessary Type Test Report For Internal Arc For 1 Sec Shall Be Furnished By The Manufacturer. 3.The Vacuum Circuit Breaker Shall Be Rated 1250A For Short Circuit Rating Of 31.5Ka For 3 Sec. The Spring Charging Of The Breaker Shall Be With Integral Spring Charging Handle. 4.The Vacuum Circuit Shall Be Completely Enclosed Vacuum Interruptors In Housing Of Polymer Material . 5.The Inspection Window On The Vcb Door Shall Be Made Of Toughened Glass Only Of Suiltable Strength To Withstand The Internal Arc. 6.The Pt Fuses Shall Be Completely Enclosed In Epoxy Housing To Prevent Any Flash Over Occurance. 7.Cable Termination Suitable For Current Ratings 1Rx3cx300 Sqmm, . Theearthing Terminal Busbar Of Size 25X5 Mm& Ct Ratings Of 300-150 / 5-5A With Cl-1.0 5P10 20Va With Multifunction Meter For Metering With Line Pt 33Kv / V3 / 110V / 3 Cl-1.0 / Ps 20Va.8.The Ais Shall Have Numerical Relay Scada Compalitble With Iec 61850 Communication Facility Suitable For Incomer Protection / Trip Ckt Supervision / Antipumping / Lock Out Relay & Accesories For Breaker On / Off Button / Mimic Diagram / Electronic Hooter / Tnc Switch / Dc&Ac On / Off, Led Lamps For Indication On Breaker Status / Live Status / Necessary Panel Status &Thermostat Based Anti Condensation Heater.9. The Pannel Shall Be Internal Arc Tested 31.5 Ka For 1 Sec. Duration A-Flr Provided With Gas Duct To Remove The Hot Gasses / Plasma Formedduring Internal Arc - Out Off The Switchgear Room.10. The Master Relay Should Be Both Electrical & Mechanical Reset Type. 90 Outgoing:1. 36Kv 1250A Copper Busbar With Short Circuit Rating Of 31.5Ka For 3 Secwith Motor Operated Spring Charging Mechanism, Control Circuit Suitable For Local And Remote Operation.The Breakers Shall Be Trip Free And Shall Have Anti Pumping Feature.2.The 33Kv Ht Panel Shall Be Internally Arc Tested For 31.5Ka For 1 Sec Duration A-Flr.Necessary Type Test Report For Internal Arc For 1 Sec Shall Be Furnished By The Manufacturer. 3.The Vacuum Circuit Breaker Shall Be Rated 1250A For Short Circuit Rating Of 31.5Ka For 3 Sec. The Spring Charging Of The Breaker Shall Be With Integral Spring Charging Handle. 4.The Vacuum Circuit Shall Be Completely Enclosed Vacuum Interruptors In Housing Of Polymer Material . 5.The Inspection Window On The Vcb Door Shall Be Made Of Toughened Glass Only Of Suiltable Strength To Withstand The Internal Arc. 6.The Pt Fuses Shall Be Completely Enclosed In Epoxy Housing To Prevent Any Flash Over Occurance. 7.Cable Termination Suitable For Current Ratings 1Rx3cx300 Sqmm, . Theearthing Terminal Busbar Of Size 25X5 Mm& Ct Ratings Of 300-150 / 5-5A With Cl-1.0 5P10 20Va With Multifunction Meter For Metering With Line Pt 33Kv / V3 / 110V / 3 Cl-1.0 / Ps 20Va.8.The Ais Shall Have Numerical Relay Scada Compalitble With Iec 61850 Communication Facility Suitable For Incomer Protection / Trip Ckt Supervision / Antipumping / Lock Out Relay & Accesories For Breaker On / Off Button / Mimic Diagram / Electronic Hooter / Tnc Switch / Dc&Ac On / Off, Led Lamps For Indication On Breaker Status / Live Status / Necessary Panel Status &Thermostat Based Anti Condensation Heater.9. The Pannel Shall Be Internal Arc Tested 31.5 Ka For 1 Sec. Duration A-Flr Provided With Gas Duct To Remove The Hot Gasses / Plasma Formedduring Internal Arc - Out Off The Switchgear Room.10. The Master Relay Should Be Both Electrical & Mechanical Reset Type. 91 Buscoupler:1.The Aisdesign Shall Be Compartmentalized Modular Typesuitable For 36Kv 1250A Copper Busbar With Short Circuit Rating Of 31.5Ka For 3 Secwith Motor Operated Spring Charging Mechanism, Control Circuit Suitable For Local And Remote Operation.The Breakers Shall Be Trip Free And Shall Have Anti Pumping Feature.2.The 33Kv Ht Panel Shall Be Internally Arc Tested For 31.5Ka For 1 Sec Duration A-Flr.Necessary Type Test Report For Internal Arc For 1 Sec Shall Be Furnished By The Manufacturer. 3.The Vacuum Circuit Breaker Shall Be Rated 1250A For Short Circuit Rating Of 31.5Ka For 3 Sec. The Spring Charging Of The Breaker Shall Be With Integral Spring Charging Handle.4.The Vacuum Circuit Shall Be Completely Enclosed Vacuum Interruptors In Housing Of Polymer Material .5.The Inspection Window On The Vcb Door Shall Be Made Of Toughened Glass Only Of Suiltable Strength To Withstand The Internal Arc. 6.The Pt Fuses Shall Be Completely Enclosed In Epoxy Housing To Prevent Any Flash Over Occurance.7.The Cable Termination Suitable For Current Ratings 1Rx3cx300 Sqmm Theearthing Terminal Busbar Of Size 25X5 Mm& Ct Ratings Of 300-150 / 5-5A With Cl-1.0 5P10 20Va With Multifunction Meter For Metering 8.The Ais Shall Have Numerical Relay Scada Compalitble With Iec 61850 Communication Facility Suitable For Ibuscouplerprotection / Trip Ckt Supervision / Antipumping / Lock Out Relay & Accesories For Breaker On / Off Button / Mimic Diagram / Electronic Hooter / Tnc Switch / Dc&Ac On / Off, Led Lamps For Indication On Breaker Status / Live Status / Necessary Panel Status &Thermostat Based Anti Condensation Heater.9. The Pannel Shall Be Internal Arc Tested 31.5 Ka For 1 Sec. Duration A-Flr Provided With Gas Duct To Remove The Hot Gasses / Plasma Formedduring Internal Arc - Out Off The Switchgear Room.10. The Master Relay Should Be Both Electrical & Mechanical Reset Type. 92 11Kv Switchgear 93 11 Kv Air Insulated Switchgearindoor Type For Power Transformeroutgoing Extensible Type & Scada Compatible As Per Iec 62271-200 With Following Featurs. 1.The Aisdesign Shall Be Compartmentalized Modular Typesuitable For 12Kv 1250A Copper Busbar With Short Circuit Rating Of 31.5Ka For 3 Secwith Motor Operated Spring Charging Mechanism, Control Circuit Suitable For Local And Remote Operation.The Breakers Shall Be Trip Free And Shall Have Anti Pumping Feature.2.The 12Kv Ht Panel Shall Be Internally Arc Tested For 31.5Ka For 1 Sec Duration A-Flr.Necessary Type Test Report For Internal Arc For 1 Sec Shall Be Furnished By The Manufacturer. 3.The Vacuum Circuit Breaker Shall Be Rated 1250A For Short Circuit Rating Of 31.5Ka For 3 Sec. The Spring Charging Of The Breaker Shall Be With Integral Spring Charging Handle.4.The Vacuum Circuit Shall Be Completely Enclosed Vacuum Interruptors In Housing Of Polymer Material . 5.The Inspection Window On The Vcb Door Shall Be Made Of Toughened Glass Only Of Suiltable Strength To Withstand The Internal Arc. 6.The Pt Fuses Shall Be Completely Enclosed In Epoxy Housing To Prevent Any Flash Over Occurance.7. Theearthing Terminal Busbar Of Size 25X5 Mm& Ct Ratings Of 600-300 / 5-5A With Cl-1.0 5P10 20Va With Multifunction Meter For Metering .8.The Ais Shall Have Numerical Relay Scada Compalitble With Iec 61850 Communication Facility Suitable For Incomer Protection / Trip Ckt Supervision / Antipumping / Lock Out Relay & Accesories For Breaker On / Off Button / Mimic Diagram / Electronic Hooter / Tnc Switch / Dc&Ac On / Off, Led Lamps For Indication On Breaker Status / Live Status / Necessary Panel Status &Thermostat Based Anti Condensation Heater.9. The Master Relay Should Be Both Electrical & Mechanical Reset Type. 94 11 Kv Air Insulated Switchgear Indoor Typeforfeeder Outgoingextensible Type & Scada Compatible, As Per Iec 62271-200 With Following Features . 1.The Aisdesign Shall Be Compartmentalized Modular Typesuitable For 12Kv 1250A Copper Busbar With Short Circuit Rating Of 31.5Ka For 3 Secwith Motor Operated Spring Charging Mechanism, Control Circuit Suitable For Local And Remote Operation.The Breakers Shall Be Trip Free And Shall Have Anti Pumping Feature.2.The 12Kv Ht Panel Shall Be Internally Arc Tested For 31.5Ka For 1 Sec Duration A-Flr.Necessary Type Test Report For Internal Arc For 1 Sec Shall Be Furnished By The Manufacturer. 3.The Vacuum Circuit Breaker Shall Be Rated 1250A For Short Circuit Rating Of 31.5Ka For 3 Sec. The Spring Charging Of The Breaker Shall Be With Integral Spring Charging Handle.4.The Vacuum Circuit Shall Be Completely Enclosed Vacuum Interruptors In Housing Of Polymer Material .5.The Inspection Window On The Vcb Door Shall Be Made Of Toughened Glass Only Of Suiltable Strength To Withstand The Internal Arc. 6.The Pt Fuses Shall Be Completely Enclosed In Epoxy Housing To Prevent Any Flash Over Occurance.7. Theearthing Terminal Busbar Of Size 25X5 Mm& Ct Ratings Of 200-100 / 5-5A With Cl-1.0 5P10 20Va With Multifunction Meter For Metering .8.The Ais Shall Have Numerical Relay Scada Compalitble With Iec 61850 Communication Facility Suitable For Outgoin Feederprotection / Trip Ckt Supervision / Antipumping / Lock Out Relay & Accesories For Breaker On / Off Button / Mimic Diagram / Electronic Hooter / Tnc Switch / Dc&Ac On / Off, Led Lamps For Indication On Breaker Status / Live Status / Necessary Panel Status &Thermostat Based Anti Condensation Heater.9. The Master Relay Should Be Both Electrical & Mechanical Reset Type. 95 11 Kv Air Insulated Switchgear Indoor Typefor Bus Coupler Outgoing Extensible Type & Scada Compatible, As Per Iec 62271-200 With Following Features.1.The Aisdesign Shall Be Compartmentalized Modular Typesuitable For 12Kv 1250A Copper Busbar With Short Circuit Rating Of 31.5Ka For 3 Secwith Motor Operated Spring Charging Mechanism, Control Circuit Suitable For Local And Remote Operation.The Breakers Shall Be Trip Free And Shall Have Anti Pumping Feature.2.The 12Kv Ht Panel Shall Be Internally Arc Tested For 31.5Ka For 1 Sec Duration A-Flr.Necessary Type Test Report For Internal Arc For 1 Sec Shall Be Furnished By The Manufacturer. 3.The Vacuum Circuit Breaker Shall Be Rated 1250A For Short Circuit Rating Of 31.5Ka For 3 Sec. The Spring Charging Of The Breaker Shall Be With Integral Spring Charging Handle.4.The Vacuum Circuit Shall Be Completely Enclosed Vacuum Interruptors In Housing Of Polymer Material . 5.The Inspection Window On The Vcb Door Shall Be Made Of Toughened Glass Only Of Suiltable Strength To Withstand The Internal Arc. 6.The Pt Fuses Shall Be Completed Enclosed In Epoxy Housing To Prevent Any Flash Over Occurance. 7. Theearthing Terminal Busbar Of Size 25X5 Mm& Ct Ratings Of 600-300 / 5-5A With Cl-1.0 5P10 20Va With Multifunction Meter For Metering .8.The Ais Shall Have Numerical Relay Scada Compalitble With Iec 61850 Communication Facility Suitable For Buscoupler Protection / Trip Ckt Supervision / Antipumping / Lock Out Relay & Accesories For Breaker On / Off Button / Mimic Diagram / Electronic Hooter / Tnc Switch / Dc&Ac On / Off, Led Lamps For Indication On Breaker Status / Live Status / Necessary Panel Status &Thermostat Based Anti Condensation Heater.9. The Master Relay Should Be Both Electrical & Mechanical Reset Type. 96 11Kv Bus Pt Panel With Necessary Bus Pt Formetering & Protection 11Kv / V3 / 110V / V3 / 110V / 3 Cl-1.0 Cl-Ps 50 Va .Epoxy Enclosed Pt Fuses Shall Be Mounted On Bus Pt. The Fuses Shall Have Fuse Failure Protection / Necessary Led Lamps For Indication To Be Provided.Numercial Relay Scada Compatible For Uv / Ov Protection With Iec 61850 Protection To Be Provided 97 Transformer, 33 / 0.4 Kv 3 Phase 98 Supplying, Installing, Testing And Commissioning Of 33 / 0.4 Kv 3 Phase 50 Cycle Oil Immersed, Naturally Cooled, Outdoor Type Transformer Connected Delta On H.T. Side And Star On L.T. Side, Hand Operated Off Load Tap Changer Switch Above 100 Kva, Rating And Diagram Plate, Two Earthing Terminal, Lifting Lugs, Oil Level Gauge, Drain Valve With Plug, Temperature Not Exceeding 50ºc On Load, Oil Conservator With Drain Plug, Oil Filling Hole With Plug, Dehydrating Silica Gel Breather On Eye Level, Four Unidirectional Roller, Arcing Horns, Explosion Vent, Terminal Arrangement Bushing On H.V. Side And Cable Box On Lv Side, First Filling Of Oil Upto Desired Level And Transformer Installing On Existing Structure With All Required Materials Arrangement As Required Isi Marked & As Per Is Specification.Energy Efficiency Level -3, 200 Kva 99 Lighting System 100 Supply And Fixing Of Surface Mounting Type Led Light Fixture, Led Of 1 To 3 Watt Each Assembled On Single Mcpcb, Having Color Temp Upto 6500K & Having 50000 Burning Hrs. Life With Minimum @ L 70, System Lumen Output Should Be Minimum With Efficacy>100 Lm / Watt. Led Driver, Pf> 0.95, Thd < 20% & Surge Protection 4Kv. The Colour Rendering Index Of Led Light Should Be More Than 70. Housing Made Of Crca Powder Coated Frame With Glare Free Diffused Polycarbonate Cover. Submission Lm 79-08 / Is16106 ( 2012 ) , Iec60598, Iec61347i / C Connection Wire, Testing Etc. To Complete The Job.Led Luminiare 2 X 2, 45Watt, Color Temp 3000- 6500K As Required. 101 Supply And Fixing Led Tube Rod Comprising Of Led Tube With Non-Integral / Integral Driver, Upto 6500K Color Temp Having 40000 Burning Hrs Life With Minimum @ L 70, System Lumen Output Should Be Minimum With System Efficacy> 100 Lm / Watt. Led Driver Pf> 0.95 & Thd < 20%. The Colour Rendering Index Of Led Light Should Be More Than 70. Submission Lm 79-08 / Is16106 ( 2012 ) , Iec60598, Iec61347i / C Connection Wire, Testing Etc. To Complete The Job. Tube Light Led 1 X 20 / 22Watt, Integral I / C Batten Aluminium Body, Pc Diffuser. 102 Supply And Fixing Street Light With High Power Led Of 3 To 6 Watt Each On Existing Bracket Assembled On Single Mcpcb And Additional Unique Peanut Lens On Each Led, System Lumens Output With Efficacy>120 Lm / Watt. Luminiare Having Color Temp Upto 6500K & 50000 Hrs. Burning Life With Minimum @ L 70, The Colour Rendering Index Of Led Light Should Be More Than 70. Luminiare Comprises Of Driver, Pf> 0.95 & Surge Protection 10Kv. Housing Made Of Pressure Die Cast Aluminium With Heat Resistant Flat Glass, Ip65 Protection. Submission Lm 79- 08 / Is16106 ( 2012 ) , Iec60598, Iec61347 I / C Connection Wire, Testing Etc. To Complete The Job. 120Watt, Color Temp 3000-6500K As Required 103 Supply And Fixing Street Light With High Power Led Of 3 To 6 Watt Each On Existing Bracket Assembled On Single Mcpcb And Additional Unique Peanut Lens On Each Led, System Lumens Output With Efficacy>120 Lm / Watt. Luminiare Having Color Temp Upto 6500K & 50000 Hrs. Burning Life With Minimum @ L 70, The Colour Rendering Index Of Led Light Should Be More Than 70. Luminiare Comprises Of Driver, Pf> 0.95 & Surge Protection 10Kv. Housing Made Of Pressure Die Cast Aluminium With Heat Resistant Flat Glass, Ip65 Protection. Submission Lm 79- 08 / Is16106 ( 2012 ) , Iec60598, Iec61347 I / C Connection Wire, Testing Etc. To Complete The Job. 40Watt To 48Watt, Color Temp 3000-6500K As Required. 104 Point Wiring :Point Wiring ( Excluding Metallic Switch Box & Sheet But Including Switches, Sockets, Lamp Holders / Ceiling Roses Etc ) With 1.5Sq. Mm. Pvc Insulated Cable Frls With Copper Multi Strand Conductor Isi Marked In Surface Rigid P.V.C. Conduit ( Mms ) Isi Marked Of Suitable Size And 1.5Sq. Mm. Pvc Frls Insulated Copper Earth Continuity Conductor Of Green Colour Inside Conduit Etc. As Required As Per Specification For 105 Light Point / Fan Points. 106 Primary Short Point 107 Primary Medium Point 108 Primary Long Point 109 ( Light Point / Fan Points ) Looping Point 110 Secondary Short Point 111 Secondary Medium Point 112 Secondary Long Point 113 3 Pin 6 Amp Socket Outlet On Separate Board 114 Short Point 115 Medium Point 116 Long Point 117 Supplying And Fixing 25Mm Pvc Conduit Isi Marked Frls Along With Accessories On Surface Etc. As Required 118 Supplying And Fixing Factory Fabricated Hot Dip Galvanized Switch Box For Normal Flush Type Accessories Of Minimum 1.2 Mm Thickness For Up To 200Mmx250mm Size Boxes And 1.6Mm Minimum Thickness For Higher Size Boxes, Earth Terminal Stud With Nut And Washer, Including 3 Mm Thick Synthetic Phenolic Resin Bonded Laminated Sheet Conforming To Grade P-I Of Is:2036- 1974 On Surface / Concealed Including All Necessary Accessories, Painting Etc. As Required As Per Specification:Ms Box 200 Mm X 150 Mm X 60 Mm 119 Supply And Fixing Of 9W, Rechargeable Inverter Led Bulb Rechargeable Inverter Led Bulb, Reduces To 40-50% ( Emergency Application ) With Lithium Ion Battery 2600Mah, Backup Upto 5 Hrs. Having Color Temp Upto 6500K, Ip- 20 Rating, Thd ( Total Harmonic Distortion ) <20% 120 415V Switchgear 121 Pcc Panel 122 Supply, Fixing, Testing & Commissioning Wall / Floor Mounted Lt Panel Primer Coated With Powder Coated Paint & Provided With Required Gasket For Dust / Vermin Proof With Degree Of Protection Ip42 Suitable For 415Volt 3 Phase, 50 Hz, 4 Wire System Fabricated Out Of Crca Sheet Upto 2 Mm Thick ( 1.6 Mm For Doors ) Duly Compartmentalized For Incomer, Bus Section, Outgoings, Cable Alleys & Ct, Pt Ampere Metre, Volt Metre, Selector Switches, Frequency Metre, Phase Indicating Lamp, Energy Metre Complete Including Cost Of Busbar Supports, Detachable Cable Gland Plates, 2 Earthing Terminals, Internal Wiring & Fixing Of Separately Supplied Mcbs, Mccbs, Acb, Panel Mounted Changeover Switch / Sfus, Etc. As Required But Excluding Cost Of Busbar Strips, Ampere Metre, Volt Metre, Selector Switch As Per Approved Design 123 400A Mccb ( Incomer ) - Mccb 36Ka Current Rating - 400 Amps 4 Pole Μ-Processor Release, Over Load 40% -100% X In. & Short Circuit 1.5 - 8 X Ir. Adjustable 124 Outgoing: Mccb 25Ka Current Rating - 40 & 100 Amps 4 Pole & Micro-Processor Release, Over Load 40% -100% X In. & Short Circuit 1.5 - 8 X Ir. Adjustable 125 Mccb 25Ka Current Rating - 160 Amps 4 Pole & Micro-Processor Release, Over Load 40% -100% X In. & Short Circuit 1.5 - 8 X Ir. Adjustable 126 Led Lamp Indicator 127 Digital Ampere Metre With Cts With Selector Switch 128 Digital Volt Metre With Selector Switch & Hrc Fuse 129 Aluminium Bus Bar Strips With Pvc Sleeves 130 Supplying And Fixing Of Ct 1A / 5A As Per Site Selectable Busbar Dimension Of Approved Make In Existing Main Panel For Power Factor Panel Including Connections Etc. As Required As Per Specification. 131 415V Capacitor Panel 132 Supply, Fixing, Testing & Commissioning Wall / Floor Mounted Lt Panel Primer Coated With Powder Coated Paint & Provided With Required Gasket For Dust / Vermin Proof With Degree Of Protection Ip42 Suitable For 415Volt 3 Phase, 50 Hz, 4 Wire System Fabricated Out Of Crca Sheet Upto 2 Mm Thick ( 1.6 Mm For Doors ) Duly Compartmentalized For Incomer, Bus Section, Outgoings, Cable Alleys & Ct, Pt Ampere Metre, Volt Metre, Selector Switches, Frequency Metre, Phase Indicating Lamp, Energy Metre Complete Including Cost Of Busbar Supports, Detachable Cable Gland Plates, 2 Earthing Terminals, Internal Wiring & Fixing Of Separately Supplied Mcbs, Mccbs, Acb, Panel Mounted Changeover Switch / Sfus, Etc. As Required But Excluding Cost Of Busbar Strips, Ampere Metre, Volt Metre, Selector Switch As Per Approved Design 133 Supplying And Fixing Of Capacitor Duty Contactor Of Approved Make In Existing Power Factor / Lt Panel Including Connections Etc.As Required As Per Specification. 134 For 25 Kvar 440V, 3Ph, 50Hz, Aux Contact-1No 135 For 15 Kvar 440V, 3Ph, 50Hz, Aux Contact-1No 136 For 5 Kvar 440V, 3Ph, 50Hz, Aux Contact-1No 137 Supplying And Fixing Of Apfc Relay 1A / 5 A Site Selectable, Measurement Of Individual Current And Voltage Harmonic ( Thd ) , Capacitor Failure Indication, Inbuilt Temperature Sensor Of Approved Make In Existing Power Factor Panel Including Connections Etc. As Required As Per Specification As Mentioned Below 138 8 Step Apfc Relay ( 144 X144mm ) 139 Wall Mounted Db 140 Supplying Of Approved Make Tpn Mcb Db Metal Double Door Ip 43 Protection With Provision For Fp Mcb / Isolator / Rccb / Rcbo As Incomer And Sp Mcbs As Outgoing Inclusive Of Busbar, Neutral Bar, Earth Bar, Connection Copper Wire Not Less Than 16 Sq.Mm & Two Earth Terminals Etc. Complete As Per Is:13032 ( Exclusive Of Mcb & Isolator ) :6 Way ( 8+18 ) 141 Supplying And Installing Of Rcbos ( Residual Current Circuit Breaker With Overload And Short Circuit Protection ) Isi Marked Complete As Per I.S. Standard Conforming To Iec:61009-1 & Is:12640-2, 240 / 415V 50 Hz With 10 Ka Short Circuit Withstand Capacity For Earth Leakage, Overload & Short Circuit Protection Including Connection In Existing Enclosure In Approved Manner As Per Specification.4 Pole 40A, 30Ma 142 Mcb Sp 6Amp To 32Amp 10Ka Rating 143 Acdb 144 Acdb415 V, Along Withthree Phase-Neutral Voltmeter, Three Phase Ammeter Andselector Switches, 1No.200 Amps Tpn Switch Fuse Unit As Incomer, 1No. 63 Amp.Tpn Mccb Switches As Outgoing Feeders & 2No. 32 Amp. Mccb As Outgoingfor Yard And Control Room Lightining And 6 No. 16 No. Mccb For Control Panels, Each Incoming & Outgoing Shall Have Indicating Lamp. Including 20% Spare 145 Earthing System 146 Earthing With G.I. Earth Pipe 4.5 Metre Long And 40 Mm Dia With Masonry Encloser In Cement Mortar, Cover Plate Having Locking Arrangement On The Top Etc. ( But Without Charcoal Or Coke And Salt ) Complete As Required 147 Earthing With Copper Earth Plate 600Mm X 600Mm X 3Mm Thick Including Accessories And Providing Masonry Encloser In Cement Mortar, Cover Plate Having Locking Arrangement On The Top And G.I. Watering Pipe 20Mm Dia 2.7 Metre Long Etc. ( But Without Charcoal Or Coke And Salt ) Complete As Required 148 Supply And Layingg.I. Wire At 0.5 Metre Below Ground Level As Conductor Earth Electrode Including Jointing Etc. As Required. 149 4.0Mm ( 8 Swg ) Dia. 150 4.87Mm 6 Swg G.I. 151 25Mm X 5Mm G.I. Strip 152 25Mm X 6Mm G.I. Strip 153 50Mm X 6Mm G.I. Strip 154 Lightning Protection System 155 Providing And Fixing Of Lightning Conductor Finial Made Of 18Mm Dia 500Mm Long Bright Nickel Plated Copper Tube Tapered Having Single Prong At Top With Bright Nickel Plated Brass Base M10 For Connection And Intersection Of Flat Or Round Conductor Including Holes, Clamp Complete As Required. 156 Fixing Of Lightning Conductor Finial Made Of 25Mm Dia 300Mm Long Copper Tube / G.I. Tube Having Single Prong At Top With Base Plate Etc. Complete As Required. 157 Riveting / Sweating And Soldering Of Copper / G.I. Tape ( With Another Copper / G.I. Tape, Base Of Finial Or Anyother Metallic Object ) As Required 158 Providing And Fixing Copper Tape 20Mm X 3Mm Thick On Parapet And Surface Of Wall Of Lightning Conductor As Required ( For Horizontal Runs ) 159 Providing And Fixing Copper Tape 20Mm X 3Mm Thick On Parapet And Surface Of Wall Of Lightning Conductor As Required ( For Vertical Runs ) 160 Providing And Fixing Testing Joint Made By 20Mm X 3Mm Thick Copper Strip 125Mm Long With 4 Nos Of Tinned Brass Bolts, Nut, Check Nuts And Spring Washers Etc. Complete As Required. 161 Providing And Laying Copper Tape 32Mm X 6Mm Thick For Earth Electrode Directly In Ground As Required 162 Laying Of Copper Tape 32Mm X 6Mm Thick For Earth Electrode Directly In Ground As Required 163 Earthing:With 3 Metre G.I. Pipes Having Outer Pipe Dia Of 50Mm Having 80-200 Micron Galvanizing, Inner Pipe Dia. Of 25Mm Having 200-250 Micron Galvanizing, Connection Terminal Dia. Of 12Mm In Nominal Soil With 50 Kg ( Two Bag ) Back Filling Bentonite Compound Ul Listed And Confirm To Relevant International / Indian Standards Around Electrode Upto Ground Level. 164 Cabling System 165 For 11Kv Underground Cable From 33 / 11Kv Transformer-1 & 2 To 11Kv Panel 166 3 Core Xlpe Cable 11 Kv Grade, High-Tension Xlpe Cable, 3 Core 300 Sq.Mm Armoured Al. Conductorsupply Of Approved High-Tension Xlpe Cable ( Conforming Is-7098 / Ii / 85 ) As Per Isi Standard 3 Core Armoured With Alu. Solid / Stranded Conductor Isi Marked As Required 167 Termination Kit 11 Kv Xlpe Cable O.D. Termination, 3 X 240-400 Sq. Mm 168 Supply Of Approved Type Cable Cover Flag Stone 200Mm Width & 32Mm To 50Mm Thick Of Required Length Inclusive Of Transport As Required. 169 Laying Of One Number 3 Core H.T Armoured / Unarmoured Power Cable Of Grade Exceeding 1.1Kv But Not Exceeding 11Kv Of Size Not Exceeding 300 Sq. Mm In The Existing Rcc / Hume / Stoneware / G.I. Pipe / Surface In Existing Trench As Required. 170 Supply Of Xlpe Insulated Power Cable ( Conforming Is-7098 Part-I ) 1100 Volt Grade, 1 Core / 2 Core / 3½ Core / 4 Core Isi Marked With Alu. Stranded / Solid Conductor, Xlpe Insulated Power Cable, Al. Conductor 171 4 Core Armoured, 300 Sq. Mm. 172 4 Core Armoured, 6 Sq. Mm. 173 Supplying And Fixing Heavy Duty Cable Gland 174 4 Core Armoured, 300 Sq. Mm. 175 4 Core Armoured, 6 Sq. Mm. 176 Supplying And Fixing Crimping Type Alum. Lugs As Per I.S.S. Specification Suitable For Following Size Of Cable With Alu. / Copper Solid / Stranded Conductor Evenly Crimped With High / Pressure Tool And Connected To Switch Gear / Bus / M.C.C.B. / M.C.B. Etc. As Required Complete. 177 4 Core Armoured, 300 Sq. Mm. 178 4 Core Armoured, 6 Sq. Mm. 179 Laying Of One Number Armoured / Unarmoured Power Cable 1.1Kv Grade Of Size Not Exceeding 25 Sq. Mm Direct In Ground Including Excavation In All Soil / Murrum / Soft Rock, Sand Cushioning, Protective Covering And Refilling The Pit Etc. As Required. 180 Supply And Erection Of Hot Dip G.I. Cable Tray Perforation Not More Than 17.5% For Specific Dimensions Along With Tees, Bends. The Cable Tray Shall Be Hang From Ceiling / Fixed To Wall With Necessary Angle / Flat Iron / Hanging Rod, For Ceiling Suspensions, Clamp, Anchor Fastener, Nuts, Bolts, Washers, Not More Than 1.0 Mtr. Apart Complete As Per Specification To Complete The Job. The Tray 181 600 X 50 X 2 Mm Thick 182 300 X 50 X 1.6Mm Thick 183 450 X 50 X 2 Mm Thick 184 Control Cables 185 Copper Control Cable 12 Core, 2.5 Sqmm Pvc Unarmored 186 Copper Control Cable 8 Core, 2.5 Sqmm Pvc Unarmoured 187 Copper Control Cable 4 Core, 2.5 Sqmm Pvc Unarmoured 188 Copper Control Cable 2 Core, 2.5 Sqmm Pvc Unarmoured 189 Cabletranch Of 1.5 Mtr Wide, 1.75 Mtr Depth With Four Layer Cable Laying Tray Supported By Wall Mount Angles With Precast Rcc Trench Cover, Water Stop, Brick Work Wherever Required Including Cement, Reinforced Steel, Steel Angle, Flats, Frame Work Cable Tray, Excavation Etc. 190 Battery System 191 110 Volt, 100Ah Battery 192 Battery Charger230 Vacinput Suitable For 110 Volt, 100Ah Battery 193 Direct Curent Distribution Board ( Dcdb ) 24 Volts Indoor Floor / Wallmounted Comprising Of 1 No. 2P / 100A Dc Mccb 5A Switch Fuse Unit As Incommer And 8 No. 2P / 40A Mccb 5A Switch Fuse Units For Each Individual Outgoing Circuit Of Indoor Control Panels, Indoor / Outdoor Vcb Panels, 1 No. 2P / 40A Mccb 5A Switch Forcontrol Room Emergency Dc Lighting Including 20% As Spare. Each Incoming & Outgoing Shall Have Indicating Lamp, 194 Safety Equipments 195 Supplying & Fixing Of Fire Extinguisher / Refills As Per Is Specification Abc Type Duly Refilled 6 Kg & Ready To Use 196 4 Buckets Set With Sand, Self-Supported M.S. Stand I / C Shed Duly Painted With Red Colour As Per Is. 197 Supply Of Rubber Mat 2 X 1.0Mtr, 1100V Tested 198 Supply Of Hand Gloves 33Kv Tested 199 Supply Of First Aid Box Complete With Medicine & Bandage As Per Specification 200 Supply Of Shock Instruction Chart Duly Framed With Glass, As Reqd. 201 Supply And Fixing As Per Specification Caution / Danger Board Of Approved Make With Necessary Material Complete.Small Size 200 X 150 Mm For Mv / Lt 202 Scada Part-A-Software Prortion 203 Remote Terminal Unit 204 Multi Function Transducer ( 5 Amp, 110 V With Rs485 Modbus Communication Protocol 205 Contact Multiplying Relays ( Cmrs ) 206 Heavy Duty Relay ( Hdr ) For Cb Trip / Close ( 48V Dc, 2 No, 1 Nc ) 207 Ldms 208 Laser Printer 209 Ldms Software 210 48 V Dc Power Supply ( Dcps ) System Based On Smps 211 Router 230 V Ac, 2 Ge Ports, 48Xfe, Wan Speed 200 Mbps 212 2 Mbps Vpn Link For Connectivity Of S / S With Scada Control Center. 213 2Kva Ups ( For Ldms ) With 160 Ah, 72 V Battery Set 214 Cat 6 Cable 215 Scada Part-B-Hardware Equipment 216 Contactors 30 V Dc, 10 Amp 217 Tap Position Indicator Transmitter 218 Windingtemperature Indicator ( Wti ) , Dial 150Mm , With Capilary, Mercury Swicth Type 219 Oil Temperature Indicator ( Oti ) , Dial 150Mm , With Capilary, Mercury Swicth Type 220 Electromechanical Isolator Contacts 221 Copper Control Cable 8 Core, 2.5 Sqmm Pvc Unarmored 222 Copper Control Cable 4 Core, 2.5 Sqmm Pvc Unarmoured 223 Copper Control Cable 2 Core, 2.5 Sqmm Pvc Unarmoured 224 Rtu Base And Foundation ( Base Should Be Capable Of Withstanding 200 Kg Load ) 225 Furniture For Control Roomtable 600Mmx 900Mm- 1No., Chair- 3No., Computer Table 1No. ( Godrej Or Equivalent ) 226 Ac For Scada Room:Supply, Installation, Testing And Commissioning Of Split Type Wall Mounted Air Conditioning Unit Of Following Capacity Including Indoor, Outdoor Unit Fitted With Inverter Based Rotary Compressor, Copper Condenser And First Charge Refrigerant R410a. The Condensing Unit Working Range Should Be Capable For Providing Cooling Between + / -5 Deg. C To 50 Deg. C & Heating Within 0 Deg. C To 15 Deg. C Including Connection Of Copper Pipe Of Required Size Upto 3 Mtr., Insulation, Cordless Remote Control, Auto Air Swing Louvers, Wall Stand For Outdoor Unit, Connection Copper Lead Wire, Condensed Water Outlet Pipe 2 Mtr. Complete Etc As Required. Outdoor / Indoor Units Should Be Of Same Make ( Brand ) . 1.8 / 2 Tr Star Rating 3 Star 227 Civil Work 228 Fencing Of S / S Land With Barbed Wire 229 Yard Fencing With Chain Link Mesh Over Rcc Beam 230 Ms Main Andwicket Gate On Rcc Column 231 Ms Sign Board, Bay Indication Board & Ryb Phase Indication Board 232 Design, Engineering And Construction Of Control Room Building Including Indoor Cable Trench / Duct / Tray Comprising Of Battery Room, Panel Room, Office Room, Toilet Etc As Required, Minimum 30Mx20m Size For Accomodating 33Kv & 11Kv Ais Panels & Control Pannels, 415V Panels, Scada / Control Room, Toilet, Battery Bank, Capacitor Bank, ) Or As Per Available Land- Including Supply Of Construction Materials, Labour, Cement, Reinforcement Steel, Frame Work, Excavation Etc, All Complete As Per Detailed Technical Specification, Approved Drawing & Scope Of Works. 233 Procedure To Avoid Grass In Sub-Station Yard- Black Cotton. By Laying Stone Cursher Dust. Base Rates Combined For Both The Layers Detailed In ( E-1 ) And ( E-2 ) In Civil Stock. 234 Approach Road ( Wbm ) With Hume Pipe Culvert 235 Approach Road ( Rcc With Ratio-1:2:4 ) From Main Gate To Power Transformer Foundation, Size- ( 20X3 ) Mtr 236 Approach Road , Made By 60 Mm Thick Factory Made Cement Concrete Paver Block Of M-30 Grade, Along The Cable Trenches Upto Various Equipments In The Yard 237 60 Mtr. Deep 150 Mm Dia Tube Well 238 Additional Digging ( If Required ) 150 Mm Dia Tube Well Including Casing Beyond 60 Mtr 239 1000 Liter P / F Sintex Overhead Tank & Gi Pipe ( With Length Of 125 Mtrs ) Fitting For Water Supply Including Providing Water Tap ( 17 No. ) Near Transformer Neutral Earthing 240 Providing And Fixing 5Hp Submersible Pump 241 Providing & Fixing Perforated Cable Tray 300 Mm Wide & 2 Mm Thick Fixed On 45X45x5 Mm M.S. Angle Stand Grouted In C.C 1:24 242 Providing And Fixing Earth Pit Of Brick Massonery 0.6 X 0.6 M Inner Size With Flag Stone Cover For Watering System For 18 No Earth Pits 243 Fire Extinguisher Cartridge Co2 10 Kgs 244 Construction Of Retaining Wall 1.5 M High As Per Site Requirement 245 Ventilation For Control Bldg ( Other Than Scada Room ) :Supplying, Erecting And Testing Of Approved Make Exhaust Fan Heavy Duty With Mounting Frame, Blades Ac 230-250 Complete Connection And Including, Frame Bolt / Anchor Hole Fasteners Etc. Complete Finished And Asrequired.450Mm Sweep Rpm 900 / 1400 246 Cctv 247 Supply, Installation Testing And Commissioning Of Outdoor Wdr Ir Rugged Ip Dome Cameras Shall Be Equipped With 1 / 2.7 Or 1 / 2.8 2 Mpprogressive Scan Imager Or 1 / 3 4 Mp Progressive Scan Imager To Capture 1080P Resolution At25 / 30 Fps Or 4 Mp At 20 Fps Images, 2.7–12 Mm Or 7–22 Mm, F1.4, Motorized Focus / Zoom Len, H.264 And Mjpeg Codec, Triple Stream Support, 50 M ( 150’ ) Ir Distance, Depending On Scene Reflectance, Waterproof ( Ip67 ) And Ik10 Vandal Resistant Camera Housing, Onvif Profile S And G Compliant, Built-Inpoe ( Power Over Ethernet ) Eliminates, Separate Power Supply And Associated Wiring, 24 V Ac / 12 V Dc Inputs Where Poe Power Is Unavailable, Supports Up To 128 Gb Micro Sdhc ( Class 10 ) Card For Local Video Storage When Network Is Interrupted. Card Not Included. 248 Supply, Installation Testing And Commissioning Of 32 Channel Nvr With 1080P Real-Time Live View H.265 / H.264 Mjpeg Dual Codec Decoding Up To 12 Mp Resolution Preview & Playback Max 320 Mbps Incoming Bandwidth Support 4 Sata Hdds Up To 32Tb, Supports Fisheye Video De-Warping In Local And Web User Interface, Supports Visual Or Auditory Notifications ( A Flashing Light, Bell, Or Siren ) Complete With Ul Certification 249 Supply, Installation Testing And Commissioning Of 24 Port Poe Switch With 4 Sfp Ports, Having Security Features Like Port Security Supports 64 Macs Per Port, Auto Surveillance Vlan, Loopback Detection Automatically Disables A Port When A Loop Is Detected, Cable Diagnostics Allows Administrators To Determine Cable Status, Utp Cat. 5, Cat. 5E ( 100 M Max. ) , Full / Half-Duplex For 10 / 100 Mbps, Full-Duplex For 1000 Mbps, Auto Mdi / Mdix Adjustment For All Twisted-Pair Ports, Switching Capacity, 56 Gbps, Maximum 64 Bytes Packet Forwarding Rate, 41.7Mbps, Ports 1 To 24 Compliant With 802.3 At 250 Workstation With Client Licensethe Work Station Shall Have The Following Specifications:- Processor Intel @ I5 750 2.66 Ghz With Internal Memory Of 4 Gb Ram. Operating System Window 7Professional 64-Bit ( Wow 64Mode ) Or Window 7 Professional 32-Bit Nvidia 1 Gb Independent Graphic Card. Resolution Support For Cameras 2560X1600 Display Resolution Capable And Direct X True Colour 32 Bit. Dual Link Vdi Outputs. Clientsoftware Shall Support Dual Monitors Each Displaying 16 Cameras Simultaneously. A Maximum Of 32 Cameras Viewing Per Workstation At A Time.Programmable To Sequence. 251 Cctv Colour Monitorsupply, Installation, Testing And Commissioning Of 32 Flat Led Colour Monitors. 252 Hard Disk - Providing &Fixing Of 4 Tb Hard Disk 253 Epabx System 254 Supply, Installation, Testing And Commissioning Of Epabx System Consist, No. Of Extension, No Of Junction, No. Of Expandable Eport, Operating Console, Current On Max. Load With Isdn Compatible Of Approved Make And Labor As Required As Per Specifications.Epabx System Consists Of 48 Nos. Extensions, 8 Nos Of Junction & Upto 96 Nos. Of Expandable Eport, With One Operating Console, 2 Amp Max. Current 255 Float Cum Boost Chargersupplying & Fixing Float Cum Boost Charger For Epabx System Of Approved Make With All Necessary Material As Required As Per Specifications. 25 Amp 48 V Float Cum Boost Charger 256 Supplying, Fixing Essential Additional Accessories To Epabx System Of Approved Make With All Necessary Material As Required As Per Specifications. 257 Epabx E-1 Card 258 Epabx System Digital Phone With 2 Line Display ( 32 Characters ) With 8 Programmable Keys. 259 Epabx System Digital Line Card 8 Line 260 Discom Supervision Charges

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 11-Mar-2022 Pre Bid Response and Corrigendum Other 16-03-2022

Key Value

Document Fees
INR 20000 /-
EMD
INR 530000.0 /-
Tender Value
INR 5.29 Crore /-

BOQ Items

Name of Work: Design, Engineering, Procurement, Construction of ABD-1 Substation and all associated infrastructure & interior works including Operation and Maintenance of entire facility for Three Years and Trail Run in Satna, Madhya Pradesh.
Sl. No. Item Description
133kV Bay Extension in the Source Substation with feeder protection
233 KV VCB, OUTDOOR PORCELAIN CLADTYPE WITH COMPLETE STRUCTURE AND ACCESSORIES
333 KV CTs (out door oil filled type)300-150/5 Amps
433 KV CONTROL & RELAY PANEL WITH SCADA COMPATIBLEFOR FEEDER PROTECTION (FOR 1 FEEDER)
533 KV ISOLATOR 600 A. (TURN & TWIST TYPE)
633 KV/110 V 3P4W CT/PT RATIO 400-200 / 5 AMP. OUTDOOR OIL IMMERSED TYPE
7COPPER CONTROL CABLE 12 CORE,2.5 SQMM PVC UNARMORED
8COPPER CONTROL CABLE 4 CORE,2.5 SQMM PVC UNARMOURED
9SHIELD CABLE FROM CONTROL PANNEL TO RTU PANEL (17 core*1.5sqmm)
10STRUCTURES AND BUS-BAR ARRANGEMENTS
11H- BEAM 9 METER 152 X 152 MM 37.1 KG/METER = 333.9 kg.FOR 33KV GANTRY STRUCTURE
12Clamp suitablefor 152 X 152 mm., 37.1 Kg./mtr 13 Mtr. Long H-Beam ( each weight 3.2 kg)
13STRAIN PLAT(IS MS FLAT 65X8X250MM) 0.65 Kg each
14ACSRPANTHER CONDUCTOR 0.20 SQ. INCH (200 SQ.MM AL.EQ.)
1533 KV,10 KN PINCOMPOSITE POLYMER INSULATOR,FRP dia 33.5mm
1633 KV Top clamps 75x75x6 mm Angle ( each weight 3.58 Kg)
1733 KV , 45 KN 16mm FRP with 25mm per kV Creepage DISC POLYMER LONG ROD TYPE T&C INSULATOR (FOR 33KV SIDE)
1833 KV COMPOSITE POLYMER STRAIN SET WITH HARD WARE SUITABLE FOR PANTHER CONDUCTOR (FOR 33KV SIDE)
1933 KV , 45 KN 16mm FRP with 25mm per KV Creepage DISC POLYMER LONG ROD TYPE T&C INSULATOR (FOR 11KV SIDE)
20Stone Block/Pre cast block for base pedding 450x450x75mm
21CONCRETING (1:3:6) OF H-BEAM @ 0.65CMT.PER POLE INCLUDING muffing
22OTHER MISCELLANEOUS ITEMS
23CONCRETING (1:3:6) OF VCB STRUCTURES 3.5 cmt per VCB & pole @0.45 CMT. PER STRUCTURE
24CONCRETING (1:3:6)OF ISOLATOR SUPPORT STRUCTURE @ 0.1 CMT. PER STRUCTURE
25R.S.JOIST 175X85MM-9 MTR. LONG FOR YARD LIGHTENING
26PVC CABLE 2 COREARMOURED 2.5 SQMM ALUMINIUM CONDUCTOR
27PVC CABLE 4 COREARMOURED 16 SQMM ALUMINIUM CONDUCTOR
28M S BOLT WITH NUT16X250 MM
29M S BOLT WITH NUT 16X200 MM
30M S BOLT WITH NUT 16X165 MM
31M S BOLT WITH NUT16X140 MM
32M S BOLT WITH NUT16X90 MM
33M S BOLT WITH NUT16X40 MM
34RED-OXIDE PAINT
35ALUMINUM PAINT
36DANGER BOARD ENAMELED 33 KV
37For 33kV Underground Cable from ABD-1 Substation to each Project Area (AAC & Lake Nectar)
3833 KV3x300 Sq mm XLPE Cable with inner side shall be waterproofing with insulation of individual core and outer side of cable shall be stretch resistance.
39Termination kit for 33 kV grade XLPE cable for 3 core 300 sq mm (3 x 240-400 sq. mm.)
40Heat shrinkable cable(Straight Through)jointing kit with lugs for 33 kV grade XLPE cable for 3 core 300 sq mm
41Supplying and installing double wall corrugated pipes (DWC) of HDPE (IS 14930 Part II -marked) for cable laid underground with necessary material and at required depth upto 90cm. below road/ground surface, including excavation, back filling with excavated material, ramming and making the surface good. 210.00mm outside dia.
42Supply of approved type cable cover flag stone 200mm width & 32mm to 50mm thick of required length inclusive of transport as required.
43Laying of one number 3 core H.T armoured/unarmoured power cable 33KV grade of size not exceeding 300 sq. mm in the existing RCC/hume/stoneware/G.I. pipe/surface in existing trench as required.
4433/11 KV Transformers
4533/11 KV Power transformer , OFTC Type5000 KVA Loss (4 KW + 23 KW), with off load tap changer, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power Transformer along with transformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators}, Vent explosion plug, control wiring between sensing equipment and marshalling box, cable supporting tray on the body of transformer, transformer wheels, Cable Junction Box LV/HV bushing etc as required as per technical specifications, approved drawings and scope of the work.
46PTR Foundation
47SCADA COMPATIBLE WINDING TEMP. INDICATOR
48SCADA COMPATIBLE OIL TEMP. INDICATOR
4933 KVLA POLYMER TYPE GAPLESS /METAL OXIDE SUBSTATION TYPE
5011 KVLA POLYMER TYPE GAPLESS /METAL OXIDE 9 KV , 10 KASUBSTATION TYPE
51REMOTE TERMINAL UNIT (RTU) INCLUDING SOFTWARE FOR 2 NO. POWER TRANSFORMER
5211 KV1500 KVAR AUTO SWITCH INDOOR CAPACITOR BANK INCLUDING ASSOCIATED EQUIPMENTS SUCH AS 11 KV VACUUM CIRCUIT BREAKER, CONTROL PANEL, 11 KV OUTDOOR CURRENT TRANSFORMER WITH ADEQUATE METERING & PROTECTION CLASS OF SERVICE, BUS & EQUIPMENT ISOLATORS WITH EARTH SWITCH, MATCHING RVT, SUITABLE GAPLESS LIGHTENING ARRESTORS, NECESSARY CABLES FOR SUCCESSFUL COMMISSIONING COMPLETE
53For 33kV Underground Cable from ABD-1 Substation to each Project Area (AAC & Lake Nectar)
5433 KV3x300 Sq mm XLPE Cable with inner side shall be waterproofing with insulation of individual core and outer side of cable shall be stretch resistance.
55Termination kit for 33 kV grade XLPE cable for 3 core 300 sq mm (3 x 240-400 sq. mm.)
56Heat shrinkable cable(Straight Through)jointing kit with lugs for 33 kV grade XLPE cable for 3 core 300 sq mm
57Supplying and installing double wall corrugated pipes (DWC) of HDPE (IS 14930 Part II -marked) for cable laid underground with necessary material and at required depth upto 90cm. below road/ground surface, including excavation, back filling with excavated material, ramming and making the surface good. 210.00mm outside dia.
58Supply of approved type cable cover flag stone 200mm width & 32mm to 50mm thick of required length inclusive of transport as required.
59Laying of one number 3 core H.T armoured/unarmoured power cable 33KV grade of size not exceeding 300 sq. mm in the existing RCC/hume/stoneware/G.I. pipe/surface in existing trench as required.
60For 11kV Underground Cable from ABD-1 Substation to each Project Area (Indoor Sports Complex)
613 core XLPE cable 11 Kv grade, High-tension XLPE cable, 3 core 300 sq.mm armoured AL. conductor Supply of approved high-tension XLPE cable (conforming IS-7098/II/85) as per ISI standard 3 core armoured with alu. solid/stranded conductor ISI marked as required
62Termination kit 11 KV XLPE cable O.D. termination, 3 x 240-400 sq. mm
63Heat shrinkable jointing kit 11 KV XLPE cable straight joint, 3 x 240-300 sq. mm.
64Supply of approved type cable cover flag stone 200mm width & 32mm to 50mm thick of required length inclusive of transport as required.
65Laying of one number 3 core H.T armoured/unarmoured power cable of grade exceeding 1.1KV but not exceeding 11KV of size not exceeding 300 sq. mm in the existing RCC/hume/stoneware/G.I. pipe/surface in existing trench as required.
66For 415V Underground Cable from Project Lake Nectar to Project Synthesis.
67Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor 4Cx300 armoured
681.1 KV XLPE/HD cable end termination (185-300 sq. mm. 3½/4 core)
691.1 KV XLPE/HD cable straight through jointing kit, 300-400 sq. mm. 3½/4core
70Supply of approved type cable cover flag stone 200mm width & 32mm to 50mm thick of required length inclusive of transport as required.
71Laying of one number 3 core H.T armoured/unarmoured power cable of grade exceeding 1.1KV but not exceeding 11KV of size not exceeding 300 sq. mm in the existing RCC/hume/stoneware/G.I. pipe/surface in existing trench as required.
72DP STRUCTURES FOR RECEIVING 33 KV INCOMING at 33kV Substation
73H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-11 mtr. Long = 408.1 kg
74DC.CROSS ARMS 8`CENTRE TO CENTRE 100X50X6 MM CHANNEL (each weight-56.32 Kg)
75Clamp suitablefor 152 X 152 mm., 37.1 Kg./mtr 13 Mtr. Long H-Beam ( each weight 3.2 kg)
76HORIZONATAL & CROSS BRACING 8" CENTRE(wt of eachX-BRACING-64.29 Kg
77Back Clamp suitable for H-Beam (MS Flat 65x8 mm)-each weight 1.92 Kg
7833 KV (45KN) Composite Polymer Disc Insulators
7933 KV Strain hardware (T&C type) fittings
8033 KV,10 KN PINCOMPOSITE POLYMER INSULATOR,FRP dia 33.5mm
81STAY SET 20 MM
82STAYWIRE 7/4.00 MM.(7/8 SWG)
83Clamp suitablefor 152 X 152 mm., 37.1 Kg./mtr H-Beam ( each weight 3.2 kg)
84Stone Block/Pre cast block for base pedding 450x450x75mm
85CONCRETING (1:3:6) OF H-BEAM @ 0.70 CMT.PER POLE INCLUDING BASE PEDDING
86Concreting of stay (20 mm / 25 mm) @ 0.3 cmt. per stay
87EARTHING COIL OF 115 TURNS OF 50 MM.DIA AND 2.5 MTR LEAD OF 4.0 MM G.I WIRE
8833kV Switchgear:33 KVAir insulated switchgearIndoor type, extensible type & SCADA compatible - as per IEC 62271-200 with following features, Compartmentalized modular typesuitable for 36kV 1250A Copper busbar with short circuit rating of 31.5kA for 3 sec.
89Incomer: 1. 36kV 1250A Copper busbar with short circuit rating of 31.5kA for 3 secwith motor operated spring charging mechanism,control circuit suitable for local and remote operation.the breakers shall be trip free and shall have anti pumping feature. 2.The 33KV HT panel shall be internally arc tested for 31.5kA for 1 sec duration A-FLR.Necessary type test report for internal arc for 1 sec shall be furnished by the manufacturer. 3.The vacuum circuit breaker shall be rated 1250A for short circuit rating of 31.5kA for 3 sec. The spring charging of the breaker shall be with integral spring charging handle. 4.The vacuum circuit shall be completely enclosed vacuum interruptors in housing of polymer material . 5.The inspection window on the VCB door shall be made of toughened glass only of suiltable strength to withstand the internal arc. 6.The PT fuses shall be completely enclosed in epoxy housing to prevent any flash over occurance. 7.cable termination suitable for current ratings 1Rx3CX300 sqmm,. theearthing terminal busbar of size 25x5 mm& CT ratings of 300-150/5-5A with Cl-1.0 5P10 20VA with Multifunction meter for metering with Line PT 33KV/V3/110V/3 Cl-1.0/PS 20VA. 8.The AIS shall have numerical relay SCADA compalitble with IEC 61850 communication facility suitable for Incomer protection/Trip ckt supervision/Antipumping/lock out relay & accesories for Breaker ON/OFF button/Mimic diagram/electronic hooter/TNC switch/DC&AC ON/OFF,LED lamps for indication on Breaker status/live status/necessary panel status &Thermostat based anti condensation heater. 9. The pannel shall be internal arc tested 31.5 KA for 1 sec. duration A-FLR provided with GAS DUCT to remove the hot gasses/plasma formedduring internal arc - out off the switchgear room. 10. The master relay should be both electrical & mechanical reset type.
90Outgoing: 1. 36kV 1250A Copper busbar with short circuit rating of 31.5kA for 3 secwith motor operated spring charging mechanism,control circuit suitable for local and remote operation.the breakers shall be trip free and shall have anti pumping feature. 2.The 33KV HT panel shall be internally arc tested for 31.5kA for 1 sec duration A-FLR.Necessary type test report for internal arc for 1 sec shall be furnished by the manufacturer. 3.The vacuum circuit breaker shall be rated 1250A for short circuit rating of 31.5kA for 3 sec. The spring charging of the breaker shall be with integral spring charging handle. 4.The vacuum circuit shall be completely enclosed vacuum interruptors in housing of polymer material . 5.The inspection window on the VCB door shall be made of toughened glass only of suiltable strength to withstand the internal arc. 6.The PT fuses shall be completely enclosed in epoxy housing to prevent any flash over occurance. 7.cable termination suitable for current ratings 1Rx3CX300 sqmm,. theearthing terminal busbar of size 25x5 mm& CT ratings of 300-150/5-5A with Cl-1.0 5P10 20VA with Multifunction meter for metering with Line PT 33KV/V3/110V/3 Cl-1.0/PS 20VA. 8.The AIS shall have numerical relay SCADA compalitble with IEC 61850 communication facility suitable for Incomer protection/Trip ckt supervision/Antipumping/lock out relay & accesories for Breaker ON/OFF button/Mimic diagram/electronic hooter/TNC switch/DC&AC ON/OFF,LED lamps for indication on Breaker status/live status/necessary panel status &Thermostat based anti condensation heater. 9. The pannel shall be internal arc tested 31.5 KA for 1 sec. duration A-FLR provided with GAS DUCT to remove the hot gasses/plasma formedduring internal arc - out off the switchgear room. 10. The master relay should be both electrical & mechanical reset type.
91Buscoupler: 1.The AISdesign shall be Compartmentalized modular typesuitable for 36kV 1250A Copper busbar with short circuit rating of 31.5kA for 3 secwith motor operated spring charging mechanism,control circuit suitable for local and remote operation.the breakers shall be trip free and shall have anti pumping feature. 2.The 33KV HT panel shall be internally arc tested for 31.5kA for 1 sec duration A-FLR.Necessary type test report for internal arc for 1 sec shall be furnished by the manufacturer. 3.The vacuum circuit breaker shall be rated 1250A for short circuit rating of 31.5kA for 3 sec. The spring charging of the breaker shall be with integral spring charging handle. 4.The vacuum circuit shall be completely enclosed vacuum interruptors in housing of polymer material . 5.The inspection window on the VCB door shall be made of toughened glass only of suiltable strength to withstand the internal arc. 6.The PT fuses shall be completely enclosed in epoxy housing to prevent any flash over occurance. 7.The cable termination suitable for current ratings 1Rx3CX300 sqmm theearthing terminal busbar of size 25x5 mm& CT ratings of 300-150/5-5A with Cl-1.0 5P10 20VA with Multifunction meter for metering 8.The AIS shall have numerical relay SCADA compalitble with IEC 61850 communication facility suitable for Ibuscouplerprotection/Trip ckt supervision/Antipumping/lock out relay & accesories for Breaker ON/OFF button/Mimic diagram/electronic hooter/TNC switch/DC&AC ON/OFF,LED lamps for indication on Breaker status/live status/necessary panel status &Thermostat based anti condensation heater. 9. The pannel shall be internal arc tested 31.5 KA for 1 sec. duration A-FLR provided with GAS DUCT to remove the hot gasses/plasma formedduring internal arc - out off the switchgear room. 10. The master relay should be both electrical & mechanical reset type.
9211kV Switchgear
9311 KV Air insulated switchgearIndoor type for POWER TRANSFORMEROUTGOING extensible type & SCADA compatible as per IEC 62271-200 with following featurs. 1.The AISdesign shall be Compartmentalized modular typesuitable for 12kV 1250A Copper busbar with short circuit rating of 31.5kA for 3 secwith motor operated spring charging mechanism,control circuit suitable for local and remote operation.the breakers shall be trip free and shall have anti pumping feature. 2.The 12KV HT panel shall be internally arc tested for 31.5kA for 1 sec duration A-FLR.Necessary type test report for internal arc for 1 sec shall be furnished by the manufacturer. 3.The vacuum circuit breaker shall be rated 1250A for short circuit rating of 31.5kA for 3 sec. The spring charging of the breaker shall be with integral spring charging handle. 4.The vacuum circuit shall be completely enclosed vacuum interruptors in housing of polymer material . 5.The inspection window on the VCB door shall be made of toughened glass only of suiltable strength to withstand the internal arc. 6.The PT fuses shall be completely enclosed in epoxy housing to prevent any flash over occurance. 7. Theearthing terminal busbar of size 25x5 mm& CT ratings of 600-300/5-5A with Cl-1.0 5P10 20VA with Multifunction meter for metering . 8.The AIS shall have numerical relay SCADA compalitble with IEC 61850 communication facility suitable for Incomer protection/Trip ckt supervision/Antipumping/lock out relay & accesories for Breaker ON/OFF button/Mimic diagram/electronic hooter/TNC switch/DC&AC ON/OFF,LED lamps for indication on Breaker status/live status/necessary panel status &Thermostat based anti condensation heater. 9. The master relay should be both electrical & mechanical reset type.
9411 KV Air insulated switchgear Indoor typeforFEEDER OUTGOINGextensible type & SCADA compatible, as per IEC 62271-200 with following features . 1.The AISdesign shall be Compartmentalized modular typesuitable for 12kV 1250A Copper busbar with short circuit rating of 31.5kA for 3 secwith motor operated spring charging mechanism,control circuit suitable for local and remote operation.the breakers shall be trip free and shall have anti pumping feature. 2.The 12KV HT panel shall be internally arc tested for 31.5kA for 1 sec duration A-FLR.Necessary type test report for internal arc for 1 sec shall be furnished by the manufacturer. 3.The vacuum circuit breaker shall be rated 1250A for short circuit rating of 31.5kA for 3 sec. The spring charging of the breaker shall be with integral spring charging handle. 4.The vacuum circuit shall be completely enclosed vacuum interruptors in housing of polymer material . 5.The inspection window on the VCB door shall be made of toughened glass only of suiltable strength to withstand the internal arc. 6.The PT fuses shall be completely enclosed in epoxy housing to prevent any flash over occurance. 7. Theearthing terminal busbar of size 25x5 mm& CT ratings of 200-100/5-5A with Cl-1.0 5P10 20VA with Multifunction meter for metering . 8.The AIS shall have numerical relay SCADA compalitble with IEC 61850 communication facility suitable for Outgoin feederprotection/Trip ckt supervision/Antipumping/lock out relay & accesories for Breaker ON/OFF button/Mimic diagram/electronic hooter/TNC switch/DC&AC ON/OFF,LED lamps for indication on Breaker status/live status/necessary panel status &Thermostat based anti condensation heater. 9. The master relay should be both electrical & mechanical reset type.
9511 KV Air insulated switchgear Indoor typefor BUS COUPLER OUTGOING extensible type & SCADA compatible, as per IEC 62271-200 with following features. 1.The AISdesign shall be Compartmentalized modular typesuitable for 12kV 1250A Copper busbar with short circuit rating of 31.5kA for 3 secwith motor operated spring charging mechanism,control circuit suitable for local and remote operation.the breakers shall be trip free and shall have anti pumping feature. 2.The 12KV HT panel shall be internally arc tested for 31.5kA for 1 sec duration A-FLR.Necessary type test report for internal arc for 1 sec shall be furnished by the manufacturer. 3.The vacuum circuit breaker shall be rated 1250A for short circuit rating of 31.5kA for 3 sec. The spring charging of the breaker shall be with integral spring charging handle. 4.The vacuum circuit shall be completely enclosed vacuum interruptors in housing of polymer material . 5.The inspection window on the VCB door shall be made of toughened glass only of suiltable strength to withstand the internal arc. 6.The PT fuses shall be completed enclosed in epoxy housing to prevent any flash over occurance. 7. Theearthing terminal busbar of size 25x5 mm& CT ratings of 600-300/5-5A with Cl-1.0 5P10 20VA with Multifunction meter for metering . 8.The AIS shall have numerical relay SCADA compalitble with IEC 61850 communication facility suitable for Buscoupler protection/Trip ckt supervision/Antipumping/lock out relay & accesories for Breaker ON/OFF button/Mimic diagram/electronic hooter/TNC switch/DC&AC ON/OFF,LED lamps for indication on Breaker status/live status/necessary panel status &Thermostat based anti condensation heater. 9. The master relay should be both electrical & mechanical reset type.
9611kV Bus PT panel with necessary Bus PT forMETERING & PROTECTION 11kV/V3/110V/v3/110V/3 CL-1.0 CL-PS 50 VA .Epoxy enclosed PT Fuses shall be mounted on BUS PT. The fuses shall have fuse failure protection / necessary LED lamps for indication to be provided.Numercial relay SCADA Compatible for UV/OV protection with IEC 61850 protection to be provided
97Transformer, 33/0.4 KV 3 phase
98Supplying, installing, testing and commissioning of 33/0.4 KV 3 Phase 50 cycle oil immersed, naturally cooled, outdoor type transformer connected delta on H.T. side and star on L.T. side, hand operated off load Tap changer switch above 100 KVA, rating and diagram plate, two earthing terminal, lifting lugs, oil level gauge, drain valve with plug, temperature not exceeding 50ºC on load, oil conservator with drain plug, oil filling hole with plug, dehydrating silica gel breather on eye level, four unidirectional roller, arcing horns, explosion vent, terminal arrangement bushing on H.V. side and cable box on LV side, first filling of oil upto desired level and transformer installing on existing structure with all required materials arrangement as required ISI marked & as per IS specification. Energy efficiency level -3, 200 KVA
99Lighting System
100Supply and fixing of surface mounting type LED light fixture, LED of 1 to 3 Watt each assembled on single MCPCB, having color temp upto 6500K & having 50000 burning hrs. life with minimum @ L 70, system lumen output should be minimum with efficacy>100 lm/Watt. LED driver, PF> 0.95, THD < 20% & surge protection 4KV. The colour rendering index of LED light should be more than 70. Housing made of CRCA powder coated frame with glare free diffused polycarbonate cover. Submission LM 79-08/IS16106 (2012), IEC60598, IEC61347i/c connection wire, testing etc. to complete the job.LED luminiare 2" X 2", 45Watt, color temp 3000- 6500k as required.
101Supply and fixing Led tube rod comprising of LED tube with non-integral/integral driver, upto 6500K color temp having 40000 burning hrs life with minimum @ L 70, system lumen output should be minimum with system efficacy> 100 lm/Watt. LED driver PF> 0.95 & THD < 20%. The colour rendering index of LED light should be more than 70. Submission LM 79-08/IS16106 (2012), IEC60598, IEC61347i/c connection wire, testing etc. to complete the job. Tube light LED 1 X 20/22Watt, Integral i/c batten aluminium body, PC diffuser.
102Supply and fixing street light with high power LED of 3 to 6 Watt each on existing bracket assembled on single MCPCB and additional unique peanut lens on each LED, system lumens output with efficacy>120 lm/Watt. luminiare having color temp upto 6500K & 50000 hrs. burning life with minimum @ L 70, The colour rendering index of LED light should be more than 70. Luminiare comprises of driver, PF> 0.95 & surge protection 10KV. Housing made of pressure die cast aluminium with heat resistant flat glass, IP65 protection. Submission LM 79- 08/IS16106 (2012), IEC60598, IEC61347 i/c connection wire, testing etc. to complete the job. 120Watt, color temp 3000-6500k as required
103Supply and fixing street light with high power LED of 3 to 6 Watt each on existing bracket assembled on single MCPCB and additional unique peanut lens on each LED, system lumens output with efficacy>120 lm/Watt. luminiare having color temp upto 6500K & 50000 hrs. burning life with minimum @ L 70, The colour rendering index of LED light should be more than 70. Luminiare comprises of driver, PF> 0.95 & surge protection 10KV. Housing made of pressure die cast aluminium with heat resistant flat glass, IP65 protection. Submission LM 79- 08/IS16106 (2012), IEC60598, IEC61347 i/c connection wire, testing etc. to complete the job. 40Watt to 48Watt, color temp 3000-6500k as required.
104Point Wiring :Point wiring (excluding metallic switch box & sheet but including switches, sockets, lamp holders/ceiling roses etc) with 1.5sq. mm. PVC insulated cable FRLS with copper multi strand conductor ISI marked in surface rigid P.V.C. conduit (MMS) ISI marked of suitable size and 1.5sq. mm. PVC FRLS insulated copper earth continuity conductor of green colour inside conduit etc. as required as per specification for
105Light point/fan points.
106Primary short point
107Primary medium point
108Primary long point
109(Light point/fan points) looping point
110Secondary short point
111Secondary medium point
112Secondary long point
1133 Pin 6 Amp socket outlet on separate board
114short point
115medium point
116long point
117Supplying and fixing 25mm PVC conduit ISI marked FRLS along with accessories on surface etc. as required
118Supplying and fixing factory fabricated hot dip galvanized switch box for normal flush type accessories of minimum 1.2 mm thickness for up to 200mmx250mm size boxes and 1.6mm minimum thickness for higher size boxes, earth terminal stud with nut and washer, including 3 mm thick synthetic phenolic resin bonded laminated sheet conforming to grade P-I of IS:2036- 1974 on surface/concealed including all necessary accessories, painting etc. as required as per specification: MS box 200 mm X 150 mm X 60 mm
119Supply and fixing of 9W, Rechargeable Inverter LED Bulb rechargeable inverter LED Bulb, reduces to 40-50% (emergency application) with Lithium Ion battery 2600mAh, backup upto 5 hrs. having color temp upto 6500K, IP- 20 rating, THD (Total harmonic distortion) <20%
120415V Switchgear
121PCC Panel
122Supply, fixing, testing & commissioning wall/floor mounted LT panel primer coated with powder coated paint & provided with required gasket for dust/vermin proof with degree of protection IP42 suitable for 415Volt 3 phase, 50 Hz, 4 wire system fabricated out of CRCA sheet upto 2 mm thick (1.6 mm for doors) duly compartmentalized for incomer, bus section, outgoings, cable alleys & CT, PT Ampere Metre, Volt Metre, selector switches, frequency Metre, phase indicating lamp, Energy Metre complete including cost of busbar supports, detachable cable gland plates, 2 earthing terminals, internal wiring & fixing of separately supplied MCBs, MCCBs, ACB, panel mounted changeover switch/SFUs, etc. as required but excluding cost of busbar strips, Ampere Metre, Volt Metre, selector switch as per approved design
123400A MCCB (Incomer) - MCCB 36kA current rating - 400 Amps 4 Pole µ-processor release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. adjustable
124Outgoing: MCCB 25kA current rating - 40 & 100 Amps 4 Pole & micro-processor release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. adjustable
125MCCB 25kA current rating - 160 Amps 4 Pole & micro-processor release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable
126LED lamp indicator
127Digital Ampere Metre with CTs with selector switch
128Digital Volt Metre with selector switch & HRC fuse
129Aluminium bus bar strips with PVC sleeves
130Supplying and fixing of CT 1A/5A as per site selectable busbar dimension of approved make in existing main panel for power factor Panel including connections etc. as required as per specification.
131415V Capacitor Panel
132Supply, fixing, testing & commissioning wall/floor mounted LT panel primer coated with powder coated paint & provided with required gasket for dust/vermin proof with degree of protection IP42 suitable for 415Volt 3 phase, 50 Hz, 4 wire system fabricated out of CRCA sheet upto 2 mm thick (1.6 mm for doors) duly compartmentalized for incomer, bus section, outgoings, cable alleys & CT, PT Ampere Metre, Volt Metre, selector switches, frequency Metre, phase indicating lamp, Energy Metre complete including cost of busbar supports, detachable cable gland plates, 2 earthing terminals, internal wiring & fixing of separately supplied MCBs, MCCBs, ACB, panel mounted changeover switch/SFUs, etc. as required but excluding cost of busbar strips, Ampere Metre, Volt Metre, selector switch as per approved design
133Supplying and fixing of capacitor duty contactor of approved make in existing power factor/LT panel including connections etc.as required as per specification.
134For 25 KVAR 440V,3Ph,50Hz, Aux contact-1NO
135For 15 kVAR 440V,3Ph,50Hz, Aux contact-1NO
136For 5 kVAR 440V,3Ph,50Hz, Aux contact-1NO
137Supplying and fixing of APFC relay 1A/5 A site selectable, measurement of individual current and voltage harmonic (THD), capacitor failure indication, Inbuilt temperature sensor of approved make in existing power factor Panel including connections etc. as required as per specification as mentioned below
1388 Step APFC relay (144 x144mm)
139Wall Mounted DB
140Supplying of approved make TPN MCB DB metal double door IP 43 protection with provision for FP MCB/ Isolator/ RCCB/ RCBO as incomer and SP MCBs as outgoing inclusive of busbar, neutral bar, earth bar, connection copper wire not less than 16 sq.mm & two earth terminals etc. complete as per IS:13032(exclusive of MCB & isolator): 6 Way (8+18)
141Supplying and installing of RCBOs (Residual current circuit breaker with overload and short circuit protection) ISI marked complete as per I.S. standard conforming to IEC:61009-1 & IS:12640-2, 240/415V 50 Hz with 10 kA short circuit withstand capacity for earth leakage, overload & short circuit protection including connection in existing enclosure in approved manner as per specification. 4 Pole 40A, 30mA
142MCB SP 6Amp to 32Amp 10kA rating
143ACDB
144ACDB415 V, along withthree phase-neutral voltmeter,three phase ammeter andSelector switches, 1no.200 Amps TPN switch fuse unit as incomer, 1no. 63 Amp.TPN MCCB switches as outgoing feeders & 2no. 32 Amp. MCCB as outgoingfor yard and control room lightining and 6 no. 16 no. MCCB for control panels, Each incoming & outgoing shall have indicating lamp. including 20% spare
145Earthing System
146Earthing with G.I. earth pipe 4.5 metre long and 40 mm dia with masonry encloser in cement mortar, cover plate having locking arrangement on the top etc. (but without charcoal or coke and salt) complete as required
147Earthing with copper earth plate 600mm X 600mm X 3mm thick including accessories and providing masonry encloser in cement mortar, cover plate having locking arrangement on the top and G.I. watering pipe 20mm dia 2.7 metre long etc. (but without charcoal or coke and salt) complete as required
148Supply and layingG.I. wire at 0.5 metre below ground level as conductor earth electrode including jointing etc. as required.
1494.0mm (8 SWG) dia.
1504.87mm 6 SWG G.I.
15125mm X 5mm G.I. strip
15225mm X 6mm G.I. strip
15350mm X 6mm G.I. strip
154Lightning Protection System
155Providing and fixing of lightning conductor finial made of 18mm dia 500mm long bright nickel plated copper tube tapered having single prong at top with bright nickel plated brass base M10 for connection and intersection of flat or round conductor including holes, clamp complete as required.
156Fixing of lightning conductor finial made of 25mm dia 300mm long copper tube/G.I. tube having single prong at top with base plate etc. complete as required.
157Riveting/sweating and soldering of copper/G.I. Tape (with another copper/G.I. Tape, base of finial or any other metallic object) as required
158Providing and fixing copper tape 20mm X 3mm thick on parapet and surface of wall of lightning conductor as required (for horizontal runs)
159Providing and fixing copper tape 20mm X 3mm thick on parapet and surface of wall of lightning conductor as required (for vertical runs)
160Providing and fixing "Testing Joint" made by 20mm X 3mm thick copper strip 125mm long with 4 Nos of tinned Brass bolts, Nut, check nuts and spring washers etc. complete as required.
161Providing and laying copper tape 32mm X 6mm thick for earth electrode directly in ground as required
162Laying of copper tape 32mm X 6mm thick for earth electrode directly in ground as required
163Earthing: With 3 metre G.I. pipes having outer pipe dia of 50mm having 80-200 micron galvanizing, Inner pipe dia. of 25mm having 200-250 Micron galvanizing, connection terminal dia. of 12mm in nominal soil with 50 kg (two bag) back filling bentonite compound UL listed and confirm to relevant International/Indian standards around electrode upto ground level.
164Cabling System
165For 11kV Underground Cable from 33/11kV Transformer-1 & 2 to 11kV Panel
1663 core XLPE cable 11 Kv grade, High-tension XLPE cable, 3 core 300 sq.mm armoured AL. conductor Supply of approved high-tension XLPE cable (conforming IS-7098/II/85) as per ISI standard 3 core armoured with alu. solid/stranded conductor ISI marked as required
167Termination kit 11 KV XLPE cable O.D. termination, 3 x 240-400 sq. mm
168Supply of approved type cable cover flag stone 200mm width & 32mm to 50mm thick of required length inclusive of transport as required.
169Laying of one number 3 core H.T armoured/unarmoured power cable of grade exceeding 1.1KV but not exceeding 11KV of size not exceeding 300 sq. mm in the existing RCC/hume/stoneware/G.I. pipe/surface in existing trench as required.
170Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core / 2 core / 3½ core / 4 core ISI marked with alu. stranded /solid conductor, XLPE insulated power cable, al. conductor
1714 core armoured, 300 sq. mm.
1724 core armoured, 6 sq. mm.
173Supplying and fixing heavy duty cable gland
1744 core armoured, 300 sq. mm.
1754 core armoured, 6 sq. mm.
176Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear/bus/M.C.C.B./M.C.B. etc. as required complete.
1774 core armoured, 300 sq. mm.
1784 core armoured, 6 sq. mm.
179Laying of one number armoured / unarmoured power cable 1.1KV grade of size not exceeding 25 sq. mm direct in ground including excavation in all soil/ murrum /soft rock, sand cushioning, protective covering and refilling the pit etc. as required.
180Supply and erection of hot dip G.I. cable tray perforation not more than 17.5% for specific dimensions along with tees, bends. The cable tray shall be hang from ceiling/ fixed to wall with necessary angle/flat iron/hanging rod, for ceiling suspensions, clamp, anchor fastener, nuts, bolts, washers, not more than 1.0 mtr. apart complete as per specification to complete the job. The tray
181600 x 50 x 2 mm thick
182300 x 50 x 1.6mm thick
183450 x 50 x 2 mm thick
184Control Cables
185COPPER CONTROL CABLE 12 CORE,2.5 SQMM PVC UNARMORED
186COPPER CONTROL CABLE 8 CORE,2.5 SQMM PVC UNARMOURED
187COPPER CONTROL CABLE 4 CORE,2.5 SQMM PVC UNARMOURED
188COPPER CONTROL CABLE 2 CORE,2.5 SQMM PVC UNARMOURED
189CableTranch of 1.5 Mtr wide,1.75 Mtr Depth with four layer cable laying tray supported by wall mount angles with precast RCC Trench Cover, water stop, Brick work wherever required including Cement, Reinforced Steel, Steel Angle, Flats, Frame work Cable Tray, excavation etc.
190Battery System
191110 Volt, 100AH Battery
192BATTERY CHARGER230 VACINPUT suitable for 110 Volt, 100AH Battery
193Direct Curent Distribution Board (DCDB) 24 Volts Indoor floor / wallmounted comprising of 1 no. 2P/100A DC MCCB 5A Switch Fuse Unit as incommer and 8 no. 2P/40A MCCB 5A switch fuse units for each individual outgoing circuit of indoor control panels, indoor/outdoor VCB panels, 1 no. 2P/40A MCCB 5A switch forcontrol room emergency DC lighting including 20% as spare. Each incoming & outgoing shall have indicating lamp,
194Safety Equipments
195Supplying & fixing of fire extinguisher/refills as per IS specification ABC type duly refilled 6 Kg & ready to use
1964 buckets set with sand, self-supported M.S. stand i/c shed duly painted with red colour as per IS.
197Supply of rubber mat 2 x 1.0Mtr, 1100V tested
198Supply of hand gloves 33KV tested
199Supply of first aid box complete with medicine & bandage as per specification
200Supply of shock instruction chart duly framed with glass, as reqd.
201Supply and fixing as per specification caution/danger board of approved make with necessary material complete. Small size 200 X 150 mm for MV/LT
202SCADA PART-A-SOFTWARE PRORTION
203REMOTE TERMINAL UNIT
204MULTI FUNCTION TRANSDUCER (5 Amp, 110 V with RS485 Modbus communication protocol
205CONTACT MULTIPLYING RELAYS (CMRS)
206HEAVY DUTY RELAY (HDR) FOR CB TRIP/CLOSE (48V DC, 2 NO, 1 NC)
207LDMS
208LASER PRINTER
209LDMS SOFTWARE
21048 V DC POWER SUPPLY (DCPS) SYSTEM BASED ON SMPS
211ROUTER 230 V AC, 2 GE ports, 48xFE, WAN speed 200 mbps
2122 MBPS VPN LINK FOR CONNECTIVITY OF S/S WITH SCADA CONTROL CENTER.
2132KVA UPS (FOR LDMS ) WITH 160 AH, 72 V Battery set
214CAT 6 CABLE
215SCADA PART-B-HARDWARE EQUIPMENT
216CONTACTORS 30 V DC, 10 AMP
217TAP POSITION INDICATOR TRANSMITTER
218WINDINGTEMPERATURE INDICATOR (WTI) , DIAL 150MM , WITH CAPILARY, MERCURY SWICTH TYPE
219OIL TEMPERATURE INDICATOR (OTI) , DIAL 150MM , WITH CAPILARY, MERCURY SWICTH TYPE
220ELECTROMECHANICAL ISOLATOR CONTACTS
221COPPER CONTROL CABLE 8 CORE,2.5 SQMM PVC UNARMORED
222COPPER CONTROL CABLE 4 CORE,2.5 SQMM PVC UNARMOURED
223COPPER CONTROL CABLE 2 CORE,2.5 SQMM PVC UNARMOURED
224RTU BASE AND FOUNDATION (BASE SHOULD BE CAPABLE OF WITHSTANDING 200 KG LOAD)
225Furniture for control roomTable 600mmx 900mm- 1no., Chair- 3no., Computer table 1no. (Godrej or equivalent )
226AC for SCADA Room: Supply, installation, testing and commissioning of Split type wall mounted air conditioning unit of following capacity including indoor, outdoor unit fitted with inverter based rotary compressor, copper condenser and first charge refrigerant R410A. The condensing unit working range should be capable for providing cooling between +/-5 deg. C to 50 deg. C & heating within 0 deg. C to 15 deg. C including connection of copper pipe of required size upto 3 mtr., insulation, cordless remote control, auto air swing louvers, wall stand for outdoor unit, connection copper lead wire, condensed water outlet pipe 2 mtr. complete etc as required. Outdoor/indoor units should be of same make (brand). 1.8/2 TR star rating 3 star
227CIVIL WORK
228FENCING OF S/S LAND WITH BARBED WIRE
229YARD FENCING WITH CHAIN LINK MESH OVER RCC BEAM
230MS MAIN ANDWICKET GATE ON RCC COLUMN
231MS SIGN BOARD, BAY INDICATION BOARD & RYB PHASE INDICATION BOARD
232Design, engineering and construction of Control Room Building including indoor Cable Trench/Duct/Tray comprising of battery room, panel room, office room, toilet etc as required, minimum 30mX20m Size for accomodating 33kV & 11kV AIS Panels & control pannels, 415V panels, SCADA/Control room, Toilet, Battery Bank, Capacitor bank,)or as per available Land- including supply of construction materials, Labour, Cement, Reinforcement Steel, Frame Work, Excavation etc, all complete as per detailed Technical Specification, approved Drawing & Scope of works.
233Procedure to avoid grass in sub-station yard- Black Cotton. By laying stone cursher dust. Base Rates combined for both the layers detailed in (e-1) and (e-2) in Civil Stock.
234APPROACH ROAD (WBM) WITH HUME PIPE CULVERT
235APPROACH ROAD (RCC WITH RATIO-1:2:4) FROM MAIN GATE TO POWER TRANSFORMER FOUNDATION, SIZE-(20X3) MTR
236APPROACH ROAD , MADE BY 60 MM THICK FACTORY MADE CEMENT CONCRETE PAVER BLOCK OF M-30 GRADE,ALONG THE CABLE TRENCHES UPTO VARIOUS EQUIPMENTS IN THE YARD
23760 MTR. DEEP 150 MM DIA TUBE WELL
238ADDITIONAL DIGGING (IF REQUIRED)150 MM DIA TUBE WELL INCLUDING CASING BEYOND 60 MTR
2391000 LITER P/F SINTEX OVERHEAD TANK & GI PIPE (WITH LENGTH OF 125 MTRS) FITTING FOR WATER SUPPLY INCLUDING PROVIDING WATER TAP(17 NO.) NEAR TRANSFORMER NEUTRAL EARTHING
240PROVIDING AND FIXING 5HP SUBMERSIBLE PUMP
241PROVIDING & FIXING PERFORATED CABLE TRAY 300 MM WIDE & 2 MM THICK FIXED ON 45X45X5 MM M.S. ANGLE STAND GROUTED IN C.C 1:24
242PROVIDING AND FIXING EARTH PIT OF BRICK MASSONERY 0.6 X 0.6 M INNER SIZE WITH FLAG STONE COVER FOR WATERING SYSTEM FOR 18 NO EARTH PITS
243Fire extinguisher cartridge CO2 10 kgs
244CONSTRUCTION OF RETAINING WALL 1.5 M HIGH AS PER SITE REQUIREMENT
245Ventilation for Control Bldg (Other than SCADA Room): Supplying, erecting and testing of approved make exhaust fan heavy duty with mounting frame, blades AC 230-250 complete connection and including, frame bolt/anchor hole fasteners etc. complete finished and as required. 450mm sweep RPM 900 / 1400
246CCTV
247Supply, installation testing and commissioning of outdoor WDR IR rugged IP dome cameras shall be equipped with 1/2.7" or 1/2.8" 2 MPprogressive scan imager or 1/3" 4 MP progressive scan imager to capture 1080p resolution at25/30 fps or 4 MP at 20 fps images, 2.7–12 mm or 7–22 mm, F1.4, motorized focus/zoom len, H.264 and MJPEG codec, triple stream support, 50 m (150’) IR distance, depending on scene reflectance, waterproof (IP67) and IK10 vandal resistant camera housing, ONVIF profile S and G compliant, built-in PoE (Power over Ethernet) eliminates, separate power supply and associated wiring,24 V AC/12 V DC inputs where PoE power is unavailable, supports up to 128 GB micro SDHC (class 10) card for local video storage when network is interrupted. Card not included.
248Supply, installation testing and commissioning of 32 channel NVR with 1080p real-time live view H.265/H.264 MJPEG dual codec decoding Up to 12 MP resolution preview & playback max 320 MBPS incoming bandwidth support 4 SATA HDDs up to 32TB, supports fisheye video de-warping in local and web user interface, supports visual or auditory notifications(a flashing light, bell, or siren) complete with UL certification
249Supply, installation testing and commissioning of 24 port PoE switch with 4 SFP ports, having security features like port security supports 64 MACs per port, auto surveillance VLAN, loopback detection automatically disables a port when a loop is detected, cable diagnostics allows administrators to determine cable status, UTP Cat. 5, Cat. 5e (100 m max.), full/half-duplex for 10/100 MBPS, full-duplex for 1000 MBPS, auto MDI/MDIX adjustment for all twisted-pair ports, switching capacity, 56 GBPS, maximum 64 bytes packet forwarding rate, 41.7mbps, Ports 1 to 24 compliant with 802.3 at
250Workstation with client license The work station shall have the following specifications:- Processor Intel @ i5 750 2.66 GHz with internal memory of 4 GB RAM. Operating system window 7professional 64-bit (WOW 64mode) or window 7 professional 32-bit NVIDIA 1 GB independent graphic card. Resolution support for cameras 2560x1600 display resolution capable and direct X true colour 32 bit. Dual link VDI outputs. Clientsoftware shall support Dual monitors each displaying 16 cameras simultaneously. A maximum of 32 cameras viewing per workstation at a time.Programmable to sequence.
251CCTV colour monitor Supply, installation, testing and commissioning of 32" flat LED colour monitors.
252Hard disk - Providing &fixing of 4 TB hard disk
253EPABX system
254Supply, installation, testing and commissioning of EPABX system consist, no. of extension, no of junction, no. of expandable eport, operating console, current on max. load with ISDN compatible of approved make and labor as required as per specifications. EPABX system consists of 48 nos. extensions, 8 nos of junction & upto 96 nos. of expandable eport, with one operating console, 2 Amp max. current
255Float cum boost charger Supplying & fixing float cum boost charger for EPABX system of approved make with all necessary material as required as per specifications. 25 Amp 48 V float cum boost charger
256Supplying, fixing essential additional accessories to EPABX system of approved make with all necessary material as required as per specifications.
257EPABX E-1 card
258EPABX system digital phone with 2 line display (32 characters) with 8 programmable keys.
259EPABX system digital line card 8 line
260DISCOM Supervision charges