}

Spl Repair / Replacement To Lt Distribution System By Conversion Of Lt Oh Line Into Lt Ug Cable And Connected Works At Otm Accn Of Signals Records Under Age E / M Of Ge ( East ) Jbalpur As Per Boq, jabalpur-Madhya Pradesh

Military Engineer Services-MES has published Spl Repair / Replacement To Lt Distribution System By Conversion Of Lt Oh Line Into Lt Ug Cable And Connected Works At Otm Accn Of Signals Records Under Age E / M Of Ge ( East ) Jbalpur As Per Boq. Submission Date for this Tender is 16-03-2022. Overhead Line Tenders in jabalpur Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

31203676
Corrigendum : Spl Repair / Replacement To Lt Distribution System By Conversion Of Lt Oh Line Into Lt Ug Cable And Connected Works At Otm Accn Of Signals Records Under Age E / M Of Ge ( East ) Jbalpur As Per Boq
Open Tender
Indian
Madhya Pradesh
jabalpur
16-03-2022

Tender Details

Spl Repair / Replacement To Lt Distribution System By Conversion Of Lt Oh Line Into Lt Ug Cable And Connected Works At Otm Accn Of Signals Records Under Age E / M Of Ge ( East ) Jbalpur As Per Boq

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 09-Mar-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 16-03-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 82400.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : SPL REPAIR/REPLACEMENT TO LT DISTRIBUTION SYSTEM BY CONVERSION OF LT OH LINE INTO LT UG CABLE AND CONNECTED WORKS AT OTM ACCN OF SIGNALS RECORDS UNDER AGE E/M OF GE (EAST) JBALPUR
Sl. No. Item Description
1Supply & lay XLPE insulated armored and PVC sheathed heavy duty electric cable with aluminum conductor 1100 Volt grade laid in tranches passing through pipes /ducts including testing complete of following cross sectional area and size Make of cable , NOTE-Rate is inclusive of cable lugs & cable gland.
22 Core,10 Sqmm cross sectional area
32 Core,16 Sqmm cross sectional area
44 Core,10 Sqmm cross sectional area
54 Core,16 Sqmm cross sectional area
64 Core, 25 Sqmm cross sectional area
73.5 Core, 35 Sqmm cross sectional area
83.5 Core, 50 Sqmm cross sectional area
93.5 Core, 70 Sqmm cross sectional area
103.5 Core, 95 Sqmm cross sectional area
113.5 Core, 120 Sqmm cross sectional area
123.5 Core, 240 Sqmm cross sectional area
13Supply, Installation, test and Commissioning CPRI APPROVED factoryfabricated, out door type, LT FEEDER PILLAR BOX of size not less then 0 .9 m width X 1.2 m heigth X 0.6 m depth,made out of 3.15 mm thick CRCA Sheetwith projected Globe roof for rain water protection Dust and Vermin Proof ,Double door withboth side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeddedwith 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete withinternal connection with suitable size of cable, cable lugs and cable glandsPCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation includingcomplete all as specified and comprising of the following :–
14(a) Aluminum bus bar 400 Amps - 01 Set
15(b) MCCB 250 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu-1 no ( incomming)
16(c)MCCB 125 A 25 KA,3 POLE ,thermal magnetic relese, Ics=100% Icu- 3 nos (O/G)
17(d)MCCB63 A 25 KA,3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T/Legrand /schneider- 2 nos (O/G)
18(e) Ammeter Class-1,digital pannal mounting type 96mmx96mmincluding CT 200X5 Amps 3 nos & selector switch
19(f) Voltmeter Class-1, digital pannal mounting type 96mmx96mm& selector switch
20(g) LED TYPE indicator lamp1 set (set of three for R,Y,B)
21Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth 32 x 6mm GI strip by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flatincluding earthingpit , charcoal common salt,Earthing lead 32x6 up to 7.5m, 20mm dia medium grade GI watering pipe, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pitcover including earth work complete all as shown in electrical plate No-5 of SSR-1991 (part-I) NOTE-: GI earth strip beyond 7.5 m & GI protection pipe shall be measured and paid for separately under relevant item of schedule.
22M & L for dismantling of LT overhead ACSR conductor of any size from its position by necessary disconnecting of conductor and removing complete all as directed by Engr-in-Charge.
23M & L for dismantling of earthing wire of any size from LT overhead poles of any size etc andremoving from site of work complete all as directed by Engr-in-Charge.
24Dismantling of U/S insulator of any size and type complete from itsposition and removing all as directedby Engr-in-Charge.
25Dismantling of U/S stay assembly carefully includingstay wire necessary excavation and earth work in any type of soil, demolition of PCC of any type and removing from site all as directed.
26M & L for dismantling of existing cross arms, angles, CI clamps, nuts etc from OH line and removing complete from LT pole of distribution span complete all as specified and directed.
27Dismantling of LT steel Tubular poles and srtting aside for re-use complete all as specified and directed Note : ((i) The Contractor would be responsible from removing the existing steel tubular poles and depositing with the MES yard. (ii) Incase erection of poles, Excavation refilling, removal and PCC will be measure and Paid seperately.
28Taking down street light Fittings any size and re-fixing again of LT pole complete all as specified and directed. Note :- Afterdismantling of ACSR/AAC, Earthing wires, cross Arms, channel, brackets, clamps, insulators etc complete and again re-fixing of street light fittings any & size and rate is deemed in included in unit rate quoted by the contractor.
29M & L for PCC 1:3:8 type D2 using 40 mm graded stone aggregate as in filling & mass concrete complete all as specified and directed.
30M & L for PCC 1:3:8 type B2 using 20 mm graded stone aggregate as in coping of pole ect including work & finishing the surface even & smooth with out using extra cement complete all as specified and directed.
31Material and labour for boring hole under the road/path/pavment/hard standing with the help of trenchless technology using ultra sound technique and necessary machine include HDPE pipe of 110 mm dia suitable for 0.4 mpa working pressure not less than one metre below ground level complete all as specified & directe buy Engr-in-charge at site. Note :- The cost of HDPE pipe shall be deemed to be include in quoted rate.
32S & F for GI Pipe light grade for cable protection passing under road/floor or for fixing to poles all as complete all as specified and directed the following :-
33100 mm Dai
3480 mm Dai
3550 mm Dai
36Supply & instll commissining and testingof CPRI Approved floor mounted outdoor cubicl type LT Feeder Pillar Box of uitabl size abricated out of 3.15 mm thick CRCA Sheet and angle iron 50X50X6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrngement on front and back with locking arrangement cable entry and exist from bottom with cble glands and gaskets, Copper bus bar 750 Amps rating fixed on porcelain insulator with inernal wiiring with suitable size of Copper strips to be used for incoming and outgoing connection of all switchs/MCCB"s & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
37(a) INCOMING
38(i) Thermal magnetic and microprocessor release MCCB 500 Amps, 4 Pole, 45 KA with front operated locking device - 01 Nos
39(b) OUTGOING
40(i) Thermal magnetic MCCB 250 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
41(ii) Thermal magnetic MCCB 225 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
42(iii) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 26 KA, Qty-02 Nos
43(iv) Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
44(v) Thermal magnetic MCCB 50 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
45(vi) Thermal magnetic MCCB 32 Amps, 2 Pole, Qty-01 Nos
46(vii) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
47(viii) (i) Voltmeter 0 - 500 Volts with selector switch - 1 Set.
48(ix) Amperemeter 0 - 200 Amps with selector switch - 1 Set
49(x) Indicator Lamp - R-Y -B (Set of three)
50(xi) Frequency meter 40-55 Hz - 01 Nos
51Supply & install commissioning and testing CPRI Approved floor mounted outdoor cubical type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, copper bus bar 450 Amps rating fixed on percelain insulator with internal wiring with suitable size of a copper strips to be used for incoming and outgoing connection of all switches/MCCB"s & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
52(a) INCOMING
53(i) Thermal magnetic and microprocessor release MCCB 300 Amps, 4 Pole, 45 KA with front operated locking device - 01 Nos
54(b) OUTGOING
55(i) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 26 KA, Qty-04 Nos
56(ii) Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
57(iii) Thermal magnetic MCCB 32 Amps, 2 Pole, Qty-01 Nos
58(iv) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
59(v) Voltmeter 0 - 500 Volts with selector switch - 1 Set.
60(vi) Amperemeter 0 - 200 Amps with selector switch - 1 Set
61(vii) Indicator Lamp - R-Y -B (Set of three)
62(viii) Frequency meter 40-55 Hz - 01 Nos
63Supply & install commissioning and testing CPRI Approved floor mounted outdoor cubical type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, copper bus bar 450 Amps rating fixed on percelain insulator with internal wiring with suitable size of a copper strips to be used for incoming and outgoing connection of all switches/MCCB"s & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
64(a) INCOMING
65(i) Thermal magnetic and microprocessor release MCCB 300 Amps, 4 Pole, 35 KA with front operated locking device - 01 Nos
66(ii)Eroload changeover switch over swutcg 320 Amp 4 pole, Qty - 01 Nos
67(b) OUTGOING
68(i) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 16 KA Qty - 04 Nos.
69(ii) Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 16 KAQty-01 Nos
70(iii) Thermal magnetic MCB 32 Amps, 2 Pole, Qty - 02 Nos
71(iv) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
72(v) Voltmeter 0 - 500 Volts with selector switch - 1 Set.
73(vi) Amperemeter 0 - 200 Amps with selector switch - 1 Set
74(vii) Indicator Lamp - R-Y -B (Set of three)
75(viii) Frequency meter 40-55 Hz - 01 Nos
76Supply & install commissioning and testing CPRI Approved floor mounted outdoor cubical type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, copper bus bar 450 Amps rating fixed on percelain insulator with internal wiring with suitable size of a copper strips to be used for incoming and outgoing connection of all switches/MCCB"s & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
77(a) INCOMING
78(i) Thermal magnetic and microprocessor release MCCB 300 Amps, 4 Pole, 45 KA with front operated locking device - 01 Nos
79(b) OUTGOING
80(i) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 26 KA, Qty-04 Nos
81(ii) Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
82(iii) Thermal magnetic MCCB 32 Amps, 2 Pole, Qty-01 Nos
83(iv) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
84(v) Voltmeter 0 - 500 Volts with selector switch - 1 Set.
85(vi) Amperemeter 0 - 200 Amps with selector switch - 1 Set
86(vii) Indicator Lamp - R-Y -B (Set of three)
87(viii) Frequency meter 40-55 Hz - 01 Nos
88Supply & install commissioning and testing CPRI Approved floor mounted outdoor cubical type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, copper bus bar 450 Amps rating fixed on percelain insulator with internal wiring with suitable size of a copper strips to be used for incoming and outgoing connection of all switches/MCCB"s & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
89(a) INCOMING
90(i) Thermal magnetic and microprocessor release MCCB 150 Amps, 4 Pole, 25 KA with front operated locking device - 01 Nos
91(b) OUTGOING
92(i) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 16 KA Qty - 01 Nos.
93(ii)Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 16 KA Qty - 01 Nos
94(iii) Thermal magnetic MCCB 32 Amps, 4 Pole, Qty-01 Nos (IV) Thermal magnetic MCCB 25 Amps, 4 Pole, 16 KAQty-01 Nos (V) Thermal magnetic MCB 32 Amps, 2 Pole, Qty-03 Nos
95(iv) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
96(v) Voltmeter 0 - 500 Volts with selector switch - 1 Set.
97(vi) Amperemeter 0 - 200 Amps with selector switch - 1 Set
98(vii) Indicator Lamp - R-Y -B (Set of three)
99(viii) Frequency meter 40-55 Hz - 01 Nos
100S&F Junction box for street lights of size 155 x210 x92 mm, 2 mm thick totally enclosed, with rubber gasket, water tight junction IP 66 protection single leaf shutter in front having proper locking arrangements and stud terminal (provision for socket bolting)-05 Nos suitable for 240 volts, 50 HZ, 2 wire internal wiring system including MCB SP 6 Amps-01 No and mounted on secutity light pole with suitable bracket nuts, bolts complete all as specified and directed.
101Taking down old unserviceable street light fitting any type & size and S&FLED street light lumanaries of size 45 CW high performance street light luminaire with single die ceramic base high power LED light source, IP 66 protectioncomplete with driver, lamp bracket with impect and corrosion resistant including thermal management arrangement with pre-wired and necessary mounting junction box including provision of 4 sq mm three core copper conductor cable multi stranded from fitting to junction box including GI pipr medium grade of 40 mm dai bracket 1.5 mtr long bend to required shape with suitable clamps made out of flate iron of size 40x6 mm- 2 sets, bolts& nuts, washers etc complete all as specified and directedMake:PHILIPS cat part No BRP 052 LED 045 CW SLMR FG S1 GR/HAVELLS/BAJAJ.
102Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth wire 4.00 mm dia by means of bolts, nuts, check nuts and washers complete up to and including test point made out of 40 x 6 mm alum flatincluding earthingpit, charcoal common salt, Earthing lead 4.00 mm dia up to 7.5 m, 20 mm dia medium grade GI watering pipe, G.I. protection pipe 15 mm dia up to 7.5 m long, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, PCC pitcover including earth work complete all as shown in electrical plate No-5 of SSR-2009 (Part-I)
103Excavation in trenches for laying of cables, poles and stay not exceeding 1.5 mtr wide and not exceeding1.50 mtr deep and getting out.in soft/loose soil.
104Returning & filling in, including spreading and leveling, watering and well ramming in layers n.exc. 25cm all as specified and directed by Engr-in-Charge.
105Removing excavated materials not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point.
106Unwashed Sand cushioning to under ground cable provided with a layer of 8 cm deepbefore laying and 15 cm covering above the top edge of cable after laying complete all as specified.Note : maesurement shall be done after puning down of sand.
107Supplying and layingBrick covering with width equal to length of bricks as mechanical protection to cable with well burnt sub class `B` bricks laid dry and flat complete all as specified and as directed.
108Supplying & laying unreinforced precast cement concrete cable covers, Class LV, Type-1 flat, size 250mm x 150mm x 40mm in trenches for cable protection, embossed with "LT 1100 Volts electric" on the top surface complete all as specified and as directed by the Engineer-in-Charge.
109S & F MCCB DB vertical type made of sheet steel, powder painted with Nutral bus Bar 200A, neutral link IP-43-IK09 protection grade, 415 Volts TPN with 4 way Double door including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and directed.
110MCCB TPN 100 Amps, 415Volts, 25KA, 4 POLE
111MCB SP 63 Amps"C" series, breaking capacity 10 KA of rating
112MCB SP 40 Amps"C" series, breaking capacity 10 KA of rating
113MCB SP 6-32 Amps"C" series, breaking capacity 10 KA of rating
114S & F MCB DB made of sheet steel, powder painted with Nutral bus Bar 200A, neutral link earth bar and Din rail, 230 voltsSPN with 8 way Double door IP-43 IK09 protection gradeincluding necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and directed.
115S&F On load change over switch 4 pole 320 Amps with sheet metal enclosure, Make : L&T/ Schneider/ Havells
116S & F cable route indicator/Marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregate) of size 900mm x 300mm x 100mm thick with "DANGER/LT 433 VOLTS CABLE /MES OR DANGER/MES" embossing on canble route Indiator/Marker including painting as per approed colour and buried in ground 45 cms including necessary earth work (as required/ordered at site) complete all as specified and as directed.
117Schedule of credit amount of Rs. 39,755.00 to be deducted during AOC
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail