| 1 | SCHEDULE \"A\" |
| 2 | Excavation in trenches not exc 1.5 m wide and not exc 1.5m in depth and getting out Soft/ Loose soil complete all as specified and directed |
| 3 | Returning filling in incl spreading levelling watering and well Ramming in layers not exc 25 cm thick complete all as specified and directed |
| 4 | Removing excavated material not exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified. |
| 5 | Supply, lay & test cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty)with stranded aluminium conductor, 1100 volts grade (Earthed ), of size 4 core 25 sq mm. all as specified and as directedby Engineer-in-ChargeMake: havells/Plaza/Finolex |
| 6 | Supply, lay & test cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty)with stranded aluminium conductor, 1100 volts grade (Earthed ), of size 4 core 16 sq mm. all as specified and as directedby Engineer-in-ChargeMake: havells/Plaza/Finolex |
| 7 | Supply and lay double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall confirming to ISI 14930 ( Part I and II) for protection of underground calbes of size 50 mm outer diawith all fittings. laid in trenches / road/ nallah or fixed along wall. poles or laid under floor (including cutting floor/Road and making good to match with existing adjoining surface etc for cable protection all as specified(excavation and earth work shall be measured and paid separately) Make: Rex/Poly/Gemini |
| 8 | S & F 90 Watt LED street light luminaire, High Performance street light luminaire having Single Die ceramic base high power LED light source, IP66 protection, PDC housing with Finless design and polycarbobate cover (IK08) rated Voltage 240 Volt ,50 HZ, operating voltage Range 120-270 Volt ,with mounting clamps, bolts and nuts,and bracket as specified with pole complete all as specified and as directed Make: Wipro LR02-102-XXX-57-G2)/Philips/CromptonNote: The contractor shall submit LM79 and LM80 test certificates of the manufacturers for the batch oflight fittings supplied. |
| 9 | Supply and fix Octagonal hot dip galvanised iron pole, 7m long with base plate, 300 mm long weather proof reinforced door opening with junction box mounting arrangement, Double arm bracket, Top dia 70mm, Bottom dia 130 mm, sheet thickness 3 mm,base plate 220X220X12mm. inbuilt junction box, \"J\"shape, EN8 foundation bolt with nuts template including RCC foundationof size as 1200x600x600 as per manuacturer\"s design conforming to IS 1786. The foundation shall extend above surrounding levels by 200mmall as directed by Engineer-in-charge. Make :Surya/ Bajaj /UtkarshNOTE :The contractor shall submit manufacturer\"s foundation drawing before commencement of foundation work. Excavation/earthwork, removal and returning filling included in the quoted rate. |
| 10 | Supply and fix Octagonal hot dip galvanised iron pole, 7m long with base plate, 300 mm long weather proof reinforced door opening with junction box mounting arrangement, Double arm bracket, Top dia 70mm, Bottom dia 130 mm, sheet thickness 3 mm,base plate 220X220X12mm. inbuilt junction box, \"J\"shape, EN8 foundation bolt with nuts template including RCC foundationof size as 1200x600x600 as per manuacturer\"s design conforming to IS 1786. The foundation shall extend above surrounding levels by 200mmall as directed by Engineer-in-charge. Make :Surya/ Bajaj /UtkarshNOTE :The contractor shall submit manufacturer\"s foundation drawing before commencement of foundation work. Excavation/earthwork, removal and returning filling included in the quoted rate. |
| 11 | Supply, laying & testing PVC insulated, PVC sheathed cable electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm , 3 core, 1100 Volts grade all as directed by Engr-in-Charge |
| 12 | Supply and fixing of time switches 415 V,three Phase integrated model with max Load 5-8 KW of 20 Amp rating with suitable MCBs and contactor fitted insideenclosure confirming to protection of IP66 with Hinged Lidall as specified and directed. |
| 13 | Supply and lay lead free uPVC pipe of 100 mm nominal diain trenches/Road Crossing or laying in floors including suitable amount of solvent for piping andall fittings including threaded and sovent base as per site requirement complete all as specified and directed. |
| 14 | Supply and fix Polycabonate Box confirming to IP 65/66 mounted on MS Stand with cable entry and gland/ lugsand necessary fitting and accessories of Cable size up to 25 Sqmm 4 core, including MCCB of 40 A Four pole 16 KA. And including PCC foundation all as specified and directed. |