Public Health Engineering Department-PHED has published Mayar Augmentation Renovation Of Water Supply Scheme Including Functional Household Tap Connection At Village Mayyar Distt Hisar Under Jal Jeevan Mission Category Ii Const Of 2 Rcc Ss Tank 2 Rcc Cwt Rcc Ss Well Pc Sv Houdi Earth Filling Raising Of Bw Dism. Submission Date for this Tender is 14-02-2022. Water Supply Project Tenders in hisar Haryana. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Construction ofwater purification plant of 1.00 MLD capacity SCADA based at Water Works,all other installation etc. comprising of DI pipe from existing raw water main/pump, inlet box of WTP and to CWT to C.W. suction well, inlet channel, Alum dozing, Flash mixing, Clari floculator, filter box, over head Reservoir for back wash including pump sets and electric control panel, waste water tank including pump sets and electric control panel, DI pipes, DI specials, manhole covers, air scour equipment, chemical house including chlorination equipment and arrangement of floe measurement and sand bed with automation complete in all respects as per NIT (Sluice valve of make IVC/ VAG ) |
2 | Supply & Erection of Horizontal spindle split casing type pumping sets of minimum Four (4) Star rating duties directly coupled to AC squirrel cage induction type motor with 1440 RPM, 3 phase, 50 Hz and accessories as described in Schedule No. II complete in all respect with priming arrangement with complete base frame. A) Raw water pump set 2 No. 600 Lpm , 12 mtr head 5.00 BHP Water Works A) Raw Water Pump Set 1800 LPM, 12.00 Mtrs. Head |
3 | Supply, erection, testing and commissioning of Wall mounted electrical panel board. fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated e deep having following items : approximate size 1200 x 900mm and 400mm a) For Raw water pump sets for 1800 Lpm x 12 M head = 2 No. AT W/W a) Main switch 100 Amp 2 No. ((L&T, Siemens, ABB) b) Volt meter 100 x 100mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) c) Amp meter 100x100mm range 0 to 100 Amp 2 No (AE/KAPPA/L&T) d) CT 100/3 Nos (AE/KAPPA/L&T) e) Vss 1 No & ASS 2 No. each of approved make f) SPP 1 No. of approved make g) motor starter, star delta, 2 No. for 1800 LPM x12 M Head Motor (L&T Siemens, AAB) h) Capacitor of suitable capacity-2 Nos i) Indicating Lamp-One set capacity = 2 No ) j) Change over switch 100 Amp = 1 No ) |
4 | For Clear water pump sets for 1800 Lpm x 40 M head = 2 No. AT W/W a) Main switch 100 Amp 2 No. ((L&T, Siemens, ABB) b) Volt meler 100 x 100mm range 0 to 500 volt 2 No:(AE/KAPPA/L&T) c) Amp meter 100x100mm range 0 to 100 Amp 2 Nos(AE/KAPPA/L&T). d) CT 100/3 Nos (AE/KAPPA/L&T) e) Vss 1 No. & ASS 2 No. each of approved make f) SPP 1 No. of approved make g) Motor Starter, star delta, 2 No. for 1800 LPM x40 M Head Motor (L&T Siemens, AAB) h) Capacitor of suitable capacity-2 No i) Indicating Lamp-One set j) Change over switch 100 Amp = 2 No ) |
5 | For Clear water pump sets for 600 Lpm x 30 M head = 2 No. for Boosting Station & W/W a) Main switch 63 Amp 2 No. ((L&T, Siemens, ABB) b) Volt meler 100 x 100mm range 0 to 500 volt 1 No:(AE/KAPPA/L&T) c) Amp meter 100x100mm range 0 to 100 Amp 2 Nos(AE/KAPPA/L&T). d) CT 100/3Nos (AE/KAPPA/L&T) e) Vss 1 No. & ASS 2 No. cach of approved make f) SPP 1 No. of approved make g) motor starter, star delta, 2 No. for 600 LPM x30 M Head Motor (L&T Siemens, AAB) h) Capacetor of suitable capacity-2 No i) Indicating Lamp-One set j) Change over switch 63 Amp = 1 No ) |
6 | Supply erection, testing of ISI marked copper wire for 6 Nos motors with under ground system in PVC and flexible pipes copper wine size complete in all respects with accessories like thimble etc. 6 sqm 3 core |
7 | 10 sq mm 3 core |
8 | 16 sqm 3 core |
9 | Providing,erection,esting of reputed make LED light 100 watts with fitting and accessories complete in all respects |
10 | Supply erection, testing of light fittings ineluding wire in the Pump Chamber with material upto 10 points including switch, button, plug. PVC conduit pipe & copper wire etc. as per approved specifications complete in respect |
11 | Less Credit of old material Bricks |
12 | Bricks Bats |
13 | Less Cerdit of old pumping machinery Raw Water= 2000 lpm 12 mtr Head |
14 | Clear Water= 2000 lpm 40 mtr Head |
15 | Operation and mantenence of WTP complete scope of work ( Distiction Material Supplied by the PHED) as per schedule - iv for a period of 5 year after 12 months during defect liability period and 3 months trial run period ( will be charged to a/mtc. estimate. Complete in all respect Operation and mantenence during defect liability period ( Operation Only ) after 3 months trial run period |
16 | For 1st Year Operation and Maintenance after defect liability period |
17 | For 2nd Year Operation and Maintenance after defect liability period |
18 | For 3rd Year Operation and Maintenance after defect liability period |
19 | For 4th Year Operation and Maintenance after defect liability period |
20 | For 5th Year Operation and Maintenance after defect liability period |