Cleaning / Maint Of Overhead Reservoir And Ug Sump Including Certain Repair Works At Water Supply Installations And Repair / Replacement Of Lt Panel Boards, Sluice Valve, Valve Chambers And Connected Items At Cme Cleaning / Maint Of Overhead Reservoir
Tender Overview
Project Description
Cleaning / Maint Of Overhead Reservoir And Ug Sump Including Certain Repair Works At Water Supply Installations And Repair / Replacement Of Lt Panel Boards, Sluice Valve, Valve Chambers And Connected Items At Cme Cleaning / Maint Of Overhead Reservoir And Ug Sump Including Certain Repair Works At Water Supply Installations And Repair / Replacement Of Lt Panel Boards, Sluice Valve, Valve Chambers And Connected Items At Cme
BOQ
| Sl. No. | Item Description |
| 1 | M & Lfor dewatering and cleaning the RCC over head tank of following capacity at the following locationby dewatering the overhead tank by any means and cleaning the complete inner surfces by rubbing / scrapping by wire brush to removethe sludge, washing with bleaching powder solution and then with water and draining out sludge, water completely and writting the details of tanks like date of cleaning, capacity of tanks etcon the out side of the tank with synthetic enamel paint with lettersize 20 cm high in white colour , over a black backgroundof size 100x60 cmall as specified anddirected for 3 lakh GLN capacity ( 2 compartment i.e. inner and outer of capacity 1.5 Lakh GLN) (Locnear FNBCP) |
| 2 | All as per ser item No. 1 above, but 25,000 GLN capacity (CTW and Sub stn No 01) |
| 3 | All as per ser item No. 1 above, but 100000 GLN capacity (SS No 9) |
| 4 | All as per ser item No. 1 above, but 20,000 GLN capacity (MAP ph-I, 454 OR PH, 80/60 single offrs) |
| 5 | M & Lfor dewatering and cleaning the RCC underground/semi under ground sumpat the following locationby dewatering the overhead tank by any means and cleaning the complete inner surfces by rubbing / scrapping by wire brush to removethe sludge, washing with bleaching powder solution and then with water and draining out sludge, water completely and details of tanks like date of cleaning, capacity of tanks etc shall be written on the out side of the tank with synthetic enamel paint with lettersize 20 cm high in white colour, over a black backgroundof size 100x60 cmall as specified anddirected of capacity 2,00,000 GLN capacity (Bhosari Pump House) |
| 6 | All as per ser item No. 5 above, but capacity 1,50,000 GLN capacity (Bhosari Pump House) |
| 7 | All as per ser item No. 5 above, but capacity 50,000 GLN capacity(Bhosari Pump House) |
| 8 | All as per ser item No. 5 above, but capacity 10,000 GLN capacity (SS No 1, BD Coy, 2x ARN) |
| 9 | All as per ser item No. 5 above, but capacity 20,000 GLN capacity (P454 PH, MAP PH II) |
| 10 | NOTE: For Item Sl No 1 to 9: cleaning ofOHT and UG sump atmentioned above will be carried out twicely with a gap of six month between two consecutive cleanings. |
| 11 | Material and Labour for dismantling the delivery pipe line of submersible pump set of capacity 10 HP from water mains, Lifting/taking out carefully the GI column pipes, submersible cable, defective submersible pump set from bore well for repair by means of chain pulley block or other T&P, transporting to workshop, opening the pump set including repair and servicing of pump, oiling/ greasing, lubricating the parts and reassembling, shifting back to bore well at various sites at CME, complete of depth up to 100 metres including installing, commissioning and testing on full load complete all as specified and as directed by Engr-in-charge. NOTE: i) The quoted rates deemed to be inclusive of jointing of submersible cable, reconnecting the delivery pipe line of submersible pump sets to water mains, testing for satisfactory running &continuous flow of water complete all as specified.ii) The quoted rates deemed to be inclusive of servicing of LT panel of bore well. |
| 12 | Material and Labour for dismantling the delivery pipe line of submersible pump set of capacity 15 HP from water mains, Lifting/taking out carefully the GI column pipes, submersible cable, defective submersible pump set from bore well for repair by means of chain pulley block or other T&P, transporting to workshop, opening the pump set including Repair and servicing of pump, oiling/ greasing, lubricating the parts and reassembling, shifting back to bore well at various sites at CME, complete of depth up to 100 metres including installing, commissioning and testing on full load complete all as specified and as directed by Engr-in-charge. NOTE: i) The quoted rates deemed to be inclusive of jointing of submersible cable, reconnecting the delivery pipe line of submersible pump sets to water mains, testing for satisfactory running & continuous flow of water complete all as specified.ii) The quoted rates deemed to be inclusive of servicing of LT panel of bore well. |
| 13 | Material and Labour for dismantling the delivery pipe line of submersible pump set of capacity 20 HP from water mains, Lifting/taking out carefully the GI column pipes, submersible cable, defective submersible pump set from bore well for repair by means of chain pulley block or other T&P, transporting to workshop, opening the pump set including Repair and servicing of pump, oiling/ greasing, lubricating the parts and reassembling, shifting back to bore well at various sites at CME, complete of depth up to 100 metres including installing, commissioning and testing on full load complete all as specified and as directed by Engr-in-charge. NOTE: i) The quoted rates deemed to be inclusive of jointing of submersible cable, reconnecting the delivery pipe line of submersible pump sets to water mains, testing for satisfactory running & continuous flow of water complete all as specified.ii) The quoted rates deemed to be inclusive of servicing of LT panel of bore well. |
| 14 | Material and Labour for rewinding of defective submersible motor by taking out burnt copper winding, cleaning the casing & slots with wire brush, washing with pressure water, drying, rewinding the motor with super enamelled copper winding wire of existing gauge and weight including replacement of all insulation material. “O” rings and other petty items required for making motor functional and checking the winding leak proof & taking out the electric connection and provision of suitable size new submersible cable up to 03 mtrs for motors of capacity 10 HP capacity complete all as specified and directed. |
| 15 | Material and Labour for rewinding of defective submersible motor by taking out burnt copper winding, cleaning the casing & slots with wire brush, washing with pressure water, drying, rewinding the motor with super enamelled copper winding wire of existing gauge and weight including replacement of all insulation material. “O” rings and other petty items required for making motor functional and checking the winding leak proof & taking out the electric connection and provision of suitable size new submersible cable up to 03 mtrs for motors of capacity 15 HP capacity complete all as specified and directed. |
| 16 | Material and Labour for rewinding of defective submersible motor by taking out burnt copper winding, cleaning the casing & slots with wire brush, washing with pressure water, drying, rewinding the motor with super enamelled copper winding wire of existing gauge and weight including replacement of all insulation material. “O” rings and other petty items required for making motor functional and checking the winding leak proof & taking out the electric connection and provision of suitable size new submersible cable up to 03 mtrs for motors of capacity 20 HP capacity complete all as specified and directed. |
| 17 | Supply and Fixing PVC insulated & PVC sheathed industrial copper conductor cable for submersible pump motor, flat three core of nominal area of conductor 10 Sqmm, 1100 volts including taking down old U/S cable complete all as specified and directed. Make: Polycab/Havells/Glostar |
| 18 | Taking out unserviceable starter from position and supply and fixing Fully automatic Star Delta starter in sheet metal enclosure Type MK1 suitable for operation on AC, Three phase four wire , 415 Volts, 50 Hz supplyfor Motor of capacity10/15HP complete Cat No SS96259 Make: L&T or equivalent in SEIMENS/HAVELLS complete all as specified and directed. |
| 19 | Taking out unserviceable starter from position and supply and fixing Fully automatic Star Delta starter in sheet metal enclosure Type MU-G20 suitable for operation on AC, Three phase four wire, 415 Volts, 50 Hz supplyfor Motor of capacity20HP complete Cat No SS95975 Make: L&T or equivalent in SEIMENS/HAVELLS complete all as specified and directed. |
| 20 | Supply and Fix 3 pole MCCB 100A capacity with S.C. rating of 50kA,415V, 50Hz, thermal and magnetic setting with provided leads on iron frame/lamination board , Type DN0-100M Cat No CM98944OOKO Make: L&T or equivalent of Standard/Havells/HPL/Indoasainwith taking down old u/s MCCB from existing panel all as specified and directed by Engineer In Charge |
| 21 | Supply and Fix 3 pole MCCB 250A capacity with S.C. rating of 50kA,415V, 50Hz, thermal and magnetic setting with provided leads on iron frame/lamination board, Type DN2-250M Cat No CM92171OOPOOG Make: L&T or equivalent of Standard/Havells/HPL/Indoasainwith taking down old u/s MCCB from existing panel all as specified and directed by Engineer In Charge |
| 22 | Supply and Fixing in repairs MCCB 4 pole, Type DU100H, 415 volts 50 Hz AC suitable for current carrying capacity 100 Amps rating, fixed and thermal magnetic release with breaking capacity 30 KACat No CM97933OOE2 Make : L&T or equivalent in Standard/Havells/Indoasian complete allas specified and directed. |
| 23 | S & F in replacement Power Contactor 3-Pole with AC Coil 300 Amps along with Aux. Contacts 02NO & 02NC ,440 volts 50Hz, MNX 250Make : L&TCat No.: CS94141 or equivalent make as approved in the existing panel, connecting up and testing all in repairs including material for wiring if required as specified and as directed. |
| 24 | S & F in replacement Power Contactor 3-Pole with AC Coil 160 Amps along with Aux. Contacts 02NO & 02NC,440 volts 50Hz MNX 110Make : L&TCat No.: CS94137 or equivalent make as approved in the existing panel, connecting up and testing all in repairs including material for wiring if required as specified and as directed. |
| 25 | S & F in replacement Power Contactor 3-Pole with AC Coil 160 Amps along with Aux. Contacts 02NO & 02NC ,440 volts 50Hz MNX 140Make : L&TCat No.: CS94138 or equivalent make as approved in the existing panel, connecting up and testing all in repairs including material for wiring if required as specified and as directed. |
| 26 | S & F in replacement side mounting Add-on Aux. contact blockfirst left/first right along with Aux. Contacts 01NO + 01NC, 440 volts 50Hzsuitable forMNX 95-650 power contactorMake : L&TCat No.: CS94205/CS94206 or equivalent make as aprroved in the existing panel, connecting up and testing all in repairs including material for wiring if required as specified and as directed. |
| 27 | S & F Thermal overload relay range type MN2 suitable for 9 to 15 Amps including taking down the old relayincluding material for wiring if required complete all as specified and directedCat No SS94142OOBO Make : L&Tor equivalent in Seimens/Havells |
| 28 | S & F in replacement MCB single pole 6A, C curve, 240/415Volts Cat No: BB10060C Make : L&T or equivalent make as approved in the existing panel, connecting up and testing all in repairs including material for wiring if required as specified and as directed. |
| 29 | S & F in replacement DIN Type Fuse links Type HN size 2, 400 A as per IS 13703 Part II suitable for Type FN 400/ FNX 400 S-D-F fuse base Make: L&T Cat No. SF 94335 or equivalent make as approved in the existing panel, connecting up and testing all in repairs including material for wiring if required as specified and as directed. |
| 30 | Supply and Fix 4 pole MCCB 250A capacity with S.C. rating of 25kA, 415V, 50Hz, thermal and magnetic setting with provided leads on iron frame/lamination board , Type DU250C Cat No CM90634OOPO Make: L&T or equivalent of Standard/Havells/HPL/Indoasainwith taking down old u/s MCCB from existing panel all as specified and directed by Engineer In Charg |
| 31 | S& F Non return valve (NRV) without by pass arrangement including provision of joining material such as insertion sheet 3mm thick, nut & bolts all as required at site 80mm dia bore ISI marked complete with rubber gasket all as directed. |
| 32 | S& F Non return valve (NRV) without by pass arrangement including provision of joining material such as insertion sheet 3mm thick, nut & bolts all as required at site 100mm dia bore ISI marked complete with rubber gasket all as directed. |
| 33 | S& F sluice valve class PN 1.6 without by pass arrangement including provision of joining material such as insertion sheet 3mm thick, nut & bolts all as required at site 100mm dia bore ISI marked complete with rubber gasket all as directed. |
| 34 | Dismantling and taking out unserviceable Dry Motor submersible sewage pump sethaving flow : 800m3/hr, 15 mtr head self cooling jacket system and solid handling capacity 100mm installed at STP Kasarwadiof capacity 70HP, Make Kishor Pumps, Model ASTRA SA 250-315 with the following work services:- a) Disconnecting water and electric connections, shifting the pump from Pump house to workshop ( to and fro) for carry out necessary repair.b) Opening the pump completelypart by part without damaging any parts, descaling and cleaning of all parts for inspection and finding serviceability / unserviceability of the parts. c) Repair and assembling of pumps by using existing serviceable parts and replacement of unserviceable parts as directed including necessary machining works required for proper setting and smooth functioning to achieve desired discharge of the pump. d) Rewinding of built in dry submersible motor 3 phase, 415 volts, 50 Hzof 70 HP capacityby using PVC insulated supper enamelled copper winding wire as per existing gaugeas per manufactures specifications and direction ,heating, varnishing complete. The repair work consisting of thoroughly cleaning of slots, removing all dirt , grease and other unwanted particle, reassembling the complete motor after repairs and re install in pump set including connecting.e) Re install the pump at its existing foundation, making electric and water connections, finally testing the pump set for its trouble free functioning complete. |
| 35 | Note : (i) Spare parts required for replacement shall be measured and paid seperately under appropriate items as supply only.(ii) Any Machining works required for balancing of inpeller /for fixing of new parts with existing shafts is deem to be included with the unit rate. No extra amount on this account shall be entertained seperately.iii) Any minor parts (Total cost less than Rs 200/) which are not covered under this schedule but inescapable requirement for repair shall also be deem to included with the unit rate quoted. No extra on this account shall be entertained by the Department. However any dispute GE\"s discussion in this regards shall be final & bindings. |
| 36 | M & L for cleaning of strainer 400mm dia including opening of strainer top cover by removing nut/bolts, removal of strainer screen and taking out dirt, mud, foreign particles accumulated inside strainer, assembling back and replacemnt of worn out nut bolts and gasket all as specified and directed by Engineer In Charge |
| 37 | Supply and Fix Selector Switch siutable for Voltmeter/ammeter for 3phase, AC supply 500 V, 50 Hz on provided box/panel and duly connecting with necesaary PVC wire leads and lugs with taking down old u/s MCCB from existing panel all as specified and directed by Engineer In Charge |
| 38 | S & F in repair Stainlesssteelwire cloth,0.71mm nominal dia of wire and average width of aperture 1.40mm, size of mesh 12mm and fixed with tinned tacks,of stainless steel wire staples including taking down old wire cloth etc and necessary fabrication/frame work for fixing wire cloth complete all as specified and directed by Engr in charge . |
| 39 | Supply andfix digital 3Ph 4 wire multi function meter, 5A, Class 1 with RS 485 model NOVA suitable for input voltage 17-520V AC (P-P) with inbuilt selector switch and CT/PT of suitable capacity Cat No WM30KFC3CRS.Make: L&T or equivalent of HPL/Seimens including taking down old u/s existing meter of any type |
| 40 | Supply andfix digital 3Ph Voltmeter Class 1model VEGA suitable for input voltage 17-520V AC (P-P) with inbuilt selector switch and CT/PT of suitable capacity Cat No WDS301FEV00. Make: L&T or equivalent of HPL/Seimens including taking down old u/s existing meter of any type |
| 41 | S & FIlluminated Push Button Projecting Head complete all as specified and directed in RED/GREEN in color, 240V AC,Cat No EG03PDL, Make: L&T/HPL with taking down old u/s push button of any type |
| 42 | S & F LED Indication lamp for LT Panel board RED/YELLO/BLUE,Surface Mounted Device LED technologyLow Power consumption < 0.6W Low Voltage GlowProtection (LVGP) Cat No: SIL 240A-240V ACMake: L&T or HPL/Havells |
| 43 | Supply and InstallSluice valve 400mm Class PN 1.0 with brass spindle and non rising stem including taking down old sluice of any type all as specified and as directed |
| 44 | Supply and InstallSluice valve 300mm Class PN 1.0 with brass spindle and non rising stem including taking down old sluice of any type all as specified and as directed |
| 45 | Material & labour for Earthing complete using galvanised iron earth plate electrode of size 60cm X 60cm X 6mm thick burried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers and protected by light grade 15 mm dia galvanised iron pipe and GI pipe light grade 20mm bore for watering, including funnel, wire mesh, CI pit cover and PCC chamber pit with PCC 1:2:4 type B-2 (including necessary excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown on electrical plate No. 3 of SSR Part-Ifor different capacities pumpsets. |
| 46 | Repair & maintenance of Vaccum circuit breaker HT 22KV, 3 phase 50 cycle outdoor type totally enclosure metal clad switch gear complete with VCB having rapturing capacity 350 MVA incl over load earth fault protection relay, ampere meter, volt meter etc maint and of up to rating cap 630 Amps complete all as specified and directed. |
| 47 | Repair & servicing of existing pump starter panels/main panel of various sizes ( for capacity of pump 70 HP) by replacing unserviceable components such as contactor, relays, single phase preventer, meters, cable lugs, etc and tightening of all connecting points, cable connections complete all as directed. (Note parts required for replacement shall be measured and paid seperately as supply only under appropriate items given here in after.) |
| 48 | M & L forrepair of u/s Electromagnetic water flow meter (EMF) ISO: 4064,Accuracy +0.5%,Make – Endress + Hauser, Model No- 10L4H-U-20A-1AN4B4AA installed at STP kasarwadi incl Transportationto & from workshopand replacement of u/s spares formeter. Installation and testing of repaired meter on same location all as specified and as direted by Engineer In Charge. |
| 49 | M & L for carry out water quality anyalysis for bacterial, chemical and biological analysis including for collection of water samples from the pump house or from location as specified by Engineer In Charge and testing from NABL approved testing laboratory, submitting of reprort for minimum following parameters(a) Turbudity (NTU) (b) pH(c) Total Hardness as CsCO2 (mg/l)(d) Sulphate as SO2 (mg/l)(e) Iron as Fe (mg/l)(f) Magnesium as Mg (mg/l)(g) E-Coli or thermotolerant coliform bacteria(h) Remarks of NABL approved testing lab |
| 50 | M & L for carry out testing of treated water of STP including for collection of water samples from the STP and testing from NABL approved testing laboratory, submitting of report for following parameters all as specified and directed by Engineer-in-Charge.(a) PH (b) TSS(c) BOD(d) COD(e) Residual Cl(f) Dissolved Oxygen(g) Coli Form (h) E-coli(j) Remarks of NABL approved testing laboratory if any Note: Rate quoted shall be deemed to be included for:(i) Cost of sterilised bottle as required (ii) To and fro transportation charges for collection of sample |
| 51 | M & L for periodical and preventive maintenance of AC, 3 Phase Induction motor of capacity 50HP by dismantling the motor completely without damaging any parts and applying air dry insulating varnish, of appropriateGrade (make Doctor Bake/Appex), cleaning bearings, refix at their existing position with bearing grease, checking terminals and thimbles, tightning all terminal joints, replace terminal plates where necessary, reinstall the motor at existing position, connecting electric connections and testing complete all as specified and directed. |
| 52 | M & L for periodical and preventive maintenance of AC, 3 Phase Induction motor of capacity 12.5HP by dismantling the motor completely without damaging any parts and applying air dry insulating varnish, of appropriateGrade (make Doctor Bake/Appex), cleaning bearings, refix at their existing position with bearing grease, checking terminals and thimbles, tightning all terminal joints, replace terminal plates where necessary, reinstall the motor at existing position, connecting electric connections and testing complete all as specified and directed. |
| 53 | M & L repair & servicing of existing pump starter panels of any size and capacity by replacing unserviceable components such as contactor, relays, single phase preventer, meters, cable lugs, etc and tightening of all connecting points, cable connections complete all as specified and directed. |
| 54 | Dismantling unserviceable Sluice Valve and Repair / servicingby opening stuffing box, MS Nut, Bolts, etc. for replacement and repairing of Spindle, Check nut, etc. and re-assembling repaired Sluice Valve and making functional and re-fixing the same including replacement of Gasket, Gland Packing, etc. of size 400mm complete all as specified and directed. |
| 55 | All as per item No. 52 above, but size 300/250/200mm |
| 56 | All as per item No.52 above, but size 150mm. |
| 57 | All as per item No. 52 above, but size 100mm. |
| 58 | Taking out foot valve from underground sump and repair / servicingof CI foot valves of any make and type fitted with suction lines of pumps installed in various pump houses by opening stuffing box, MS Nut, Bolts, etc. and replacement of unserviceable parts, Check Nut, etc, re-assembling the foot valves and refix its existing position including replacement of Gasket, Gland Packing, etc checking its functionability complete. size of foot valve 200mm.(Unit rate includes replacement of damaged parts of foot valve) |
| 59 | All as per item No. 56 above, but size of foot valve 100mm |
| 60 | All as per item No. 56 above, but size of foot valve 80mm |
| 61 | M & L for angle iron framed works of Fe-410 W (Gde-E-250) qualtiy - B all as specified and as directed including applying synthetic enamel paint two coats over a coat of red oxide primer complete all as specified and directed. |
| 62 | Taking out carefully existing valve pit cover along with frame/hold fast of any size (made of MS sheet/angle section) without damaging the existing brick work and keeping aside for reuse complete all as specified and directed. |
| 63 | Fixing only valve pit cover with frame on brick work properly without damaging any portion of valve pit and making good disturbed surfaces complete as directed ( valve pit cover and frame obtained against item No. 12 shall be used). |
| 64 | Taking out damaged MS sheet from Valve pit covers and supply and fixing of new MS sheet 3mm thick cut to pieces as required, fixing with and including either hooks or hinges or fixed by means of Electric arc/gas welding, providing locking arrangement complete all as specified and directed. |
| 65 | M & L for preparation of new metal surfaces of any description, over 10cm in width or girth and applying two coat of synthetic enamel paint over a coat of red oxide complete all as specified and directed. |
| 66 | M & L for preparation old paintedmetal surfaces of any description, over 10cm in width or girth and applying one coat of synthetic enamel paint.of approved tint complete all as specified and directed. |
| 67 | M & L for preparation of old painted metal surfaces of any description, over 10cm in width or girth and applying one coat of Aluminium paint complete all as specified and directed. |
| 68 | Demolition of old concrete/ Brickwork or stone/boulder masonry, built in cement mortarincluding ashlar facings, dressed stonework, precast concrete articles andprecastconcrete block walling complete all as specified and directed. |
| 69 | M & L for brick work with sub class \"B\" bricks, straight or curved on plan exc 6m mean radius and built in cement mortar 1:4 as in repair/raising /makingof valve pit chamber complete all as specified and directed. |
| 70 | M & L rendering 15mm thick plaster on fair faces of brick work or concrete surfaces with CM 1:4 finished the surface fair and even without using extra cement complete all as specified and directed. |
| 71 | M & L for cement concrete 1:4:8, type D-2, using 40mm graded stone aggregate as in foundations, filling and mass concrete complete all as specified and directed. |
| 72 | M & L for PCC1:2:4 type B1 with 20mm graded stone aggregate, in lintels upto1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, water troughs and the like including weathering, slightly rounded or chamfered angles and throating complete all as specified and directed. |
| 73 | M & L for Pre-cast cement concrete block masonry with solid blocks, exc. 10cm in width complete with PCC 1:3:6, type C-1, 20mm graded stone aggregate set in cement mortar 1:4 for walls of valve chamber and similar works all as specified and as directed |
| 74 | Dismantling and taking out from its positionexisting unserviceable sluice valveof any size (80mm to 100mm) by unscrewing of nut & boltsetc complete and removing from site all as directed. |
| 75 | Dismantling and taking out from its positionexisting unserviceable sluice valveof any size (150mm to 200mm) by unscrewing of nut & boltsetc complete and removing from site all as directed. |
| 76 | Supply, fix, and testing non rising spindle type sluice valves both end flanged with stainless steel spindle with gun metal control nut conforming to ISI mark IS 14846/2000, PN-1.6 including provision of joining material such as insertion sheet 3mm thick, nut & bolts with washerall as required at site of the following sizes of make : KIRLOSKAR/ VENUS/BIR/SIR VALVES/UPADHAYAY./KALPANA VALVES. :- |
| 77 | 80 mm dia |
| 78 | 100 mm dia |
| 79 | 150 mm dia. |
| 80 | 200 mm dia. |
| 81 | Suply, fix and testingBrass Spindle with check Nut/ Hub nut (Gun metal)and collars suitable forexisting Sluice Valve of size 400 mm of any make, incl taking down unserviceable complete all as specified and directed. |
| 82 | All as per item No. 75 above, but for 350mm Sluice Valve of any make |
| 83 | All as per item No. 75 above, but for 300mm Sluice Valve of any make |
| 84 | S & F in repair ball (float) valves high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball, screwed for 20mm bore iron pipe, including replacement of adjacent GI fittings complete, weight not less than 210 grm. Make : Prayag / Polytuff |
| 85 | S & F in repair ball (float) valves high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball, screwed for 15mm bore iron pipe, including replacement of adjacent GI fittings complete, weight not less than 142 grm. Make : Prayag / Polytuff |
| 86 | Supply and fix in repairs for bib tap standard of PTMT any colour of size 20mm high pressure screwed for iron pipe and fixed. (Minimum weight 125gms).Make : Prayag / Polytuff |
| 87 | Supply and fix in repairs for bib tap standard of PTMT any colour of size 15mm high pressure screwed for iron pipe and fixed. (Minimum weight 90gms).Make : Prayag / Polytuff |
| 88 | Supply ,installing, testing and commissioning ,factory made and testedCPRI approved LT panel board in door type, weather, vermin proof,platform mounted, suitable for 415 Volts,3 Phase 4 wire 50 HZ AC supply system all as specified and directed, with necessary bus bar arrangement with insulated aluminium bus bar 100 Amps rating installed on porcelain insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tappings, copper control wiring of required size,the panel shall be dust and vermin proof,IP-54 class protection andmade of 3 mm CRCA mild steel with 40x40x6mm angle iron frame and support with 0.3m above ground level and fixed with nut bolts,hinged doors, front& rear opening and locking arrangement and dulypowder coated on the out side and inside, cable gland and lugs for incoming and outgoing cable etc.,independent chambers to accommodate complete all as specified and directed includingthe following accessories:- |
| 89 | Incomer4 pole 63 A 25 KA ,MCCB,sL frame adjustable thermal and fixed magnetic setting- 01 No. |
| 90 | Outgoing 3 pole 16 A 16 kA MCCB- 03 Nos. |
| 91 | Digital Ammeter 0 to 50 Amps – 01 No. |
| 92 | Digital Voltmeter 0 to 500 Volts – 01 No. |
| 93 | Indicator lamp set (R,Y,B) - 01 Set |
| 94 | Starter suitable for 5 HP non clog submersible pump -03 Nos. and separate ammeter and voltmeter to each pump compartment |
| 95 | Single phase preventer -01 No. |
| 96 | M&L for earthing complete using copper earth plate electrode of size 60cmx60cmx3.15mm thick burried directly in ground vertically at a depth not less than 2.25mtr below normal ground level with top edge of earth plate at a depth not less than 1.5mtr below normal ground level earth plate surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using copper strip of size 20x3mm by means of bolts nuts check nuts and washers made of GI and protected by light grade 40mm dia galvanised iron pipe and GI pipe light grade 20mm bore for watering including funnel with wire mesh CI pit cover and PCC chamber pit with PCC 1:2:4 type B2 with MS angle iron frame, (including necessary excavation and earth work in any type of strata including fill up the earth pit with soil and disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown on electrical plate No 3 of SSR Part 1 2009Note :-Earth protection pipe and earthing lead upto and including 7.5m length is deemed to be included in the unit rate quoted by the contractor. |
| 97 | M&L earth continuity conductor or main earthing lead of size 25x4mm galvanised iron strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed. |
| 98 | S&F earth continuity conductor or main earthing lead of size 20x3 mm copper strip fixed to wall with S&F of porcelin /PVC insulator buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as directed by Engr-in-Charge |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender