Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Electrification |
| 2 | 90.2.1.1 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLSPVC insulated stranded single core copper conductor cable 650V grade, including providingswitch boardmain and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point |
| 3 | 90.2.1.2 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLSPVC insulated stranded single core copper conductor cable 650V grade, including providingswitch boardmain and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).TwinControl light point with 6A, plate ceiling rose - Short point |
| 4 | 90.2.1.3 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLSPVC insulated stranded single core copper conductor cable 650V grade, including providingswitch boardmain and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control light point without ceiling rose - Short point |
| 5 | 90.2.1.4 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLSPVC insulated stranded single core copper conductor cable 650V grade, including providingswitch boardmain and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point |
| 6 | 90.2.1.5 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLSPVC insulated stranded single core copper conductor cable 650V grade, including providingswitch boardmain and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Call bell point with 6 A bell push at one end and 6 A, 3 plate ceiling rose at other end - Short point |
| 7 | 90.2.1.6 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLSPVC insulated stranded single core copper conductor cable 650V grade, including providingswitch boardmain and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points |
| 8 | 90.2.1.7 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLSPVC insulated stranded single core copper conductor cable 650V grade, including providingswitch boardmain and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point |
| 9 | 90.3.22.3 : Supply & installation of light fittings on flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made of CRCA sheet of .5mm thickness complete with all accessories andlamps etc. directly on wall using 2 nos. flat iron brackets made from 25x6mm flat iron, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture |
| 10 | 90.3.20.3 : Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thicknesscomplete with all accessories andlamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture |
| 11 | 90.3.24.3 : Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories andlamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture |
| 12 | 90.3.24.4 : Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories andlamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 2X20W LED Lamp with box type fixture |
| 13 | od136420/2020_2021 : Supply, installation, testing and commissioning of pre-wired light fitting of all types complete with all accessories and LED panel square fitting etc. suspended from ceiling using 4 nos steel chain (16 SWG or nearest available size) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. Recess mounting type LED panel square fitting 36 W 2X2 100 lm/W using 4 nos steel chain.( LUXPOWER FGHE 36W 865 of Osram/equivalent make ) |
| 14 | 90.15.4.2 : Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea withpower factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance(LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 15 | 90.3.18.2 : Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps |
| 16 | od65685/2021_2022 : Supply and fixing pressure die cast aluminium housing bulk head fitting having IP 65 protectionwith 6.5W/700lmn LEDto wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required. |
| 17 | 90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 18 | od64901/2021_2022 : Supply ,installation testing and commissioning of ceiling fan of the following sizes using standard accessories excluding resistance type regulator ,wiring the down rod with 16/.2mm PVC insulated and PVC sheathe650/1100 V grade 3 core round copper conductor flex wire with extendedoriginal wiring etc as required.1200mm ceiling fan complete with service value minimum 4 (cub meter/minute/watt),air delivery minimum 210( cubic meter/minute) 300mmdown rod, 2 NOs canopies,wshackle kit,copper winding ,3 Nos blades and all remaining accessories including safety pin,nut,bolts,washers etc suitable for 230 V/240 V single phase AC supply complete as required |
| 19 | 1.58 : Supplying and fixing PVC batten/ angle holder including connection etc. as required. |
| 20 | od68905/2020_2021 : supply and providing 200 mm plastic shade for angle batten holder |
| 21 | od68901/2020_2021 : Supply and providing the 9W LED lamp in the existing fittings as required |
| 22 | 90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required. |
| 23 | od68965/2020_2021 : Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. -300/ 305 mm, single phase light duty exhaust fan in metal frame |
| 24 | 90.6.10.1 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm |
| 25 | 90.6.10.2 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm |
| 26 | 90.9.1.1 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required.50x50mm CableManagement System with base and lid |
| 27 | 90.9.1.2 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree |
| 28 | 90.9.1.4 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required.Internalangle 90 degree |
| 29 | 90.9.1.7 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required.End cap |
| 30 | 90.9.2.1 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid |
| 31 | 4.1.4 : Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness |
| 32 | 1.17.2 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 1.5 sq. mm |
| 33 | 1.17.4 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm |
| 34 | 1.17.11 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm |
| 35 | 1.17.13 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm |
| 36 | 1.17.20 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm |
| 37 | 1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 38 | 1.17.22 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm |
| 39 | 1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 40 | 1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm) |
| 41 | 1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 42 | 1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 43 | 1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 44 | 1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 45 | 90.10.3.15 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator |
| 46 | 90.14.28.2 : S & F Motor starters of the following ratingsThree phase DOL starters for 0.25HP to 7.5 HP motor |
| 47 | 2.16 : Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 48 | 90.11.1.14 : Supply and installation ofsheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) -double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 49 | 90.11.1.10 : Supply and installation ofsheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43) |
| 50 | 2.3.3 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door |
| 51 | 2.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door |
| 52 | 90.14.10.3 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 53 | od64263/2021_2022 : Supply, conveyance and fixing the following types & current rated Surge protection device conforming to IEC 161643 suitable for 385V, 50 Hz, AC supply with In=30kA, Imax=50kA,Vmax -1.6kV and response time less than 25ns with non-extinguishing zinc oxide varistor arrestor , in the existing panel assembly as required . OBO Combination arrestor V25-B+C, 3-pole + NPE 320 V |
| 54 | 90.11.1.20 : Supply and installation ofsheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+24) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 55 | 2.1.3 : Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N |
| 56 | 2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 57 | 2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 58 | 2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 59 | 2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 60 | 2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole |
| 61 | 2.14.2 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 62 | 2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 63 | 2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 64 | od39714/2021_2022 : Supply installation 33W LED post top lantern/gate light fitting with IP 66 rating with aluminium housing, stove enameled , acrylic cover complete with THD <10%, power factor >0.98, RoHS compliant, duly wired up for use on 230 V AC supply. directly on the existing pipe/ pole and giving connections with the existing wiring etc as required(K lite Id 4985 Prince Orna midi/equivalent) |
| 65 | 90.15.4.5 : Supply Conveyance, installation, testing and commissioning of 40W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea withpower factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance(LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 66 | od68983/2020_2021 : Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. 63 A, 415 V, 50 Hz, AC 23 A duty, 4 pole on-load change over switch |
| 67 | 90.14.1.2 : Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 68 | 90.14.2.1 : Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 69 | 90.14.3.1 : Supply and providing heavy duty \"A\" section neoprene gasket in the panel boardA\" section neoprene beeding suitable for 1.60/ 2.00 mm sheet |
| 70 | 90.14.4 : Supply and fabrication conveyance and installation of base frame of panel board using75 x 40 mm rolled steel channel (ISMC) |
| 71 | 90.14.5 : Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 72 | 90.14.6 : Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 73 | 90.14.7 : Supply and providing copper earth bus in the panel board |
| 74 | 90.14.11.14 : MCCB AccessoriesSupply and fixing rotary handle, Directtype(including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A |
| 75 | 90.14.11.2 : MCCB AccessoriesSupply and fixing one number earth fault Relay up to 125A to 200A with CBCT. |
| 76 | 90.14.11.12 : MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A. |
| 77 | 90.14.11.13 : MCCB AccessoriesSupply and fixing rotary handle, External type(including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A |
| 78 | od69002/2020_2021 : Supply, conveyance and fixing the following types & current rated control gears & switch gears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 63A Isolator switch disconnector |
| 79 | 90.12.7.40 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 80 | 90.12.7.28 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp |
| 81 | 90.12.7.41 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 82 | 90.12.7.42 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp |
| 83 | 90.12.5.2 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 6 sq mm |
| 84 | 9.1.2 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm) |
| 85 | 9.1.21 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 86 | 9.1.34 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm) |
| 87 | 9.2.29 : Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm |
| 88 | 9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 89 | 5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 90 | od39702/2021_2022 : Providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system |
| 91 | od39704/2021_2022 : Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate |
| 92 | 90.16.1.1 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG) |
| 93 | 90.16.1.2 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 94 | 90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 95 | 90.16.5.1 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG) |
| 96 | 90.16.5.2 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG) |
| 97 | 90.16.5.3 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 98 | od183856/2019_2020 : Supplying and fixing 63 A, 2 Way neutral links mounted on DMC/SMC base with connections, in existing meter board |
| 99 | od183857/2019_2020 : Supplying and fixing 63A, HRC Fuse Base with HRC Fuse link with connections, in existing meter /panel board |
| 100 | 90.16.2.1 : Supply and laying of the following sizes of B class GIpipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class) |
| 101 | 14.10 : Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). |
| 102 | 90.12.5.40 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm |
| 103 | 90.12.10.2 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size |
| 104 | od54879/2020_2021 : SITC of following KVA and capacity Diesel Generator set with integral acoustic enclosure as per latest CPCB norms with standard accessories as per technical details given below.A)20KVA DG set, with 32A 4 pole MCCB. Capacity - 20 KVA/16 K W @ 0.8PF1. Engine :a) Make of Engine -Cummins/Volvo/perkins/kirloskarb) Type of Engine - Diesel Enginec) No. of Cylinders - As per manufactures standards.d) Method of Cooling - Liquid Cooled e) Design - Suitable for generating set operation2.Standard accessories with Diesel Enginea) Fly wheel to suit flexible couplingb) Close Couplingc) Air cleanerd) Radiator with fan provided with fan guard.e) Fuel Pumpf) Fuel filterg) Lubricating oil filterh) Exhaust silencer i) Exhaust Muffler j) Battery Charger/Generator3. Engine Instrument Panel with the following itemsa) Starting switch with key or buttonb) Lubricating oil pressure gauge.c) Water temperature gauge.d) RPM Indicator with hour metere) Battery charging Ammeter4. Safety Controls for Enginea) Trip for low lubricating oil pressureb) Trip for high water temperature.5. Brushless Alternatora) Make -KEL/Kirloskar/stamford/LS b) Type - Self exited and self regulated.c) System of Voltage - 3 phase, 415 V,d) Frequency - 50 Hze) Insulation - Class F/H The Alternator should confirm to IS 4722. Operation and service manual, spares and tools shall be provided.6. Fuel Tank Suitable size built in type integrated with the acoustic enclosure Fuel connection shall be done as per standards7. Battery Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. Automatic Battery charger Solid state phase indication lamp for supply ON/OFF with HRC protection. standard control panel as per Kerala Electrical Inspectorate requirements and accessories such as Multi function meter and separate Energy meter etc. Complete. The DG set shall have a guarantee period of 3 years from date of commissioning. 8).Annual maintenance shall be carried out for at least three years after commissioning by the selected contractor. |
| 105 | od183865/2019_2020 : Supply and providing cladding for the 50 mm dia / nearest size exhaust pipe of the DG set by wrapping mineral wool around the pipe, fixing it firmly with in the pipe using chicken mesh, applying over all coating to the system using 0.40mm thick aluminium sheet and make it air tight to ensure sound and thermal proof to the system |
| 106 | 14.1 : Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 107 | 14.7 : Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required. |
| 108 | 14.9 : Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 109 | od183866/2019_2020 : Charges for preparation of Electrical/fire Drawing per A3 sheet first copy |
| 110 | od183867/2019_2020 : Copying chargesof Electrical/fire Drawing per A3 sheet additional copies |
| 111 | od183868/2019_2020 : Supply and providing 2.5mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 11 KV dielectric strength. |
| 112 | od183869/2019_2020 : Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint \"FIRE\" mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required. |
| 113 | od183870/2019_2020 : Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision. |
| 114 | od183871/2019_2020 : Providing and fixing Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5 mm cut out dia in existing panel and giving connection complete |
| 115 | od183872/2019_2020 : Providing and fixing Blue colour LED indicator, AC/DC, 22.5 mm cut out dia in existing panel and giving connection complete |
| 116 | od183873/2019_2020 : Providing and fixing following multi function meter to read: V, A, F, 3 phase accuracy class 1 in existing panel and giving connection complete |
| 117 | od183874/2019_2020 : Providing and fixing following metering ct 150/5A 5VA /1Aaccuracy class 0.5 existing panel and giving connection complete |
| 118 | od183876/2019_2020 : Providing and fixing Danger notice board 250x200mm enamelled in existing panel and giving connection complete |
| 119 | od39237/2021_2022 : Supply and Fixing of Cable alley, 100 x 40 mm aluminium anodised legend plates. |
| 120 | od39239/2021_2022 : Supply and fixing of Bus bar chamber, 100 x 40 mm aluminium anodised legend plates |
| 121 | od183877/2019_2020 : Supply and providing brass bolt and nut 25x6mm |
| 122 | od183878/2019_2020 : Supply and providing brass bolt and nut 25x3mm |
| 123 | od183879/2019_2020 : Supply and providing brass bolt and nut 12x3mm |
| 124 | od183880/2019_2020 : Painting letters or figuresof the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required 2.50 cm, 4 cm or 5 cm height |
| 125 | od183881/2019_2020 : Fee to be paid to KSELB towards scrutiny & inspection , meter testing etc (actual amount will be reimbursed on production of original documents) |
| 126 | Lightning Protection System |
| 127 | 6.7 : Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightningconductor complete as required.(For horizontal run) |
| 128 | 6.8 : Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightningconductor complete as required.(For vertical run) |
| 129 | 6.12 : Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 130 | 6.14 : Providing and laying G.l. tape 32 mm X 6 mm from earth. electrode directly in ground as required. |
| 131 | 6.4 : Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail