| 1 | Supplying and erection of150x150mmx6mm RS Joist pole of 13mtr long with concreting of support with PCC 1:3:6 using 40mm BHG metal 2.02mtrx0.3mtrx0.3mtr=0.182cumincluding earth excavation workof size 7\"0\"x2\"x2\" with all accessories, labour, material, T&P to complete the work as per the direction of EIC |
| 2 | Supplying and erection of150x150mmx6mm RS Joist pole of 11mtr long with concreting of support with PCC 1:3:6 using 40mm BHG metal 1.83mtrx0.3mtrx0.3mtr=0.165cumincluding earth excavation workof size 6\"x2\"x2\" with all accessories, labour, material, T&P to complete the work as per the direction of EIC |
| 3 | Supplying and erection of 9mtr. longLT PSC pole (300KG)with concreting of support with C:C 1:4:8 using 40mm BHG metal size 5\"6\"x2\"x2\" = 0.62 cumpadding 900x600x150mm =.081cum total 0.701cum including earth excavation workof size 5\"6\"x2\"x2\" with all accessories, labour, materials, T&P etc to complete the work as per the direction of EIC |
| 4 | Supply, & fixingof 100X50X6mm MS channel including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 5 | Supply, & fixingof 75X40X6mm MS channel including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 6 | Supply, & fixingof 50X50X6mm MS angle including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 7 | Supply & Fixing of GI Nut, Bolt & Washer including all materials, labour cost, T&P etc complete work as per Direction of EIC. |
| 8 | Supply, Installation & commissioning of 33KV disc Insulator(90KN)of Polymer type including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 9 | Supply, Installation & commissioning of 33KV Hardware Fittings (B&S 90KN,4bolt)including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 10 | Supply, Installation & commissioning of 33KV pin Insulatorof Polymer type including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 11 | Supply, Installation & commissioning of 33KV post insulator ( 2X24KV post insulator stack) including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 12 | Supply, Installation & commissioning ofHT stay set (Complete) with stay Insulator, stay Clamp,7/8 SWG GI stay wire (10Kg each),concreting of stay with PCC 1:3:6 in 0.5mtr*0.5mtr*0.5mtr=0.125cumincluding earth excavation workincluding excavation work, all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 13 | Supply and fixing of medium40mm dia medium GI pipe Earthing device 3 Mtr longincluding charcoal ,salt construction of earthing chamber with RCC slab cover, earth excavation work and all accessories, cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 14 | Supply & Drawal of 232 Sqmm AAA conductor including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 15 | Supply, Installation & commissioning of 33KV, (30KV,10KAmp) Lightning Arrester including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 16 | Supply& fixing of 33KVO/D VCB of 1600A,with indoor CR panelwithout PT and with outdoorCT (CTR 600-300-150/1-1A,15VA,STC 25KA/3second, class 0.5 & 5P10) for FEEDER and TRANSFORMER protection includingall accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 17 | Supply, Installation & commissioning of 33 KV 1250 Amp double break (turn & twist centre rotating) Isolator with out earth switch with PI (polymer)including all materials and accessories, labour cost, T&P etc complete work as per direction of EIC. |
| 18 | Supply& fixing of 33KV single phasePT(33KV/V3/110/V3) Oil cooled class 0.5/3Pwith O/P burden 100VA )includingall accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 19 | Supply &fixing of 24V DC power pack with internal wiring including all materials,accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 20 | Supply &fixing of Al. cable socket for VCB connection & MU arrangement including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 21 | Supply & laying of 10 Core 2.5Sq mm Cu. control cable ( unarmoured) including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 22 | Supply & laying of 4 Core 2.5Sq mm Cu. control cable ( unarmoured) including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 23 | Supply & laying of 2 Core 2.5Sq mm Cu. control cable ( unarmoured) including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 24 | Supply & Fixing of T clamp for 232sqmm AAAconductor including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 25 | Supply and fixing of 25x6mm GI flat including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 26 | Supply and fixing of 50x6mm GI flat including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 27 | Supply and fixing of GI medium pipe suport for pressure channel including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 28 | Sundries for survey, tree cutting, small size nut & bolt with washer, Allm. Binding Tape, Danger Board, etc including all associries, labour cost, T&P etc complete work as per Direction of EIC. |
| 29 | Supply and construction of brick masonary plinth for transformer & VCB as per TPNODL specification including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 30 | Supply and construction of Control room of size (20\"x30\"x12\") with foundation, brick masonary wall, lintal, RCC roof, flooring, colour washing (Inside & out side), doors and windows with M.S grill and all other required work as per building code including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 31 | Supply, Installation & commissioning of 33KVV-Cross arm including all accesories, labour cost, T&P etc complete work as per Direction of EIC. |
| 32 | Supply, Installation & commissioning of 33KV F-clamp including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 33 | Supply, Installation & commissioning of 33KV back clamp for V-Cross arm including all accesories, labour cost, T&P etc complete work as per Direction of EIC. |
| 34 | Supply, Installation & commissioning of Coil type Earthing Support including all associries, labour cost, T&P etc complete work as per Direction of EIC. |
| 35 | Supply & Drawal of 100 Sqmm XLPE insulated AAA conductor including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 36 | Supply & Fixing of PG clamp for 100sqmminsulated conductor including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 37 | Supply, Installation & commissioning of Anticlimbing device of GI barbed wire with clamping arrangement etc. including all associries, labour cost, T&P etc complete work as per Direction of EIC. |
| 38 | Supply & painting of Red Oxide Paint including all materials, labour cost, T&P etc complete work as per Direction of EIC. |
| 39 | Supply & painting of Aluminium Paint including all materials, labour cost, T&P etc complete work as per Direction of EIC. |
| 40 | Supply & painting of black Paint including all materials, labour cost, T&P etc complete work as per Direction of EIC. |
| 41 | Supply, Installation & commissioning of 33KV, 3-pole,400Amp AB switch including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 42 | Supply, Installation & commissioning of 33KV,3Phase, 400AmpHG fuse including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 43 | Supply, Installation , testing & commissioning of indoor LT distribution panel Board for 100 KVA Sub-station made with 16 SWG CRCA sheet with 03 Nos. Kitkat fuse, three pole alluminium bus-bar, neutral busbar,earth bar,,hinged acrylic cover with indicator lamp, selector switch, digital Ammeter & Voltmeter, required wiring and connections duly painted Incoming- 160Amp,36kA, 4 Pole MCCB=1no.Outgoing- 125Amp,36kA, 4 Pole MCCB=2no. incuding all accessories, cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 44 | Supply and Installation of 33/0.415 KV 100KVA, ,50 Hz, 3phase, BIS energy level-IICore type, oil immersed type, ONAN cooling, out door type Copper wound transformer , LT cable end boxand all accessories, cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 45 | Supply, Installation , testing & commissioning of LT out door distribution box made out of 2mm CRCA sheet incuding Kitkat fuse with MCCB for 1000 KVA Sub-Station as per the specification of TPNODL including all accessories, cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 46 | Supply, Installation,testing & commissioning of1000KVA,33/0.433 KV, Outdoor,ONAN, Dyn 11 with off load Tap Changer ,50 Hz, 3phase, BIS energy level-IICore type, Copper wound transformer with following spoecificationsTap range-+5% to -10% in steps of 2.5%, 07 positions.Temp rise(Oil/Winding/amb):-40/45/50 deg. CLosses & impedance at 75 deg.C impedance-5% (Subject to its tolerence)and all other standard accessories like Rating and terminal marking plate, two earthing terminals, Pressure release device with trip contact, oil filling hole with Cap,, Oil level Indicator, Dehydrating Silica Gel Breather, Thermometer Pocket, Filter and drain Valve, Jacking Pads and lifting lugs, Detachable type Cooling Radiators, Winding Temp. Indicator with contact alarm & Trip (WTI), Oil Temp Indicator with contact alarm(OTI),Marshalling Box IP-55, Buchhloz Relay with Alarm and Trip Contact, Off Load Tap Changer, Transformer Oil as per IS: 335, Terminal arrangement (HV-Outdoor Bushing, LV- Cable Box), cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 47 | Supply, Installation & commissioning of no.6/8 SWG GI wire for earth connection including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 48 | Supply & laying of 3.5 Core 500Sq mm, 1100 Volt grade XLPE insulatedAluminium unarmoured cable of 1.1 KV grade including cable gland,Cable Socket, all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 49 | Supply & Fixing of Al. Cable socket,lug ofdifferent sizeincluding all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 50 | Supply & Fixing of 33 KV danger boardincluding all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 51 | Supply, Installation,testing & commissioning of 2000KVA, 33/0.433 KV, Outdoor,ONAN, Dyn 11 with off load Tap Changer ,50 Hz, 3phase, BIS energy level-IICore type, oil immersed type,Copper wound transformer with following spoecificationsTap range-+5% to -10% in steps of 2.5%, 07 positions.Temp rise(Oil/Winding/amb):-40/45/50 deg. CLosses &impedance at 75 deg.C impedance-6.25% (Subject to its tolerence)and all other standard accessories like Rating and terminal marking plate, two earthing terminals, Pressure release device with trip contact, oil filling hole with Cap,, Oil level Indicator, Dehydrating Silica Gel Breather, Thermometer Pocket, Filter and drain Valve, Jacking Pads and lifting lugs, Detachable type Cooling Radiators, Winding Temp. Indicator with contact alarm & Trip (WTI),Oil Temp Indicator with contact alarm(OTI),Marshalling Box IP-55, Buchhloz Relay with Alarm and Trip Contact, Off Load Tap Change, Transformer Oil as per IS: 335, Terminal arrangement (HV-Outdoor Bushing, LV- Cable Box), cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 52 | Supply, Installation , testing & commissioning of outdoor LT distribution panel Board for 1000 KVA Sub-station made with 14SWGCRCA sheet metal ,1600A alluminium bus-bar, neutral busbar,earth bar,,hinged acrylic cover withrequired wiring and connections duly painted with the following specifications.Incoming- 1600Amp, 50kA, 4 Pole,EDO ACB with MP based release for O/C, S/C, E/F, S/T, Release, U/V(LSING+Display+BCD switch for selection)-01 NoRYB Indication Lamps-3 NosON/OFF/TRIP/Trip Healthy/Spring Charge Indication Lamps,-05 Nos TripCkt Health push Botton-01 No2A SP MCB, 10KA, C-Curve-04 NosAnalog Ammeterwith selector switch-0 to 1600A, Cl-1- 01 NO Analog Voltmeter with selector switch-0 to 500A, Cl-1- 01 NODigital MFM Meter with RS485 Port, Class-1=1 NoResin Cast CT-5000/5A,15VA, Cl-1=03 Nos Resin Cast CT-1600/5A,15VA, Cl-5P10=03 Nos Aux Contactors-2NO+2NC=10 NosRestricted Earth Fault RelayUV/OV Relay(LVM)+10A 4P MCB=01 NoMaster Trip Relay, On delay Timer, a Power supply unit, Emergency stop push botton, TNC Breaker Control Switch, L/R Selector Switch, Panel Space Heater, Thermostart, Panel Lamp, Power Socket, 1.6-2.5A TP MPCB, Control Transformer(415V/110V/230V AC, 500 VA, 50HZ) 6A DP MCB-05 Nos, Control Terminals etc |
| 53 | Outgoing-800Amp,3P+NL,50KA MCCB with TM based releases for O/C,S/C, E/F+RHOM+SPR+Auxiliary 1C/O+TAC 1 C/O= 02 Nos200Amp,3P+NL,50KA MCCB with MP based releases for O/C,S/C, E/F+RHOM+SPR+Auxiliary 1C/O+TAC 1 C/O=2 Nos125Amp,3P+NL,50KA MCCB with TM based releases for O/C,S/C, E/F+RHOM+SPR+Auxiliary 1C/O+TAC 1 C/O=2 NosPanel Enclouser-3200W x 2200H x 1000D mm(outdoor type ,IP-55 double door with canopy) incuding all accessories, cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 54 | Supply, Installation , testing & commissioning of outdoor LT distribution panel Board, for 2000 KVA Sub-station made with 14 SWG CRCA sheetwith ,2500A alluminium bus-bar, neutral busbar,earth bar,,hinged acrylic cover withrequired wiring and connections duly painted with the following specifications.Incoming- 1600Amp, 50kA, 4 Pole,EDO ACB with MP based release for O/C, S/C, E/F, S/T, Release, U/V(LSING+Display+BCD switch for selection)-01 NoRYB Indication Lamps-3 NosON/OFF/TRIP/Trip Healthy/Spring Charge Indication Lamps,-05 Nos TripCkt Health push Botton-01 No2A SP MCB, 10KA, C-Curve-04 NosAnalog Ammeterwith selector switch-0 to 2500A, Cl-1- 01 NO Analog Voltmeterwith selector switch-0 to 500A, Cl-1- 01 NODigital MFM Meter with RS485 Port, Class-1=1 NoResin cast CT-5000/5A,15VA, Cl-1=03 Nos Resin cast CT-1600/5A,15VA, Cl-5P10=03 Nos Aux Contactors-2NO+2NC=10 NosUV/OV Relay(LVM)+10A 4P MCB=01 NoMaster Trip Relay, On delay Timer, a Power supply unit, Emergency stop push botton, TNC Breaker Control Switch, L/R Selector Switch, Panel Space Heater, Thermostart, Panel Lamp, Power Socket, 1.6-2.5A TP MPCB, Control Transformer(415V/110V/230V AC, 500 VA, 50HZ) 6A DP MCB-05 Nos, Control Terminals etc |
| 55 | Outgoing-800Amp,3P+NL,50KA MCCB with MP based releases for O/C,S/C, E/F+RHOM+SPR+Auxiliary 1C/O+TAC 1 C/O= 02 Nos400Amp,3P+NL,50KA MCCB with TM based releases for O/C,S/C, E/F+RHOM+SPR+Auxiliary 1C/O+TAC 1 C/O=2 Nos200Amp,3P+NL,50KA MCCB with TM based releases for O/C,S/C, E/F+RHOM+SPR+Auxiliary 1C/O+TAC 1 C/O=2 Nos125Amp,3P+NL,50KA MCCB with TM based releases for O/C,S/C, E/F+RHOM+SPR+Auxiliary 1C/O+TAC 1 C/O=2 NosPanel Enclouser-3700W x 2200H x 1000D mm(outdoor type ,IP-55 double door with canopy) incuding all accessories, cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 56 | Construction of boundary wallwith grill gate, metal& sand spreading including all accessories, labour cost, T&P etc complete work as per Direction of EIC and as per specification of TPNODL. |
| 57 | Supply & laying of 33KV,3core ,300sq mm XLPE insulated armouredaluminium cable including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 58 | Supply & Fixing of out door type Heat shrinkable type jointing kitfor 33KV,3core ,300sq mm XLPEcable including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 59 | Supply & Fixing of Indoor type Heat shrinkable type jointing kit for 33KV,3core ,300sq mm XLPE cableincluding all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 60 | Cable laying in the cable trench with brick lining,sand coutioning along with romovable cover slab as per IS specification includingall acessories , labour cost, T & P etc. complete work as per direction of EIC. |
| 61 | Suppl & fixing of150 MM dia medium GI pipe including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 62 | Construction ofcubicle room (15\"X15X10\") withincluding supply ofall materials , labour cost, T & P etc. complete work as per TPNODL specification and direction of EIC. The Cubicle room should be with a door of suitable size and a grilled window for installation of metering cubicle and meter. The window is to be provided with proper M.S grills and mesh arrangement adjecent to the door, so that the metering arrangement remains visible from outside. |
| 63 | Supply, Installation & commissioning ofLT stay set (Complete) with stay Insulator, stay Clamp,7/12 SWG GI stay wire ,concreting of stay with PCC 1:3:6 in 0.5mtr*0.5mtr*0.5mtr=0.125cumincluding earth excavation workincluding excavation work, all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 64 | Supply and Fixing of suspension clamp with eye hook for the AB cable including all acessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 65 | Supply and fixing of Dead end Clamp for AB cable including all acessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 66 | Supply & Drawal of 3x95+1x70+1x16sqmm LT XLPE ABcable including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 67 | Supply, Installation , testing & commissioning of outdoor LT distribution double door panel Board for made with 16 SWG M.S sheet metal with 03 Nos. Kitkat fuse, three pole alluminium bus-bar, neutral busbar,earth bar,,hinged acrylic cover with indicator lamp, selector switch, digital Ammeter & Voltmeter, required wiring and connections duly painted Incoming- 250 Amp,36kA, 4 Pole MCCB=1no.Outgoing-125,36kA, 4 Pole MCCB=2no.for two bay incuding all accessories, cost of labour, materials, T&P etc complete work as per direction of EIC. |
| 68 | Supply and Fixing of piercing connector of type-A main & tap-16 to 95sq mm AB Cable including all acessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 69 | Supply & drawl of 4 Core 16Sq mm, XLPE insulated Aluminium armoured cable includingall accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 70 | Supply & drawl of 3.5 Core 95Sq mm,XLPE insulated Aluminium armoured cable includingall accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 71 | Supply & drawl of 3.5 Core 150 Sq mm, XLPE insulated Aluminium armoured cable includingall accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 72 | Supply and fixing 120W,240V LED street light fitting including GI pipe bracket, necessary wiring from loop-in-box with 1.5 sqmm copper wires inside PVC pipes etc complete as required withaccessories and lamp etc.including all labour cost,T&P etc complete work as per direction of EIC |
| 73 | Supply & Drawal of 3x50+1x35+1x16sqmm LT XLPE insulated ABcable including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 74 | Supply & laying of 2.5sqmm 3core copper CTS wire including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 75 | Supply & fixing of junction box of size 8\"x6\" with IP 65 protected including all accessories, labour cost, T&P etc complete work as per Direction of EIC. |
| 76 | Supply and Fixing ofout door type street light Panel board of required size with 16 SWG MS sheet including front & end Enclousers, locking arrangement, painting, febrication work, R-Y-B indicator,anlogue timer switch,auto manual selector switch , indicator, 4pole connector and 63Amp, 415V TPN MCCB & concreting work with all accessories, cost of labour, T&P etc as per direction of EIC. |
| 77 | Supply & laying of 3.5 Core 50Sq mm, 1100 Volt grade XLPE insulated Aluminium armoured cable of 1.1 KV grade including cable gland,Cable Socket, all accessories, labour cost, T&P etc complete work as per Direction of EIC. |