Military Engineer Services-MES has published Ge ( U ) / Chm-48 / 2021-22 Provn Of Repairs / Maintenance Steel Tubular Pole Mccbs Earthing Xlpe Cable And Other Allied Works At Chandimandir Ge ( U ) / Chm-48 / 2021-22 Provn Of Repairs / Maintenance Steel Tubular Pole Mccbs Earthing Xlpe Cable An. Submission Date for this Tender is 25-01-2022. Electrification Work Tenders in chandimandir Haryana. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 15-Jan-2022 | Amendment in BOQ | Other | 18-01-2022 |
2 | 18-Jan-2022 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 25-01-2022 |
Sl. No. | Item Description |
1 | Excavation in trenches for foundations, laying / taking out of cables, erecting of poles etc, in any type of soil, not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr in width and getting out, complete all as specified and as directed. |
2 | All as per the description of Srl item No 1 herein above but depth exceeding 1.50 metre but not exceeding 3.00 metre |
3 | Returning, filling in soils, in trenches including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed |
4 | Removing excavated soils to a distance exceeding 50 metres and not exceeding 100 metre and depositing where directed at a level not exceeding 1.50 metre above the starting point. |
5 | Cement concrete (1:4:8) type D-2 (using 40mm graded crushed stone aggregates) as in foundation and mass concrete etc complete all as specified and as directed. |
6 | Cement concrete (1:3:6) type C-2 (using 40mm graded crushed stone aggregates), in foundation and mass concrete etc complete all as specified and as directed. |
7 | Cement concrete (1:2:4) type B-1 (using 20mm graded crushed stone aggregates) as in coping, blocks, bed plates, kerbs etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary formwork as required complete all as specified and directed. |
8 | Supply, erection and fixing in position 9.00 metre long, steel tubular swaged poles complete with mild steel base plate, flat topwelded type 410, SP-31 IS:2713 marked, drilling of necessary holes including bolts, nuts and washers as required and pointed with two coats of Aluminium paint over a coat of red oxide primer on exposed, surfaces of poles and two coats of black bituminous paint throughout internally and externally upto the planting depth including providing reflective strips of width 10cm upto a height of 1.20m from ground level in alternate colour yellow and black around the pole of pattern as approved by GE and marking pole number at appropriate height with shade and colour as approved by Engineer-in-Charge complete all as specified and as directed, with and including dismantling and taking up old existing damaged steel tubular pole and removing from site of work complete all as directed. Note : Excavation earthwork and concrete work shall be measured and paid for separately. |
9 | Supply and laying 50mm outer dia, double walled, corrugated HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed. |
10 | Supply and laying 100mm outer dia, double walled, corrugated HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed. |
11 | 50mm bore (internal dia) steel water tubing, galvanized light grade, laid in trenches /fixed to wall/ along pole or laid in trenches or under roads etc as protection to cable, with all fittings and fixtures like mild steel flat iron clamps of appropriate size and shape, nuts, bolts and washers as approved by Engineer-in-Charge complete all as specified and as directed, with and including taking up/down old damaged steel pipe and removing from site of work complete all as directed. |
12 | All as per the description of serial item-11 here-in-above but of 80mm bore (internal dia) |
13 | All as per the description of serial item-11 here-in-above but of 100mm bore (internal dia) |
14 | All as per the description of serial item-11 here-in-above but of 150mm bore (internal dia) |
15 | MCCB four pole 630Amps, 415 volts, 50HZ breaking capacity not less than 36 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links 1cs = 100% of 1 cu, in replacement (taking down old damaged MCCB) complete all as specified and as directed. Make : ABB/Schnieder/Siemens |
16 | All as per the description of serial item-15 here-in-above but of 400 Amps. Make : ABB/Schnieder/Siemens |
17 | All as per the description of serial item-15 here-in-above but of 320/350 Amps. Make : ABB/Schnieder/Siemens |
18 | All as per the description of serial item-15 here-in-above but of 250 Amps. Make : ABB/Schnieder/Siemens |
19 | All as per the description of serial item-15 here-in-above but of 200 Amps. Make : ABB/Schnieder/Siemens |
20 | All as per the description of serial item-15 here-in-above but of 160 Amps. Make : ABB/Schnieder/Siemens |
21 | All as per the description of serial item-15 here-in-above but of 125 Amps and breaking capacity not less than 16 KA. Make : ABB/Schnieder/Siemens |
22 | All as per the description of serial item-15 here-in-above but of 100 Amps and breaking capacity not less than 16 KA. Make : ABB/Schnieder/Siemens |
23 | MCCB three pole 630 Amps, 415 volts, 50HZ breaking capacity not less than 52 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links 1cs = 100% of Icu, in replacement (taking down old damaged MCCB) complete all as specified and as directed. Make : ABB/Schnieder/Siemens |
24 | Supply and fixing, in replacement, high voltage electrical insulation rubber matas per IS - 15652 of size 5 m x 1 m, 3 mm thickcomplete all as specified and directed by Engr-in-Charge. |
25 | Change over switch ON LOAD type, 415 volt, 50 Hz, AC 4 pole, in steel metal enclosure, capacity 100 Amps rated current manually operated conforming to IS : 13947 or latest edition with high thermal and dynamic strength to withstand short circuit current level of 80 KA rms, in replacement, (taking down old damaged change over switch) complete all as specified and as directed. |
26 | All as per the description of serial item-25 here-in-above but capacity 315/320 Apms |
27 | All as per the description of serial item-25 here-in-above but capacity 400 Apms |
28 | All as per the description of serial item-25 here-in-above but capacity 600 Apms |
29 | Straight through joint (jointing kit) heat shrinkable for XLDE/PVC insulated and sheathed aluminium conductor underground cable, 1100 volts 3.5/4 core 400 sqmm, supplied, jointed and tested, below normal ground in trenches or any other location including necessary earthwork as required, complete all as specified and as directed. |
30 | All as per the description of serial item-29 here-in-above but for cable 240 Sqmm to 300 Sqmm |
31 | All as per the description of serial item-29 here-in-above but for cable 185 Sqmm |
32 | All as per the description of serial item-29 here-in-above but for cable 120 Sqmm |
33 | Aluminium conductor steel reinforced (ACSR) over head lines, on poles, 6/1 x 2.59mm (weasel), straining properly on in sulators and binding with and including Aluminium tape/copper winding wire, connections, PG clamps, jumpers etc complete all as specified and as directed with and including dismantling of existing worn out/damaged ACSR conductor and earth wire, any size and removing from site of work, all as directed. NOTE :(i) Weight of binding wire/tape shall not be included in the weight of conductor. (ii) Weight of ACSR conductor drawn for over head lines will be determined by measuring taut horizontal distance between centres of two adjacent poles and compounding the weight of conductor and 3% extra added for sag, jointing, jumpers etc. |
34 | Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, binding cold or hot, drilling holes for bolts, in any shape or size as indicated or directed inclusive of one coat of red oxide/Zinc chrome primer and two coats of aluminium paint and fixed erected in position on overhead poles complete all as specified and as directed including dismantling and taking down old unserviceable cross arms, bracing, claps etc from overhead poles and removing from site of work complete all as directed. |
35 | Pin type insulator porcelain vitreous white/brown including one galvanized mild steel spindle, two galvanized iron nut, 100mm height, 65 mm dia for 1100 volts grade, supplied and fitted / fixed on over head poles, complete all as specified and as directed including taking down old insulator and removing from site of work complete all as directed. |
36 | Disconnecting and taking out old damaged/defective LT cable from trenches or taking down from poles or taking out from pipes below or above ground level, or for rerouting of cable aluminium conductor 1100 volts grade, size 6.00 sqmm 2 core to 10 sqmm 2 core, testing for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 41 herein after and removing unserviceable cable from site of work including taking out cable cover and pipe segregating serviceable/reusable cable cover and pipe, complete all as specified and as directed. Note : Excavation and earth work shall be measured and paid for separately. |
37 | All as per the description of serial item-36 here-in-above but for of size 16 sqmm 3.5/4 core to 35 sqmm 3.5/4 core testing for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 42 herein after ---- ditto---- |
38 | All as per the description of serial item-36 here-in-above but for of size 50.00 sqmm 3.5 core to 95.00 sqmm 3.5 core testing for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 43 herein after ---- ditto---- |
39 | All as per the description of serial item-36 here-in-above but for of size 120.00 sqmm 3.50 core to 185.00 sqmm 3.50 core testing for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 44 herein after ---- ditto---- |
40 | All as per the description of serial item-33 here-in-above but for of size 240.00 sqmm 3.50 core to 400.00 sqmm 3.50 core testing for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 45 herein after ---- ditto---- |
41 | Laying only, jointing and testing LT cable PVC insulated armoured, heavy duty 1100 volts grade with aluminium conductor of size 6.00 Sqmm 2.00 core 10.00 sqmm, 2.00 core, in trenches or thorugh ducts/ pipes or fixed to poles or walls through pipes under road, jointing to OH conductor, LT panle, main swithces etc, serviceable cable as retrieved vide serial item No 36 here in above complete all as directed. NOTE : (i) Unit rate quoted is inclusive of cutting chases, if any in wall or under floor. (ii) Excavation and earth work if required shall be measured and paid for seperately. |
42 | All as per the description of serial item-41 here-in-above butof size 16.00 sqmm 3.50/4.00core to 35 .00 sqmm 3.50 core, serviceability cable as retreived vide serial item No 37 herein above -------ditto---- Note : ------- ditto------ |
43 | All as per the description of serial item-41 here-in-above but of size 50.00 sqmm 3.50 core to 95 .00 sqmm 3.50 core, serviceability cable as retreived vide serial item No 38 herein above -------ditto---- Note : ------- ditto------ |
44 | All as per the description of serial item-41 here-in-above but of size 120.00 sqmm 3.50 core to 185.00 sqmm 3.50 core, serviceability cable as retreived vide serial item No 39 herein above -------ditto---- Note : ------- ditto------ |
45 | All as per the description of serial item-41 here-in-above but of size 240.00 sqmm 3.50 core to 400.00 sqmm 3.50 core, serviceability cable as retreived vide serial item No 40 herein above -------ditto---- Note : ------- ditto------ |
46 | Supply,laying , jointing and testing LT underground electric cable XLPE insulated, PVC sheathed armoured heavy duty 1100 volts grade heavy duty multystranded aluminium conductor laid in trenches / ducts or passing through under road or fixed to poles or walls complete all as specifed and as directed of followingsize :-- NOTE : Excavation and earth work shall be measured and paid for separately. |
47 | Cross sectional area 6.00 sqmm 2.00 core |
48 | Cross sectional area 10.00 sqmm 2.00 core |
49 | Cross sectional area 16.00 sqmm 4.00 core |
50 | Cross sectional area 25.00 sqmm 4.00 core |
51 | Cross sectional area 35.00 sqmm 4.00 core |
52 | Cross sectional area 50.00 sqmm 3.50 core |
53 | Cross sectional area 70.00 sqmm 3.50 core |
54 | Cross sectional area 95.00 sqmm 3.50 core |
55 | Cross sectional area 120.00 sqmm 3.50 core |
56 | Cross sectional area 150.00 sqmm 3.50 core |
57 | Cross sectional area 185.00 sqmm 3.50 core |
58 | Cross sectional area 240.00 sqmm 3.50 core |
59 | Cross sectional area 300.00 sqmm 3.50 core |
60 | Cross sectional area 400.00 sqmm 3.50 core |
61 | Laying only, jointing and testing LT cable PVC insulated armoured heavy duty 1100 volts grade with aluminium conductor of size not exceeding 95 sqmm 3.5 core laid in trenches/ducts/along poles/wall/ through pipe under road, jointing to OH conductor, LT panels, main switches etc with new cable size aluminium lugs complete all as specified and as directed. Note :(i) Cable will be issued under Sch "B" from AGE E/M - store to contractor. (ii) Cutting chases in walls/ floor if required at site shall be deemed included in the quoted rate. (iii) Excavation & Earth work, pipe if required shall be measured and paid for separately. |
62 | All as per item No 47 above but of size 3.5 core 120Sqmm complete all as specified and as directed. |
63 | All as per item No 47 above but of size 3.5 core 185Sqmm complete all as specified and as directed. |
64 | All as per item No 47 above but of size 3.5 core 400Sqmm complete all as specified and as directed. |
65 | Material and labour for cutting existing bituminous/cement concrete road/hard standing/pavement of size 30 cm x 30cm for passing through the cables/pipes and surrounding /filling the entire cut space with cement concrete 1:3:6 type C-I after laying of pipe/cable and finishing the top surface fair and even complete all as specified and as directed. |
66 | Labour only for fixing straining and tightening ACSR conductor on overhead poles/lines including all necessary/required arrangements with and including 2mm dia binding wire/aluminium tape and ACSR jumpers complete all as specified andas directed. |
67 | Removing wild grass vegetation, creeper etc around LT panel/transformer/poles, stay assembly, climbing upwards including cleaning bottom surfaces on ground of area not less than 1.00m x 1.00m including surface dressing n.exc 15cm deep in any type of soil and removing rubbish to outside mob lad complete all as directed. |
68 | Trimming of tree branches around the LT over head conductor, poles (n. less than 3.00 metre) to clear the approach of overhead lines including removing nests wild grass creeper, unwanted vegetation etc from pole/stay including cleaning of creepers climbed on poles, cross cerms, all as directed, to the entire satisfaction of Engineer-in-Charge, including removing all rubbish to outside the MOF lard complete all as directed. NOTE :Span of 30 metre to 50 metre shall be considered / accounted for as one span for payment purposes. |
69 | Disconnecting of electric connections from LT Panels and dressing of cable including replacement of burnt out aluminium lugs with new lugs nuts, bolts as required including necessary wiring of feeder pillar box with copper conductor cable, excavation and earth work, if required, complete all as firected to the entire satisfaction of Engineer-in-Charge. |
70 | Painting of existing steel tubular poles 9.00 metre long with one coat of Aluminium paint on pole and cross arm, clamps, brackets fitted/fixed on pole, above GL / coping to full height of pole including preparing the steel surfaces to the entire satisfaction of Engineer-in-Charge and providing reflective stripes of width 10 cm (03 No) at a height of 1.20 metre from ground level, in alternate colour (green, white, green) alround the pole and marking pole number at appropriate height with shade and colour as approved by Engieer-in-Charge complete all as specified and as directed. |
71 | Electric panel doors fabricated out of mild steel sheet of thickness as directed by Engineer-in-Charge, made to shape and size as per existing with proper closing/opening arrangements including necessary welding/ fabrication as required and fitted/fixed in position including taking down old damage panel doors and removing from site of work, with and including two coats of aluminium paint over a coat of red oxide/zinc chrome primer, complete all as specified and as directed. |
72 | Aluminium bus bar of different size and capacity as per site requirement and as directed by Engineer-in-Charge including PVC insulating materials and cutting, welding as required, making holes and fixed in position including taking down old bus bar and removing from site of work, all as directed. |
73 | Earthing complete with galvanized iron or steel plate electrode 600mm X600mm X 6.0 mm burried directly in ground vertially in a pit of depth not less than 2.25m below normal ground level with top edge of the earth plate at a depth of not less than 1.50m below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to with and including GI/ Steel strip of size 32mmx6mm upto a length of 7.50 metre by means of bolts, nuts, check nuts & washers of galvanized iron /steel, earth strip protected by and including galvanized steel pipe light grade of bore 40 mm (internal dia) & connected to main control board / switch board or any other electrical equipment complete all as shown in electrical plate No : 3 MES SSR including necessary excavation & earth work, disposal of surplus soil not exceeding 50m, in any type of soil. (The rate also includes for cost of charcoal & salt in alternate layers of 15 cm thickness, 20 mm bore internal dia GI/steel pipe light grade) for watering, funnel, wire mesh, PCC chamber in cement concrete (1:3:6) type C-1, 40mm thick RCC(1:2:4) type B-0, reinforced with XPM of weight not less than 4.00 kg/Sqm and mild steel frame of angle 50mmx50xxx6mm and testing on competion including dismantling / taking out existing earthing and removing dismantling / taken out materials outside the defence land complete all as directed. |
74 | Taking down old unserviceable ACB any type andSupply, installation testing and commissioning new LT ACB of 800 Amps 415 Volts, 50 Hz,four pole mannual draw out microprocessor based, with LCD display with complete set of LSIG protection with self power release with fault indication and with 20 trip history with time stamping suitable for existing location alongwith replacement ofburnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed Make : ABB/Schnieder/L&T/Siemens |
75 | Taking down old unsv LT panel and Supply, installation testing and commissioning of out door type LT Panel factory made CPRI approved openable from front & rear double door type, dust and vermin proof,fabricated out of 3.15 mmCRCA sheetduly painted with two coats of synthetic enamel paint over a coat of red oxide primer with 4 Nos heat shrink insulated bus bar of rating 1.5 of incoming MCCB including all connection with aluminium strip pillar board shlal be provide with danger notice plate with skull and bone sign, making all electrical incoming and out goingelectrical cable connection with new lugs, glands to be provided at cable entries, including MS channel frame of ISMC 75 at base of panel only and 04 Nos legs of not less than 75 em long each below the base of panel made of angle iron 50 x 50 x 6 mm for grouting purpose in PCC 1 :2:4 type B1 [ using 20 mm graded stone aggregate) including disconnecting and taking out old unserviceable panel and removing from site of work complete all as specified and directed and comprising of following accessories :- |
76 | INCOMING:- (a) MCCB four pole, 415 Volts, 50 HZ, 200 Amps, breaking capacity 36 KA with adjustable thermal and adjustable magnetic release with Ics = 100% leu -01 Nos.(b) MCCB four pole, 415 Volts, 50Hz, 200 Amps breaking capacity 36 KA with adjustable thermal and adjustable magnetic release with Ics = 100% leu -01 No,(c) MCCB TP 415 Volts, 50 HZ, 160Amps, breaking capacity 25 KA adjustable thermal and adjustable magnetic release with Ics = 100% leu - 01 No (d) Phase indicator lamp complete with copper control wiring and suitable size of CT complete -01 (Set of three). Make : ABB/Schnieder/L&T/Siemens |
77 | Taking down old unserviceable LT feeder pillar box of any size/ capacity including all accessories from its existing position after disconnecting all electric connections, supply, installation, testing and commissioning of new out door type LT feeder pillar box of size not less than 1.8mx1.2mx0.40m, factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated with angle iron 40x40x6mm and 2.00mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated copper bus bars of 1000 Amp rating including all connections with copper busbar strip. LT panel /feeder pillar box shall be provided with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories:- |
78 | INCOMING :-(i)MCCB four pole 415 volts, 50 Hz, 630 Amps, breaking capacity 35/36 KA with adjustable thermal & adjustable magnatic protection release = 01 No,(ii) Change over switch ON LOAD type, 415 Volt 50 Hz, AC, 4 pole I-O-II, open execution capacity 630Amps - 01 No (iii) Phase indicator lamp RBY complete with copper control wiring = 01 set of three,(iv)Panel mounted multifunctional digital meter 3 lines LCD display in96x96 Sqmm flush mounted case accuracy class-I. complete with all accessories including 3 Nos 200/5A CT =1 No. OUTGOING :- (i) MCCB TP415 volts, 250 Amps, breaking capacity 25 KA with adjustable thermal adjustable magnetic protectionrelease = 01Nos. (ii) MCCB, TP 160 Amp, 415 volt, 50 Hz breaking capacity not less than 25 KA with adjustable thermal and adjustable magnetic protection release complete = 03Nos (iii) MCCB, TP 100 Amp, 415 volt, 50 Hz breaking capacity not less than 25 KA with adjustable thermal and adjustable magnetic protection release complete = 04Nos Make : ABB/Schnieder/L&T/Siemens. |
79 | Providing refelctive stripes of width 10 Cm (03 No) at a height of 1.20 metre from ground level in alternate colour (green, white, green) alround the existing pole, complete all as specified and as directed |
80 | NOTE:Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit Revised in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site. |