| 1 | Earthwork in excavation of foundation in hard soil including dressing & levelling of bed within initial lead of 50mt. & lift of 1.5mtr etc complete as per the direction of the Engineer-incharge. |
| 2 | Filling in foundation & plinth with sand including watering & ramming etc complete as per the direction of the Engineer-incharge. |
| 3 | Cement concrete (1:4:8) with 4cm size h.g.c.b. metal of approved quality from approved quarry with ramming watering and curring etc. complete including cost, taxes, royalty convence charge of all material to worksite, supply of cement T&P required etc. complete as per the direction of the Engineer-incharge. |
| 4 | R.C.C. work in C.C. (1:2:4) including hoisting & laying & curring for 28 days using 12mm. Size clean black hard granite crusher broken chips of approve quality and from approve quarry including cost taxes conveyance charges of all materials to the worksite with supply of all labour and T&P required for the work etc complete as directed by the Engineer-incharge. |
| 5 | Rigid smooth centering & shuttering for R.C.C. works including false work & dismateling then after including cost of materials in ground floor complete an directed by the Engineer-incharge. |
| 6 | M.S. reinforcement for R.C.C. work including supplying, cutting, bending, binding & tying the grills & placing in position including cost of binding wire 18 to 20 guage per Qntl. Including cost of HYSD Still Bar (FE 415/ FE 500) |
| 7 | Dismantling of lime concrete, cement concrete M-10 |
| 8 | Brick work with Fly Ash Brick 25cm x 12cm x 8cm size having crushing strength not less than 75kg / cm2 with dimensional tolerrance + 8% in cement mortar (1:6) in foundation & plinth etc. complete as per the Engineer-incharge. |
| 9 | Brick work with Fly Ash Brick 25cm x 12cm x 8cm size having crushing strength not less than 75kg / cm2 with dimensional tolerrance + 8% in cement mortar (1:6) in Superstructure etc. complete as per the Engineer-incharge. |
| 10 | 12mm cement plaster in cement mortar (1:6) finished smooth to brick work after racking out joints including waterring and curring with cost, taxes, royalty and conveyance charges of all material to the worksite and supply of all labour and T&P required for the work etc complete as directed by the Engineer-incharge. |
| 11 | Filling the foundation and plinth with excavated material as directed by the Engineer-incharge. |
| 12 | Cost for fittings of Air Release Valve |
| 13 | Cost of Iron gate made of 18 gauge sheet with locking arrangements and fixing in the wall etc complete. |
| 14 | Dry Brick Khoa rammed to 10cm |
| 15 | 2.5cm A.S Flooring in cement concrete ( 1:2:4) with 12mm size HG chips including punning etc complete. |
| 16 | Priming of M.S.Door |
| 17 | Painting 2 coats over a coat of primer with approved shade of paints including all cost. |
| 18 | White washing 2 coats of approved shadeincluding cost conveyance charges of materials including supply of labour, gum, indigo etc. required for the work complete as directed by the Engineer-incharge. |
| 19 | Labour charges for writting of required information and data on both side of the transperancy pillar including supplying of approved paints and required material for writing etc. complete as per the direction of the Engineer-incharge. |
| 20 | Fitting of un-plasticised 160/200mm diaPVC Pipe for following inside dia mtr. for all classes of pipe including jointing the pipe with solvent cement by non-head application method including fitting and fixing of required no. of PVC Tee for outlet and PVC Shaddle and PVC Riser nipple for fitting air valve, equal Tee etc. complete including conveyance pipe from village to worksite and testing of pipe line etc. complete as per the direction of the Engineer-incharge. |
| 21 | Supply of solvent cement of approve quality for joiniting of PVC Pipe with all cost and all tax etc. complete as per the direction of the Engineer-incharge. |
| 22 | Labour charges for connection of main switch to starter and starter to motor with connection ofother electrical fittings etc. complete as per direction of the Engineer-incharge. |
| 23 | Cost of 10HP Monoblock pump set having total head of 25 Mtrs capable to discharge 900 LPM withsquirrel cage induction motor fitted with bronze impeller TB-2 of IS 318/1981, companion flanges & Class \"F\" insulation suitable for operation 415 volt +6%-15% 3 phase, 50Hz AC Power Supply suction delivery= 100mmx100mm with BEE Star rated energy efficiency pump |& as per IS-9079/2002 with overall efficiency 62 to 65% of reputed brand having wide dealership net work for easy availability of spares. |
| 24 | Cost of Automatic Star Delta Starter, sheetsteel enclosure suitable for operation of Squirrel cage induction motor up to 10 HP with 16 Amp (AC -3) duty contractor at 415 Volt+6%-15%, 3 phase, 50 Hz AC supply with over load relay range 8.9 to 13.5 Amp &no volt coil with electronic timer suitable for operation at voltage range of 300 to 440 V. |
| 25 | Cost of 63 Amp. Main Switch Triple pole & natural of voltage range 440 volt of re-wirable fuse and shall confirming to IS-4064(PT-I& ) with ISI markincluding all taxes etc. |
| 26 | Cost of 3 Phase Energy Meter tested by DISTCO. |
| 27 | Cost of Panel Board made out of 18 gauge CR Sheet |
| 28 | Cost of Motor Hood Cover maade out of 18gauge CR Sheet |
| 29 | Cost of Motor Base Plate |
| 30 | Cost of 4 KVR Power shunt capacitor including all taxes and royalities etc. |
| 31 | Cost of3 Core x 16mm2 Tarpodar cable XLPE (Cross link polyethylin)confirming to IS-7098(part-II ) including laying below 0.9mtr of the ground and filling the excavated materials including watering and rammin including all taxed etc. |
| 32 | Cost of 7/20 PVC Wire |
| 33 | Cost of 100mm. dia nominal bore G.I.pipe having wall thickness 4.5mm.Elecrical resistance welded.Medium class confirming to IS 1239(Pt-1/2004) with socketed at one end the otherend protected with plastic thread protector.The socket confirming to IS-1239 ( pt-I/1992) with latest amendmewnts in random length of 4 to7 mtrs. Each pipe should bear ISI Certfication & manufacturers name/Trade mark including all taxes etc. with guarantee. |
| 34 | Cost of 200mm diaMS Pipe (Medium Duty) |
| 35 | Fabrication of special joint including cutting, welding of pipes, one end with other end suitable for connection to delivery pipeline of pumpset including cost of cutting, welding materials, and fitting it in proper alignment with delivery pipeline works,cutting & threading of pipe line etc. |
| 36 | Cost of 100mm dia G.I. Bend confirming to IS-1239(Pt-II 1992) including all taxes etc. |
| 37 | Cost of 100mm dia G.I.Flange confirming to IS-6392/1971 including all taxes etc. |
| 38 | Cost of 200 x 100 mm G.I.Reducer |
| 39 | Cost of 200mm dia M.SFlange. |
| 40 | Cost of 100mm diaCI double flanged Sluice Valve with gated system. |
| 41 | Cost of 100mm CI double flanged Non-Return Valve swing type PN-1.0 as per IS:5312 part-I with by pass arrangement. |
| 42 | Cost of 50mm dia Air release valve with saddle &Raiser pipe.The air release valve shall confirm to IS14845 with ISImark including all taxes &royality etc. |
| 43 | Cost of 200 mmØ Butter Fly Valve |
| 44 | Cost of 200mm x 200mmx200mm dia PVC Tee |
| 45 | Cost of 200mm dia PVC Bend. |
| 46 | Cost of 100 x100 x25 mm G.I Tee with plug for priming. |
| 47 | Cost of200 mmØ PVC Flange Socket |
| 48 | Cost of160 mmØ PVC End Cap( W.P. 10 Kgf/cm2 ) |
| 49 | Cost of 160 mmØ PVCCoupler(4 Kgf/cm2 agricultural PVC fitting ). |
| 50 | Labour charges forInstallation of monoblock pumpset and delivery fitting including fitting of Sluice Valve, NR Valve, Air Release Valve, PVC Tee and lowering of pump and transportation etc complete. & fixing suction and delivery pipe to motor, NR Valve, Foot Valve, Sluice Valve and other fitting materials including cutting, welding etc. complete as per the direction of the Engineer-incharge. |
| 51 | Supply of 200mm dia unplasticised riged UPVCpipe ivory in colour having specific gravity of 1.40 to1.46 gms/cc of straight length of 6(six) meter for portable water supplies conforming to IS-4985/2000 of BIS-Amendment-2 read with Table-1 of IS-specification bearingISImarks for working pressure CI-I UPVC pipe to withstand pressure of 2.5kgf/sqcm& the specification and manufacture name should be prominently marked on body of each pipe as per the latest Amendment of IS-4985. It includes the cost of sockets in case of plain ended pipe. PDI test are to be condcuted and should be marked on body of each pipe and report is to be obtained from CIPET, Bhubaneswar necessary approval of authority including transporation to work site in complete shape and handed over to Pani Panchayat President or Secretary. |
| 52 | Cost of 200mm x 200mmx110mm dia MS Tee with control arrangements. |
| 53 | Laying and fittings of 200mm dia M.S.Pipe and fittings with fittings materials |
| 54 | Electrical Earthing including all materials as per the direction of the Engineer- incharge |
| 55 | Foundation Nut and Bolt, Rubber Insertion, 7/20 PVC wire etc |
| 56 | Construction anderection of 11 /0.4 KV ,25KVA Double Pole mounted Substation Star rated confirming to RE Rules 1956, mounted on 2.44 Mtr. Long structure, supported in 300 kg 9 mtr long PSC pole,transformer hard channel & top channel made of 2.8 M long 100 X 50 X 6 mm M.S.Channel, Transformer belting on 2.80 M long 50 X 50 X 5 mm M.S.Angle, (all REC SPN Std.F-3) with all accessories like 3 pole 11 KV HG Fuse(F-5)& A.B.Switches(F-9) both mounted on 2.8 M long 75 X 40 X 6 mm M.S.Channel and supported by 1.0 M long 50 X 50 X 5 mm M.S.Angle, with 3 No. 11 KV Lightening Arrestors & Distribution box for25 KVA S/S, G.I.pipe earthingwith 25X5mm G.I.Flatsincluding cost of 25 KVA 11/0.4 K.V.Transformer , 35 Sqmm 3 1/2 Core PVC Cable - 40 mtr couping & padding of Poles, Danger board at each Pole, Anti climbing Devices & all other necessary fittings i.e required size Nuts & Bolts, Brackets, Cable, Cable Sockets, barbed fencing ( size (15\"x10\") with constn. of retaining wall, erection of RCC fencing post , sand filling and metal spreading ,fixing of iron grill gate etc as per cesu specification etc. including cost of all materials, labour , transportation complete with liasioning for testing inspection & commissioning. |
| 57 | Construction of 3 phase 11 KV line as per REC standard confirming to IE Rules 1956 with 300 kg 9 M long PSC Pole with 55 Sqmm XLPE insulated cable single core,11 KV \"V\" Cross arm, with required No.of 11 KV T & C Disc. Insulators in tension point &11 KV Pin insulators, Couping & Padding of Poles. Danger Board at each Pole, Anti Climbing Devices, Stay Set at Bending point & double stay at end point with 18 mm G.I.H.T.Stay, concreting of Stay with Anchor plate, guarding at Road crossings etc. including cost of all materials, labour transportation,inspection & commissioning etc. complete. |