| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in Existing surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Supplying andfixing of following sizes of medium class PVCconduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 3 | 20mm |
| 4 | 25mm |
| 5 | 32mm |
| 6 | 40mm |
| 7 | Wiring for Light /Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in Existing surface/Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required. |
| 8 | Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable insurface/Recessed medium class PVC conduit as required. |
| 9 | 2 X 2.5 SQ.MM + 1 X 2.5 SQ.MM EARTH WIRE |
| 10 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 11 | 2X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 12 | Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required |
| 13 | Supplying and fixing Stepped Type Electronic Fan Regulator on the existing Modular Plate Switch Box including Connections but Excluding Modular Plate etc. as Required |
| 14 | Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 15/16amps modular socket outlet and 15/16 amps modular switch,connection,painting etc. as required. |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modularswitch, connections etc. as required. |
| 16 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 17 | 6way (4 + 18), Double door |
| 18 | Supplying and fixing following rating, four pole, 415 V, TPN in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 19 | 63 Amps |
| 20 | Supplying and fixing 5 amps. to 32 amps.rating240 volts \"C\" series, miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 21 | Single Pole |
| 22 | Double Pole 63 amps |
| 23 | Supply and Fixing Single Pole Blanking Plate in the Existing MCB DB complete as Required |
| 24 | ENVIRONMENTALLY SAFE MAINTENANCE FREE EARTHING SYSTEM |
| 25 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of2.7 meter long etc. with charcoal/ coke and salt as required. |
| 26 | Earth pit chamber (300mm x 300mm) with CI cover for the above. |
| 27 | Providing and Fixing 25 mm x 5 mm G.I Strip in 40 mm dia. G.I Pipe FRL Earth Electrode including connection with Brass nut, bolt, spring, washer, excavation and refilling etc. as required. |
| 28 | SITC of Ceiling Fan,Capacitor type suitable for low voltage operation including wiring the down rods of standard length(Upto 30 cm)with 1.5 sq.mm FR PVC insulated, copper conductor, single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. |
| 29 | 1200 MM SWEEP |
| 30 | SITC of pre-wired Recess/SurfaceMounted 4Ft 20 watts or near to 20 watts LED Fitting with ,Driver Etc. including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required .commercial light fixture |
| 31 | SITC of pre-wired Recess /Surface Mounted LED CeilingLight12 W or near to 12 watts including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required comercial light fixture |
| 32 | Supplyof AC230/250 Volts, 50 Hzexhaust fan with louveres of Following Sizes including connection etc. complete as required . |
| 33 | 300 mm |
| 34 | Supplying,Installation,Testing and Commissioning of Cubical Type LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking ,A.M.F Logic etc. as required as per the Following Description(.5.5x5x1 =27.5 cft) Double bus bar |
| 35 | INCOMER |
| 36 | MCCB 250 Amps 4 P 36 KAbased with (Icu=Ics=100%)(1 Nos) |
| 37 | MCCB 100 Amps 4 P 36 KAbased with (Icu=Ics=100%)(1 Nos) |
| 38 | Indicating Lamps RYB (2 Set) |
| 39 | Voltmeter-0-500 Volts(2 Nos) |
| 40 | Ammeter(0-400 A)(2 Nos) |
| 41 | Selector Switch (4 Nos) |
| 42 | Current Transformer 300/5 A 10 VA Burden, Class-1(2 Sets) |
| 43 | Aluminium Busbar 400 Amps FP E-91 E Grade Electrolytic Aluminium |
| 44 | 200 AChangeover 4 Poles |
| 45 | OUTGOINGS |
| 46 | MCB 63Amps 4 P (6 Nos) |
| 47 | DP MCB 63 A 10 KA .(6 Nos) |
| 48 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 49 | Supplying and Laying of 1 No. PVC/XLPE insulated and PVC Sheathed /XLPE Power Cable of 1.1 KV Grade of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe/Cable Tray as Required. |
| 50 | 3.5C x 240mm² LT XLPE (A2XFY) insulated Aluminium conductor PVC outer sheathed Armoured cable. |
| 51 | Laying and fixing of 3.5 core 240sqmm one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. |
| 52 | 3.5C x 240mm² LT XLPE (A2XFY) insulated Aluminium conductor PVC outer sheathed Armoured cable.End termination |
| 53 | Supplying,Installation,Testing and Commissioning of Cubical Type LTfeeder Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,(2.5x1.5x1 =5 cft) including MS angle stand complete in all respects |