Repair / Replacement And Maintenance Of Vcbs, Servo Stabilizer, Isolation Transformer, Rmu And Ht Cable And Their Allied Works At Af Station Purnea-Bihar

Military Engineer Services-MES has published Repair / Replacement And Maintenance Of Vcbs, Servo Stabilizer, Isolation Transformer, Rmu And Ht Cable And Their Allied Works At Af Station Purnea. Submission Date for this Tender is 18-01-2022. Servo Stabilizer Tenders in Bihar. Bidders can get complete Tender details and download the document.




Tender Notice

30523483
Corrigendum : Repair / Replacement And Maintenance Of Vcbs, Servo Stabilizer, Isolation Transformer, Rmu And Ht Cable And Their Allied Works At Af Station Purnea
Open Tender
Indian
Bihar
18-01-2022

Tender Details

Repair / Replacement And Maintenance Of Vcbs, Servo Stabilizer, Isolation Transformer, Rmu And Ht Cable And Their Allied Works At Af Station Purnea

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 11-Jan-2022 Other Corrigendum Other 18-01-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 70000.0 /-
Tender Value
INR 35 Lakhs /-

BOQ Items

NAME OF WORK: REPAIR/REPLACEMENT AND MAINTENANCE OF VCBS, SERVO STABILIZER, ISOLATION TRANSFORMER, RMU AND HT CABLE AND THEIR ALLIED WORKS AT AF STATION PURNEA.
Sl. No. Item Description
1Note :Prior to commencement of the subject works, the contractor needs to submit valid Electrical License in the name of himself/them self or Agreement with agency having valid Electrical License alongwith Agency"s Electrical License to the Accepting Officer for his approval through GE. In absence of such documents, no work will be executed at site and to be treated as defaulter on the Contractor"s part . In addition, Supervisor for execution of electrical works employed by the Contractor shall posses Supervisory Certificate of competency issued by concerned State Govt/Union Territory and the Worker/Tradesman for execution of Electrical Works must hold necessary permit issued by concerned State Govt/Union Territory.
2Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 m in depth for taking out/laying of under ground cables/pipes etc n. exc 10 sqm on plan and n. exc 1.5m in depth and getting out and in soft/loose soil complete all as specified and directed.
3Returning, filling in soft/loose soil including spreading, leveling, watering and well ramming in layers n.exc.25cm thick complete all as specified and directed.
4Removing excavated materials (soils) n.exc.50 mtr and depositingwhere directed at a level n.exc.1.5 mtr above the starting point complete all as specified and directed.
5Material and labour providing sand cushioning with a layer of clean, dry, fine sand for protection of electric cable laid in trenches/ducts, punned down to desired thickness complete all as specified and directed. (Note: For payment purposes only punned down thickness of sand shall be measured )
6Supply & laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 450mm x 230mm x 50 mm all as specified & directed.
7Relaying un-reinforced precast concrete cable cover, class EHV, type 1 with peak, size 450mm x 230mm x 50 mm all as specified & directed.
8Taking out oldunserviceableHT cable , any size & type from the trenches of pipe including taking out brick cable protection if required and deposited as directed (Note: Excavation and earth work will be measured & paid separately).
9Relaying in trenchesold serviceableXLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, heavy dutyelectric cable with aluminium conductor, 11000 volts grade (earthed) 150 sq. mm 3 core after thoroughlychecking/testing and repair/replacement of jointing kit complete all as specified and as directed by Engineer-in-Charge. (Note : Cable obtained from taking out under serial item No 8.00 will be used. Cable joint kit/material will be measured & paid separately)
10Supply and laying in replacementXLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, heavy dutyelectric cable with aluminium conductor, 11000 volts grade (earthed), 150 sq. mm,3 core in trenches/ on walls/ through duct complete all as specified and directed.
11Take down old unserviceable cablejointing kit 11 KV grade, any type & any size complete all as specified and as directed by Engineer -in - Charge.
12Material and labourin replacement cable jointing kit for 11 KV (Earthed)grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories, suitable for 3 core XLPE, armoured, aluminiumconductor cable of size 120 sqmm to 185 sqmmcomplete all as specified and directed.
13Material and labourcable jointing kit for 11 KV (Earthed)grade cable for straight through joint, heat shrink typecomplete with jointing material and accessories, suitable for 3 core XLPE, armoured, aluminiumconductor cable of size 150 sqmm complete all as specified and directed.
14Taking down/taking out old unserviceableGI pipe any size complete all as specified and as directed by Engineer -in - Charge.
15Supply and laying GI tubing 100 mm bore, light grade for protection of underground electriccablecomplete all as specified and as directed by Engineer -in - Charge.
16Material and labour dehydration and filtration of transformer oil at site of installation for 11kV, 433 volts step down transformer of any capacity and any make, mounted indoor/outdoor and obtaining di-electric strength minimum 50 kV (r.m.s) with in one minute with 2.5 mm gap with portable filter-cum-dehydration machine complete all as specified and as directed by Engineer -in - Charge.(Note:- Testing of di-electric strength of dehydrated transformer oil of each transformer will be carried out in the presence of concerned Engineer -in - Charge.)
17Material and labourproviding new transformer oil in replacement of old unserviceable transformer oil of di-electric strength not less than 50 kV after draining out old oil complete all as specified and as directed by Engineer -in - Charge.
18Material and labour in replacement of old unserviceable lightning arrestor, expulsion type with all fittings, transmission class, discharge capacity 65 kilo-amp including taking down old one complete all as specified and as directed by Engineer -in - Charge.
19Dismantling VCB (Vacuum Circuit Breaker) by disconnecting its HT cable connection from both sides and 11 KV GOD and segregating/ checking all unserviceable parts, motor etc,reassembling allserviceable parts and also replacing unserviceable parts with the new parts, rewiring of internal circuit with new cable as per existing size, testing, calibration of relays, CT connection, PT alignment, Cleaning, polishing of VCB including final testing after fixing complete all as directed by Engineer -in - Charge.
20Supply and fix in replacement the following components/parts of VCB complete all as specified and as directed by Engineer-in-Charge :-
21Upper Arm
22Lower Upper Arm
23Closing & Tripping Coil
24Auxiliary switch
25Supporting Insulator
26VCB body
27Protection relay
28Current Transformer as per existing sample (Make: NPP/PLASTOFAB/ABB)
29Bus bar all as specified and directed
30Supply and installation of power pack unit of Input 110VAC 50 C/S,3 phase, Out put 110,Cap-300, make Cromptonsafety devices complete suitable for existing breakers including taking down oldpower pack unit all as directed all as specified and directed
31Supply only numerial IDMT 3-0/C+1-E/F protection relay with high set, Model No : ADR-141C(Make: ASHIDA/Schneider/Crompton Greaves or equivalent).
32Supply onlyindicator lamp (LED) (Make- EMCO/STS).
33Supply onlyCRC Chemical all as specified and as directed.
34Supply only HT Monoplast tape, size 3 mm x 35 mm x 1 meter rollof approved make all as specified and as directed.(Make: M-Seal/3M/Mega Seal)
35Supply onlyspace heater, 230 volts, 100 watt all as specified and as directed. (Make: Reco/GIRISH)
36Supply onlyTNC Switch, 25 Amp, operational voltage 660 volts, Utilization CategoryAC-23/AC-21, as Per IEC 60947-5-1:2003, I.S.13947 Part I & V / Sec. 1:2004 all as specified and as directed (Make: Kayee/Rishabh/ABB)
37Supply and fixing resin cast current transformer of Ratio : 50/30/5-5A, Core-1 : 15VA,CI : 1.0, Core-II 15VA, CI : 5P10, STC : 26.3 KA/1 Sec (Make: NPP/PLASTOFAB/ABB)
38Supply and fixing resin cast dual core current transformer of Ratio : 100/75/5-5A, Core-I : 15VA, Burden CI :1.0, Core-II 15VA, Burden CI : 5P10, STC : 26.3 KA/1 Sec,(Make: NPP/PLASTOFAB/ABB)
39Supply and fixingPT fuses for 11KV PT (Make - Anand or equivalent in ABB/Crompton Greaves/ABB)
40Material and labour carrying out repairs to transformer of capacity 63 KV to 315 KV after disconnecting HT/LT connections, opening the top cover, draining out transformer oil and preserving incontainer, replacement of all gaskets, nuts, bolts etc for prevention of leakage, replacement of broken HT/LT bushes complete all as per existing specifications & size, refixing , refilling transformer oil, connecting to the electrical system and testing on loadcomplete all as specified and as directed by Engineer-in-Charge.
41Material and labour in replacement of porcelain vitreous H.T. bushing suitable for distribution transformer of capacity upto 315 KVA complete with copper spindle, checknuts, oil seal, bolts, nuts & washers etc complete all as specified and as directed by Engineer-in-Charge.
42Material and labour in replacement ofporcelain vitreous L.T. bushing suitable for distribution transformer of capacity upto 315 KVA complete with copper spindle, checknuts, oil seal, bolts, nuts & washers etc complete all as specified and as directed by Engineer-in-Charge.
43Material and labour in replacement breather assembly of suitable size filled with Silica gel complete set all as specified and as directed by Engineer-in-Charge.
44Material & labour providing PCC 1:3:6, type C-2(using 40 mm graded stone aggregate)as in foundation of poles/struts/stays complete all as specified and as directed by Engineer-in-Charge
45Material and labour providing one primer coat, one under coat and one finishing coat of aluminium paint to LT/HT steel tubular poles, including angle iron cross-arms of channel/angle sections, clamps etc, painting upto 2.0 m height above G.L. as border and re-writing of pole number with synthetic enamel paint complete including necessary preparation of old painted surfaces complete all as specified and directed by Engineer-in-Charge.
46S&F in replacementwater proof LED glow sign board of dimension 8 ft x 3 ft size and having the following specifications for outdoor installation alongwith all connecting items required for installation of the sign board complete all as specified and directed by Engineer-in-Charge :- (a) High quality star flex printing on Eco-solvent printing (Matter of printing as given by Engineer-in-Charge). (b) LED tubes of Havells/Philips/Syska/Crompton Greaves (Water proof) -06 Nos (c) PVC insulated electric cables of suitable size for connection. (d) Signage box with square M.S. pipe frame of size 25mm x 25mm/32mm x 32 mm (as directed),duly painted with rust proof Asian Paint/Berger Paint
47Supply, install, testing and commissioning in replacementGang operated air brake switch (GOD),outdoor,tilting type, current rating 400 Amps,11KV, triple pole,complete withsquare shaft, operating pipe of suitable length for operating mechanism worked from ground level , handle, guide clamp etc complete all as specified and directed by Engineer-in-Charge. (Make : Pactil (Madras)/Southern Switchgear/ Universal/ BHEL/ ELPRO/Rastriya)
48S&F Drop out fuse,two post insulator per pole complete with FRP fuse barrel, Channel type complete set for 3 Phase HT 11 kV with fixing arrangement complete all as specified and directed by Engineer-in-Charge. (Make : Pactil (Madras)/Southern Switchgear/ Universal/ BHEL/ ELPRO/Rastriya)
49S&F Drop out fuse,two post insulator per pole complete with FRP fuse barrel, Bracket type complete set for 3 Phase HT 11 kV with fixing arrangement complete all as specified and directed by Engineer-in-Charge. (Make : Pactil (Madras)/Southern Switchgear/ Universal/ BHEL/ ELPRO/Rastriya)
50Material and labour for 10 cm dia 8 mm thick CI cable route indicator HT/LT in round shape, fixed on angle iron post of size 25x25x4mm, 45 cm long complete, embedded in PCC 1:3:6, type C-1 block of size 250x250x250mm , duly marked /engraved HT cable 11 KV / LT cable (HT cable brown colour and LT cable blue colour ), including all necessary excavation , returning filling and removal of surplus soil to a distance n.exc. 50mcomplete all as specified and directed.
51Disconnecting LT connection both side from the isolator Transformer and lifting of core and winding assembly complete from inside the transformer"s chamber after unscrewing all bolts, nuts, washers and cleaning complete transformer and drawn out used transformer insulating oil and cleaning including repair of core portion of transformer, after that reassembly core and connecting incoming and outgoing connection, refilling transformer oil and testing complete all as specified and directed by Engineer-in-Charge.
52Taking shut down from main receiving sub station and disconnecting HT/LT connection and earthing strip from Transformer complete all as specified and directed by Engineer-in-Charge.
53Supply and fix Silicon Polymer Pin Insulator for HT 11KV, 400Amps complete all as specified and directed by Engineer-in-Charge.
54Material and labour for servicing and repair of isolation Transformer of capacity 100 KVA including, microprocessor based card of isolation, servicing of isolation mechanism, replacement of Ammeter and Voltmeter complete all as specified and directed by Engineer-in-Charge.
55Material and labour for Servicing and repair of SERVO stabilizer of capacity 100KVA including repair of variac of each phase ,microprocessor based card of servo, servicing of gear mechanism ,replacement of Ammeter and voltmeter all as specified and as directed
56Material and labour for calibration and servicing of SF6 TYPERMU(ABB SAFE LINK CB,RMU IEC 62271-200 TYPE:CVC+) including cleaning and refixing of all three input and output cable, servicing of spring charge mechanism, servicing of self powered relay including replacement of battery of the relay, calibration of RMU as per existing HT load of RMU, replacement of hydraulic link of opening cover and necessary connections complete all as specified and as directed.
57Material and labour for lifting of transformer 63 KVA after disconnecting HT/LT connection and earthing connection from 2/4 pole structure with the help of mobile crane and shifting to workshop for repair and taking back to the site after repair complete all as directed by Engineer -in - Charge
58Material and labour for complete repair of transformer 63 KVA capacity, outdoor type, 11/0.433 kV, step up/down including replacement of the following old unserviceable parts by new one complete all as directed by Engineer -in - Charge :- (a) Lifting of core and winding assembly complete from inside the transformerafter unscrewing all bolts, nuts, washers and cleaning complete transformer after draining out used transformer insulating oil complete all as specified and as directed by Engineer -in - Charge. (b)Rewinding of primary and secondary winding with existing size of super enamelled copper wire as approved and directed by Engineer -in - Charge. (c) Replacement of LT bushing complete with copper spindle, check nuts oil seal, bolts nuts and washer etc. complete all as directed by Engineer -in - Charge. (d) Replacement of HT bushing complete with copper spindle, check nuts oil seal, bolts nuts and washer etc. complete all as directed by Engineer -in - Charge. (e) Replacement of breather complete setwith silica gel Indicating type with blue crystals conforming to IS: 3401-1992 complete all as specified and as directed by Engineer-in- Charge. (f) Replacement of insulating paper and rubber gasket as required during repair all as specified and as directed by Engineer-in- Charge. (g) Reassembling the transformer, transportation to the location, installation testing and commissioning upto the entire satisfaction by Engineer -in - Charge.
59Material and labour for Danger notice plate of size 25 cm X 20 cm made out 1.6 mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skull & bones in signal red colour writing in Hindi, English and local language and fixed with MS clamps, Bolts & nuts of size for HT, complete all as specified and as directed.
60Material and labour for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts,washers, welding,bending cold or hot drilling holes for bolts, in any shape of size as indicated or directed and inclusive ofone primer coat, one under coat and one finishing coat of aluminium paint including preparation of surfaces complete all as specified and directed
61Supply and fix HT OH lines on Existing Poles with ACSR conductor of size3 of 6/1x3.50 mm (Rabbit)
62Material and labour for steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP 55, 11 metres long including two coats of aluminium paint over a coat of red oxide primer after preparation of surfaces complete all as specified and as directed
63Material and labour for providingPCC 1:3:6, type C-2 (using 40mm graded stone aggregate) as in foundation of poles/struts/stays complete all as specified and as directed.
64Material and labour for PCC 1:2:4, type B-1 (using 20mm graded stone aggregate) as in coping or plinth block of electric poles including necessary form work, to achieve fair finish surfaces without using extra cement complete all as specified and as directed.
65Supply only Electric rubber hand gloves 11 KV as per electrical specification ,tested and certified only
66Material and labour for calibration and servicing of Air Break Switch LT(ABB SACE EMAX E1) including cleaning and refixing ofinput and output cable, servicing of spring charge mechanism, servicing of self powered relay ,calibration of Air Break Switch as per existing LT loadall as specified and as directed.
67Material and labour for Rubber mat of 1 meter x 2 meter x 19 mm size all as specified and as directed
68Material and labour for battery 2 volt maintenance free suitable for existing battery bank(Power stack,Amarraja) all as specified and directed
Disclaimer :