Public Works Department-PWD has published Electrification Of Bio Medical Waste Storage Room For Chc Chiktan Kargil Electrification Of Bio Medical Waste Storage Room For Chc Chiktan Kargil. Submission Date for this Tender is 03-01-2022. Electrification Work Tenders in Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 30-Dec-2021 | Corrigendium | Other | 03-01-2022 |
Sl. No. | Item Description |
1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group B |
2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
3 | a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
4 | b) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
5 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
6 | Supplying/installation//testing and commissioning of (08 W) LED Surface panel round shape with complete accessories. |
7 | Supplying/installation//testing and commissioning of (12 W) LED slim panel round shape with complete accessories. |
8 | Supplying/installation//testing and commissioning of (15 W) LED slim panel round shape with complete accessories. |
9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
10 | 25MM |
11 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
12 | a)1 or 2 Module (75mmX75mm) |
13 | b) 3 Module (100mmX75mm) |
14 | c) 4 Module (125mmX75mm) |
15 | d) 6 Module (200mmX75mm) |
16 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
17 | a) 5/6 A switch |
18 | b) 15/16 A switch |
19 | c) 3 pin 5/6 A socket outlet |
20 | d) 6 pin 15/16 A socket outlet |
21 | e) indicator Lamp |
22 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
23 | Upto 450 mm sweep |
24 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
25 | a) 8 way , Double door |
26 | a) 12 way , Double door |
27 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
28 | a) Single pole 6A, SP MCB |
29 | b) Single pole16A , SP MCB |
30 | c) Double pole 32A, DP MCB |
31 | d) 32A ,DP Changeover switch |
32 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
33 | a) 40 A |
34 | Installation, testing and commissioning of wall fan with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
35 | Supply, installation, testing and commissioning of 300 mm sweep 230 Volt AC size 1200 RPM metal body Heavy Duty exhaust fan with guard and mounting arrangement etc. as required |
36 | Supplying, installing, testing & commissioning of Single Phase Electronic Energy Meter, tested as per Electricity Boards requirement. |
37 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
38 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
39 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
40 | Supply of First aid box as approved by St. John Ambulance Brigade /Indian Red Cross society conforming to IS : 2217 - 1963. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail