Military Engineer Services-MES has published Provn Of Rcc Oh Tank And Ug Sump For Ad Regt Workshop At Jhansi Provn Of Rcc Oh Tank And Ug Sump For Ad Regt Workshop At Jhansi. Submission Date for this Tender is 29-01-2022. Sump Tenders in JHANSI Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 18-Jan-2022 | Revision of critical dates | Date | 29-01-2022 |
2 | 18-Jan-2022 | Revision of BOQ and certain pages of tender documents | BOQ | 29-01-2022 |
3 | 19-Jan-2022 | Amendment to Item No.1 of Sch A Part I | Other | 29-01-2022 |
Sl. No. | Item Description |
1 | Note:-(i) Please refer schedule "A" notesbefore quoting the tender. (ii) Amount of Schedule of credit shall be deducted off line by the department. |
2 | GENERAL SUMMARY |
3 | Lump sum price worked out by the contractor for BUILDING WORK - OH TANK & UG SUMP as listed in Schedule ‘A’Part- I (Ref prepriced schedule attached seperately) |
4 | Lump sum price worked out by the contractor for LIGHTNING PROTECTION & AVIATION OBSTRUCTION LIGHT as listed in Schedule ‘A’Part- II (Ref prepriced schedule attached seperately) |
5 | Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLYas listed in Schedule ‘A’Part- III (Ref prepriced schedule attached seperately) |
6 | MISC |
7 | BOQ SCHEDULE "A" PART - II (LIGHTNING PROTECTION & AVIATION OBSTRUCTION LIGHT) |
8 | S&F integral LED aviation light fitting comprising of aluminium housing with polycarbonate enclosure complete all as specified and directed. |
9 | S&F Analog time switch with inbuilt batterybackup, 3 module size, 24 hours program, programmable every 15 minutes, backup of 100 hours, current capacity 16A with polycarbonate enclosure for wall mounting complete all as specified and directed. |
10 | BOQ SCHEDULE "A" PART - III (EXTERNAL WATER SUPPLY) |
11 | Supply, installation, testing and commissioning of vertical open well submersible pump set of capacity 5 KW / 7.5 HP, 3 Phase, 415 Volts, 50 Hz suitable for not less than 600 LPM discharge at a minimum head of 37 meter with 3 stages, Cast Iron Impeller, Cast Iron NRV body, Cast Iron Motor body and Stainless Steel Pump Shaft with copper winding motor, Insulation Class "B", IP 68 degree of protection complete all as specified and directed. |
12 | Design, fabricate, supply, installation, testing and commissioning of Outdoor Type cubicle panel board compartmentalized suitable for 3 phase 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with power coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mmx50mmx6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel / PVC cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards(02 Nos) LT 415/440 Volts, and manufacturer"s name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall suitablefor accommodating and including provision of following switchgear, control gear and accessories including internal wiring complete:- Note: The Contractor shall submit drawings of the LT panel board and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. |
13 | BOQ Serial Item No.3.22 Contd/- (i) Bus bar: TPN copper bus bar of suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and Continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel. (The rating of main bus bar should be 1.5 times of ampere rating of incomer MCCB.) (ii) Incomer: (a) MCCB, 63 A, 4 Pole, 25 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal - magnetic release - 01 No (b) Digital Voltmeter with selector switch - 01 Set. (c) Digital Ammeter with selector switch & suitable ratio of CT"s - 01 set of 03 (d) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03 (iii) Outgoing:- (a) Motor Protection Circuit Breaker (MPCB), rotary type, 16 Amps, 3 Pole, 50 KA, with short circuit & overload protection along with Direct Online Starter (DOL) startersuitable for 7.5 HP 3 ph, 415 V, 50 HZ, AC motor along with LED pilot light indication lamps to indicate motor ON & OFF position - 02 Sets (b) MCB TPN 40 Amps, 10 KA, "C" curve - 02 Nos. (c) MCB SPN 40 Amps, 10 KA, "C" curve - 02 Nos |
14 | Supply, connecting & testing of Flat Three Core 4.0 sqmm PVC Insulated & PVC Sheathed Industrial Cable for Submersible Pump Motors 1100 Volts grade, conforming to IS: 694 complete all as specified and directed. |
15 | Supply, laying, jointing and testing of Centrifugally Cast (Spun) Ductile Iron Pressure Pipe with Socket and Spigot ends suitable for Push-on-Jointing, Class "K-9" of size DN 100mm duly applied with Zinc Coating with finishing layer of Bitumen on external surfaces and Cement Mortar Lining with Bituminous Seal Coat on internal surfaces complete confirming to IS-8329(2000) duly ISI marked and all as specified and directed. |
16 | M&L for Ductile Iron (DI) fittings, class K-12, such as Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (sockets or socket and spigot or flanged ends as per site requirement) collars, caps and plugs etc suitable for up to 150mm dia pipe complete all as specified and directed. |
17 | Supply, install, testing and commissioning of chemical dosing system suitable to inject chlorine solution up to 25 LPH comprising of dosing pump, electric motor, FRP solution preparation cum settling tank of capacity 100 Liters with lid, port hole, inlet / outlet/ drain connection, level guage etc and fitted with speed reducing motor and SS-316 agitator complete unit mounted on heavy duty MS fabricated frame duly applied with two coats of arrocorosive paint complete all as specified and directed. |