Installation And Electrification Of Odasingha-I Rl Project Under Athmallik Block Installation And Electrification Of Odasingha-I Rl Project Under Athmallik Block

Issued by Government Departments · Angul, Odisha
Tender Value
13.15 Lakhs
Estimated cost
Bid Submission
21 Dec 2021
0 days left
EMD
Ref. Documents
Bank guarantee accepted
Document Fee
6000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Angul → Odisha
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Installation And Electrification Of Odasingha-I Rl Project Under Athmallik Block Installation And Electrification Of Odasingha-I Rl Project Under Athmallik Block

BOQ

Name of Work: INSTALLATION AND ENERGISATION OF ODASINGA-I L.I. PROJECT UNDER STATE PLAN 2021-22 IN ATHMALLIK BLOCK OF ANGUL DISTRICT
Sl. No. Item Description
1Civil Works (Part-A)
2Earth work excavation in foundation in hard soil with 50 mtr initial lead 1.5 m initial lift including rough dressing and breaking clodsto 2 cm to 7 cm and laying in layers not exceeding 0.3 m in depth as per direction of Engineer-in-charge
3Filling foundationand plinth with sand watered and rammed as per direction of Engineer-in-charge.
4Cement concrete (1:4:8) with 4 cm size h.g metal as per direction of engineer-in-charge.
5Cement concrete (1:2:4) with 12 cm size h.g Chips as per direction of engineer-in-charge.
6Rigid and smooth centering and shuttering for RCC work including false work and dismentalling them after casting including cost of materials complete.
7a) in foundation
8RCC (1:2:4) with 12 mm size HG chips as per direction of engineer-in-charge.
9Supplying, fitting and placing oncoatedHYSD (TISCON) bar reinforcement complete as per drawing and technical specification including cutting, binding, bending and cost of binding wire.
10Fly Ash Brick (25cmx12cm x8 cm) having crushing strength not less than 35kg/cm with dimensional tolerance ± 5% in cement mortar (1:6) in foundation and plinth.
1112mm thick cement plaster (1:6 ) over brick masonary as per direction of Engineer-in-charge.
126mm thick cementplaster (1:6) as per direction of Engineer-in-charge.
13Filling F & P with excavated materials, moorum including watering and ramming as directed by the engineer-in-charge
14White washing three coats with shell time as per direction of Engineer-in-charge.
15Cement punning over cement plaster as per direction of Engineer-in-charge.
16Supplying of unplasticised rigid UPVC pipe ivory gray in colour having specific gravity of 1.40 to 1.46 gms.cc, of straight length of 6 (six) meter for portable water suppliers conforming to IS-4985/2000 of BIS- Amendment 2 read with Table =1 of IS specification bearing ISI marks for working pressure CI -IUO=PVC pipe to withstand pressure of 2.5 Kgf/sqcm/4.0 Kgf/sqcm/6.0 Kgf/sqcm/8.0 Kgf/sqcm and the specification and manufacturer name should be prominenity marked on body of each pipeas per the latest Amendment of IS 4985.it includes the cost of sockets in case of plain ended pipe PDI test are to beconducted and should be marked on body of each pipe and report is to be obtained from CIPT, Bhubaneswar/ EPM, Orissa, Bhubaneswarnecessary approval of authority including transporotation and laying at site all complete with cost of solvent cement.
17i) 160 mm dia (Class-I)
18ii) 200 mm dia (Class-I)
1910 HP Monoblock centrifugal pump set at total of 16mtr capable to discharge 1700 LPMsquirrel cage induction motor fitted with companion flanges and class -F insulation suitable for operation 415 volt+6%-15%, 3phase, 50Hz AC power supply and full load current 15.6 amp with size of suction and delivery 100mmx100mm dia with overall efficiency 60 -65. The materials of construction as given below.a) Casing:F.C. 200 as per IS 210/1978b) Impeller: Bronze grade LTB-2 of IS c) Shaft : High carbon steel grade 40c8 of IS 1570(Part-2)318/1981d) GAsket: As per IS 5120/1977 and the pump sets must be as per IS-9079/2002 of reputed brand havingwide dealership net work for easy availability of spares.
20Supplying fitting fixing control pannel starter, BCH make with arrangement of volt meter, Amp, Meter mfitted with MCB control switch complete including indicator lamp with irrigation pannel bozard of apaproved design made out of 16gauge CR sheedt basement MS angle with double lock powder coat painting over one coat primere including fixing danager board with lucking devices and fixing of suitable stand for control pannel unit.
213 oh 4 wire20-100Amp3x230Volt (P-N) 50 AMP energy meter with ISI mark as approved by DISTCO CEDSU with matching fibre glass TP box for current meter including supplying, testing and energisation with Kit-kat.
22Motor hood cover of 18 gauge C.R. sheet with double coat painting over one coat primer so as to cover the motor
23MS base plate for fitting of pannel and pump as per sample as per direction of Engineer-in-charge.
243 x 16 sqm Tarpodar Cable XLPE (Cross like polythylin) confirming to IS-7098 (Part-II) including laying below 9 mtr of the ground & fitting the excavated materials including watering & ramming.
2563/100 AMP 415 volt T.P. main switch confirming to IS 4064 (Pt-I & Pt-II) with utilisation category Ac-22.
26Supply, fittintg and placing of 100mmdia Nominal Bore GI pipes having wall thickness 4.5 mm electrical resistance welded of medimum class confirming to IS-1239 (part-I/2004) with latest amendments, screwed at both ends as per IS-554 socketed at 1 end and other end protected with plastic threaded protector. The socket confirming IS-1239 (Part-II/1992) with latest amendments in rendom length of 4 to 7 mtrs. Each pipe shouldbear ISI certification and manufacturers name /trade mark.
27Labour charges for fitting, fixing of suction, delivery fitting including M.S. Tee set, NR valve, Switch valve and Air release valve etc minor welding transportation of materials to site etc. including nut, bolt rubber insallation etc complete.
28Supplying ,fitting materials at site.as per specification
29100mm dia C.I. Screw base foot valve (Kirloskar make ) IS
30100mm dia G.I. bend IS No 1239 (Part-II/1992)
31100mmdia G.I. flange IS No 6392/1971
32100 mm dia C.I. N.R valve IS No 5312 (Part-I) with ISI mark
33100mm dia C.I. sluice valve IS No 14846-2000 (Part-I)
34200x200x100mm MS Tee set with bend,closing and opening arrangement
35200x200x160mm PVC Tee set with bend,closing and opening arrangement
36160x160x100mm PVC raisar Tee with assoceries
37Cost of Butter fly valve
3850mm dia C.I. Air Release Valve IS Mark14845(SI)with 1 mtr long G.I.Short piece with saddle
39100x100x25mm dia G.I. Tee with Plug for Priming set
40200mm dia PVC end cap confirming to I\PL-R PVC-IS 2000 F
41200x100mm/PVC/GI/M.S Reducing Socket IS 2000F
42Labour charge for laying and fitting 160mm PVC pipe
43Labour charge for laying and fitting 200mm PVC pipe
44Empty Panel Board
45Electrical Works (Part-B)
46Construction & erection of 11 / 0.416 KV ,25 KVA/ 63 KVA, (3 star rated transformer) D.P. Substation confirming to RE Rules 1956, mounted on 2.44 Mtr long structure, supported in 300 Kg 9 Mtr long PSC 35pole, transformer hard channel & top channel made of 2.8 M long 100x50x6 mm M.S. Channel, Transformer belting on 2.80 M long 50x50x5 mm M.S. Angle, (all REC SPN. Std. F-3) with all accessories like 3 pole 11 KV HG Fuse (F-5) & A.B. Switches (F-9) both mounted on 2.8 M long 75x40x6 mm M.S. Channel and supported by 1.0M long 50x50x5 mm M.S. Angle, with 3 No. 11 KV Lightening Arrestors & Distribution box for 63 KVA S/S, Pipe earthing (F-2) , including cost of 50 Sqm 3.5 CorePVC Cable carpping & padding of Poles, Danger board at each Pole, Anti Climbing Devices, barbed wire fancing & all other necessary fittings i.e. required size Nuts & Bolts, Brackets, Cable, Cable Sockets etc. including cost of all materials, labour, transportation complete with liasioning for testing inspection & commissioning.
47ii) 63KVA Transformer only
48Construction of 3 phase 11 KV line as per REC standard confirming to RE Rules 1956 with 300 Kg 9 M long PSC Pole support in 70 M span, 55 Sqmm AAA Conductor, 11 KV \"V\" Cross arm , with required No.of 11 KV T & CDisc.Insulators & 11 KV Pin Insulators, Carping & Padding of Poles, Danger Board at each Pole, Anti Climbing Devices, Stay Set at Bending point & Double Stay at end point with 18 mm G.I. H.T Stay , concreting of Stay with Anchor plate, guarding at Road crossings etc.including cost of all materials, labour, transpotation, inspection & commissioning etc. complete.
49KB Brick wall boundary around sub-station
50Electrical installation & energisation

AI Tender Summary

OUR REF NO 30257121
AUTHORITY Government Departments
TENDER VALUE 13.15 Lakhs
LAST DATE 21-12-2021
Authority
Authority Name Orissa Lift Irrigation Corporation Limited
Work Description Installation And Electrification Of Odasingha-I Rl Project Under Athmallik Block Installation And Electrification Of Odasingha-I Rl Project Under Athmallik Block
Basic Detail
Tender No ANGUL/OLIC/02/2021-22
Bidding Type Tender
Location
City Angul
State Odisha
Key Dates
Publish Date 13 Dec 2021
Submission Date 21 Dec 2021
Open Date 22 Dec 2021
Finance
Tender Value 13.15 Lakhs
Tender Fee 6000
EMD Ref. Documents
Exemption Not Available
Document List
Tendernotice_2.pdf
c816bd61-3761-47e8-91e3-b2b6901bfd26.html
BOQ_382866.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Dec 13, 2021
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 21, 2021
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Dec 22, 2021

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
pdf

Tendernotice_2.pdf

html

c816bd61-3761-47e8-91e3-b2b6901bfd26.html

xls

BOQ_382866.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders