Rajasthan State Road Development And Construction Corporation Limited has published supply , installation testing , commissioning Of Electrical Sub Station Work At Medical College, Sri Ganganagar Sitc Of Electrical Sub Station Work At Medical College, Sri Ganganagar. Submission Date for this Tender is 28-12-2021. Electrical Substation Tenders in Medical College, Sri Ganganagar Rajasthan. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | S I T C of star ratedCopper wound distribution Transformerof following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, as per BEE star level- 2 & BIS approved with lossesas defined as per IS 1180 part I 2014. including standardaccessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cableboxes, Off -LTC (+5% to - 10% @ 2.5%) winding temperature rise of 50/55 degree C, ISI marked drain valve, Dial type Temperature gauge, first fill of oil, Epoxy based paint,including carrying of pre-commission Testing & Charging of Transformer. ( Transformer Should be CTL Tested , w/o any extra cost ) |
2 | 1000 KVA |
3 | SITC of Silent DG Set (As per latest CPCB emissionnorms) complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled. Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown). Engine shall have residential silencer (isolated from main DG chamber), up to 3 M exhaust piping (with insulation & cladding), electronic / Mechanical governor, Manual & electric Start ,Batteries,Engine instruments panel, AVM and with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mmCRCA sheet steel (structure) with side wall fabricated from 1.6 mm CRCA sheet & filled with 100mm thick glass wool (96Kg/m3)/Foam. as per IS 8183 the doors of 100 mm thick and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/ opening are sealed with neoprene/EPDN gaskets. |
4 | The enclosure has built in fuel tank, with protection and tripping of DG set against temperature of more than 50 degree centigrade. All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring & control system, MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dBA at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity : Approved Make :- Alternator:- Stamford/Kirloskar Engine:- Cummins/Caterpillar/Koel |
5 | Radiator Cooled & Turbo Charged /AC |
6 | 380 KVA at 0.8 pf 415V 50Hz 3-? Gr - I |
7 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to IS:694 with flexible copper conductor including making connection etc. as required. Group-1. |
8 | 6.0 Sq.mm 3 core flat / Round |
9 | P&F 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C/ D tripping characteristic) ISI marked IS 8828(1996)]/ conforming to IEC 60898 in existing board/sheets including making connections, testing etc. as required.Group-1 |
10 | Single pole MCB |
11 | 0.5 A to 5 A rating |
12 | 6 A to 32 A rating |
13 | Triple pole MCB |
14 | 6 A to 32 A rating |
15 | 40 A 63 A rating |
16 | Four pole MCB |
17 | 40 A 63 A rating |
18 | Supplying and fixing of Aluminium / Copper bus barby means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
19 | Electrolytic grade Aluminium bus bar |
20 | SF ofCurrent Transformer, with all necessary support in existing panel including connection etc. as required. Group-1 . |
21 | up to 150 / 5 Ratio , 5 VA , class 1 accuracy |
22 | from 200 / 5 to 400/5Ratio , 10 VA , class 1 accuracy |
23 | from 500 / 5 to 1600/5 Ratio , 15 VA ,class 1 accuracy |
24 | from 2000 / 5to 3200 /5 Ratio , 15 VA, class 1 accuracy |
25 | SF of110/220 V, LED (22.5 mm dia ) Indicatinglamp with integral circuit, terminal block, including connection etc. as required. Group-1. |
26 | Red/yellow/Green colour |
27 | Blue colour |
28 | P & F of ventilating fans, Capacitor start, single phase with PVC impeller, ABS body, automatic openable louver shutter in existing opening including making connection, testing etc. as required. Group-1. |
29 | 150 mm sweep |
30 | P & F of Multy functionmeter with LCD/ LED display capable of measuringelectrical parameters like V, I, F, PF, KW, Kva, Kvar, Kwh, Kvah, Kvarh display with 1A/5A CT input for LV/ HV network, RS 485 communication port etc. complete in all respect. |
31 | S & F of Electricalinsulating rubber mattsconfirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. Group-1. |
32 | 3.3 KV,2 mm thick with proof voltage 10 KV / 3 min. and Break Down Voltage 30 KV |
33 | 11 KV,2.5 mm thick with proof voltage 22 KV / 3 min. and Break Down Voltage45 KV |
34 | SITC of self healing MPP/MP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz and total wattage loss less than 0.5 Watt per KVAR . including making connections with suitable capacity conductors/cables testing etc. as required. Group-1. |
35 | Heavy duty Three phase 440 V , 50 Hz capacitor (Bank) |
36 | SITC of microprocessor based three phase sensingpower factor correction relay having following sensing capacitysecondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR,metering facility as required. Group-1. |
37 | 12 to 14 stage |
38 | sensitivity up to 50 milli Amp |
39 | P & F Cam operated rotary switches on existing panel with 2 way and off position Group-1. |
40 | one pole |
41 | 16 A |
42 | P & F of440 Volt 3 pole capacitor(AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current, conforming to IS:13947-4-1/IEC:947-4-1, Din rail mounting type including making connections, testing etc. as required. Group-1. suitable for following capacity capacitor bank. |
43 | up to 6 KVAR |
44 | 7 to 10 KVAR |
45 | 11 to 20 KVAR |
46 | 30 KVAR |
47 | 50 KVAR |
48 | 60 KVAR |
49 | P&F of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming etc. as required. Group-1 |
50 | One day reserve (mechanical type ) |
51 | SITC of Fixed /Draw out type 4 pole Air Circuit Breaker conforming to IS 60947 P - 2 in existingLT panel suitable for LT installation 440 V, 50 Hz and havingadjustable over load short-circuit, earth fault andmicroprocessor based release withseparate LED indication for each type of fault ,LCDdisplay , Thermal memoryat least 4NO & 4NC auxiliary contacts safety shutter and fault position acknowledgement mechanism . type ACB shall have separate indication for service, test, isolation, maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ), Uimp - 12 KV, including making connectionsetc. as required. |
52 | Draw out type (Manual spring charged) |
53 | 630 A Rating, 50kA |
54 | 800 A Rating, 50kA |
55 | 1000 A Rating , 50kA |
56 | 1600 A Rating ,50 / 65kA |
57 | Draw out type ( Motorised charging type ) |
58 | 2000 A Rating ,50 / 65 kA |
59 | SITC of Fixed /Draw out type 3 pole Air Circuit Breaker conforming to IS 60947 P - 2 in existingLT panel suitable for LT installation 440 V, 50 Hz and havingadjustable over load short-circuit, earth fault andmicroprocessor based release withseparate LED indication for each type of fault ,LCDdisplay , Thermal memoryat least 4NO & 4NC auxiliary contacts safety shutter and fault position acknowledgement mechanism . type ACB shall have separate indication for service, test, isolation, maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , Uimp - 12 KV, including making connectionsetc. as required. Group-1. |
60 | Draw out type (Manual spring charged) |
61 | 630 A Rating, 50kA |
62 | Supply and fixing of following accessories for Air circuit breakers. |
63 | Shunt Trip Release |
64 | Under Voltage Release |
65 | SITC of quick make and quick break4 POLEcurrent limiting MCCB having following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings and conforming to IS 60947-2 / IEC 60947-2 with front face and centralised adjustable, line load interchangeability, having positive isolation capability, provision for UVR , shunt trip ,earth fault trip, push( test) to trip , including making connections with lugs & spreaders,etc. as required. Group-1. |
66 | With Thermal Magnetic release |
67 | up to 100 Amp , 16 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
68 | up to 125 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
69 | 160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
70 | 250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
71 | 400 Amp ,35 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu |
72 | Supply and fixing of following accessories for MCCB |
73 | Extended Rotary Handle |
74 | P/Laying P.V.C./ XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required. Group-1 of size. Armoured |
75 | 6.0 Sq.mm |
76 | 4 core |
77 | 10.0 Sq.mm |
78 | 4 core |
79 | 16.0 Sq.mm |
80 | 4 core |
81 | 35.0 Sq,mm |
82 | 3.5 core |
83 | 300.0 Sq.mm |
84 | 3.5 core |
85 | 630.0 Sq.mm |
86 | 1 core |
87 | P/Laying P.V.C./ XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with Copper conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required. Group-1 of size. Armoured |
88 | 1.5 Sq.mm |
89 | 12 core |
90 | 2.5 Sq.mm |
91 | 12 core |
92 | Supplying and making one end termination with heavy duty single compression brass gland SIBG type, heavy duty aluminium lugs duly crimped with crimping tool, PVC tape etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. Group-1 of size. |
93 | 3.5 x 300.0 sq.mm |
94 | 3.5 x 35.0 sq.mm |
95 | 4 x 6.0 sq.mm |
96 | 4 x 10.0 sq.mm |
97 | 4 x 16.0 sq.mm |
98 | Supply, Fabricating & installing following sizes of powder coatedperforated M.S. cable trays including horizontal and vertical bends, reducers tees, cross members and other accessories as required. Group-1 and duly suspended from the ceiling with M.S. suspenders, fastners, supports etc. as required. Group-1. |
99 | 300mm x 50mm x 1.6mm |
100 | P / L of Double wall corrugated HDPE pipe confirming to IS : 14930 P - 1 & 2with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required. Group-1 of Gemini or IS:14930 marked make.Outer Dia. / Inner dia. |
101 | 180 / 152 mm |
102 | 50/55 mm |
103 | 90 / 76 mm |
104 | 110 / 95 mm |
105 | P & Laying XLPE insulated IS:7098/II/85 of Group1 and approved make H.T.cable for working voltage 11 K.V. Earthed direct in ground including excavation of 30cmx100cm size trench, 25cmlayer of river sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection testing etc.as required. Group-1 of size. |
106 | 3 core 185.0 Sq.mm |
107 | 3 core 300.0 Sq.mm |
108 | P & Laying XLPE insulated IS:7098/II/85 of Group1 and approved make H.T.cable for working voltage 33 K.V.Earthed direct in ground including excavation of 30cmx120cm size trench, 25cmlayer of river sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection testing etc.as required of size. |
109 | 3 core 300.0 Sq.mm |
110 | Providing & making heat shrinkable type indoor / outdoor/ straight through terminations / joint kit of Group1 and approved make suitable for XLPE insulated 11 KV / 33 KV cable, with required components, prepration of cable ends,testing etc. as required. Group-1 of following sizes . |
111 | 11 KV End Termination Kit Indoor type |
112 | 3 core 120/150/185/225 Sq.mm |
113 | 3 core 240/300 Sq.mm |
114 | 11 KV End Termination Kit Outdoor type |
115 | 3 core 120/150/185/225 Sq.mm |
116 | 3 core 240/300 Sq.mm |
117 | 11 KV Straight Through JointKit |
118 | 3 core 120/150/185/225 Sq.mm |
119 | 33 KV End Termination Kit Indoor type |
120 | 3 core 240/400 Sq.mm |
121 | 33 KV End Termination Kit Outdoor type |
122 | 3 core 240/400 Sq.mm |
123 | S.I.T.C. of bus trunking arrangement in convenient sections complete with housing of galvanized sheet steel of minimum 1.5 mm thickness, aluminium bus bar for use on 3 phase, 4 wire, 415 volts, A.C. supply with degree of protection IP-42 for the following current carrying capacity, including jointing of sections, flexible joints. expansion joints, bends, and earthing with 2 runs of alum. strips etc. as required. Group-1. |
124 | 1250 amps |
125 | 2500 amps |
126 | Plate Earthing as per IS:3043 withcopper Earth plate of size 600mm x 600mm x 3.0mm by embodying3 to 4 mtr. below the ground level with 25mm dia. G.I. "B" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. Group-1. |
127 | Maintenance free Gel EarthingwithPipe in pipe / Pipein striptechnologyfilled with anti corrosive conductive compound ( CPRI Tested )below the ground in 150 - 200 mm dia. earth pit & surrounding filled with required mineralfillingcompound ( MFC should have hygroscopic property to retain the moisture for long time to create low resistance zone) and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete testing of earth resistance as required. Group-1. of following sizes. |
128 | With Pipe in Pipe Technology (Inner pipe dia. / Outer pipe dia. ) 80 - 100 micron GI Coating |
129 | GI pipe 3000 mm long, 50 / 25mm, Terminal 14 mm GI Strip |
130 | Add Extra for Gel / Pipe earthing in Rocky Strata for making pit by Boring machine |
131 | S & Laying following size earth wire / stripin horizontal or vertical run in ground / surface / recess including riveting, soldering, saddles, making connection etc. as required. Group-1. |
132 | 32mm x 6mm copper strip |
133 | 50mm x 6mm copper strip |
134 | 8 SWG G.I. ( Hot Dipped) Wire |
135 | 50mm x 6mm G.I. ( Hot Dipped) Strip |
136 | S & Laying following size" B " class G.I. Pipe confirming to IS : 1239 P - 1 ( 1990 ) with accessories for laying earth conductor/strip / cable in ground/surface/recess as required. Group-1 |
137 | 125 mm dia. |
138 | Making hole in stone masonary/ RCC with core cutter for accomodating cables/earthing strip and making same with cement plasterincludingusing solvent to make water proof |
139 | 50mm to 150mm |
140 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required. Group-1 complete in all respect of rating: |
141 | 24 V DC |
142 | SITC of FCBC ( Float cum boost charger)suitable for 415V +/-10%, 50 Hz , 1-? / 3 -? Input & 24/ 48 /110 V DC OutputNatural Cooled, free standing in Sheet Steel enclosure,SCR controlled , regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,Built in DC Distribution Board (6 No MCB), indication , control as required. Group-1 of following rating: |
143 | 15A + 15A |
144 | Supply, Installation, Testing & Commissioning of HT metering cubical panel as approved By DISCOMs fabricated out of 14 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX6mm having provision for Following: (i)Provision for fixing Trivector Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set (To be supplied by DISCOMs), (iii)TT Block, (iv) 6mm Bakelite sheet on all sides, (V) 3/6 core copper cable for interconnections etc. as required. Group-1. |
145 | SITC of Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stopcommands, control Relays , selector switches for Ammeter & Voltmeter, Ammeter & Voltmeter , Control & Power Contactors, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets: Group1 |
146 | PLC Based: |
147 | 180 to 250 KVA |
148 | 320 to 500 KVA |
149 | SITC of 11 KV, 400/630 A, 20kA / 3 sec, Out door,Extensible type Ring main unit (RMU) in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, earthing switch, mechanical ON / OFF /Earth indication, Voltage presence indicator, Ring core protection CT 2.5 VA, 10P10 as per transformer rating, Shunt trip coil, Anti reflex operating handle, right angle boots etc. as required. |
150 | SITC of 11 KV, 400/630 A, 20kA / 3 sec, Out door Extensible type Ring main unit (RMU) in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, ring core protection & metering CT, Auxiliary relay for WTI, OTI ,Bucholz alarm & trip along with annuciator panel, master trip relay, mechanical ON / OFF /Earth indication, Voltage presence indicator, Shunt trip coil, 24 V DC power pack, Digital multi function meter, with Bus PT panelwith 3 Nos single phase voltage transformers of the ratio 11kV/v3 / 110 V/v3, 25 VA, Class 1.0 with HT fuses in the primary and MCB on the secondary side, Voltmeter with selector switch, R Y B phase indication. etc. as required. Group-1, Anti reflex operating handle, right angle boots etc. as required. Group-1. |
151 | Add extra for 1 no. VCB / SF6 circuit breaker coupled with existing extensible type RMUwith over load, Earth fault, short circuit relay, copper bus bar, Ring core protection CT 2.5 VA, 10P10 as per transformer rating, mechanical ON / OFF /Earth indication, Voltage presence indicator, Anti reflex operating handle, right angle boots etc. as required. Group-1. |
152 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , Painting etc. as required. Group-1. |
153 | Supplying and fixing of chain link fencing with angle iron posts 50x50x6mm placed at every 3 Mtr. apart 30cm in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner and every tenth post to be strutted with (50 x 50 x 6cm) angle iron provided and fixed and fitted with posts including earth work in excavation etc. complete with chain link size. |
154 | 50mm x 50mm x 3.15mm |
155 | Providing, Fixing, Jointing, Testing & Commissioning of Medium duty MS B class pipes conforming to IS 3589 / 1239 part-I for DG Exhaust applicationsincludingcutting,welding etc & fittings like elbows,flanges, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts . including the cost of thermal insulation with 50 mm thick layers of LRB rock wool (64 kg/m3 density) & 24 SWG aluminium sheet claddings etc complete as required. |
156 | 200 mm dia |
157 | Supply & FixingISI marked( IS : 15683 )Poratable Fire Exitnguisher,Trolleymounted Mech. Foam type capacity09 ltrs withgun-metalcapandnozzleandcompleterespectsinall respects includinginitial fill and wall suspension. |
158 | Supply & Fixing ISI marked ( IS : 15683 )Portable fire Extinguisher, Carbon-dioxidetype flat base including valve, dischargehose of not less than 10 mm dia. min. 600 mm long& completeinall respectsincluding initial fill with C02 gas confirming to IS:307-1966 filled to a filling ratio ofnot morethan0.667andwallsuspension bracket. Capacity 4.5 Kg. |
159 | Supply & FixingISI marked( IS : 15683 )Portable Fire Exitnguisher, ABC type, finished externally with red enamel paint, completein all respects includinginitial fill and wall suspension of following capacity. |
160 | 6 kg |
161 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existingsurface or recessed conduit/casing capping including making connections etc. as required. Group-1. |
162 | 1 x 2.5 sq.mm |
163 | 1 x 4.0 sq.mm |
164 | 1 x 6.0 sq.mm |
165 | 1 x 10.0 sq.mm |
166 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to IS:694 with flexible copper conductor including making connection etc. as required. |
167 | 2.5 Sq.mm 3 core flat / Round (Gr - I) |
168 | P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and enamel paint including cutting, welding, holes etc.of following sizes as required. Group-1. |
169 | 50mm x 50mm x 6mm |
170 | P & F paper phenolic resin bondedlaminates confirming to IS : 2036 -1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc platednut and bolts as required. Group-1. |
171 | 6.4 mm thick |
172 | P & F ofac operated heavy duty 230 /440 Volt power contactor conforming to IS:13947-4-1/IEC:947-4-1 having provision of mechanical interlocking, auuxilary contacts, Din rail mounting type including making connections, testing etc. as required. Group-1. |
173 | 4 pole Power contactorswith following AC 1 Rating |
174 | 63 Amp |
175 | P&F of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming etc. as required. Group-1 |
176 | One day reserve (mechanical type ) |
177 | Supply and erection of GI Octagonal / Conical pole of following length and dimension as per table E-10 with base plate on the cement concrete foundation of M-20 grade (1:1.5:3) with the help of anchor bolts of grade 6.8 (IS: 1367 P III ).The pole shall have a weatherproof flush door and locking arrangements. The complete work shall be supervised and certified by the manufacturers for satisfactory supply, erection, testing and commissioning. |
178 | Octagonal MS Polesmade of S-355JO grade steel sheet , folded lengthwise to obtained Octagonal shape, having single longitudinal seam weld and hot dipped galvanised internally & externally in accordance with IS 2629. (See Table E - 10 for specs.) (Gr - AI) |
179 | 3 Mtr. |
180 | 7 Mtr. |
181 | Supply, Erection and Fixing of hot dipped galvanised Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles (Gr - A1) |
182 | Single arm overhang |
183 | Double arm overhang |
184 | P & F of IP 65 protected LED Street Light fixture 70-75 Wall fwith surge protection device 1OKA) applicable for area lighting with extruded pressure diecast aluminium housing, system lumens efficacy of 100 lm/watt minimum, toughened glass with diffuser, suitable lenses on LED, 240V,50 Hz of High Power LED lamps supplied with pre-wired cable of 1 mtr. Integrated Driver shall be high efficiency having efficiency > 85% and in compliance to IEC standards System life of 50,000 Burning Hours, CRI >80, PF>0.90 at full load, CCT 5700-6500 I( fas per direction of Engineer incharge]. Fixtures shall be CE compliance. |
185 | P & F of IP 65 protected LED Flood LightLuminaire made of single piece powder coated pressure die cast/Extruded Aluminium housing with heat dissipation fins on housing. Toughened glass over with suitable lens on LEDs to achieve various beam angles. Input power (including driver loss) not more than 40W/60W/90W/120W/160W with luminous Efficacy > 80 Lumen/W (warm white) & > 85 Lumens/W (cool white) (As per LM 79). Appropriate beam angle lesn 45°/60°/80°/70° x 140° (High Mast) to be used as per requirement. LEDs of Cree/Nichia/Osram/Philips make is to be used at 1W/2W, CRI > 70 and CCT 2700 K - 6500 K.The integral SMPS based electronic driver must have efficiency > 85%, Power factor >0.95, THD<20% and input Voltage range of 90-270 VAC at 50Hz. System life of 25000 Burning Hours with 70% of initial Lumens maintained. Fixtures must be in compliance with IS/CE Standards. |
186 | High Power LED Flood Light 120W |
187 | SITC of high mast lighting system (as per CP3-TR7/1996 of ILE, UK) consisting of totally hot dip galvanised by single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm, mast head frame assembly with full cover, aviation obstructionlights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement ( winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, suitable ropes (AISI 316, 7 / 19 costruction ), EPR insulated PCP sheathed trailing cable, outdoor type control panel for auto on / off, reverse / forward motor operationand CC foundationof M - 25 grade complete as required. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised and certified by the manufacturers for satisfactory supply, erection, testing and commissioning of high mast. (See table E - 13 for specs.) |
188 | 20.0 Mtr HM (in 2 section) |
189 | P & F of aviation obstruction light luminaire comprising of yellow painted die cast aluminium alloy housing, built in 75 VA step up transformer, heat resistant clear glass cover, neon spiral lamp / 2x100W GLS Lamp / LED Lamps complete in all respect |
190 | aviation obstruction LED light luminaire |
191 | NON BSR |
192 | P & F of IP 65 protected LED Post-Top-Light system with Die casthousing, poycarbonate diffuser, Maximum 40 watt,Mininum Lumnes 3600 Watt 220-240V, 50Hz (integrated Driver), LED lamps supplied with pre-wired cable of 1 mtr. Driver shall be high efficiency having efficiency > 85% and in compliance to IEC standards (Integral with light fixture).system life of 50000 Burning Hours with 70% of initial Lumens maintained.Light output in Cool white or Warm White Colour as per engineers choice. Fixtures shall be CEcompliance.Make :- Philips/Wipro/Crompton |
193 | Supply & installation of cable identification plates duly secured to cables for identification suitable for cable sizes taken in the BOQ. |
194 | P & F of ventilating fans with thermostate and ON/OFF selector switch including making connection, testing etc. as required. |
195 | 100 mm sweep |
196 | S & Laying following size earth wire/strip of 1.5 mtr length for connecting earth strip of DG netural terminal including riveting, soldering, saddles, making connection etc. as required. |
197 | 50mm x 6mm flexible copper strip |
198 | SITC of wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel made out of2 mm thick CRCA sheet , required hardware,duly powder painted in required shade after rinsing . The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel , door handle, hinged door with locking arrangement for equipment/switchgear.. Side walls and cable alley compartments having bolted type doors with detachable extension type structure. (only outer area on all sides shall be measured ) Make : Engineers & Engineers / John"s Electric Co. / Milestone / Advance Panels /Ankit Electrical |
199 | HT BREAKER |
200 | Supplying, Installation, Testing and Commissioning of indoor type floor mounted made of AluZinc metal sheet 33 KV integrated VCB panel with 4 nos. VCBs (Incoming - 2 nos. & Outgoing - 2 nos.) totally enclosed, horizontal draw out, horizontal/vertical isolation type breaker, as per IS 13118, IEC:62271-100& 200, having capacities as mentioned below, single break, trip free mechanism, motorised / manually spring charged and auto / manually closing breaker suitable for use on 33 KV, 3 phase, 50 Hz AC supply with short circuit fault level of 25 KA for 3 sec, IAC AFLR classification as per IEC62271 -200 complete with self contained draw out type arc-proof design confirming to relevant IEC standards complete with self-contained, fully interlocked, rack in and rack out mechanism, vacuum bottles, copper busbars of 800 Amps capacity, breaker featured with ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switches as required and equipped with following switchgears and accessories i/c necessary foundation & end termination box for terminating HT XLPE 33 KV cable (cable entry from bottom) on primary and secondary side, necessary strip heaters to prevent absorption of moisture during winter and monsoon season, protection arrangement shall comprise of overcurrent, overvoltage and earth fault with Numerical relays. Vacuum interrupter for VCB shall have minimum 100 nos. operations at full short circuit current rating as specified. Please Note: Panel, VCB, VI & Relay shall be of same make. |
201 | Incoming: 2 nos. (Each comprising of following i/c all required accessories) |
202 | 1 no 800 Amp, VCB having 33 KV, 25 kA for 3 sec with motorized universal spring charging mechanism, internal spring charging handle for manual spring charge with tripping coil and closing coil for 24 V DC |
203 | Set of 3 Nos, 33 KV / 110 Volts PT Class 0.5 accuracy and 100 VA burden with protection MCBs of suitable rating |
204 | DigitalMultifunction Meter having V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Maximum Demand (kW & kVA), MD reset with battery charging arrangement for storage of 75 Nos. Events. Accuracy Class : 0.5, Communication Prot: RS485 with suitable Accessories- 1 Set |
205 | 1 No Numerical based flush mounted Protection and Control device shall be of numerical type and designed to meet a high degree of dependability and security. The device shall include an LCD display which supports mimic (e.g. single line diagram can be drawn) and at least 8 LEDs at the front. The device shall have screw terminals for connection of wires for all CT/VT inputs, power supply, logic inputs and outputs. The device shall have 4 CT inputs and 4 VT inputs. The PCB cards of the device shall be conformal coated. The device shall be provided with at least 16 digital inputs and 8 digital outputs. Both digital input and output shall be freely programmable. The device shall have USB / RS232 communication port in the front for the setting software use and at the rear there shall be 2 x RJ-45 Ethernet port. Relay shall support PRP and RSTP redundancy. The IEC 61850 communication has to support peer to peer communication (GOOSE). The device shall have KEMA IEC61850 edition 2 certificates which are within 5 years from the date of issue of the certificate. The device shall have facility to store at least 5 fault records, 1000 event records and disturbance record (in COMTRADE format). The device shall offer complete set of measurement functions. The measurement functions cover phase and residual currents, voltages, power, energy, system frequency and harmonics. Condition monitoring has to monitor continuously trip circuits, breaker wear and current transformers. The devices shall have inbuilt fault-locator feature. The device shall support webserver/web-HMI through which we can monitor and control the relays over an ethernet LAN network. Full licensed copy of relay configuration software shall be provided at each substation. The device shall contain at least following necessary protections; 1) Phase overcurrent (50/51) 2) Directional phase overcurrent (67) 3) Earth fault (50N/51N) 4) Directional earth fault (67N) 5) Undervoltage (27) / Overvoltage (59) 6) Circuit breaker failure (50BF) 7) Fault Locator |
206 | Electromechanical Under/Overvoltage relay with timer for prevent tripping in case of light failure from source |
207 | Pluggable Relays for contact multiplication, anti-pumping, spring-charging indication etc. where applicable. |
208 | 1 set of dual core dual ratio 3 CTs 200/150/1/1 Amp of 15 VA burden and accuracy Class - 0.5 for metering and class 10P10 for protection. |
209 | 1 no. Annunciators. |
210 | Indications : (i) LED type indication for phase (R-Y-B ) (ii) |
211 | LED type indication for status (ON / OFF / TRIP /TCH / Spring Charge ) (iii) LED type indication for breaker position (Test / Service ) (iv) LED type indication for aux. supply availability ( AC Healthy, DC Healthy ) |
212 | Outgoing : 2 nos. (Each comprising of following i/c all required accessories) |
213 | 1 no 800 Amp, VCB having 33 KV, 25 kA for 3 sec with motorized universal spring charging mechanism, internal spring charging handle for manual spring charge with tripping coil and closing coil for 24 V DC |
214 | DigitalMultifunction Meter having V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Maximum Demand (kW & kVA), MD reset with battery charging arrangement for storage of 75 Nos. Events. Accuracy Class : 0.5, Communication Prot: RS485 with suitable Accessories- 1 Set |
215 | 1 No Numerical based flush mounted Protection and Control device shall be of numerical type and designed to meet a high degree of dependability and security. The device shall include an LCD display which supports mimic (e.g. single line diagram can be drawn) and at least 8 LEDs at the front. The device shall have screw terminals for connection of wires for all CT/VT inputs, power supply, logic inputs and outputs. The device shall have 4 CT inputs and 4 VT inputs. The PCB cards of the device shall be conformal coated. The device shall be provided with at least 16 digital inputs and 8 digital outputs. Both digital input and output shall be freely programmable. The device shall have USB / RS232 communication port in the front for the setting software use and at the rear there shall be 2 x RJ-45 Ethernet port. Relay shall support PRP and RSTP redundancy. The IEC 61850 communication has to support peer to peer communication (GOOSE). The device shall have KEMA IEC61850 edition 2 certificates which are within 5 years from the date of issue of the certificate. The device shall have facility to store at least 5 fault records, 1000 event records and disturbance record (in COMTRADE format). The device shall offer complete set of measurement functions. The measurement functions cover phase and residual currents, voltages, power, energy, system frequency and harmonics. Condition monitoring has to monitor continuously trip circuits, breaker wear and current transformers. The devices shall have inbuilt fault-locator feature. The device shall support webserver/web-HMI through which we can monitor and control the relays over an ethernet LAN network. Full licensed copy of relay configuration software shall be provided at each substation. The device shall contain at least following necessary protections; 1) Phase overcurrent (50/51) 2) Directional phase overcurrent (67) 3) Earth fault (50N/51N) 4) Directional earth fault (67N) 5) Undervoltage (27) / Overvoltage (59) 6) Circuit breaker failure (50BF) 7) Fault Locator |
216 | Electromechanical Under/Overvoltage relay with timer for prevent tripping in case of light failure from source |
217 | Pluggable Relays for contact multiplication, anti-pumping, spring-charging indication etc. where applicable. |
218 | 1 set of dual core dual ratio 3 CTs 200/150/1/1 Amp of 15 VA burden and accuracy Class - 0.5 for metering and class 5P10 for protection. |
219 | 1 no. Annunciators. |
220 | Indications : (i) LED type indication for phase (R-Y-B ) (ii) |
221 | LED type indication for status (ON / OFF / TRIP /TCH / Spring Charge ) (iii) LED type indication for breaker position (Test / Service ) (iv) LED type indication for aux. supply availability ( AC Healthy, DC Healthy ) |
222 | Panel Make: SCHNEIDER/SEIMENS/ABB. Panels fabricated in OEM plant shall be acceptable. |
223 | Supplying/Receiving,Installation / Erection, Testing and Commissioning ofcopper wound 33/11 KV, 50 C/S, ONAN Delta-star connected, Dyn11 vector group transformer,as per CTL specification withtype test certificate with Off circuit tap changer for Voltage regulation from -10% to plus 5% in steps of 2.5% on HV side and complete with MOG level, Oil level indicator, conservator, silica gel breather, radiator, fins, HT cablebox & LT cableboxes, Bucolz realy, Marshal box,RTCC panel as required of rating. The transformer is to be provided with all required accessories as per OEM recommendation including suitable size foundation of Cement Concrete as per drawing approved by Engineer-in-Charge. The core of transformer shall be made up of high grade low loss CRGO with M4 Grade or Better Electrical steel, perfectly insulated and clamped to minimize noise and vibrations.Inspection of transformer shall be done at manufacturer’s premises. 3.15MVA. (Make: Danish/Vardhman/RTS / Uttam Bharat). |