Repairs / Maintenance / Replacement Of Ceiling Fan, Wall Mounted Fans, Electric Geysers, Electric Meter, Solar Water Heater, Outdoor Worn Out Lt Panels And Connected Accessories And Connected Allied Works At Ins Kalinga, Ins Karna And Nad Bheemuni, Garrison Engineer P Navy Kalinga Visakhapatnam-Andhra Pradesh

Military Engineer Services-MES has published Repairs / Maintenance / Replacement Of Ceiling Fan, Wall Mounted Fans, Electric Geysers, Electric Meter, Solar Water Heater, Outdoor Worn Out Lt Panels And Connected Accessories And Connected Allied Works At Ins Kalinga, Ins Karna And Nad Bheemuni. Submission Date for this Tender is 01-01-2022. Electrical Panel Tenders in Garrison Engineer P Navy Kalinga Visakhapatnam Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

30247830
Corrigendum : Repairs / Maintenance / Replacement Of Ceiling Fan, Wall Mounted Fans, Electric Geysers, Electric Meter, Solar Water Heater, Outdoor Worn Out Lt Panels And Connected Accessories And Connected Allied Works At Ins Kalinga, Ins Karna And Nad Bheemuni
Open Tender
Indian
Andhra Pradesh
Garrison Engineer P Navy Kalinga Visakhapatnam
01-01-2022

Tender Details

Repairs / Maintenance / Replacement Of Ceiling Fan, Wall Mounted Fans, Electric Geysers, Electric Meter, Solar Water Heater, Outdoor Worn Out Lt Panels And Connected Accessories And Connected Allied Works At Ins Kalinga, Ins Karna And Nad Bheemunipatna Repairs / Maintenance / Replacement Of Ceiling Fan, Wall Mounted Fans, Electric Geysers, Electric Meter, Solar Water Heater, Outdoor Worn Out Lt Panels And Connected Accessories And Connected Allied Works At Ins Kalinga, Ins Karna And Nad Bheemunipatna

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Dec-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 01-01-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 30000.0 /-
Tender Value
INR 15 Lakhs /-

BOQ Items

Name of Work : REPAIRS/ MAINTENANCE/ REPLACEMENT OF CEILING FAN, WALL MOUNTED FANS, ELECTRIC GEYSERS, ELECTRIC METER, SOLAR WATER HEATER, OUTDOOR WORN OUT LT PANELS AND CONNECTED ACCESSORIES AND CONNECTED ALLIED WORKS AT INS KALINGA, INS KARNA & NAD BHEEMUNIPATNAM UNDER GE(P) NAVY KALINGA
Sl. No. Item Description
1Excavation in trenches n. exc 1.5 mtr wide and n. exc 1.5 mtr in depth for laying of cable, foundation poles/stay and getting out in soft /loose soil complete all as directed.
2Returning, filling in, including spreading, levelling, watering andwell ramming in layers n. exc. 25cm complete all as specified and as directed by the Engineer-in-Charge.
3Removing excavated soil to a distance n. exc. 50m and depositing where directed at a level n. exc. 1.5m above the starting point complete all as specified and as directed by the Engineer-in-Charge.
4Supply and spread clean river sand as cable cushioning for protection of cable to be laid in trenches all as per SSR Part-I complete all as specified and as directed by the Engineer-in-Charge. Note: Only punned thickness of 18cm will be measured for the purpose of payment.
5S&F unreinforced precast concrete cable cover of Class LV, Type I, flat, size 250mm x 150mm x 40mm for protection of cable laid in trenches.
6M&L for cutting of existing road crossing, PCC hard standing for taking out/laying of cable including making good the exiting damaged surface with same specification to match the original finish complete all as specified and as directed.
7Supply and laying steel tubing galvanised 50mm bore medium grade with all fitting for cable protection complete all as specified and as directed by the Engineer-in-Charge.
8Supply and laying steel tubing galvanised 80mm bore medium grade with all fitting for cable protection complete all as specified and as directed by the Engineer-in-Charge.
9Supply and laying LT underground cable XLPE insulated and sheathed armoured cable 1100 Volts 4 core 16 Sq.mm. aluminium conductor in trenches/poles and connecting with all accessories complete all as specified and as directed by the Engineer-in-Charge.
10Supply and laying LT underground cable XLPE insulated and sheathed armoured cable 1100 Volts 3.5 core 185 Sq.mm. aluminium conductor in trenches/poles and connecting with all accessories complete all as specified and as directed by the Engineer-in-Charge.
11M&L heat shrinkable straight through joint for LT UG XLPE/PVC cable 1100 Volts grade with necessary jointing materials and ferrule including cutting unserviceable portion of cable of size 2/4 core10/16Sq.mm. complete all as specified and as directed by the Engineer-in-Charge.
12M&L heat shrinkable straight through joint for LT UG XLPE/PVC cable 1100 Volts grade with necessary jointing materials and ferrule including cutting unserviceable portion of cable of size 3.5/4 core 25 to 50 Sq.mm. complete all as specified and as directed by the Engineer-in-Charge.
13M&L heat shrinkable straight through joint for LT UG XLPE/PVC cable 1100 Volts grade with necessary jointing materials and ferrule including cutting unserviceable portion of cable of size 3.5/4 core 70 to 120 Sq.mm. complete all as specified and as directed by the Engineer-in-Charge.
14M&L heat shrinkable straight through joint for LT UG XLPE/PVC cable 1100 Volts grade with necessary jointing materials and ferrule including cutting unserviceable portion of cable of size 3.5/4 core 150 to 185 Sq.mm. complete all as specified and as directed by the Engineer-in-Charge.
15M&L heat shrinkable straight through joint for LT UG XLPE/PVC cable 1100 Volts grade with necessary jointing materials and ferrule including cutting unserviceable portion of cable of size 3.5/4 core 240 to 400 Sq.mm. complete all as specified and as directed by the Engineer-in-Charge.
16Supply and Replace in proper position MCCB, four pole of capacity 250 amps, 415 Volts, 50 KA, 50 Hz,AC supply,lcs-100% adjustable over load 80-100% thermal magnetic release mechanism including necessary cable lugs and wire complete all as specified and as directed.
17All as per item No. 16 above but capacity of 200A, 4 pole, lcu=26 KA
18All as per item No. 16 above but capacity of 125A, 4 pole, lcu=25 KA
19All as per item No. 16 above but capacity of 63A, 4 pole, lcu=25 KA
20M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground(earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised earth strip 32x6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanisediron or steel all as shown in electrical plate No 3, connected to earthing point of outdoor panel boards all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber & RCC 1:2:4 type B1 cover 40mm thick, with 8mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 20mm dia GI medium grade pipe for watering , water funnel,complete all as specified and testing on completion.
21M&L for repairs and replacement of LT panels door hinges, mild steel of suitable size including cutting and welding and brazingcomplete all as specified and directed by Engineer-in-Charge.
22M&L for painting of LT panels at site and applying two coat of synthetic enamelled grey paint after removing all dust & rust and paint shall confirm to IS 2032complete all as specified and directed by Engineer-in-Charge.
23Supply, install ,test & commissioning LT panel Outdoor, Floor mounted/pedestal type,cubical,self supported, CPRI approved make, front and rear openable, double door hinged type with locking arrangement and suitable ventilations on both sides IP 54 protection with dust and vermin proof etc,fabricated out of 3.15 mm CRCA sheet duly powder coated, with angle iron frame including bus bar of suitable size for 3 phase 4 wire system, 415 volt, 50 Hz, AC supply with bus bar aluminium 400 Amps capacity with PVC sleeves/ taps RYB colours for phase indication, mounted/ fixed on raised PCC platform of suitable size with PCC 1:2:4, type B-1 (using 20 mm graded aggregate) with control wiring copper stranded PVC insulated FRLS cables compressing cable gland brass, copper/ brass lugs etc conforming to CPRI approved manufacturer.
24(a) MCCB 4 pole 400 Amps 50Hz, 415 V, 50 KA-01 no (for incoming)
25(b) MCCB 4 pole 250 Amps 50Hz, 415 V, 37 KA-01 no (for Outgoing)
26(c) MCCB 4 pole 200 Amps 50Hz, 415 V, 26 KA-01 no (for Outgoing)
27(d) MCCB 4 pole 125 Amps 50Hz, 415 V, 26 KA-04 no (for Outgoing)
28(e) LED type three Phase indicator with controlling fuses for RYB -01 set
29(f) 3Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96 x 96 mm, Current Transformer of suitable rating - Set of three
30(g) Digital time switch with contactor 2NO + 2NC, 4 pole, 63 Amps, 1 TPN
31(h) Electrolyte Aluminium busbars PVC colour sleeved 400 Amps capacity TP and 200 Amps for neutral mounted on hygroscopic insulator duly colour coded RYB & Green sleeves
32Supply, install ,test & commissioning LT panel Outdoor, Floor mounted/pedestal type,cubical,self supported, CPRI approved make, front and rear openable, double door hinged type with locking arrangement and suitable ventilations on both sides IP 54 protection with dust and vermin proof etc,fabricated out of 3.15 mm CRCA sheet duly powder coated, with angle iron frame including bus bar of suitable size for 3 phase 4 wire system, 415 volt, 50 Hz, AC supply with bus bar aluminium 400 Amps capacity with PVC sleeves/ taps RYB colours for phase indication, mounted/ fixed on raised PCC platform of suitable size with PCC 1:2:4, type B-1 (using 20 mm graded aggregate) with control wiring copper stranded PVC insulated FRLS cables compressing cable gland brass, copper/ brass lugs etc conforming to CPRI approved manufacturer.
33(a) 4 Pole MCCB 250A 50HZ 415 Volts 26 KA -1 No (incoming)
34(b) 4 Pole MCCB 125A 50HZ 415 Volts 16 KA -03 No (Out going)
35(c) 250 A 4 Pole Change over switch, 50 KA, 415V, 50 Hz, AC supply,manual type, open construction or closed type construction as per site requirement, adjustable type of thermal and magnetic setting, handle,including necessary cable lugs & wire etc complete all as specified and directed.
36(d) Digital time Switch with contactor 2NO+2NC 4 pole 63 amps
37(e) 3Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96 x96 mm, Current Transformer of suitable rating - Set of three
38(f) LED type three Phase indicator with controlling fuses for RYB -01 set
39(g) Electrolyte Aluminium busbars PVC colour sleeved 400 Amps capacity TP and 200 Amps for neutral mounted on hygroscopic insulator duly colour coded RYB & Green sleeves
40Supply, install ,test & commissioning LT panel Outdoor, Floor mounted/pedestal type,cubical,self supported, CPRI approved make, front and rear openable, double door hinged type with locking arrangement and suitable ventilations on both sides IP 54 protection with dust and vermin proof etc,fabricated out of 3.15 mm CRCA sheet duly powder coated, with angle iron frame including bus bar of suitable size for 3 phase 4 wire system, 415 volt, 50 Hz, AC supply with bus bar aluminium 400 Amps capacity with PVC sleeves/ taps RYB colours for phase indication, mounted/ fixed on raised PCC platform of suitable size with PCC 1:2:4, type B-1 (using 20 mm graded aggregate) with control wiring copper stranded PVC insulated FRLS cables compressing cable gland brass, copper/ brass lugs etc conforming to CPRI approved manufacturer.
41(a) MCCB 4 pole 200 Amps 50Hz, 415 V, 35 KA-01 no (for incoming)
42(b) MCCB 4 pole 100 Amps 50Hz, 415 V, 25 KA-03 no (for Outgoing)
43(c) LED type three Phase indicator with controlling fuses for RYB -01 set
44(d) 3Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96 x 96 mm, Current Transformer of suitable rating - Set of three
45(e) LED type three Phase indicator with controlling fuses for RYB -01 set
46(f) Electrolyte Aluminium busbars PVC colour sleeved 400 Amps capacity TP and 200 Amps for neutral mounted on hygroscopic insulator duly colour coded RYB & Green sleeves
47Supply, install ,test & commissioning LT panel Outdoor, Floor mounted/pedestal type,cubical,self supported, CPRI approved make, front and rear openable, double door hinged type with locking arrangement and suitable ventilations on both sides IP 54 protection with dust and vermin proof etc,fabricated out of 3.15 mm CRCA sheet duly powder coated, with angle iron frame including bus bar of suitable size for 3 phase 4 wire system, 415 volt, 50 Hz, AC supply with bus bar aluminium 400 Amps capacity with PVC sleeves/ taps RYB colours for phase indication, mounted/ fixed on raised PCC platform of suitable size with PCC 1:2:4, type B-1 (using 20 mm graded aggregate) with control wiring copper stranded PVC insulated FRLS cables compressing cable gland brass, copper/ brass lugs etc conforming to CPRI approved manufacturer.
48(a) MCCB 4 pole 400 Amps 50Hz, 415 V, 36 KA-01 no (for incoming)
49(b) MCCB 4 pole 250 Amps 50Hz, 415 V, 35 KA-02 no (for Outgoing)
50(c) MCCB 4 pole 125 Amps 50Hz, 415 V, 25 KA-03 no (for Outgoing)
51(d) LED type three Phase indicator with controlling fuses for RYB -01 set
52(e) 3Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96 x96 mm, Current Transformer of suitable rating - Set of three
53(f) Electrolyte Aluminium busbars PVC colour sleeved 400 Amps capacity TP and 200 Amps for neutral mounted on hygroscopic insulator duly colour coded RYB & Green sleeves
54(g) 400 Amp 4 pole change over switch , 50 KA, 415 volt, 50 Hz, AC supply, manual type, open construction or closed type construction as per site requirement, adjustable type of thermal and magnetic setting, handle, including necessary cable lugs & wire etc
55Supply, install ,test & commissioning LT panel Outdoor, Floor mounted/pedestal type,cubical,self supported, CPRI approved make, front and rear openable, double door hinged type with locking arrangement and suitable ventilations on both sides IP 54 protection with dust and vermin proof etc,fabricated out of 3.15 mm CRCA sheet duly powder coated, with angle iron frame including bus bar of suitable size for 3 phase 4 wire system, 415 volt, 50 Hz, AC supply with bus bar aluminium 400 Amps capacity with PVC sleeves/ taps RYB colours for phase indication, mounted/ fixed on raised PCC platform of suitable size with PCC 1:2:4, type B-1 (using 20 mm graded aggregate) with control wiring copper stranded PVC insulated FRLS cables compressing cable gland brass, copper/ brass lugs etc conforming to CPRI approved manufacturer.
56(a) MCCB 4 pole 400 Amps 50Hz, 415 V, 36 KA-01 no (for incoming)
57(b) MCCB 4 pole 200 Amps 50Hz, 415 V, 25 KA-02 no (for Outgoing)
58(c) MCCB 4 pole 100 Amps 50Hz, 415 V, 25 KA-02 no (for Outgoing)
59(d) MCCB 4 pole 63 Amps 50Hz, 415 V, 25 KA-02 no (for Outgoing)
60(e) LED type three Phase indicator with controlling fuses for RYB -01 set
61(f) 3Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96 x96 mm, Current Transformer of suitable rating - Set of three
62(g) Electrolyte Aluminium busbars PVC colour sleeved 400 Amps capacity TP and 200 Amps for neutral mounted on hygroscopic insulator duly colour coded RYB & Green sleeves
63(h) Digital time switch with contactor 2NO + 2NC, 4 pole, 63 Amps, 1 TPN
64Supply, install ,test & commissioning LT panel Outdoor, Floor mounted/pedestal type,cubical,self supported, CPRI approved make, front and rear openable, double door hinged type with locking arrangement and suitable ventilations on both sides IP 54 protection with dust and vermin proof etc,fabricated out of 3.15 mm CRCA sheet duly powder coated, with angle iron frame including bus bar of suitable size for 3 phase 4 wire system, 415 volt, 50 Hz, AC supply with bus bar aluminium 400 Amps capacity with PVC sleeves/ taps RYB colours for phase indication, mounted/ fixed on raised PCC platform of suitable size with PCC 1:2:4, type B-1 (using 20 mm graded aggregate) with control wiring copper stranded PVC insulated FRLS cables compressing cable gland brass, copper/ brass lugs etc conforming to CPRI approved manufacturer.
65(a) MCCB 4 pole 400 Amps 50Hz, 415 V, 36 KA-01 no (for incoming)
66(b) MCCB 4 pole 250 Amps 50Hz, 415 V, 35 KA-01 no (for Outgoing)
67(c) MCCB 4 pole 125 Amps 50Hz, 415 V, 35 KA-02 no (for Outgoing)
68(d) MCB 4 pole 63 Amps 50Hz, 415 V, 10 KA-02 no (for Outgoing)
69(e) LED type three Phase indicator with controlling fuses for RYB -01 set
70(f) 3 Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96 x 96 mm, Current Transformer of suitable rating - Set of three
71(g) Electrolyte Aluminium busbars PVC colour sleeved 400 Amps capacity TP and 200 Amps for neutral mounted on hygroscopic insulator duly colour coded RYB & Green sleeves
72Supply, install ,test & commissioning of VTPN Distribution board with provision for100Amps MCCB as incomer and MCB 8 way IP43 as outgoing with all connecting fitting and fixtures including internal connections complete all as specified and directed by Engr-in-charge. Make-: C&S cat No. CSDBMCCB100DD08IP43S or equivalent as approved by GE
73Taking Down LT panel/Distribution boxes of any type , any size and any capacity from their existing place and further disposal including making good the disturbed surface whatever required(as per the existing condition) all as specified and directed by Engr-in-charge.
74Taking Down LT panel any type , any size and any capacity from their existing place and Refix the same one in other place including making good the disturbed surface whatever required(as per the existing condition) all as specified and directed by Engr-in-charge. Note-Connecting item like cables, lugs, joints are paid separately on their respective item of this schedule
75Supply, install ,test & commissioning of VTPN Distribution board with provision for250Amps MCCB as incomer and MCB 4 way IP43 as outgoing with all connecting fitting and fixtures including internal connections complete all as specified and directed by Engr-in-charge. Make-: C&S cat No. CSDBMCCB225DD04IP43S or equivalent as approved by GE
76Supply, install ,test & commissioning of VTPN Distribution board with provision for100Amps MCCB as incomer and MCB 4 way IP43 as outgoing with all connecting fitting and fixtures including internal connections complete all as specified and directed by Engr-in-charge. Make-: C&S cat No. CSDBMCCB100DD04IP43S or equivalent as approved by GE
77Checking of ceiling fan 1200mm sweep at site when and where required asMES complaint slip on daily basis if required except Sunday and holidays in existing position including Supply and fixing as replacement at site in position ceiling fan condenser 2.5 mfd all as specified and as directed.
78All as per item No. 34 here-in-before but ceiling fan 1400mm sweep when and where required asMES complaint slip on daily basis if required except Sunday and holidays and ceiling fan condenser 3.15 mfd all as specified and as directed.
79Taking down carefully existing ceiling fan of any sweep and any make after disconnecting the electrical connections, dismantling the blades and removing fan including blades to the workshop including cleaning and dismantling the fan into parts and segregation of unserviceable parts, replacement of unserviceable spare parts with new parts including necessary machining works and lubricating with approved grade of grease and necessary minor soldering work (if required) and re-assembling the fan complete and testing and refixing the fan in same position including all electrical connections and material and labour for replacement of two nos split pins, one connection block and one rubber reel complete all as specified and as directed.
80Note:- (i) Rewinding work of armature (if any) shall be measured and paid separately (ii) New spare parts required for replacing old burnt out parts other than connector, split pins, connection block and rubber reel shall be measured and paid separately under relevant item as supply only. (iii) Labour cost for replacing spare parts are deemed to be inclusive in the quoted rate of item No. 36
81Taking down carefully existing exhaust fan of size upto 300 mm sweep and any make after disconnecting the electrical connections and removing the exhaust fan with blades to the workshop including cleaning of dust and dismantling the fan into parts and segregation of unserviceable parts, replacement of unserviceable spare parts with new parts including necessary machining works and lubricating with approved grade of grease and necessary minor soldering work (if required) and re-assembling the fan complete, testing and refixing the fan in same position including all electrical connections and material and labour for replacement of one connection block complete all as specified and as directed.
82Note :- (i) Rewinding work (if any) shall be measured and paid separately (ii) New spare parts required for replacing old burnt out parts other than connector shall be measured and paid separately under relevant item as supply only. (iii) Labour cost for replacing spare parts are deemed to be inclusive in the quoted rate of item No. 37
83All as per Item No. 37 here-in-before but for exhaust fan of size upto 450 mm sweep complete all as specified and as directed.
84Taking down and refixing after repair air circulation fan of any make/ model and sweep in its original position, connecting and testing complete all as specified and as directed.
85Taking down and refixing after repair wall mounted fan of any make/ model and sweep in its original position, connecting and testing complete all as specified and as directed.
86Taking down and refixing after repair pedestal fan of any make/ model and sweep in its original position, connecting and testing complete all as specified and as directed. Note for Item Nos. 39.00 to 41.00 : Bearing/ Gun metal bush/ rubber bush & bolts/ capacitor/ rewinding/ flexible cord/ shaft etc will be measured and paid separately.
87M&L for taking out and removing burnt copper winding, cleaning the armature, rewinding the fan armature for 1200 mm sweep fan with new super enamelled copper wire of existing gauge including supply and fixing necessary insulating materials etc and varnishing with approved grade of insulation varnish and heating up and testing complete all as specified and as directed.
88All as per Item No. 42 here-in-before but for ceiling fan of size 1400 mm sweep complete all as specified and as directed.
89All as per Item No. 42 here-in-before but for exhaust fan of size upto 300 mm sweep complete all as specified and as directed.
90All as per Item No. 42 here-in-before but for exhaust fan of size upto 400/450 mm sweep complete all as specified and as directed.
91All as per Item No. 42 here-in-before but for wall mounted fan of size upto 400/450 mm sweep complete all as specified and as directed.
92All as per Item No. 42 here-in-before but for air circulator/ pedestal fan of size 450 mm sweep complete all as specified and as directed.
93All as per Item No. 42 here-in-before but for flame proof ceiling fan of size 1200/ 1400 mm sweep complete all as specified and as directed.
94All as per Item No. 42 here-in-before but for flame proof exhaust fan of size 400/ 450 mm sweep complete all as specified and as directed.
95All as per Item No. 42 here-in-before but for flame proof wall mounted fan of size 400/450 mm sweep complete all as specified and as directed.
96Supply only ball bearing, bearing No. 6201/ 6202 for ceiling / exhaust fan complete all as specified and as directed.
97Supply only ball bearing, bearing No. 6203/ 6204 for ceiling / exhaust fan complete all as specified and as directed.
98Supply only oil filled capacitor of 2.15 mfd suitable for ceiling fan complete all as specified and as directed.
99Supply only oil filled capacitor of 3.15 mfd suitable for ceiling fan complete all as specified and as directed.
100Supply only gun metal bush suitable for ceiling fan/wall mounting fan/exhaust fan/pedestal fan of any sweep complete all as specified and as directed by the Engineer-in-Charge.
101Supply only mounting clamp assembly for ceiling fan of 1200 mm/ 1400 mm sweep with amp, blot, nut, washers, safety/ split pins and rubber bush complete all as specified and as directed.
102Supply only MS down rod 15mm bore and 450mm long including two coats of synthetic enamel paint over one coat of red oxide primer for ceiling fan of 1200 mm/ 1400 mm sweep complete all as specified and as directed.
103S&F electronic deluxe rotary step type fan regulator including taking down old unserviceable one complete all as specified and as directed.
104S&F modular step type fan regulator 120W, 2 module complete all as specified and as directed.
105M&L for cleaning/preparation of surfaces of ceiling fan 1200mm/ 1400mm sweep thoroughly and painting with one coat of spray painting using synthetic enamel white paint over the existing paint and writing of serial/ MES number with black paint having each letters/figures in Block of height n.exc 2 cm over it complete all as specified and as directed by the Engineer-in-Charge.
106All as per Item No. 60 here-in-before but for painting to exhaust fan with blade ofany size complete all as specified and as directed.
107All as per Item No. 60 here-in-before but for painting to air circulator/ pedestal fan of 400 mm sweep complete all as specified and as directed.
108S&F in repair louver shutters for exhaust fan of size upto 450 mm sweep suitable for any make made of MS sheet including two coats of synthetic enamel paint over a coat of red oxide primer and bolt, nut, washer etc including taking down old unserviceable one complete all as specified and as directed.
109Supply only cord flexible copper conductor three core 23/0.0076 Sqmm PVC insulated sheathed 1100 V grade complete all as specified and as directed by the Engineer-in-Charge.
110M&L for comprehensive repair/ maintenance of storage type electric water heater (geyser) vertical or horizontal type of capacity 25 ltrs comprising of the following :-
111(a) Inspection, taking down, opening or dismantling, de-scaling, brushing and thoroughly cleaning the storage tank upto the satisfaction of the Engr-in-Charge.
112(b) Checking of all stop cock, pressure release valves, fusible plugs for its serviceability etc in situ to ensure free movement of the parts including supply and replacing then washers/ gasket nut etc.
113(c) Checking and rectifying earth continuity of the electrical circuits of the geyser and power point.
114(d) Checking and refixing thermostat and re-adjust
115(e) De-scaling the immersion type heating element and siphon assembly with diluted hydro chloric acid or clear pedette solution.
116(f) Checking of indicator lamp for its serviceability
117(g) Re-assembling the Geyser, re-install and testing complete.
118Note : Parts/ components of geysers found unserviceable shall be replaced by the contractor. New parts/ components required shall be measured and paid separately under Item No. 67 to 76 here-in-after as supply only and labour charges required for replacement are deemed to be included in the quoted rate of item No. 65
119M&L for comprehensive repair/ maintenance of solar water heater (geyser) horizontal type of capacity 100/500 ltrs comprising of the following :-
120(a) Inspection, taking down, opening or dismantling, de-scaling, brushing and thoroughly cleaning the storage tank upto the satisfaction of the Engr-in-Charge.
121(b) Checking of all stop cock, pressure release valves, fusible plugs for its serviceability etc in situ to ensure free movement of the parts including supply and replacing then washers/ gasket nut etc.
122(c) Checking and refixing solar flat plate collector/ tube collector and re-adjust
123(d) De-scaling the immersion type heating element and siphon assembly with diluted hydro chloric acid or clear pedette solution.
124Note : Parts/ components of geysers found unserviceable shall be replaced by the contractor. New parts/ components required shall be measured and paid separately under item No. 67 to 76 here-in-after as supply only and labour charges required for replacement are deemed to be included in the quoted rate of item No. 66
125Supply only thermostat of Type EST 11/ 20 A, 250 volt of approved make and having ISI marked complete all as specified and as directed.
126All as per item No. 67 here-in-before but for Type EST 7/ 5 A, 250 volt of approved make and having ISI marked complete all as specified and as directed.
127Supply only heating element of capacity 2 KW AC 240 volts suitable for storage type electric water heater as per site requirement (press type/ screw type/ triangular/ circular base or ceramic cartridge type), ISI marked complete all as specified and as directed.
128Supply only heating element of capacity 2/3 KW AC 240 volts suitable for storage type solar water heater as per site requirement (press type/ screw type/ triangular/ circular base or ceramic cartridge type), ISI marked complete all as specified and as directed.
129All as per item No. 70 here-in-before but of capacity 1.5 KW AC 240 volts ISI make and as per sample complete all as specified and as directed.
130Supply only copper siphon assembly suitable for 25 ltrs capacity geysers of any make as required at site of approved make complete with inlet and outlet and provision for thermostat pipe with drain pipes with drain plug, screws, studs, clamp for fixing heating element etc including gasket complete all as specified and as directed.
131Supply only plug top 3-pin 15 Amps ISI marked complete all as specified and as directed.
132Supply only PVC insulated PVC sheathed flexible round stranded copper conductor of size 2.5 sqmm, 3 core complete all as specified and as directed.
133Supply only LED Neon type indicator lamp 240 Volt AC suitable for 25/50 ltrs geyser complete all as specified and as directed.
134Supply only safety valve/high pressure release valve with ISI marked suitable for 25/50 ltrs geyser complete all as specified and as directed.
135S&F earth plug socket with MCB DP 20 Amps including taking down old unserviceable one complete all as specified and as directed.
136S&F 2 pin earth plug top upto 20 Amp complete all as specified and as directed.
137M&L for tracing and arresting of leakage in storage tank of 25 ltrs capacity geysers by brazing and soldering at leakage point and testing on completioncomplete all as specified and as directed.
138Taking down Geyser of capacity25 ltrs from its existing position after disconnecting inlet and outlet water connection including M&L for spray painting to Geysers of capacity 25 ltrs with one coat of Ist grade synthetic enamel paint of approved tint after preparation of old steel surfaces including writing serial / MES number (with black colour paint with each letters/ figures (in Block) of height n. exc 2 cm) and refixing the Geysers to its existing position on completion of painting including making inlet/outlet water connection and testing complete all as specified and as directed.
139S&F in repair PVC connection pipe with two brass adaptors 450mm long & fixing in position including taking out old unserviceable one complete all as specified and as directed.
140S&F in repair chromium plated connection pipe for hot water of length upto 600 mm, with two brass connecting nut with gasket and connecting up including taking out old unserviceable one complete all as specified and as directed.
141S&F in repair non-return valve, ISI marked 15mm dia including connection complete all as specified and as directed.
142S&F Anchor bolts of size 10mm dia, 100mm long including nuts and washer for mounting thegeyser complete all as specified and as directed.
143S&F MS ceiling fan hook suitable for hanging ceiling fan complete all as specified and as directed.
144Supply only ceiling fan energy saving type 5 Star 1200 mm sweep decorative blades pearl white with fan regulator and hook at proper position and making connection by using flexible copper conductor wire all as specified and as directed. (Cart Part No. ES 40 of Make Havells or equivalent model of Crompton Greaves / Orient)
145Supply only wall mounted air circulator fan PVC body 400 mm sweep 230 volt, SP and making connection by using flexible copper conductor wire all as specified and as directed. (Cat Part No. Turbo force of Havells or equivalent model of Orient / CG)
146Supply only pedestal fan PVC body 400 mm sweep 230 volt, SP complete with all accessories all as specified and as directed. (Cat Part No. Turbo force of Havells or equivalent model of Orient / CG)
147S&FPVC Exhaust fan of size 200 mm sweep, 230 volt ACwith connection from existing ceiling rose with louver shutter complete all as specified and as directed.
148S&FPVC Exhaust fan of size 250 mm sweep, 230 volt ACwith connection from existing ceiling rose with louver shutter complete all as specified and as directed
149S&F exhaust fan metal body heavy duty with louver shutter of sweep 300 mm, 230 volt, SP 1400 RPM with all nut bolt and other accessories with cutting a hole and making good after fixing of exhaust fan including taking out old unserviceable one and depositing to MES store yard completeall as specified and directed. (Make : Havells Cat Part No. Turbojet SPor equivalent as approved by GE)
150S&F exhaust fan metal body heavy duty with louver shutter of sweep 450 mm, 230 volt, SP 1400 RPM with all nut bolt and other accessories with cutting a hole and making good after fixing of exhaust fan including taking out old unserviceable one and depositing to MES store yard completeall as specified and directed. (Make : Havells Cat Part No. Turbojet SPor equivalent as approved by GE)
151S&F AC Single phase static Electronic KWH energy meter of accuracy class 1.0, 240 volt, 50 Hz , with Backlite LCD display ,optical port of rating 10-60 amp 06 months history with transparent hinge type box all as specified and as directed. (Make : L&T Cat Part No. WM101BC7DDH or equivalent as approved by GE)
152S&F AC Three phase static Electronic KWH energy meter of accuracy class 1.0, 240v, 50 HZ , with Backlite LCD display of rating 10-60 amp six months history with transparent hinge type box all as specified and as directed. (Make : L&T Cat Part No. WR300BC73BOXH or equivalent as approved by GE)