Creation Of 100 Kva Substation At Bilal Coloney Within The Jurisdiction Of Ediv Khanyar Creation Of 100 Kva Substation At Bilal Coloney Within The Jurisdiction Of Ediv Khanyar
Tender Overview
Project Description
Creation Of 100 Kva Substation At Bilal Coloney Within The Jurisdiction Of Ediv Khanyar Creation Of 100 Kva Substation At Bilal Coloney Within The Jurisdiction Of Ediv Khanyar
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 20-Dec-2021 | 1STEXTENSIONTO E NIT 66 | Date | 24-Dec-2021 |
| 2 | 26-Dec-2021 | 2nd extension to enit NO 66 | Date | 30-Dec-2021 |
| 3 | 31-Dec-2021 | 3rd extension to enit 66 | Date | 04-Jan-2022 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of: |
| 2 | 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, ( Al wound100 kVA, and with LV Cable Box having detachable Aluminium Gland plateapproved by the Department including earthing of Transformer along with fixing of flat iron strip to be fixed on earthling insulating boots of Sub Stations on two poles structure as per REC Standard F1,F2, F3 F4 &F10 (SITC) conditional Kindly read condtion No 11 of the SBD |
| 3 | 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, ( Copper wound100 kVA or higher kVA ratings) , and with LV Cable Box having detachable Aluminium Gland plateapproved by the Department including earthing of Transformer along with fixing of flat iron strip to be fixed on earthling insulating boots of Sub Stations on two poles structure as per REC Standard F1,F2, F3 F4 &F10 ( Transformer to be provided by thedepartment which is tobelifted from Diviisonal stores Khanyar) conditional Kindly read condtion No 11 of the SBD |
| 4 | 9 mts steel tubular pole post 410 (SP-33) IS 2713 (part-II) 1990 as per REC Standard (SITC) conditional Kindly read condtion No 11 of the SBD |
| 5 | 9 mts steel tubular pole post 410 (SP-33) IS 2713 (part-II) 1990 as per REC Standard( poles be provided by thedepartment which is to belifted from Diviisonal stores Khanyar (ITC only) conditional Kindly read condtion No 11 of the SBD |
| 6 | GI Channel100x50x50x6 mm 9\" long (2 No) duly fabricated as per site requirement & as per REC Standard . |
| 7 | GI Channelcross-arm (ISLC 75 designation)75x40x40x6 mm 9\" long (8No) duly fabricated as per site requirement& as per REC Standard . |
| 8 | GI Channelcross-arm (ISLC 75 designation)75x40x40x6 mm 6\" long (2 No) duly fabricated as per site requirement& as per REC Standard . |
| 9 | MS Angle iron braces (ISA 5050 designation) 50x50x6mm 6\" long (6 No) duly fabricated as per site requirement& as per REC Standard . |
| 10 | Providing of Chemical Earthing of Sub-Station for neutral earthing 2 mtr long 50mm dia GI to copper with additional 1 length GI pipe 38mm connected with chemical earthing and with extension of GI strip 25*3mm upto all equipments.Earthing has been laid through insulators to avoid with the existing structure for LA. |
| 11 | Galvanized Nuts & Bolts & washers of sorts. (Galavinsied as per IS-2633/1986) |
| 12 | 185mm² PVC single coreLT cableconnforming to IS 1554 (part -I) 1988 for incoming and outgoing circuits to be connected with LT Network including thimbling with 185 mm sq Al lugs |
| 13 | Bimatellic Clamps19mm². |
| 14 | 11KV 400 AMP Gang Operated switch gear |
| 15 | Drop-out set (Horn-gap type) as per REC standard F6 |
| 16 | 11KV Lighting Arrester Set (Station type)as per REC standardconforming to IS 3070 part -III and as per REC standard |
| 17 | LT fuse set |
| 18 | 11KV pinwithinsulatorsBrown glazed porcelain insulator confirming to IS-731/1971 Amendments 1 to 5 type B with 320mm minimum creepage distance and with lead/Zinc thimbles suitable for use with G.I forged pin having small steel heads as per IS-4l86 (P.I) 1993 and IS-2486 (P.II)1989 and revision with latest amendments if any as per REC Standard C-1 |
| 19 | Supplying and erection of Danger Plates with clamps with writing in English and Regional Language |
| 20 | Earthing Rods as per REC Standard (J-1) (Spiral Type) |
| 21 | Earthing insulating boots |
| 22 | Providing, Erection,testing & commissioning of MS Angle iron for Transformer Belt(ISA 5050 designation) 50x50x6mm 10\" long duly fabricated as per site requirement and painted with two coats of Red oxide and Al. Paint as per REC Standard |
| 23 | GI wire for Anticlimbing Device as per REC Standard |
| 24 | Sign Board |
| 25 | Supply and laying of Cement bottoming 1:2:4 mix as per REC standards 0.50 cum/pole, muffing 20 cm above ground level ,including plaster and curing of concrete in size of 600x600x1700mm for 9 mtrs Long ST Poles (410, SP-33) (the leftover pit after concreting to be filled with soil and boulders) |
| 26 | Supply and painting of each Pole 1 coat red oxide paint and 2 coats of aluminium paint (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint) |
| 27 | Supply, installation, testing and commissioning of: |
| 28 | 9 mts steel tubular pole post 410 (SP-33) IS 2713 (part-II) 1990 as per REC Standard (SITC) conditional Kindly read condtion No 11 of the SBD |
| 29 | 9 mts steel tubular pole post 410 (SP-33) IS 2713 (part-II) 1990 as per REC Standard( poles be provided by thedepartment which is to belifted from Diviisonal stores Khanyar (ITC only) conditional Kindly read condtion No 11 of the SBD |
| 30 | GI Channelcross-arm 75x40x40x6 mm 9\" long (6No) duly fabricated as per site requirement& as per REC Standard . |
| 31 | GI Angle iron braces50x50x6mm 6\" long (6No) duly fabricated as per site requirement and as per REC Standard |
| 32 | Galvanized Nuts & Bolts & washers of sorts. (Galavinsied as per IS-2633/1986) |
| 33 | Supplying and erection of Danger Plates with clamps with writing in English and Regional Language |
| 34 | Earthing Rods as per REC Standard (J-1) (Spiral Type) |
| 35 | 50 mm ²ACSR as per REC Standard. Conductor(Rabbit)IS 4826/1979 and laid as per REC standard (SITC) conditional Kindly read condtion No 11 of the SBD |
| 36 | 50 mm ²ACSR as per REC Standard. Conductor(Rabbit )IS 4826/1979 and laid as per REC standard ( Conductor be provided by thedepartment which is to belifted from Diviisonal stores Khanyar (ITC only) conditional Kindly read condtion No 11 of the SBD |
| 37 | Pole clamps fabricated out ofMS channel |
| 38 | Cement bottoming 1:2:4 mix as per REC standards 0.50 cum/pole, muffing 20 cm above ground level ,including plaster and curing of concrete in size of 600x600x1700mm for 13/11/9 mtrs Long ST Poles (410, SP-33) (the leftover pit after concreting to be filled with soil and boulders) |
| 39 | painting of each Pole 1 coat red oxide paint and 2 coats of aluminium paint (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint) |
| 40 | Supply, installation, testing and commissioning of: |
| 41 | 8 Mtr. Long ST Poles (410 SP15) with pit excavation ( poles be provided by thedepartment which is to belifted from Diviisonal stores Khanyar (ITC only) conditional Kindly read condtion No 11 of the SBD |
| 42 | 8 Mtr. Long ST Poles (410 SP15) with pit excavation ( poles be provided by thedepartment which is to belifted from Diviisonal stores Khanyar (ITC only) conditional Kindly read condtion No 11 of the SBD |
| 43 | 50 mm ²ACSR as per REC Standard. Conductor(Rabbit)IS 4826/1979 and laid as per REC standard (SITC) conditional Kindly read condtion No 11 of the SBD |
| 44 | 50 mm ²ACSR as per REC Standard. Conductor(Rabbit )IS 4826/1979 and laid as per REC standard ( Conductor be provided by thedepartment which is to belifted from Diviisonal stores Khanyar (ITC only) conditional Kindly read condtion No 11 of the SBD |
| 45 | Cement bottoming 1:2:4 mix as per REC standards 0.45 cum/pole, muffing 20 cm above ground level ,including plaster and curing of concrete in size of 600x600x1700mm for 8 mtrs Long ST Poles (410, SP-15) (the leftover pit after concreting to be filled with soil and boulders) |
| 46 | pole Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip(25x3) to eachpole including supply and welding of GI channel 70x40x150 on pole for earth connection |
| 47 | Galvanized Nuts and Bolts of sizes. |
| 48 | painting of each Pole 1 coat red oxide paint and 2 coats of aluminium paint (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint) |
| 49 | LT Shackle insulators as per REC standard |
| 50 | MukKI Clamps fibricated out of 50x8 mm flat iron of appropiate size and specification for holding LT Shackle insulators. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender