Military Engineer Services-MES has published Repairs / Replacement Of Summer Cooling Appliance And Certain E / M Maintenance Works At Parundu8190. Submission Date for this Tender is 03-01-2022. Electromechanical Work Tenders in Ramnad Tamil Nadu. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 21-Dec-2021 | Amendment to BOQ | Financial Bid | 27-12-2021 |
2 | 27-Dec-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 03-01-2022 |
Sl. No. | Item Description |
1 | SCHEDULE "A" PART-I [ E/M SUMMER COOLING APPLIANCE] |
2 | Providing comprehensive annual maintenance periodical/preventive maintenanceincluding annual maintenance of cooling appliances ( Split type Air Conditioners, Water coolers, Refrigerators and Deep Freezers) as per manufacturer specificationby providing one AC/Refrigeration mechanic including replacement ofcomponents as listed in subsequent items here in after. The maintenance of cooling appliances includes the following:- (a) Cleaning of coil unit with dust blower, lubricate the indoor and outdoor fan motor with oil. (b) Cleaning of air filters, indoor unit grills & filters through air blower. (c) Checking and cleaning the drain connection and air filter periodically, washing of coil with ventiklean solution once in a contract period. (d) Check and replace the refrigerent pipe once in a contract period or as and when required. (e) Check and repair the minor electrical fault in incoming supply. (f) Check and replace the water PVC pipe. (g)Replacementof faulty spares/components (h) Carry out the monthly, quarterly and annual maintenance of all cooling applicances of any make & capacity with job card and making the Cooling Appliances functional (Each Job contains 3 Complaints) |
3 | Supply only the following new items for 1.5 / 2.00 Ton CapacitySplit type AC including testing and commissioning etc complete all as directed. |
4 | Capacitor60 MFD. |
5 | Air filters. |
6 | Condenser fan motor 1.5 HP with blade set . |
7 | Blower fan motor 1.6 HP with blade set. Make: |
8 | Blower with circular leaf. |
9 | Copper condenser coil unit (for A/C) |
10 | Copper cooling coil unit (for A/C) |
11 | Indoor motor capacitor 2.5 MFD. Make: |
12 | Stainer tube (copper) |
13 | Capillary tube (copper) |
14 | Non return valve (For gas top up charging) |
15 | Remote control suitable for Non inverter model Split AC. Make :LG |
16 | Remote control suitable for Non inverter model Split AC. Make :Bluestar |
17 | Remote control suitable for Non inverter model Split AC. Make :Daiken |
18 | Remote control suitable for Non inverter model Split AC. Make : Universal |
19 | Remote control suitable forinverter model Split AC. Make :Bluestar |
20 | Remote control suitable for inverter model Split AC. Make :Daiken |
21 | PCB board suitable for indoor unit of Non inverter model split AC 1.5/2.0 TRMake :LG |
22 | PCB board suitable for indoor unit of Non inverter model split AC 1.5/2.0 TRMake :Bluestar |
23 | PCB board suitable for indoor unit of Non inverter model split AC 1.5/2.0 TR Make :Daiken |
24 | PCB board suitable for indoor unit of Inverter model split AC 1.5/2.0 TR . Make :LG |
25 | PCB board suitable for outdoor unit of Inverter model split AC 1.5/2.0 TR . Make :LG |
26 | PCB board suitable for indoor unit of Inverter model split AC 1.5/2.0 TR . Make :Daiken |
27 | PCB board suitable for outdoor unit of Inverter model split AC 1.5/2.0 TR . Make :Daiken |
28 | Copper pipe of size 1/2" for suction line with foam insulation |
29 | Copper pipe of size 1/4" for discharge line with foam insulation |
30 | Swing Motor for indoor unit |
31 | Outdoor unit stand |
32 | Condenser fan motor blade |
33 | Indoor Motor blower |
34 | Supply and fixPVC insulated unsheathed cables of size 2.5 sqmm 3 core multi-stranded Copper conductor wire suitable for geysers complete all as specified and as directed. |
35 | Supply and fixMetal plug top for ACcomplete all as specified and as directed |
36 | Supply only the new following items for for 3.00 Ton Capacity Floor standing /Voltas make Tower AC including testing and commissioning etc complete all as directed. |
37 | Air filters. |
38 | Condenser fan motor with blade set . |
39 | Blower fan motorwith blade set. |
40 | Blower with circular leaf. |
41 | Condenser coil unit (for A/C) |
42 | Cooling coil unit (for A/C) |
43 | Indoor motor capacitor 2.5 MFD. |
44 | Stainer tube (copper) |
45 | Capillary tube (copper) |
46 | Non return valve (For gas top up charging) |
47 | Remote control suitable for Non inverter Tower AC. |
48 | PCB board suitable for outdoor unit. |
49 | PCB board suitable for indoor unit. |
50 | Copper pipe of size 5/8" for suction line with foam insulation |
51 | Copper pipe of size 3/8" for discharge line with foam insulation |
52 | Swing Motor for indoor unit |
53 | Outdoor unit stand |
54 | Condenser fan motor blade |
55 | Indoor Motor blower |
56 | Supply and fixPVC insulated unsheathed cables of size 4 sqmm 5 core multi-stranded Copper conductor wire suitable for geysers complete all as specified and as directed. |
57 | Supply and fix Three phase metal plug topcomplete all as specified and as directed |
58 | Supply only the new following items for water cooler 40/80 Litres capacityincluding testing and commissioning etc complete all as directed. |
59 | Relay unit |
60 | PVC float valves , high pressure with polythene float and fly nut screwed to iron pipe or ferrule of bore 15 mm. |
61 | Thermostatasssembly |
62 | Water tap suitable for water cooler. |
63 | Starting Capacitor 80-100 MFD |
64 | Running capcitor 36 MFD |
65 | Condenser fan motor 1.6HP with blade set |
66 | Over load protector (OLP) |
67 | Supply only new compressor including pumping out oil, cleaning the refrigeration system with CO2 and charging refrigerant gas (M-22/F-22) providing NRV for further topping up of gas and re-fixing in the position including complete testing and commissioning all as directed for the following appliances :- |
68 | Split type AC 1.5 Ton capacity. Make: Bluestar or Voltas /LG/Samsung/Panasonic |
69 | Split type AC 1.5 Ton capacity. Make: Bluestar or Voltas /LG/Samsung/Panasonic |
70 | Water cooler 40/80 Litres capacity . Make: Samsung or Voltas /LG/Bluestar |
71 | Floor standing/Tower AC3 Ton Capacity. Make : Voltas or LG/Bluestar/Samsung |
72 | Repair to stabilizer of capacity 4 or 5 KVA capacity by removing the old / burnt transformer and replaced with new transformer complete all as directed. |
73 | Repair to stabilizer by removing the old / burnt relay board suitable for Voltage stabilizer of capacity 4 KVA / 5 KVA capacity |
74 | M & L Painting complete with super enamel paint of approved colour for water coolerall as specified and directed. |
75 | Supply and fix condensed water PVC flexible pipe of standard quality of suitable size fixing with suitable clamps on wall for split type AC of capacity of 1.5/2.0 Ton complete all as specified and as directed. |
76 | Supply only R22 /R32 /R410 Gas complete all as specified and directed. |
77 | Supply only R134a Gas complete all as specified and directed. |
78 | Dismantling and dis connecting carefully the existing split AC 1.5/2.0 Ton capacity after disconnecting the copper pipe and electrical connection, Cleaning the refrigeration system with CO2 and fixing in a new position including, brazing, testing and commissioning complete all as directed for the following cooling appliances :- NOTE : The wt of refrigerent used for filling/top up shall be measured and paid under respective item. |
79 | Supply only 2 nos of1/2" x 3/8" Foam Heat Insulated Pipe Black for Air Conditioner |
80 | Material and lobour for making good of surface withsealing the cavity /hole drilled to facilitate tubing, using white cement/POP and cleaning the surface to match with existing surface complete. |
81 | Material only for following items for refrigerators/Deep Freezers 320 Litres capacity including testing and commissioning etc complete all as directed. |
82 | (a) Relay unit. |
83 | (b) Thermostat assembly. |
84 | (c)Condenser coil |
85 | (d) Freezer for double door refrigerator |
86 | Supply only new compressor including pumping out oil, cleaning the refrigeration system with CO2 and charging refrigerant gasproviding NRV for further topping up of gas and re-fixing in the position including complete testing and commissioning all as directed for the following appliances :- |
87 | (a) Refrigerators 310/320 litres capacity.Make: Samsung or Voltas /LG/Bluestar |
88 | (b) Deep Freezers 320 litres capacity.Make: Samsung or Voltas /LG/Bluestar |
89 | M & L Painting complete with super enamel paint of approved colour for Refrigerator/ water coolerall as specified and directed. |
90 | SCHEDULE "A" PART-II [ E/M INTERNAL WIRING] |
91 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc., removing materials to store for keeping in safe custody for taking creditand making good disturbed surfaces of walls, floors etc. |
92 | M&L for Point wiring with 1.5 sqmm (Nominal area) unsheathed multi-stranded copper conductor PVC insulated cable 1100 volts grade FRLS single core drawn into and including non-metallic rigid PVC conduit of 20 mm dia/ PVC Casing cappingalong with 1.5 sqmm unsheathed multi stranded copper conductor cable PVC insulated 1100 volts grade FRLS as earth continuity conductor connected to common earth dolly fixed to wall/ ceiling roof with and including 1.6 mm thick MS sheet fabricated terminal boxes flush mounted for mounting the switches, sockets, fan regulator etc as required with 3mm thick laminated hylum sheet top cover all as specified and directed for :- |
93 | (a) One light point controlled by one switch |
94 | (b) One fan point controlled by one regulator / switch. |
95 | (c)One 3 pin socket outlet 5 amps socket onindependent board |
96 | (d) One 3 pin socket outlet 5 amps socket on Same Board board |
97 | (e) One light point controlled by two Nosof two way switches |
98 | (f) One bell/buzzer point controlled by one push button |
99 | All description as per item No. 25 here-in-before but with 4 sqmm cable for one 3 pin socket outlet 15 Amps on independent board with 4 sqmm cable as earthing conductor. |
100 | S&F in repair Socket outlet 2 in 1, 3 pin, 5A complete all as specified and as directed. |
101 | Supply and fix in repair switch piano flush type single pole one way 5 A 240 Volts complete all as specified and as directed including taking down old unserviceable switches complete all as specified and as directed. |
102 | Supply and fix in repair switch flush type single pole two way 5 A 240 Volts complete all as specified and as directed. |
103 | Supply and fix in repair switch Socketcombination 2 in 1,5 Amps Flush type 240 Voltscomplete all as specified and as directed. |
104 | Supply and fix in repair switch Socketcombination 5 Amps / 16 amps, 5 in 1 flush type 240 Voltscomplete all as specified and as directed. |
105 | Supply and fix in repairceiling rose3 ways PVC / Polycarbonate, isolated body complete all as specified and as directed. |
106 | Supply and fix in repair Call bell, ding-dong, suitable for working on 230 volts AC supply, single pole, complete all as specified and as directed. |
107 | Supply and fix in repairStepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc completeall as specified and as directed. |
108 | Supply and fix in repair Bell push flush type5 A 240 Volts complete all as specified and as directed. |
109 | S/ F in repair Modular switch 1 way 5A, 1 Module including taking down old unserviceable switch andremoving the material for taking credit complete all as specified and as directed. |
110 | S / F in repair Modular switch 1 way 16A, 1 Module including taking down old unserviceable switch andremoving the material for taking creditcomplete all as specified and as directed. |
111 | S/ F in repair Modular bell push ,5 A, 1 Module including taking down old unserviceable bell push andremoving the material for taking credit complete all as specified and as directed. |
112 | S / F in repair Modular Socket 5A-2/3 pin combined 2 Module. including taking down old unserviceable socket andremoving the material for taking credit complete all as specified and as directed. |
113 | S / F in repair Modular Socket5A / 15A - 2 / 3 pin combined 2 Module. including taking down old unserviceable socketandremoving the material for taking creditcomplete all as specified anddirected. |
114 | S/F in repair Modular fan Regulator Step type , 2 Module including taking down old unserviceable fan regulatorandremoving the material for taking credit complete all as specified and as directed. |
115 | Supply and fix in repair Modular switch 5 Amps twoway flush typeincluding taking down old unserviceable modular switchandremoving the material for taking creditcomplete all as specified anddirected. |
116 | Supply & fix in repairModular White cover plate with frame, 1 Moduleincluding taking down old unserviceable modular cover plate andremoving the material for taking creditcomplete all as specified anddirected. |
117 | Supply & fix in repair Modular White cover plate with frame, 2 Module including taking down old unserviceable modular cover plateandremoving the material for taking creditcomplete all as specified anddirected. |
118 | Supply & fix in repairModular White cover plate with frame, 3 Module including taking down old unserviceable modular cover plate andremoving the material for taking credit complete all as specified anddirected. |
119 | Supply & fix in repair Modular White cover plate with frame, 4 Module including taking down old unserviceable modular cover plate andremoving the material for taking credit complete all as specified anddirected. |
120 | Supply & fix in repair Modular White cover plate with frame, 6 Module including taking down old unserviceable modular cover plateandremoving the material for taking creditcomplete all as specified anddirected. |
121 | Supply & fix in repair Modular White cover plate with frame, 8 Module including taking down old unserviceable modular cover plateandremoving the material for taking creditcomplete all as specified anddirected. |
122 | Supply and fix in repair Modular metal flush box 1/2module including taking down old unserviceable metal box removing the material for taking credit and making good the disturbed surface of wall complete all as specified anddirected. |
123 | Supply and fix in repair Modular metal flush box 3module including taking down old unserviceable metal box removing the material for taking credit and making good the disturbed surface of wall complete all as specified anddirected. |
124 | Supply & fix in repairModularMetal flush Box 4 Module including taking down old unserviceable metal box removing the material for taking credit and making good the disturbed surface of wall complete all as specified anddirected. |
125 | Supply & fixin repair Modular Metal flush Box 6 Module including taking down old unserviceable metal box removing the material for taking credit and making good the disturbed surface of wall complete all as specified anddirected. |
126 | Supply & fixin repair ModularMetal flush Box 8 Module including taking down old unserviceable metal box removing the material for taking credit and making good the disturbed surface of wall complete all as specified anddirected. |
127 | Supply and fix in repair 3mm thick laminated sheet top cover on switch boards including cutting, fixing and scwering etc including taking down old unserviceable hylum sheet, removing the material for taking credit and making good the disturbed surface of wall complete all as specified anddirected.all as specified and directed at site. |
128 | Supply and fix in repair flushed to wall 1.6 mm thick Galvanised Iron sheet fabricated terminals box of following sizesand dismantling corroded metal box from wall, removing the material for taking credit and making good the disturbed surface of wall including plastering the sides complete all as specified anddirected.:- |
129 | Box Size-79 mm x 75 mm x 46 mm (1 or 2 module) |
130 | Box Size-79 mm x 99 mm x 46 mm (3 module) |
131 | Box Size- 79 mm x 135 mm x 52 mm (4 module ) |
132 | Box Size-79 mm x 207 mm x 52 mm (6 module ) |
133 | Box Size- 79 mm x 230 mm x 52 mm (8 module ) |
134 | Box Size- 132 mm x 135 mm x 56 mm (8 module ) |
135 | Supply & fix in repair PVC casing caping of size 25 mm ISI marked on wall/roof/ceiling work etc with all accessories and drawing any type of cables through caping casing all as directed at site including and making good the disturbed surface of wall complete all as specified anddirected. Note: - Drawing out existing cable of any size , keeping it in safe custody ,taking down the old unserviceable PVC casing /caping , removing the pipe for taking credit are measured as seperate item. |
136 | Supply and fix in repair PVC conduit of size 25 mm ISI marked on wall/roof/ceiling work etc with all accessories and drawing any type ofcables through PVC conduit all as directed at site including making good the disturbed surface of wall complete all as specified anddirected. Note: - Drawing out existing cable of any size , keeping it in safe custody ,taking down the old unserviceable PVC Pipe, removing the pipe for taking credit are measured as seperate item. |
137 | Supply and fix in repair PVC conduit of size 32 mm ISI marked on wall/roof/ceiling work etc with all accessories and drawing any type ofcables through PVC conduit all as directed at site including making good the disturbed surface of wall complete all as specified anddirected. Note: - Drawing out existing cable of any size , keeping it in safe custody ,taking down the old unserviceable PVC Pipe, removing the pipe for taking credit are measured as seperate item. |
138 | Supply and fix in repair PVC conduit of size 40 mm ISI marked on wall/roof/ceiling work etc with all accessoriesand drawing any type ofcables through PVC conduitall as directed at site including making good the disturbed surface of wall complete all as specified anddirected. Note: - Drawing out existing cable of any size , keeping it in safe custody ,taking down the old unserviceable PVC Pipe, removing the pipe for taking credit are measured as seperate item. |
139 | Removing serviceable wiring of any size from conduit/batten/casing/caping on surface of wall, ceilingand keeping in safe custody for resuse and redrawing through PVC Conduit / PVC Caping casing complete all as specified and directed. |
140 | Taking down unserviceable PVC conduit / casing /caping of any sizeand removing the material for taking credit complete all as specified and directed. |
141 | Taking down carefully old unserviceable submain wiring with aluminum /copper conductor cable 4/6/10/16 Sqmm in PVC conduit complete removing the materials and taken as credit and making good the disturbed surface of wall / floor etc. |
142 | M&L for Sub main wiring with two run single core 4 sqmm multi stranded copper conductor PVC insulated unsheathed cable 1100 volts grade FRLS and one run of 4 sq mm multi stranded copper conductor cable as earth continuity conductor drawn into and including non-metallic rigid PVC conduit 25 mm dia/PVC casing capping 25 mm including conduit accessories all as specified and directed. Note: Three runs of 4 Sqmm cable and one run of 25mm conduit / casing capping will be measured as one unit length. |
143 | M&L for Sub main wiring with two run single core 6 sqmm multi stranded copper conductor PVC insulated unsheathed cable 1100 volts grade FRLS and one run of 6 sq mm multi stranded copper conductor cable as earth continuity conductor drawn into and including non-metallic rigid PVC conduit 32 mm dia/PVC casing capping 25 mm including conduit accessories all as specified and directed. Note: Three runs of 6 Sqmm cable and one run of 32mmconduit / casing capping will be measured as one unit length. |
144 | M&L for Sub main wiring with four runs single core 4sqmm multi stranded copper conductor PVC insulated unsheathed cable 1100 volts grade FRLS and two runs of 4 sqmm multi stranded copper conductor cable as earth continuity conductor drawn into and including non-metalic rigid PVC conduit, 25mm dia/PVC casing caping 32 mmand conduit accessories concealed/surface of wall/roof/ceiling etc complete all as specified and directed. Note: Four runs of 4sqmm and two runs of 4 sqmm cable and one run of 25mm dia conduit/casing capping shall be measured as one unit length. |
145 | M&L for Sub main wiring with four runs single core 6 sqmm multi stranded copper conductor PVC insulated unsheathed cable 1100 volts grade FRLS and one run of6 sqmm multi stranded copper conductor cable as earth continuity conductor drawn into and including non-metallic rigid PVC conduit 32 mm dia/PVC casing capping 32 mm including conduit accessories all as specified and directed. Note: five runs of 6 Sqmm cable and one run of 32 mm conduit / casing capping will be measured as one unit length. |
146 | Supply and fix in repair Sheet metal enclousers with socket plug top and MCB SPN 20A, 240 volts, with a two pin and earth plug socket complete with one single MCB 20 Amps, 240 volts (for AC ) including taking down old unserviceable old unserviceable Sheet metal enclousers with socket plug top complete all as specified and directed |
147 | Supply and fix in repair sheet metal enclosure powder coated double doorfor Distribution Board, SPN 4 way DB,240 V with detachable Gland Plate, Box Insertion Marks ,Circuit Identification Label ,Neutral Link ,Earth Link , Tin Plated Copper Bus Bar including , Disconnecting electric connections, dismantling from position unserviceable DBs for taking into credit complete all as specified and as directed. |
148 | Supply and fix in repair sheet metal enclosure powder coated double doorfor Distribution Board, SPN 8 way DBwith 200 A bus bar ,240 V with detachable Gland Plate, Box Insertion Marks ,Circuit Identification Label ,Neutral Link ,Earth Link , Tin Plated Copper Bus Bar including , Disconnecting electric connections, dismantling from position unserviceable DBs for taking into credit complete all as specified and as directed. |
149 | Supply and fix in repair sheet metal enclosure powder coated double doorfor Distribution Board, SPN 12 way DBwith 200 A bus bar ,240 V withdetachable Gland Plate, Box Insertion Marks ,Circuit Identification Label ,Neutral Link ,Earth Link , Tin Plated Copper Bus Bar including , Disconnecting electric connections, dismantling from position unserviceable DBs for taking into credit complete all as specified and as directed. |
150 | Supply and fix in repair sheet metal enclosure powder coated double door forDistribution Board,TPN 4 wayDB ,415 V with Detachable Gland Plate, Box Insertion Marks ,Circuit Identification Label ,Neutral Link ,Earth Link , Tin Plated Copper Bus Barincluding , Disconnecting electric connections, dismantling from position unserviceable DBs complete for taking into credit all as specified and as directed. |
151 | Supply and fix in repair sheet metal enclosure powder coated double door for Distribution Board,TPN 8 wayDB ,415 V with Detachable Gland Plate, Box Insertion Marks ,Circuit Identification Label ,Neutral Link ,Earth Link , Tin Plated Copper Bus Bar including , Disconnecting electric connections, dismantling from position unserviceable DBs complete for taking into credit all as specified and as directed. |
152 | Supply and fix in repair sheet metal enclosure powder coated double door for Distribution Board,TPN 12 way DB ,415 V with Detachable Gland Plate, Box Insertion Marks ,Circuit Identification Label ,Neutral Link ,Earth Link , Tin Plated Copper Bus Bar including , Disconnecting electric connections, dismantling from position unserviceable DBs complete for taking into credit all as specified and as directed. |
153 | Supply and fix in repair sheet metal enclosure powder coated double door for Distribution Board,VTPN 4 way DB with Degree of ProtectionIP 54 including , Disconnecting electric connections, dismantling from position unserviceable DBs for taking into credit complete all as specified and as directed. |
154 | Supply and fix in repair sheet metal enclosure powder coated double door for Distribution Board,VTPN 8 way DB with Degree of Protection IP 54including , Disconnecting electric connections, dismantling from position unserviceable DBs for taking into credit complete all as specified and as directed. |
155 | Supply and fix in repairMCB SP 5 A to 32 A, B curve, 10 kA including , Disconnecting electric connections, dismantling from position unserviceable MCB for taking into credit completeall as specified and as directed. |
156 | Supply and fix in repairMCB SP 40 Amps , B curve 10 kA including , Disconnecting electric connections, dismantling from position unserviceable MCB for taking into credit completeall as specified and as directed. |
157 | Supply and fix in repairMCB SPN 32 Amps, C curve 10 kAincluding , Disconnecting electric connections, dismantling from position unserviceable MCB for taking into credit completeall as specified and as directed. |
158 | Supply and fix in repairMCB SPN40 A- 63Amps, C curve 10 kA including , Disconnecting electric connections, dismantling from position unserviceable MCB for taking into credit completeall as specified and as directed. |
159 | Supply and fix in repairMCB TP25A - 63 A, C curve 10 kA including , Disconnecting electric connections, dismantling from position unserviceable MCB for taking into credit completeall as specified and as directed. |
160 | Supply and fix in repairMCB TPN 16 A- 32 Amps, C curve 10 kAincluding , Disconnecting electric connections, dismantling from position unserviceable MCB for taking into credit completeall as specified and as directed. |
161 | Supply and fix in repairMCB TPN40A- 100 A, C curve 10 kA including , Disconnecting electric connections, dismantling from position unserviceable MCB for taking into credit completeall as specified and as directed. |
162 | M & L for earthing complete with galvanised steel earth plate electrode60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 32x6mm GI strip as earthing lead by means of bolts, nuts, check nuts and washers of copper all as shown in electrical plate No.3 connected to earthing test point,including 20 mm GI pipe (Medium grade) for watering and 40 mm GI pipe (Medium grade) for protection of earth strip andetc..including testing on completion ,PCC chambers in PCC1:3:6 type C1, RCC M25 type cover slab 50mm thick with 8mm dia TMT HCR/CRS steel bars at 140mm C/C both way and lifting handle GI funnel & wiremesh ,funnel,lugs and charcoal,salt etc all as applicableincluding taking down old unserviceable earthing complete for taking into creditall as specified and as directed by the Engineer-in-Charge. Note:-(i) The rates quoted is inclusive of32x6mm GI strip earthconductor upto a length of 7.5m from the earth pit. |
163 | Supply and lay earth continuity conductor or main earting lead fixed to wall on batten or recess or burried in ground or drawn in conduit / conduit pipe or fixed to poles or any other indicted situation for loop earthing etc of galvanised steel earth stripof size 32 X 6mm including taking down old unserviceable earth strip complete for taking into credit complete all as specified and as directed by the Engineer-in-Charge |
164 | M & L for earthing complete with galvanised steel earth plate electrode60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised steel earth wire 4mm diaas earthing lead by means of bolts, nuts, check nuts and washers of copper all as shown in electrical plate No.3 connected to earthing test point,including 20 mm GI pipe (Medium grade) for watering and 40 mm GI pipe (Medium grade) for protection of earth strip andetc..including testing on completion ,PCC chambers in PCC1:3:6 type C1, RCC M25 type cover slab 50mm thick with 8mm dia TMT HCR/CRS steel bars at 140mm C/C both way and lifting handle GI funnel & wiremesh ,funnel,lugs and charcoal,salt etc all as applicable including taking down old unserviceable earthing complete for taking into credit complete all as specified and as directed by the Engineer-in-Charge. Note:-(i) The rates quoted is inclusive of32x6mm GI strip earthconductor upto a length of 7.5m from the earth pit. |
165 | Supply and lay earth continuity conductor or main earting lead fixed to wall on batten or recess or burried in ground or drawn in conduit / conduit pipe or fixed to poles or any other indicted situation for loop earthing etc of galvanised steel earth wire 4mm dia including taking down old unserviceable GI earth wirecomplete all as specified and as directed. |
166 | Supply and fix in repair Lightning Protection Single point air termination aluminum rod 12mm dia 300mm long with base plate including taking down old unserviceable aluminium rodfor taking into credit complete all as specified and as directed by the Engineer-in-Charge . |
167 | Supply and fix in repair Test point terminal box made out of Gun metal or Phosphorous bronze of size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hex head screwsincluding taking down old unserviceable test point terminal box for taking into credit complete all as specified and as directed by the Engineer-in-Charge . |
168 | Supply and fix in repair Aluminium strip of 25x 3.15mm fixed with screws/ clamps / insulators for roof conductors and down conductors above ground level complete including taking down old unserviceable Aluminium strip for taking into credit complete all as specified and as directed by the Engineer-in-Charge. |
169 | Supply and fix in repair MCCB4 pole 415 volts, 100 Amps, with rupturing capacity 16 KA complete all as specified and as directed including taking down old unserviceable MCCB for taking into credit complete all as specified and as directed by the Engineer-in-Charge . |
170 | Supply and fix in repairMCCBfour pole 415 volts 50 Hz , 125 amps, with rupturing capacity 16 KA complete all as specified and as directed including taking down old unserviceable MCCBfor taking into credit complete all as specified and as directed by the Engineer-in-Charge . |
171 | Material and labour for Painting the DB Boxes as required at site after scraping out completely the old paint with one coat of redoxide primer and two coats of synthetic enammel paint including carrying out minor welding works if reqired as directed by the Engineer in charge NOTE:Colour of paint shall be decided by the Engineer-in-charge. |
172 | Supply and fix in repair ON LoadChange over switch 415V in shet metal enclosures 4 pole 125 Ampsincluding taking down old unserviceable ON Load Change over switch for taking into credit complete all as specified and as directed |
173 | Supply and fix in repairON Load Change over switch 415V in shet metal enclosures 4 pole 200 Ampsincluding taking down old unserviceable ON Load Change over switch for taking into credit complete all as specified and as directed |
174 | Material and labour for Writing letters (Block.Roman, Italic or Indian) with thick paint ,stand out boldly and solidly without showing signs of brush marks, or by Stickering, upto 10 cm height and painting with contrasting colour in the background of letter complete as directed. NOTE:Colour of paint/ stickering shall be decided by the Engg-in-charge. |
175 | Demolition, Cement concrete (unreinforced) in ground floors and pavings n exe 15 cm thickness (below or above ground level) complete all as specified and as directed by the Engineer-in-Charge. |
176 | M & L for 85 mm thick cement concrete 1:2:4 type B-1, using 20mm graded aggregate for making good the disturbed road surface after laying of pipe line over returned filled and compacted earth surface to match with existing road level complete all as specified and as directed. |
177 | Supply and fix in repairs plug top 3 pin 5 A including removing old unserviceable item for taking into credit complete all as specified and directed |
178 | Supply and fix in repairs plug top 3 pin 15 A including removing old unserviceable item for taking into credit complete all as specified and directed |
179 | Supply and fix in repairs copper tubular terminal socket of following sizecomplete including crimping it properly all as specified and directed :- |
180 | Size 2.5 sq.mm |
181 | Size 4 sq.mm |
182 | Size 6 sq.mm |
183 | Size 10 sq.mm |
184 | Supply and fix in repairs ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) including taking down unserviceable fan complete all as specified and directed |
185 | Supply and fix in repair exhaust fan in repairs, steel body AC single Phase. 230V of size 300mm sweep with, blades, and frame and louversincluding taking down unserviceable fan complete all as specified and directed |
186 | Supply and fix in repair exhaust fan in repairs, steel body AC single Phase. 230V of size 450mm sweep with, blades, and frame and louvers including taking down unserviceable fan complete all as specified and directed |
187 | Supply and fix in repairFlame proof Exhaust fan in repairs 300mm sweep, heavy duty , Rust proof body and blades, double ball bearing with noisless operation, 1400 RPM complete with Wall Mounting with M.S. Supporting channel and M.S. mesh as a guard. including makingsuitable opening at suitable height,and provision of nuts and bolts on the wall for fixing the exhaust fan fan complete all as specefied and as directed . |
188 | Supply and fix in repair wall mounted fan in repairs 450 mm with Powder Coated Guard with Aluminum Die Casting Blade, minimum Three speeds control,vertical adjustment from 22° to 45°, 1440 RPM..90 degree oscillation . Make: ALMONARD.Model: Wall Fan 18" M-II. |
189 | Supply and fix in repairs electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostat, NRV, connection piece etc.including connecting Heavy Stainless Steel(SS) braided hoses (Flexible Hoses) of required length having a minimum pressure rating of 8 bar and compatible for hot water applications including making end connections for water inlet/ outlet from/to water heater or to the discharge line |
190 | Supply and fix in repairin repairs Lamp holderPVC / Polycarbonate for LED bulb 18 W, isolated body including taking down old unserviceable lamp holdersand removing the material for taking credit complete all as specified and directed. |
191 | Supply and fix in repairing in repairs LED lights fitting 1x 20 W, 220V,AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. and taking down old U/S fittingsfor taking into credit complete all as specified and directed Make :Crompton/ Bajaj / Wipro / Philips/Havells |
192 | S & F LED light fitting in repairs 1x9W/1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed including taking down old U/S fittingsfor taking into credit . Make :Crompton/ Bajaj / Philips /Wipro/Havells |
193 | Supply and fix in repairing in repairs LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete including taking down old U/S fittings for taking into credit. Make :Crompton/ Bajaj /Philips /Wipro/Havells |
194 | Supply and fix in repairsrecessed mounting 2 ft x 2 ft LED luminaire 36W or nearest higher wattage 6500 K suitable for amtrong/grid ceiling with super bright LED etc. complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size including taking down old U/S fittings for taking into credit . Make : Crompton / Philips/ Bajaj/ WIpro/Havells. |
195 | Supply and fix in repairsof LED 15W light fitting round/square recess mounting downlighter fittingincluding taking down old U/S fittings for taking into credit and minor alteration to false ceiling as required at site and making the surface good complete all as specified and directed Make :Bajaj / Philips/ Crompton/Wipro/Havells. |
196 | Supply and fix in repairs Electronic Ballast 36 watts /40Watts including taking down old unserviceable ballast andremoving the material for taking credit complete all as specified and as directed. |
197 | Supply and fix in repairs Electronic Ballast 28 Wattsincluding taking down old unserviceable ballast andremoving the material for taking credit complete all as specified and as directed. |
198 | Supply and fix in repair 2x28 watts electronic ballast suitable for FTL fitting including removing old one complete all as specified and directed |
199 | Supply and fix in repair 2x36 watts electronic ballast suitable for FTL fitting including removing old one complete all as specified and directed |
200 | Supply and fix in repair tube rod LED, 15 watts T5double side connection, 4" longafter taking out old burnt choke and fluorescent tube complete all as specified and directed. Make : Wipro/Crompton/ Bajaj/ Phlips/Havells. |
201 | Supply and fix in repairtube rod LED, 20 watts T8double side connection, 4" longafter taking out old burnt choke and fluorescent tube complete all as specified and directed. Make : Crompton/Bajaj/Phlips/Wipro/Havells |
202 | Supply and hang in repairs vertical mounting integral highbay/ mediumbay in hanger ceiling at 10 meter height LED IP65 luminaire, 100 watts ,efficacy upto 100Lm/W , IP65.Surge protection of internal 4kV and external 4kV complete all as specified and directed Make: Crompton/Bajaj/Phlips/Wipro/Havells |
203 | Supply and fix in repair LED bulb 16 watts complete all as specified and as directed. |
204 | S&F in repair energy saving LED security light fittings, 30Wattsor nearest higher wattage, with in-built electronic driver, IP 66 class of protection with versatile pressure die-cast aluminium body, toughened glass cover with silicon gaskets and energy efficient LEDand connecting up light fitting with copper conductor cable of suitable size from junction box to connector blockincluding all accessories and dismantling of old unserviceable fittingfor taking into credit complete all as specified and as directed. Make:Crompton/Philips/Bajaj/ Wipro/Havells |
205 | Supply and fix in repair LED light fitting 2x 16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size including all accessories and dismantling of old unserviceable fittingfor taking into credit complete all as specified and as directed. Make:Crompton / Philips/Bajaj/ Wipro/Havells |
206 | Schedule of credit amount brought back from Ser Page No.44- Rs. 91,303.00 will be deducted from the above quoted amount to derive the contract sum. SIGNATURE OF CONTRACTOR |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail