Public Health Engineering Department-PHED has published Empanelment Of Eligible Contractors At Provincial Level And Fixing Of Item Rates For Lift Schemes Of Plain Areas Of District Baramulla For Execution Ofjal Jeevan Mission ( Jjm ) Works More Then 50 Lacs Upto 100 Lacs - Group Iii Phe Division Sopore . Submission Date for this Tender is 21-12-2021. Construction Material Tenders in Sopore Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Dismantling of GI pipeincluding earthwork excavation, removing of pipe, stackingwithin 50m lead and refilling of trenches complete |
2 | Above 40mm |
3 | Below 40mm |
4 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated upto 1mt from cutting edge earth as directed: |
5 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated upto 1mt from cutting edge earth W. B.Macadem |
6 | Earth work in excavation by manual means over areas (exceeding 30cm and up[to 1.5mtr in depth, 1.5mtr in width as well as 10 sqm on plan) including disposal of excavated earth upto 1mtr from cutting edge disposal earth to be leveled and neatly dressed .All kinds of soil |
7 | Earth work in excavation by manual means over areas (exceeding 30cm and up[to 1.5mtr in depth, 1.5mtr in width as well as 10 sqm on plan) including disposal of excavated earth upto 1mtr from cutting edge disposal earth to be leveled and neatly dressed .Ordinary rock |
8 | Extra for every additional lift of 1.5 mtr. or part thereof in all kinds of soil |
9 | Laying and fitting of D.I Pipes100mmto 250mm |
10 | Providing push on joints |
11 | 100mm dia D.I |
12 | Providing flanged joints to G.I pipes |
13 | 100mm dia G.I |
14 | 80mm dia G.I |
15 | Welding charges of leakage spots 50 to 100 |
16 | Fabricationg, providing and fixing M.S bends etc |
17 | Laying and fitting of G.I Pipes100mm |
18 | Laying and fitting of G.I Pipes80mm ø G.I = |
19 | Laying and fitting of G.I Pipes 65mm GI |
20 | Laying and fitting of G.I Pipes50mm ø G.I = |
21 | Laying and fitting of G.I Pipes40mm ø G.I = |
22 | Laying and fitting of G.I Pipes25mm ø G.I = |
23 | Laying and fitting of G.I Pipes20mm ø G.I = |
24 | Laying and fitting of G.I Pipes15mm ø G.I = |
25 | Providing and fixing of 10m thick MS flangesto Gi pipes incl cutting of pipes , incl c/o flanges , nuts ,bolts , RI cloth and all sorts of carriage of pipes complete job100mm |
26 | Providing and fixing of 10m thick MS flangesto Gi pipes incl cutting of pipes , incl c/o flanges , nuts ,bolts , RI cloth and all sorts of carriage of pipes complete job80mm |
27 | Providing and fabrication of MS/Gi bend, TEES ,as per various goundprofile pipe specials at site made out of GI/MS pipe incl c/o pipe , flanges , nuts, bolts , RI cloth and all sorts of carriage upto site of work complete job |
28 | Flanged100mmTee,bend |
29 | flanged GI150mmbend |
30 | Rethreading of damaged ends of various dia pipes |
31 | 50mm |
32 | 65 mm |
33 | Back-filling of available excavated soil into the trench excluding rock. |
34 | Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing Tee, including cutting and threading the pipe etc. complete |
35 | 25 to 40 mm nominal bore |
36 | 40 to 80 mm nominal bore |
37 | Providing and laying S&S Centrifugally Cost ( Spun ) Iron Pipes ( class K7) 150mm Dia |
38 | Providing push on joints to centrifugally Cast of Psun Iron S&S including testing of joints & Cost of rubber gasket |
39 | Providing and laying DI speciala of Class K-12 suitabe for pusch on jointing as per IS 9532 600mm dia |
40 | Providing fixing of sluice valve with Cap ( Shiv Durga /Zolto) make complete with bolts nuts rubber insertion etc omplete Job |
41 | 100mm dia Sluice valve |
42 | 150mm dia Sluice valve |
43 | 200mm dia sluice valve |
44 | 250mm dia Sluice valve |
45 | Providing and fixing CI double acting air valve of approved quality with bolts nuts rubber insertions etc complete ( The tail pieces, tapers etcif required will be paid sepately ) |
46 | 50m dia Double acting |
47 | 80mm dia Double acting |
48 | 100mm dia Double acting |
49 | Providing and Fixing of MS Surface boxes ( 0.75x0.75x0.75) 6mm thick plate for hoisting of 100/80mm dia sluice valves . The job includes fixing of 40x40x5mm Angle Iron frmae with required legs to be grouted in cement concrete mix 1:2:4 mix with proper locking arrangements |
50 | Providing and fixing of MS bends of required dia and TEE"s including carraige of welding machine upto site of work and fixing at site including cost of rubber gasket/washers/ nuts & bolts etc as complete job |
51 | Providing fixing of 10 to 12mm thick flanges to GI pipe including cost of rubber washers nuts bolts etc all work as complete job including carraiges of welding machine & Gen set involving welding at site as per ground profile complete job 80mm dia |
52 | Providing and fixing of reputated make gate vlve including all sorts of carriage. |
53 | 25 mm dia |
54 | 40 mm dia |
55 | 50 mm dia |
56 | 65 mm dia |
57 | Providing and Fixing of , NRVof approved make including tail pieces, flanges required at site and all sorts of carriage complete80mm of approved make double flanged |
58 | Structural steel work in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. Welded |
59 | Providing and fixing of sluice valve,NRV & Air valves of reputed make including tail pieces,flanges required at site and all sorts of carriage complete |
60 | Sluice valve 100 mm |
61 | 80mm |
62 | 150mm s/v |
63 | NRV 150 mm |
64 | Air valve 25 mm |
65 | Providing laying and fixing/jointing (rich mix concrete) of spun pipe NP3 type including earthwork excavation of tenches as specified to withstand the traffic load including sand coushioning by 2nd class sand and cost of pipe.The job omc;ides a;; sprts pf carriage upto site of work complete job (TO BE UTILISED AS SLEEVES) 300mm |
66 | Cutting of road and making good the same incl all aggtegates required to complete the job |
67 | Providing and laying stone soling hand packed on level |
68 | Providing and laying cement concrete in1:4:8with 40 mm stone size agg. Crushed excluding cost of shuttering |
69 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts any struts, etc. upto floor five level excluding cost of centering, shuttering, finishing and reinforcement in1 : 1.5 : 3 (1 cement : 1.5 coarse sand : 3 graded stone agg. 20mm nominal size). |
70 | Reinforced cement concrete work in walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc upto floor five level excluding cost of centering, shuttering finishing and reinforcement 1 : 1.5 : 3 ( 1 cement : 1.5 coarse sand : 3 graded crushed stone aggregate 20mm nominal size). |
71 | Reinforced cement concrete work in walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc upto floor five level excluding cost of centering, shuttering finishing and reinforcement 1 : 1.5 : 3 ( 1 cement : 1.5 coarse sand : 3 graded crushed stone aggregate 20mm nominal size). S/Floor |
72 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts any struts, etc. upto floor five level excluding cost of centering, shuttering, finishing and reinforcement in1 : 2 : 4 (1 cement : 2 coarse sand : 4 graded stone agg. 20mm nominal size). |
73 | Reinforced cement concrete work in arches, archibs, domes, vaults, shells, folded plate and roofs having slope more than 15º upto floor five level incld. curing but excld. The cost of centring, shuttering finishing and reinforcement with 1 cement : 1.5 coarse sand : 3 graded stone agg.) 20mm nominal size incld. all carriages |
74 | Reinforcement for RCC work including straightening, cutting ,bending ,binding and placing in position complete |
75 | Extra for providing water proofing compound to cement concrete works. |
76 | Fabrication of flanges incld. Cutting, welding, insertion of rubber Gasket, nuts bolts incld. Earth work & refilling complete job. 80mm dia G.I = 1000Mtr |
77 | Centering and shuttering incl strutting , propping etc and removal of same complete |
78 | Foundation, footing bases of columns |
79 | Walls (any thickness) including attached pilasters, buttresses, plinth and string courses |
80 | Arches, domes valuts upto 6m span |
81 | Suspended floors |
82 | Lintels, beams, plinth beams, girders, bressumers and cantilevers |
83 | Column, Pillar |
84 | Edges |
85 | Extra for shuttering In circuilar work (20 % of respective centring and shuttering items): Foundations, footing, bases of columns etc for mass concrete |
86 | Extra for shuttering in circular works. Walls |
87 | Extra for shuttering in circular works. Dome |
88 | Extra for shuttering In circuilar work (20 % of respective centring and shuttering items): Suspended floors |
89 | Extra for shuttering In circuilar work (20 % of respective centring and shuttering items): Linets beams |
90 | 12mm cement plaster of mix 1 : 3 (1 cement : 3 fine sand) incld. all carriages |
91 | 12mm thick C. Plaster in 1:4 mix |
92 | Providing and incorporating during Construction joints GP Sheet |
93 | Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete. Measurements to be taken of the face area timbered. Depth exceeding 3m but not exceeding 4.50m |
94 | Providing and laying of reinforced cement concrete work in walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, pots and struts etc upto floor five level excluding cost of centring, shuttering, finishing and reinforcement 1 : 1.5 : 3 (1 cement : 1.5 coarse sand : 3 graded stone agg. 20mm nominal size) |
95 | RCC work in walls 9any thickness) including attached pilasters, fillets, columns upto the floor V level, excluding the cost of centring, shuttering, finishing and reinforcement in 1 : 1 : 2 mix with 20mm agg. Crushed. |
96 | Pumping out water caused by springs, tidal or river seepage, broken water mains or drains and the like |
97 | Structural steel weldedbuilt up sectiosfor steel ladder |
98 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
99 | Boulder filling in rooms inclduing handpacking and laying etc complet |
100 | Providing and laying incement concrete of specified grade upto plinth level etc. excluding the cost of centering and shuttering. All work upto plinth level 1: 2: 4 (1 cement : 2 coarse sand : 4 graded stone) aggregate 20mm nominal size Crushed. |
101 | Brick work with common burnt clay F.P.S (non-modular) bricks of class designation 75 in foundation and plinth in Cement mortar1:4 mix (1 cement: 4 fine sand) |
102 | Brick work with common burnt clay F.P.S (non-modular) bricks of class designation 75 in foundation and plinth in Cement mortar1:6 mix (1 cement: 4 fine sand) |
103 | Extra for brick work in super structure above plinth level upto floor V level. (by manual level) |
104 | Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia and length (hold fast lugs or with dash fasteners shall be paid for separately): First class kail wood |
105 | Cement concrete flooring in 1:2:4 mix finished with floating coat of neat cement |
106 | Providing and fixing of tie bolts, spring coil in well shuttering (12mm dia & 100m length) |
107 | Providing and fixing panelled or panelled &glazed shutters for door windows using 4mm thick glass panes including MS pressed butt hinges bright finished off required size with necessary screws excl c/o glass panes |
108 | Providing and fixing wire gauze shuttersof 30mm thickness butt hinges bright finished off required size with necessary screws |
109 | Providing and fixing planneled and glazed shutters 35mm thick |
110 | Providing and fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with |
111 | Providing , hoisting and fixing trusses / purlins , rafters , posts , plates or like componenets incl c/o screws etc complete Popular wood |
112 | Providing CGI sheet roofing incl GI washers of specified size excl c/o purlins , etc incl cutting to size & shape wherever required (0.50mm) |
113 | Providing CGI sheet roofing incl GI washers of specified size excl c/o purlins , etc incl cutting to size & shape wherever required (0.63mm) |
114 | Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia and length (hold fast lugs or with dash fasteners shall be paid for separately): 2nd class KD WOod SIlver |
115 | P/F of paneled or paneled doors, windows & celestory windows (area of opening for paneling insert excluding portion inside groves or rebates to be measured) paneling for paneled or panelled and glazed shutters 25 to 40mm thick. 2nd class kail wood. |
116 | Providng and fixing of 200mm eves market made PGI sheets boarding inc all supports frames required at site complete job |
117 | Providing 40x5mm flat iron hold fasts 40cm long incl. fixing to frame with 10mm dia bolts, nuts and wooden plugs and embedings in cement concreate block 30x10x15 cm (1:3) mix (20mm nominal size) |
118 | Providing & fixing aluminium sliding door bolt ISI marked annodized (Anodic coating not less than grade AC 10 as per IS-1868) transparent or dyed to required colour or shade with nuts and screws etc. complete |
119 | Providing & fixing aluminium tower bolt ISI marked annodized (Anodic coating not less than grade AC 10 as per IS-1868) transparent or dyed to required colour or shade with nuts and screws etc. complete |
120 | 150x10mm |
121 | 100x10mm |
122 | Providing & fixing aluminium handles ISI marked annodized (Anodic coating not less than grade AC 10 as per IS-1868) transparent or dyed to required colour or shade with nuts and screws etc. complete |
123 | 125mm |
124 | 100mm |
125 | Providing & fixing aluminium hanging floor door stopper ISI marked annodized ( Anodic coating not less than grade AC 10 as per IS-1868) transparent or dyed to required colour or shade with nuts and screws etc. complete Single Rubber Stopper |
126 | Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturers specifications including appropriate priming coat preperation of surfaces, etc complete. |
127 | Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top smooth and curing complete |
128 | Providing & fixing MS grill of required pattern in frames of windows etc. with Ms flat,square or round bars etc. including priming coat with approved steel primer. All complete. |
129 | Providing & fixing White vitreous china water closet squatting pan(Indian type) along with “S” or “P” trap including dismantling of old WC seat and “S” or “P” trap at site complete with all operations including all necessary materials, labour and disposal of dismantled material i/c malba, all complete as per the direction of Engineer-in charge.Orissa pattern W.C Pan of size 580x440 mm |
130 | Providing and fixing Salem Stainless Steel A lSI 304 (18/8) kitchen sink as per I.S. 13983 with C.l. brackets and stainless steel plug 40 mm including painting of fittings and brackets, cutting and making good the walls wherever required:Kitchen sink with drain board 510 x1040mm Bowl depth 250mm |
131 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) R.C.C. top slab with 1 :2:4 mix ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size) inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement: 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finsihed with a floating coat of neat cement complete as per standard design.Inside size 90x80 cm and 45 cm deep including C.l. cover with frame (light duty) 455x61 Omm. internal diamensions total weight of cover and frame to be not less than 38 |
132 | Providing & fixing PVC soil waste and vent pipe. |
133 | 100mm |
134 | 75mm |
135 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality and colour.450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms. |
136 | Providing & fixing GI pipes complete with GI fittings and clamps including cutting and making good the walls etc. (Internal works). |
137 | 15mm dia nominal bore ( Light weight ) |
138 | 20mm dia nominal bore ( light weight ) |
139 | Providing & fixing GI pipes complete with GI fittings including trenching and refilling etc. (External works).15mm dia nominal bore. (light weight) |
140 | Providing & fixing of 1200mm sweep ceiling fans complete with accessories including dimmer of ISI mark complete. |
141 | Providing & fixing of Exaust fan in 1.5 sqmm stand wire to be laid in conduits complete. |
142 | Providing & fixing of 16-A MCB of Indocap complete. |
143 | Providing & fixing MCB distribution box 10 way main double door system. |
144 | Taking outOld filter media for Filter beds from Filter media |
145 | Taking out Baramulla Store |
146 | Washing of bleaching and cleaning of bed and side |
147 | Providing and shrouding filter media including laying, including all carriages by mechanical transport from Gandrabal and head load complete job. |
148 | P/ F of ridges / hips |
149 | Providing and fixing of 200mm wide Eaves boarding |
150 | Providing and fixing of soffit boarding ornamental incld. Cost of buttoms II |
151 | Providing/laying of plain cement concrete in 1 : 3 : 6 mix excluding cost of centring and shuttering, finishing and reinforcement. All works upto plinthlevel for thrust blocks. |
152 | 15mm thick c. plaster on the rough side of single or half brick in 1:4 mix |
153 | 15mm thick cement plaster finished with floating coat of neat cement of mix 1: 4 mix (1 cement : 4 fine Sand). |
154 | Dry Random Rubble stone masonry hard stone |
155 | P/F WC indian type(0.45x 0.60) |
156 | P/F PVC low level flushingof 10 ltr capacity |
157 | Providing and fixingof kitchen sink |
158 | P/F of trap 100 dia |
159 | P/F 50mm PVC ventpipe |
160 | P/F of PVC specials |
161 | Tee 100x100 |
162 | 100 Bend |
163 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps,including cutting and making good the walls etc |
164 | Providing & fixing on Terrace ( at all floor levels) polyetheline water storage tank ISI 12701 marked indicating the BIS license no. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and over flow pipes but without fittings and the base support for tank ( Syntex,Electroplast,Star,Lotus or equivalent having valid ISI license. |
165 | Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturers) of 1st quality conforming to IS: 15622 of approved make, laid on 20 mm thick bed of cement mortar 1: 4 ( 1 cement : 4 coarse sand) including pointing the joints with white cement and matching pigment etc., complete. |
166 | P/ F of ceramic glazed tiles of approved quality on 20mm thick bed of cement mortar 1:4 mix incl pointing of joints with white cement |
167 | Pointing on brick work in 1:3 mix |
168 | Painting ofwood work with synthetic enamel paint of approved brand and manufacture ( Two or more coats) |
169 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade on New work (two or more coats) over and including priming coat with water thinnable cement primer ( Qty as per item no 19) |
170 | Providing and fixing 100mm aluminium handles |
171 | P/f of tower bolts |
172 | P/ F of Sliding door bolts |
173 | Providing and fixing 15 mm nominal bore C.P. brass bib cock of app Quality |
174 | Providing and fixing 15 mm nominal bore C.P. brass angle valve forbasin mixer and geyser points of approved make. |
175 | Providing and fixing 15mm nominal bore CP mixer of approved make |
176 | Electrification of Quarter including cost of wire 1.5mm /4mm ,gadjets,switches, bakelite board , main board and MCB etc complete job as directed by Site Engineer |
177 | Lightening point |
178 | Heating Points |
179 | Providing and fixing of chain link fencing |
180 | Providing and fixing of wood work in trusses, purlins, rafters etc |
181 | Contruction of production well by way of drilling/boring |
182 | Contruction of production well by way of reaming/ ODEX method |
183 | Lowering and fitting of hevy duty of MS casing pipe |
184 | Providing and shrouding of pea gravel |
185 | Devlopment of tubewell after complication of drilling, boaring, lowering casing pipe and filling of pea gravel job |
186 | Providing and fitting of service line 7/16 of specified specificationcomplete job |
187 | Providing , Installation of approved make Gyser of 50ltr capacity including CP pipe,nipplesetc as per directions of Engineer incharge complete job |
188 | Providing, laying and fixing /jointing (rich mix concrete) of spun pipe NP3 type including earthwork excavation of trenches as specified to withstand the traffic load including refilling by 2nd class sand and cost of pipe. The job includes all sorts of carriage upto site of work complete job ( TO BE UTILISED AS SLEEVES) |
189 | Carraige of pipes fromsoure upto actual site of work by mechanical transport including loading and unloading for an avg lead of 25kms |
190 | below 100mm dia G.I pipe |
191 | 100mm dia D.I pipe for avg. lead 10 kms |
192 | 150mm dia D.I pipe |
193 | Carraige of materials from actual site upto dumping site of work by mechanical transport including loading unloading and stacking for avg. lead 25kms |
194 | Cement and Steel |
195 | Sand |
196 | Stone soling |
197 | Aggregate 20mm |
198 | Bricks for avg. lead 75km |
199 | Head load from different materials from dumping site upto actual site of work by 400 mtr |
200 | Pipes |
201 | 100 mm dia DI pipes |
202 | Cement /steel |
203 | Stone aggregate/Sand |
204 | Stone soiling |
205 | MechanicalComponents |
206 | Design, fabrication , launching and commissioning ofM.S.FloatingPlatformatrawwaterStageof Water Supply Scheme GujherPatieBinner Janbazpora,and Chakla Nadiahal.The job shall be conformable to:----Theworkingspacenotbelessthan 3.5X5.5 meter. Height of the housing not less than 2.75 meters.Load bearing capacity not less than 3.5 MT excluding the weight of structure. Single Door, of size 1x2 meter. Four Windows of size 0.75x1 meter.Two openings of size 0.5x0.5 meter in the floor to accommodate suction pipes.The top of the housing shall be covered with green culturedsteelcorrugatedsheetsfittedonDouble slide truss.The gauge of the sheet shall be choose keeping into consideration the snow load and overall load of the structure.Gantry is to be fitted for installing and dismantling of the pumping units.Chain Pulley Block of capacity 02 Ton and lift 6 meter of reputed/ Indeff make is be provided and fitted to the Gantry Mechanism.Suitablearrangementistobemadeforboarding and deboarding the platform.Suitable anchoring mechanism is to be provided to restrict undesirable movement of the boat. |
207 | Design,supply,installation,testingand commissioning of Horizontal Pump unit with necessaryMSbaseframeandfoundationbolts, having following specifications: Pump: Type: Horizontal Make: Kirloskar / Crompton Greaves Speed: 1450 RPM Discharge: 20000GPH Dynamic head: 30m Liquid to be handled: Clear Water Suction and delivery: 80mm x 65mm (preferably) Efficiency: not less than 75% at duty point Impeller:Bronze Shaft: Stainless steel Sleeves: Bronze Pump casing: Cast Iron Prime Mover: Type : Horizontal, AC 3-phase induction Motor Make : Kiroskar / Crompton Greaves Speed :1450 RPM Capacity:CompatiblewithPumpheadand discharge. Efficiency : not less than 75% at duty point . Testcertificate:Therequisitematerialandtest certificateoftheofferedequipmentshallhaveto beprovidedtothedepartmentbeforethe installation of equipment |
208 | Non-Return Valve: Supply at site, Installation, testing & commissioning of NB 150mm Non return valve. The technical specifications for the valve are as under:- Nominal size:-NB 150 Inside & outside Surface Coating:-Epoxy- powder coating (EP-P) Pressure Rating :-PN16/PN1.6 (kg/cm2/MPa) Material for the valve parts a) Body & cover, disc:- Ductile Iron (GGG-40) b) Disc sealing :-with EPDM Features of the valve 1. Soft sealing. 2. Face to Face length as per the standard 3. Low torque for the operation of valve. Acceptable makes are : VAG/IVC/Sigmaflow. The valve shall be supplied with the manufacturers test certificate clearly stating the testing pressures forthebody&seat,&durationoftesting.The nuts&boltsrequiredforfasteningofthevalve shall be made of SS material |
209 | Sluice Valve: Supplyatsite,Installation,testing& commissioningofNB150mmsluicevalve.The technical specifications for the valve are as under:- Nominal size:- NB 150 Inside & outside Surface Coating:-Epoxy-powder coating (EP-P) Pressure Rating :-PN16/PN1.6(kg/cm2/MPa) Material for the valve parts a. Body, Wedge & bonnet:- Ductile Iron (GGG- 40) b. Wedge vulcanized all over :- with EPDM c. Stem& nut :-Chrome steel & brass respectively Features of the valve 1. Soft sealing. 2. Face to Face length as per the standard 3. Low torque for the operation of valve. 4. Hand wheel of suitable size with proper locking arrangement with the stem. 5. Mode of Operation:- Manual Acceptablemakesforthevalveare VAG/IVC/Sigma flow The valve shall be supplied with the manufacturers test certificate clearly stating the testing pressures for the body & seat, & duration of testing. The nuts & bolts required for fastening of the valve shall be made of SS material |
210 | Supply, installation, commissioning offoot value 100mmdiameterKirlosker/VAGmakeincluding cost of reducer increaser washer nut bolts etc. |
211 | Fabrication, providing and fitting of Suction/ delivery manifold out of 150/150 mm diameter MS pipes,5.4mm thick, with following details Deliveryside:(outof150mmdiameter) Fabrication,providingandfittingofflangedY- junctionhavingeacharmnotlessthan1meter, flangedpipe ondeliveryside05feetlong01No each, flanged MS easy bend 02 No Any modification required at site for proper fitment/ alignment, and necessary nuts, bolts, washers is included in the job |
212 | Providing and fitting of reinforced flexible rubber, 6 layers, 10mm thick, pipe150mm diameter (flanged both ends) 3 M long capable to withheld pressure of 16kgf/cm2 and temperature -10 to 500 |
213 | Providing, laying &fixing withadhesive/bonding material ofinsulation rubber mats on thefloor of thepumphouse,coveringareaaroundelectro- mechanical machinery for safeguarding the life of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material &moisturefree.ThematsshallbeasperIS 15652:2006 & shall have the following specifications:- Composition : Rubber(syntheticmatsfor electrical purpose) Thickness:- 25mm Size : - 1M wide Make :- Safe Volt/Joyti Therubbermatsshallbeacceptedwith manufacturers test certificate. Size: - 1M wide. Make :- Safe Volt/Joyti . |
214 | Providing, laying, fitting and testing of submersible cable, multi-stranded copper (16mm2) PVC insulated, heavy duty double covering type |
215 | Providing and fittingof Modular control panel of appropriatesizefabricatedoutof 14SWG sheet havingrequiredopenings/ventsandprotection Class : 1P55 & fitted with accessories as under:- Change over Switch:- Qty. = One No.Rating =63Ampere Type = Front operated,On load 4 poles, 400 + 15% volts, 50 + 3% C/S.Make= L&TModel=SS95984COCO/. SS95984DOCORelay range=13-21Distribution buses: - = Electricgrade Aluminum with red, blue and yellow tapping of adequatesection.Rating = 63 Amp. Qty. = 4 No’s.Circuit Breakers:- = MCCB. Qty. = 3 No’s Make = L & TModel/Version = SS95975COFO/. SS95975DOFO,4P-01 No incoming & D-sine seriesHighDN0-125D-02Nos.(63A,3p) outgoingRatedoperationalvoltage=415V+ 15 %Rated frequency = 50 +/- 3 % Hz Ambient temperature = 40C° Ultimate S.C Breaking Cap. at(415, ac, 50 Hz)Main MCCB = 50 KAOutgoing MCCB =36KA Typeofrelease=Thermal MagneticOverloadprotection =0.8–1inadjustableShort-circuitprotection=3-6inadjustable.AuxiliaryforHeating/LightingCircuitBreaker: MCCBQty. =1No’sake/CAT=Havel’s/IHLGSF0063No. of poles = 4PRated Current = 63 Amp.Ratedoperationalvoltage=415 V + 15 %Ultimate S.C Breaking Cap. at (415, ac, 50 Hz)= 10 KA Starters:-fully automatic Star delta starters.Make = L&TModel=MUG 20 Star/ DeltaPower specs= 3 phase., 415 + 15%V, 50 + 3% Hz.Relay Range = 14 - 23 Ampere. Relay= MUGContact= MUGBackupHRCfuse= HF-63Ampere.Switch dis connector fuse unit.=FN-100Qty.= 03NoS.Ampere Meter:- Size = 96 mm Sq. Range = 0 – 50 AMP Make = L & T / RishabhCTCoils=Requisite5VA–10 VA capacity & CT ratio. CTcoilspermeter=03No’s (Rishbh / L & T).Selector Switches per meter = 01No.(Rishbh / L & T). Type = Analogous Qty. = 02 No’s. Voltmeter:-Size = 96mm Sq. Range = 0-500 volts Type = AnalogousMake = L & T / Rishabh Selector Switches=03 No’s (L &T / Rishabh)Qty. = 01No’s.Frequency meter = 0-50 Hz. Type = Analogous Make = L&T / Rishabh Qty.= 01 C. Job Fault Analyzer= Digital Motor Protection Relay with LCD Display Protections= Under Voltage, Over Voltage,UnderLoad,OverLoad,LockedRotor, Current unbalance,VoltageUnbalance, Phase failure &Phase reversal. DisplayParameters = Line Voltage, Phase Voltage, Line Current, Frequency, KW, KV, PF, Fault history. Make= Western/Proton/INDSUN The enclosureshallbeofexcellentfinish, corrosion resistant treated and powder coated gliding hinges for smooth and noiseless movement ofwindowsandlatestlockingarrangements.The internalcopperwiringoftheGadgetsshallbe flameretardantandsmokelessandofadequate section. Thepanelshallbeconnectedwithmainpower supplythroughvoltagestabilizerandother necessary gadgets, shall be tested on full load |
216 | Supply, Installation of 35 mm Sq. 3.5 core XLPE Armored Al. Cable of 1.1 KV(650/1100V Grade), as service linefrom sub- station to the main control panel. The job also including proper thimbling, tightening etc |
217 | Providing, Fitting, Installation, testing and commissioning of open well, Non Clog type submersible pumping unit (Vertical type) for washout system of SSFP. The technical specifications of the pumping unit shall be as follows: Pump i) Make :Kirloskar/Darling/CRI/KSB ii) Type:Open Well, Non – Clog iii) Discharge :5000 GPH iv) Dynamic Head :10 Meters v) Speed:1450 rpm vi) Fluid to be handled: Raw water vii) Strainer : Stainless steel viii) Material of Impeller:Stainless Steel ix) Shaft material :Stainless Steel x)Diffuser:Cast Iron xi) Solid Handling size :Up to 100mm |
218 | The pump shall have a mechanical seal which should not require any additional external supply of oil or water and shall not be subject to pumping media. Motor i) Rating: Corresponding to head & discharge ii) Speed : 1450 rpm (Syn) iii) Frequency :50 Hz iv) Voltage :415±15% v) Efficiency :not less than 65% vi) Method of starting : star –Delta / Soft Start The job includes providing and fitting of suitable increaser/reducer on the delivery manifold and necessary piping of suitable size and length along with steel clamps and other allied works for successful testing and commissioning of the equipment. The motor shall be made of corrosion resistant material to resist corrosion under normal conditions and the motor shall have a name plate depicting all specifications. Mechanical seal (01 no) and bearings (02 nos) for each pumping unit must be provided by the firm as spare parts for preventive maintenance. The requisite test certificate of the offered equipment shall have to be provided to the department before the installation of equipment. |
219 | Supply, providing, fitting, testing of 80mm diameter PN 16 Sluice valve and Reflux/non-return valves (01 no each) of VAG/AVK make including providing & fitting of nut- bolts, RI cloth etc. |
220 | A) Supply, providing, fitting, testing and commissioning of fully automatic Star-Delta Starter (L&T Make, Model MU-G 5). The starter shall be sheet enclosure type suitable for operating on 3 – phase, 380 V, 50 Hz AC Power Supply. The starter shall be able to provide single phase, phase reversal, phase imbalance and overload protection to the motor. The starter shall also have On/OFF, voltage and current indication. (02 nos). B) Providing and fitting of 32 amps 3-pole MCCB, 25Ka ultimate breaking capacity with thermal magnetic release of L&T/Havells make (02 nos). A set of neon type phsase indicating lamps to be provided alongwith voltmeter of range 0-500V and Ampere meter 0-30A (01 no each) with selector switches of AE/Rishabh/L&T make. The job includes fitting of all above equipments on suitable size panel boardfabricated out of ISA 50x50x6 angle iron frame. The frame shall be provided and fitted with 19mm thick plywood board covered with Bakelite sheet for holding of various switch gear equipments. |
221 | Providing and laying of ISI marked3-core 6 sq.mm water proof Submersible cable of Finolex/reputed make from starter to motor. Job includes cost of 2 inch dia PVC conduit, earth excavation for its underground from sump to panel board/starter as per site requirement proper amperage thimblesetc |
222 | Supply, Laying (underground as per site requirement), Testing and Commissioning of flanged MS pipe, 80mm NB, 4mm thick in suitable lengths (3-6 meters) as Rising Main. The job includes fabrication, supply & welding of offset/bends as per the site requirement, nuts and bolts, RI gaskets between flanged joints. The Pipe shall conform to IS 1239, 2005 part1(or latest IS standards),the acceptable make are Jindal/Prakash/Surya/Bushan/any other reputed make. Earth work: The pipe shall be laid underground as per the defined contour/site requirement after carrying out the earth work excavation. The job includes backfilling of the excavated soil after laying, complete in every respect. The road cuts and safe overburden thereof with oversized pipe jacketing, head load from road side to the site of installation, painting of pipes after cleaning are also included in the job. |
223 | Bio-toilet of size 4/x4/x8/ with FRP bio-digester tank of capacity 700 liters with anaerobic bacterial incolumn 200 liters complete with all accessories: Providing/construction/installation/commissioning of onsite brick masonry constructed/pre cast, re-inforced concrete constructed/fiber reinforced plastic constructed toilet block with bio-digester super structure shall be: General specifications .On site constructed/ factory made .Single unit/ paneled form as per site requirement . Easy to maintain and clean .All weather protection .Well ventilated .Shall have no effect on natural calamity with regard to Effluent drawn out .Shall be feasible for operation under -15 to 40 degree celcius temperature. Technical specification for onsite constructed/pre cast RCC toilet super structure . Toilet block size: 4ft x4ft x 8ft .Material-Precast concrete M25, onsite brick masonry or fiber reinforced Plastic |
224 | Desired features of toilet block: .Tiles- upto 3ft on side walls or as material of construction ,Floor-Tiles or as material of construction .Paint on outside walls and inside walls as per material of construction . Western toilet sheet made of ceramic (as per site requirement) .Taps and flushing system- Water tap at a nominal height of minimum 13inches for Orissa Pan .Flushing system .Electric wire to connect the bulb .Stand for water tank-Mild steel of ISA 40x 40 x5mm with CGI roof and proper frost protection during winter .Door-PVC/AL/FRP any other water proof material .Water tank of capacity 300liters of HDPE(with an openable lid) for the supply of water ( to be placed on top with suitable frame) .Hand washing basin with tap etc |
225 | Technical specification for Sanitation Unit for solid waste management (Bio digestor) .Capacity of bio-digestor: 900liters .Design- With four chambers to ensure long hydraulic retention time .Construction of bio digestor- UPVC/on site concrete constructed/ any other chemically in-active material .Catalyst-Highly effective Bio catalyst .Incolumn-The cocktail of bacteria duly certified by DRDE of 30% of the volume of digestor .Bio digestor lining-Inert vulcanized 1.0mm thick butyl/EPDM rubber CE marked and non-voven geo textile for bacteria retention .Thickness of lining- 2mm .Material of portion waffle-concrete/any other chemically inactive material .Lifting-lugs .3-4 people usage Further, job includes all types of works like earth work excavation for bio digester, carriage, transportation, handling, pipes for inlet connection for tank, other pipes etc for disposal of effluents as per latest Govt norms, electric connection, lock etc |
226 | Standby equipments for existing / running scheme (2 stages) |
227 | Providing, fitting, installation, testing and commissioning of 25KVA balanced Voltage Stabilizer involves following specifications: (a). Rating: 25KVA. (b). Range: 180V – 415 V c. Copper wound with adequate insulation and thickness suitable for the load. d. Cores should be of cold rolled high silicon steel laminations held together with the help of steel clamps, material should be such that both magnetized currents and the core losses are minimum. The core laminations to be of minimum thickness but of adequate strength. e. Hysteresis losses to be minimum and temperature not to exceed 70 Degree Celsius. (f). Air gap to be minimum to avoid Eddy formations for the coils to be immersed in insulating varnish and dried by suitable means. g. Regulator to be Double Plate type with cylindrical copper contacts having six boosting steps. The contacts to be suitable to with stand over loading current at least double the rated current over considerable period of time. |
228 | h. The container to be sufficient to accommodate cores, windings, internal connections, and insulating media. Suitable cooling tubes to be provided along with oil level indicators. The container should be manufactured out of MS sheet of suitable thickness strong enough to withstand stresses produced by jacking and lifting. It should be provided with lifting lugs and should be duly Painted form inside and outside. i. The container at its top to be fitted with proclain insulators for housing poles on the 19mm Bakelite plate. j. Seven numbers of brass poles to be fitted in the plate, three each for incoming and outgoing poles and one for neutral. The space between the poles to be sufficient enough to accommodate the required size tube terminals to prevent arcing. |
229 | k. The top of the container to have a display panel for housing 02 numbers voltmeters 0- 500V, square dial flush type Rishabh make one for incoming & other for outgoing for each phase with one neon indicators for every incoming & Outgoing circuits. l. Insulating media (T. oil) of 11 KV grade to be provided and filled with dielectric strength of 5 KV at 4mm air gap. m. Steel Castor wheels to be fitted to the container at the bottom for easy positioning of the stabilizer. n. Providing and fitting of suitable copper terminals duly crimped and taped to the incoming and outgoing cables. |
230 | Providing and filling of fresh T-oil for old transformers and stabilizers of the existing scheme(2 stages) |
231 | Supply, installation, testing and commissioning of submersible pumping unit of below mentioned parameters to be lowered inside well. Pump: TypeSubmersible[Multistage Bowl Type] Speed 2900 RPM Discharge6000 GPH. With Bronze/SS Impeller Dynamic Head80 Mrs. Make KSB/Kirloskar/M&P ImpellerChrome Steel/SS MOTOR /PRIME MOVER: Type Submersible Speed 2900 RPM Phases3 - Phase AC supply , 50 Hz frequency MakeKSB/Kirloskar/ABB Capacity(As recommended by Pump Manufacturer) (Preferably not Below than 16 HP) Submersible motor should be water filled, water lubricated having capacity for above pumping parameters and working on 3 phase; AC supply ranging from 380 to 420 volts, 50 HZ .The motor should be sealed by radial rings to avoid mixing of well water with motor filled water. The job includes providing and fitting of interlocking arrangement against any failure of coupling. It must be fabricated out of MS strips/rods of suitable size and length. The job includes providing and fitting of appropriate size M/S nipple 2 feet long threaded on one end and welded to MS flange of 80 mm Dia, 10 mm thick at other end .The threaded portion should be as per size of pumping out let for proper fixing. The job includes proper testing and commissioning of pumping unit on full load at site. |
232 | Providing and laying of 16 sq. mm 3-core specially formulated PVC compounded insulated sheathed with abrasion resistant PVC compound impermeable to water, oil, grease etc. copper submersible cable from starter to motor including, thimbles etc. |
233 | Design, manufacturing ,providing , fitting, testing & commissioning of LT Control Starter Panel fabricated out of 2 mm CRCA Sheets Modular, compartmentalized, Free Standing, Floor Mounting, Front hinged doors for indoor use, removable bottom gland plates for incoming cables, dust and vermin proof (IP: 42 protection) with TPN Copper Buses, complete with connection, internal wiring, name plates, painting ,vents etc. generally as per details furnished below: Rated Voltage of the Panel --440 Volts. Frequency ----- 50 HZ No of Phases ----- Three Enclosure Details ----- Free Standing, Floor mounted, Compartmentalized Design. Material ----- CRS Thickness of sheet steel used ----- 02mm Three phase Indication Lumps in Red, yellow &green Shades Application ----- Indoor. Cable Entry ----- Bottom Painting ----- Shade Siemens grey. Change over Switch Qty ----- One No Type ----- Front Operated on load “4 pole” Rating ----- 200 Amp Make ----- L&T/ Schneider b) Distribution bus bar Type -----Electric grade “Cu” with red, blue & yellow tapings Of adequate section. Rating ----- 200 AmpCircuit Breaker incoming combined Type ----- MCCB 200 A D-Sine seriesQty ----- 1 NosMake ----- L & T No. of poles ----- 4Breaking cap: at (415 volt A C , 50 Hz ) ----- 50 kAType of release ----- Thermal release range [32-40]”A”Breaking cap: at (415 volt A C , 50 Hz ) ----- 50 kA Type of release ----- Thermal release range [32-40]”A”Auxiliary Circuit Breaker units for 3 nos. starters Qty ----- 3 No’s No. of poles------3 Make ----- L & T /Schneider Rated current -----100 Amp Rated operational voltage----- 415 V± 15% Rated frequency ----- 50± 3% Hz Ultimate S.C Breaking capacity at (415 volt AC, 50 Hz ) -----50 kA Starters Starters fitted with Single phase Protection relay arrangement [SPPR], Dual Analog voltmeter Cum Ampere Meters of Rishabh/L&T make of applicable range with Phase selector switch for Volt meter & ammeter. Type:- MUG-20H Make = L & T Model = MUG-20 H star / Delta Contactor= ML4 (wide band) Overload Relay=MN5 Pickup-up Voltage= 65% to 110% Uc Drop-off Voltage= 20% to 50%Uc Service Temperature= -5oC to + 55oC Qnty ----- Three Numbers Power Specification -----3 phase, 415 ± 15% v & 50 Hz. Backup HRC fuse=HF – 63A Switch Disconector fuse unit=FN 63:-Two No’s Aux. Cubical. One Auxiliary Cubical for use of auxiliary equipments of Pump House and premises like lightening/Heating with 63 amps |
234 | 2 Pole MCB’s and Change over Switch. Circuit breaker---MCB Qnty---02 no. Make---L&T/Havells/ Schneider No. of poles---02 Rated current---63 A Rated operational Voltage---220+15% Change over Switch Qty ----- One No Type ----- Two way centre off MCB Type 2 pole. Rating ----- 63 Amp Make ----- L&T/Havells Meter Module. Meter module comprising ofSeparate:- 1) Digital Volt-meter. 2) Digital ammeter. 3) Digital frequency meter.4) Digital power factor meter. 5) Digital Intelligent Panel meter which shall display line current in RYB phases, record and display trip counts and indicate trip status for over load, under load, single pahse, etc. The meter shall also analyse, display and record no. Of operations and duration of motor running. [All Components of L&T/Havells/Reputed make only confirming to ISI Specifications] |
235 | Providing, installation, testing and commissioning of 50 KVA Voltage Stabilizer with of following specifications: i. Range: 180 V – 415 V ii. Copper wound with adequate insulation and thickness suitable to the duty to be performed. iii. Core should be of cold rolled high silicon steel laminations held together with the help of steel clamps; material should be such that both magnetized currents and the core losses are minimum. The core laminations to be of minimum thickness but of adequate strength. iv. Hysteresis loses to be minimum and temperature not to exceed 700C. v. Air gap to be minimum to avoid Eddy formations for it the coils to be immersed in insulating varnish and dried by suitable means. vi. Voltage regulator switch to be of plate type with copper contact points having six boosting steps. The contacts to be suitable to withstand over loading current at least double the rated current over the considerable period of time. vii. The container to be sufficient to accommodate cores, windings, internal connections, and insulating media. Suitable cooling tubes to be provided along with oil level indicators. The container should be manufactured out of MS sheet of suitable thickness strong enough to withstand stresses produced by jacking and lifting. It should be provided with lifting lugs and should be duly painted form inside and outside. viii. The container at its top to be fitted with porcelain insulators for housing poles. ix. Seven numbers of brass poles to be fitted in the plate, three each for incoming and outgoing poles and one for neutral. The poles to be marked. The creapage distance between the poles to be sufficient enough to accommodate the required size tube terminals to prevent arcing. x. The top of the container to have a display panel for housing 02 numbers voltmeters 0- 500V, square dial flush type along with 4 way selector switch and set of neon indicators. xi. Insulating media (T. Oil) of 11 KVA grade to be provided and filled with dielectric strength of 5 KV at 4m air gap. xii. Steel Castor wheels to be fitted to the container at the bottom for easy positioning of the stabilizer. Rating of stabilizer: 50 KVA The job shall also include providing and fitting of suitable copper terminals dully crimped and taped to the incoming and outgoing cables. (The Voltage stabilizer to be manufactured in a registered workshop in presence of person authorized by the undersigned). The T-Oil of specific grade should be provided in a separate barrels. |
236 | Providing, Installation, testing of multi-stranded copper conductor PVC insulated single core unsheathed 35 mm sq.Copper cable for internal distribution wiring. The multi-stranded copper cable to be laid through PVC conduits on wooden plain boards fixed on walls with suitable plugs, nails and clamps. The job also includes termination of ends of cable with suitable rating of Cu. thimbles duly taped.Make: Havells/ National/Standard/Plaza/Imperial |
237 | Providing, laying, installation and testing of 1.1KV, 3-1/2 Core, 95 sq. mm. Aluminum Conductor, PVC insulated, armored cable from distribution box of Transformer to the voltage stabilizer at both stages of the scheme. The Job also includes providing and installation of Aluminum thimbles of appropriate ratings (24 No.) duly crimped and taped. Make: Finolex/ Polycab/ Havells |
238 | FLOOD LIGHTS P/F of 48 Watt LED type street light assembly of Havells make (JETA Type) on GI 50 mm Dia. 3mm thick tabular pole/pipe having 5 meter height fabricated out of pipe 50 mm Dia. GI pipe with MS Plate to be welded at bottom. The Pole/pipe is to be erected in a trench 2.5 feet deep and then grouted in 1:2:3 C.C. block and the Top of the pole/pipe is to be bend at an angle of 135 degree for holding above light assembly by way of arm/holder arrangement. The Job includes Coating of pole with two coats of red oxide paint and one coat of enamel silver paint and P/f of 2 core 10 sq.mm armored al. cable up to control panel along with P/f of 16 amp MCB. The job includes providing of necessary wirings. |
239 | Power Inverter Providing and fitting of Power Inverter of 850VA Rating of Exide/Luminous/V-Guard Make including providing of 150 A Lead acid Battery Tubular Type complete in all respects. The job includes P/F of necessary plugs (SS Combine)- 2 nos. Socket for charging the inverter with necessary cable for incoming and outgoing power supply. |
240 | Providing / fitting 80 mm Dia Non Return valve with specifications Nominal Dia 80 mm. Rating – PN 16. Make – AVK, VAG /TALLIS/Sigma Flow Body: DuctileIron (DI) Bonnet : Ductile Iron (DI) Check valve disk: Ductile cast iron all around EPDM vulcanized. Cover bolting: Stainless steel. Inside and outside epoxy coating. Shall have flange ends on both sides. Shall have Low pressure loss due to full bore type (100%). Shall have Integrated limit stops in the disk to protect the seal. Shall have No bearing friction due to suspension of disk. Shall have Pre-stressed disk closing for rubber suspension. Incrustation- and corrosion-free rubber lined disk shall be used. Shall have Quick and easy disassembly of body cover and disk for maintenance. Included is cost for table flanges of 18 mm thick at respective ends of the raising main Make= VAG/Kirloskar (DI)/Flowmore |
241 | Providing / fitting 80 mm Dia Sluice valve with specifications Nominal Dia 80 mm. Rating – PN 16. Make – AVK, VAG /TALLIS/Sigma Flow Body: DuctileIron (DI) Bonnet : Ductile Iron (DI) Check valve disk: Ductile cast iron all around EPDM vulcanized. Cover bolting: Stainless steel. Inside and outside epoxy coating. Shall have flange ends on both sides. Shall have Low pressure loss due to full bore type (100%). Shall have Integrated limit stops in the disk to protect the seal. Shall have No bearing friction due to suspension of disk. Shall have Pre-stressed disk closing for rubber suspension. Incrustation- and corrosion-free rubber lined disk shall be used. Shall have Quick and easy disassembly of body cover and disk for maintenance. Included is cost for table flanges of 18 mm thick at respective ends of the raising main Make= VAG/Kirloskar (DI)/Flowmore |
242 | P/I/T/C cubical fitted with 200 A D-Sine MCCB with breaking capacity of 50 kA along with MUG-50 Starters (FASD) fully automatic starter delta starter fitted with SPP relay arrangement, dual analogue voltmeters, cum ammeter of Rishabh/L&T make of applicable rangewith phase selector switch for volt meter and ampere meter type /model = MUG- 30 star delta starter Qty = 02 no’s Power Specification = 3 phase, 415 +15% V and 50 HZ Relay range = 45-75Amp Back up HRC fuse= HF – 100 Amp Switch disconnector fuse unit= FN63 – two no’s |
243 | Supply, installation, testing and commissioning of submersible pumping unit of below mentioned parameters to be lowered inside well. Pump: TypeSubmersible[Multistage Bowl Type] Speed 2900 RPM Discharge7000 GPH. With Bronze/SS Impeller Dynamic Head80 Mrs. Make KSB/Kirloskar/M&P ImpellerChrome Steel/SS MOTOR /PRIME MOVER: Type Submersible Speed 2900 RPM Phases3 - Phase AC supply , 50 Hz frequency MakeKSB/Kirloskar/ABB Capacity(As recommended by Pump Manufacturer) (Preferably not Below than 20 HP) Submersible motor should be water filled, water lubricated having capacity for above pumping parameters and working on 3 phase; AC supply ranging from 380 to 420 volts, 50 HZ .The motor should be sealed by radial rings to avoid mixing of well water with motor filled water. The job includes providing and fitting of interlocking arrangement against any failure of coupling. It must be fabricated out of MS strips/rods of suitable size and length. The job includes providing and fitting of appropriate size M/S nipple 2 feet long threaded on one end and welded to MS flange of 80 mm Dia, 10 mm thick at other end .The threaded portion should be as per size of pumping out let for proper fixing. The job includes proper testing and commissioning of pumping unit on full load at site. |
244 | Providing and laying of 16 sq. mm 3-core specially formulated PVC compounded insulated sheathed with abrasion resistant PVC compound impermeable to water, oil, grease etc. copper submersible cable from starter to motor including, thimbles etc. |
245 | Design, manufacturing ,providing , fitting, testing & commissioning of LT Control Starter Panel fabricated out of 2 mm CRCA Sheets Modular, compartmentalized, Free Standing, Floor Mounting, Front hinged doors for indoor use, removable bottom gland plates for incoming cables, dust and vermin proof (IP: 42 protection) with TPN Copper Buses, complete with connection, internal wiring, name plates, painting ,vents etc. generally as per details furnished below: Rated Voltage of the Panel --440 Volts. Frequency ----- 50 HZ No of Phases ----- Three Enclosure Details ----- Free Standing, Floor mounted, Compartmentalized Design. Material ----- CRS Thickness of sheet steel used ----- 02mm Three phase Indication Lumps in Red, yellow &green Shades Application ----- Indoor. Cable Entry ----- Bottom Painting ----- Shade Siemens grey. Change over Switch Qty ----- One No Type ----- Front Operated on load “4 pole” Rating ----- 200 Amp Make ----- L&T/ Schneider b) Distribution bus bar Type -----Electric grade “Cu” with red, blue & yellow tapings Of adequate section. Rating ----- 200 Amp Circuit Breaker incoming combined Type ----- MCCB 200 A D-Sine series Qty ----- 1 Nos Make ----- L & T No. of poles ----- 4 Breaking cap: at (415 volt A C , 50 Hz ) ----- 50 kA Type of release ----- Thermal release range [32-40]”A” Breaking cap: at (415 volt A C , 50 Hz ) ----- 50 kA Type of release ----- Thermal release range [32-40]”A” Auxiliary Circuit Breaker units for 3 nos. starters Type ----- MCCB Qty ----- 3 No’s No. of poles------3 Make ----- L & T /Schneider Rated current -----100 Amp Rated operational voltage----- 415 V± 15% Rated frequency ----- 50± 3% Hz Ultimate S.C Breaking capacity at (415 volt AC, 50 Hz ) -----50 kA Starters Starters fitted with Single phase Protection relay arrangement [SPPR], Dual Analog voltmeter Cum Ampere Meters of Rishabh/L&T make of applicable range with Phase selector switch for Volt meter & ammeter. Type:- MUG-50 Make = L & T Model = MUG-250 H star / Delta Contactor= ML4 (wide band) Overload Relay=MN5 Pickup-up Voltage= 65% to 110% Uc Drop-off Voltage= 20% to 50%Uc Service Temperature= -5oC to + 55oC Qnty ----- Two Numbers Power Specification -----3 phase, 415 ± 15% v & 50 Hz. Backup HRC fuse=HF – 63A Switch Disconector fuse unit=FN 63:-Two No’s Aux. Cubical. One Auxiliary Cubical for use of auxiliary equipments of Pump House and premises like lightening/Heating with 63 amps 2 Pole MCB’s and Change over Switch. Circuit breaker---MCB Qnty---02 no. Make---L&T/Havells/ Schneider No. of poles---02 Rated current---63 A Rated operational Voltage---220+15% Change over Switch Qty ----- One No Type ----- Two way centre off MCB Type 2 pole. Rating ----- 63 Amp Make ----- L&T/Havells Meter Module. Meter module comprising ofSeparate:- 1) Digital Volt-meter. 2) Digital ammeter. 3) Digital frequency meter.4) Digital power factor meter. 5) Digital Intelligent Panel meter which shall display line current in RYB phases, record and display trip counts and indicate trip status for over load, under load, single pahse, etc. The meter shall also analyse, display and record no. Of operations and duration of motor running. [All Components of L&T/Havells/Reputed make only confirming to ISI Specifications] |
246 | Providing, installation, testing and commissioning of 50 KVA Voltage Stabilizer with of following specifications: i. Range: 180 V – 415 V ii. Copper wound with adequate insulation and thickness suitable to the duty to be performed. iii. Core should be of cold rolled high silicon steel laminations held together with the help of steel clamps; material should be such that both magnetized currents and the core losses are minimum. The core laminations to be of minimum thickness but of adequate strength. iv. Hysteresis loses to be minimum and temperature not to exceed 700C. v. Air gap to be minimum to avoid Eddy formations for it the coils to be immersed in insulating varnish and dried by suitable means. vi. Voltage regulator switch to be of plate type with copper contact points having six boosting steps. The contacts to be suitable to withstand over loading current at least double the rated current over the considerable period of time. vii. The container to be sufficient to accommodate cores, windings, internal connections, and insulating media. Suitable cooling tubes to be provided along with oil level indicators. The container should be manufactured out of MS sheet of suitable thickness strong enough to withstand stresses produced by jacking and lifting. It should be provided with lifting lugs and should be duly painted form inside and outside. viii. The container at its top to be fitted with porcelain insulators for housing poles. ix. Seven numbers of brass poles to be fitted in the plate, three each for incoming and outgoing poles and one for neutral. The poles to be marked. The creapage distance between the poles to be sufficient enough to accommodate the required size tube terminals to prevent arcing. x. The top of the container to have a display panel for housing 02 numbers voltmeters 0- 500V, square dial flush type along with 4 way selector switch and set of neon indicators. xi. Insulating media (T. Oil) of 11 KVA grade to be provided and filled with dielectric strength of 5 KV at 4m air gap. xii. Steel Castor wheels to be fitted to the container at the bottom for easy positioning of the stabilizer. Rating of stabilizer: 50 KVA The job shall also include providing and fitting of suitable copper terminals dully crimped and taped to the incoming and outgoing cables. (The Voltage stabilizer to be manufactured in a registered workshop in presence of person authorized by the undersigned). The T-Oil of specific grade should be provided in a separate barrels. |
247 | Providing, Installation, testing of multi-stranded copper conductor PVC insulated single core unsheathed 35 mm sq.Copper cable for internal distribution wiring. The multi-stranded copper cable to be laid through PVC conduits on wooden plain boards fixed on walls with suitable plugs, nails and clamps. The job also includes termination of ends of cable with suitable rating of Cu. thimbles duly taped. Make: Havells/ National/Standard/Plaza/Imperial |
248 | Providing, laying, installation and testing of 1.1KV, 3-1/2 Core, 95 sq. mm. Aluminum Conductor, PVC insulated, armored cable from distribution box of Transformer to the voltage stabilizer at both stages of the scheme. The Job also includes providing and installation of Aluminum thimbles of appropriate ratings (24 No.) duly crimped and taped. Make: Finolex/ Polycab/ Havells |
249 | FLOOD LIGHTS P/F of 48 Watt LED type street light assembly of Havells make (JETA Type) on GI 50 mm Dia. 3mm thick tabular pole/pipe having 5 meter height fabricated out of pipe 50 mm Dia. GI pipe with MS Plate to be welded at bottom. The Pole/pipe is to be erected in a trench 2.5 feet deep and then grouted in 1:2:3 C.C. block and the Top of the pole/pipe is to be bend at an angle of 135 degree for holding above light assembly by way of arm/holder arrangement. The Job includes Coating of pole with two coats of red oxide paint and one coat of enamel silver paint and P/f of 2 core 10 sq.mm armored al. cable up to control panel along with P/f of 16 amp MCB. The job includes providing of necessary wirings. |
250 | Power Inverter Providing and fitting of Power Inverter of 850VA Rating of Exide/Luminous/V-Guard Make including providing of 150 A Lead acid Battery Tubular Type complete in all respects. The job includes P/F of necessary plugs (SS Combine)- 2 nos. Socket for charging the inverter with necessary cable for incoming and outgoing power supply. |
251 | Providing / fitting 80 mm Dia Non Return valve with specifications Nominal Dia 80 mm. Rating – PN 16. Make – AVK, VAG /TALLIS/Sigma Flow Body: DuctileIron (DI) Bonnet : Ductile Iron (DI) Check valve disk: Ductile cast iron all around EPDM vulcanized. Cover bolting: Stainless steel. Inside and outside epoxy coating. Shall have flange ends on both sides. Shall have Low pressure loss due to full bore type (100%). Shall have Integrated limit stops in the disk to protect the seal. Shall have No bearing friction due to suspension of disk. Shall have Pre-stressed disk closing for rubber suspension. Incrustation- and corrosion-free rubber lined disk shall be used. Shall have Quick and easy disassembly of body cover and disk for maintenance. Included is cost for table flanges of 18 mm thick at respective ends of the raising main Make= VAG/Kirloskar (DI)/Flowmore |
252 | Providing / fitting 80 mm Dia Sluice valve with specifications Nominal Dia 80 mm. Rating – PN 16. Make – AVK, VAG /TALLIS/Sigma Flow Body: DuctileIron (DI) Bonnet : Ductile Iron (DI) Check valve disk: Ductile cast iron all around EPDM vulcanized. Cover bolting: Stainless steel. Inside and outside epoxy coating. Shall have flange ends on both sides. Shall have Low pressure loss due to full bore type (100%). Shall have Integrated limit stops in the disk to protect the seal. Shall have No bearing friction due to suspension of disk. Shall have Pre-stressed disk closing for rubber suspension. Incrustation- and corrosion-free rubber lined disk shall be used. Shall have Quick and easy disassembly of body cover and disk for maintenance. Included is cost for table flanges of 18 mm thick at respective ends of the raising main Make= VAG/Kirloskar (DI)/Flowmore |
253 | P/I/T/C cubical fitted with 200 A D-Sine MCCB with breaking capacity of 50 kA along with MUG-50 Starters (FASD) fully automatic starter delta starter fitted with SPP relay arrangement, dual analogue voltmeters, cum ammeter of Rishabh/L&T make of applicable rangewith phase selector switch for volt meter and ampere meter type /model = MUG- 30 star delta starter Qty = 02 no’s Power Specification = 3 phase, 415 +15% V and 50 HZ Relay range = 45-75Amp Back up HRC fuse= HF – 100 Amp Switch disconnector fuse unit= FN63 – two no’s |
254 | Providing, installation, testing and commissioning of vertical turbine pumping unit driven by hollow shaft motor for pumping water at WSS Takya Khan Mundji (JJM) an altitude of 1584 M (AMSL). The specification are as under as per DPR: “A” Pump: 1. Discharge =6000 GPH 2. Type = Self water lubricated, vertical turbine pump, open line shaft type with delivery above floor level. 3. Liquid to be handled = Contaminated water having solids in suspension 4. RPM = 1450 5. Head = 64 Meters 6. Efficiency = 75% without negative tolerance 7. Material of Impeller = Semi enclosed open shrouded impellers mixed flow (Bronze grade V of BIS 318) 8. Material of Line shaft and line shaft coupling = Stainless steel AISI-410 9. Material of impeller shaft = Stainless steel AISI-410 10. Intermediate shaft = Stainless steel 11. Column pipe = Mild steel column pipe as per IS226/2062, 100mm nominal dia, total length not to increase 10m (lengths for columns shall be 3.04m+2.43m+1.52m+1.52m+0.61m) i.e. to be fabricated in suitable pieces 12. Suction strainer = MS fabricated 13. Bell mouth = CI 14. Pump Bowl = CI (pump bowls should be fastening through screws) 15. Levels: Sump bed level = 100 Meters Machinery floor level = 112 Meters Minimum water level = 1.5 Meters Minimum submergence = 1.5 Meters Level are as per design of sump/cum pump house. Pump bowl to be designed with minimum number of stages not more than 4 Stages. Make= WIPL / Kirlorkar / Mather Platt |
255 | "B" Motor 1. Type = Hallow Shaft AC Squirrel cage induction motor 2. Rating = not less than 12.5 HP (Standard Rating) 3. Frequency = 50 ± 3 % Hz 4. Working Voltage = 380 ± 15 V, 03 phase 5. RPM = 1450 (sync) 6. Efficiency = Not less than 80% 7. Class of insulation = F 8. Enclosure = TEFC 9. IS standard = IS 325-1970 10. Quantity = One Number 11. Make = Kirlosker/ABB 12. Bearings = Thrust bearing shall be suitable and of adequate capacity to carry the weight of all rotating parts and the hydraulic down thrust. 13. Ratchet = Non-reversing ratchet or similar mechanism should be provided to the motor to prevent reverse rotation. 14. Continuous maximum rating = Continuous maximum rating of the motor shall be at least 20% above the maximum power absorbed by the pump under any operating point within stipulated head range of the pump or at least 10% above the power required at shut-off, whichever is higher. 15. Discharge Head: Discharge head shall be fabricated from MS. It shall be incorporated in full diameter elbow mounting flange for motor with suitable tapping for pressure gauge. The discharge head shall be of robust construction and shall be designed to support entire static and dynamic load of pump assembly, water column and motor. The discharge head shall have an arrow indicating direction of rotation of pump. The discharge head may have a stuffing box with renewable bushing. The location shall be easily accessible. The lantern ring and gland follower shall be split type. It shall incorporate suitable arrangement to collect gland leakage and lead to sump with suitable piping. The discharge head should have suitable size valve arrangement for air release |
256 | Fabrication , Providing , Fittingand testing of delivery manifold Y-junction system fabricated out of M S ( heavy class) 100mm dia pipes. The job also includes fabrication, providing and fitting of 100mm dia MS bends, including flanges, tabular flanges, increasers, reducers, nuts and bolts, gaskets as per site requirement. The job also includes p/f of 02 No’s 100mm dia NRV PN 1.6 of VAG/AVK make and 02 No’s 100mm dia Sluice Valve PN 1.6 of VAK/AVK make. Job Also includes fabrication of base frame in ISMC 200 -17m, 8mm thick MS Plate 5 sq m for V.T. Pumping units as per side requirement . Job also includes painting of delivery manifold with one coat of red oxide and two coat of paint.(Colour as per direction of site engineer) . Thejob also includes fabrication providing and fitting of washout system in 100 mm dia MS Pipe (Heavy class) 18mts includingP/F fittingof 100 mm dia sluice valve 01 no, bends,offsets , flanges as per site requirement. |
257 | Providing and fitting and 35 sq mm ABC HT cable 30 mtrs in lengthfor making connections at tapping point and providing and fitting of 35 sq mm ABC HT insulator kit-02 sets (one set comprises of 3 pieces) |
258 | Providing & Fitting of25 sq mm Single Core Copper Conductor (Flexible) PVC Insulated Heavy Duty Industrial Cables (Unsheathed), 1100 Volts Conforming to IS: 694- for connecting VT motors from panel , stabilizers in rubber conduit . Job includes providing& laying of flexible conduit for cu cable with lugs as per requirement .make phenolix/havells/KEI |
259 | Providing, installation ,testing of power service cablefor workingvoltage up to and including 1100 volts;50 mm2 armored aluminum 3.5 core cable as service line from output terminals of HT/LT transformer / AVR to cubical panel. Cost includes laying of cable in trenches in Pvc conduit where ever itis to be laid underground as per site requirement included is termination of ends with suitable Aluminum tube terminals dully crimpled & taped. Make Gloster, Havells, Legend. |
260 | Scope: Design, manufacturing ,providing , fitting, testing & commissioning of Star-delta Motor control gear Panel The Star-delta Motor control gear Panel shall be fabricated out of 2 mm CRCA Sheets Modular, compartmentalized, Free Standing, Floor Mounting, Front hinged doors for indoor use, removable bottom gland plates for incoming cables, dust and vermin proof (IP: 42 protection) with TP Aluminum Buses, complete with connection, internal wiring, neon indicators for each phase ,starter buttons, name plates, painting ,vents etc. generally as per details furnished below: Rated Voltage of the Panel ----- 440 Volts Frequency ----- 50 HZ No of Phases ----- Three Enclosure Details ----- Free Standing, Floor mounted, Compartmentalized Design. Material ----- CRS Thickness of sheet steel used ----- 02mm Application ----- Indoor Cable Entry ----- Bottom Painting ----- Shade Siemens grey. a) Circuit Breaker incoming combined Type -----Front Operated micro processor release type on load 4 pole Qty ----- 1 Nos Make ----- L & T / Schneider No. of poles ----- 4 Thermal relay range.------63-160A Rated operational voltage----- 415 V AC± 15% Rated frequency ----- 50± 3% Hz Ultimate S.C Breaking cap at (415 volt A C , 50 Hz ) ----- 36kA Type----- Microprocessor control |
261 | b) Distribution bus bar Type -----Electric grade AL with red, blue & yellow tapings Of adequate section. Rating ----- 150 Amp Make --------L & T / Schneider c) Change over Switch Qty ----- One Type ----- Front Operated on load 4 pole (open execution) Rating ----- 200 Amp Make ----- L&T/ Schneider d) Circuit Breaker units Type ----- MPCB (Type MOG-H2 (Rotary Type) - Frame 2) Qty ----- 2 Nos No. of poles------3 Make ----- L & T /Schneider Rated current -----63 Amp Thermal release range-28-40 Rated operational voltage----- 415 V± 15% Rated frequency ----- 50± 3% Hz Ultimate S.C Breaking capacity at (415 volt A C , 50 Hz ) -----36kA e)Starters (FASD) Power Specification -----3 phase, 415± 15% v &50 Hz Contactors : MNX / Schneider Line Contactor -----AC3 70 A Delta Contactor --- AC370 A Star Contactor -----AC3 50 A Contactor Make = L & T / Havells Timer ----- Star Delta Electronic Overload relay – direct/CT operated (35-75A range) Coil Voltage : 220/240V Qty ----- 2 No’s f)Aux. panel Circuit breaker---MCCB Qnty---01 no. Make---L&T /Schneider No. of poles---04 Thermal release range -------63-80 A Rated operational Voltage---415+15% Ultimate S.C. Breaking Capacity---35 KA at (415AC,50 Hz) |
262 | g)Stabilization unit Qnty---01 no Rating---- 1 KvA single phase automatic voltage stabilizer Input :90V-300 Out Put : 220/240 ( as per coil voltage of contractors) Enclosure--- to be housed within the cubical panel in separated chamber with additional meter , LEDfitted outer side Make : V-guard, microtec, luminious MCB DP ---10A----1nos h)ProtectionDetails: Motor Protection Relay including other related accessories like single phase preventer relay, timer relay , overload-under load, phase difference etc. Display -----LED/LCD Compact motor protection relay Qnty :01 nos) Make : L&T(MM10)/ Schneider Protections : • Flush Mounting with display • Last trip data recording • Protections: - Thermal Overload with pre- alarm - Short Circuit - Earth fault - Phase loss, Unbalance, Phase reversal - Under Current - Prolong starting, Locked Rotor. -Single phase protection- Single Phasing condition- Phase Reversal condition- Phase Unbalance condition-Modes of Operation i) Auxiliary Protection Earth Fault Relay -----3 phase Earth fault, ground fault module Type -----GF Range 100-200A MCB ----- MCB SP , 10A (10 Ka) Make : L&T/Schneider |
263 | j) Water level controlrelay for including wiring and capsules required at site keepind depth of sump 10 meters in consideration: 01 unit complete g) Metering Details: • Incomers (Panel Mounted) (a) Multi-Function MetersLCD Display (1 No) Voltage of each phase , Current of each phase 3ø power (Active, Apparent) , 3ø Power factor Frequency, Energy (b) Analog voltmeter S/S operated (1 No) - Rishabh make. • (b) Outgoing (Analog voltmeter (0-500) S/S operated (1Nos) . Analog Ammeters 0-100 Amp(2Nos)for both starters Each outgoing with S/S CT operated (Rishabh make ) Note: Name of Scheme ; Allotment No ; should be imprinted on the machine with capital letters The job also includesproviding and fitting of MUG-30 FASD (relay range 20-33)starter-01 number(as standby arrangement |
264 | Providing and fitting of 60 W LED Street light (outdoor type) with angular stand fixture in MS/Steel. The LED should be environmental friendly long life versatile pressure dia cast aluminum IP65 roadway luminaires with high power LEDS as light source & exclusively designed polycarbonate cover along with electronic driver. The LED is to be controlled inside pump house and connected to the automatic voltage stabilizer through panel. The wire used should be 2.5 sq mm multistranded single core 1100 volts pvc insulated copper conductor minimum 20 m for each connection throuvh PVC pipe by way of p/f of MCB duly fitted on Bakelite phylum switch board with frame as per site requirement. |
265 | Providing and fitting of 5 Kva Single phase automatic copper wound stabilizerfitted with digital meter .Job includes providing and fitting of cable input and output side. The job includes p/f of 16 A SS combine on inputside with 16 top. the said unit is used for illumination purpose. The name of water supply scheme is to be printed on top of the stabilizer. |
266 | Providing, installation, testing and commissioning of 50 KVA Voltage Stabilizer of following specifications at Stage 2nd A i. Range : 200V – 415 V i. Copper wound with adequate insulation and thickness suitable to the duty to be performed. ii. Core should be of cold rolled high silicon steel laminations held together with the help of steel clamps; material should be such that both magnetized currents and the core losses are minimum. The core laminations to be of minimum thickness but of adequate strength. iii. Hysteresis loses to be minimum and temperature not to exceed 700 C. iv. Air gap to be minimum to avoid Eddy formations for it the coils to be immersed in insulating varnish and dried by suitable means. v. Regulator to be of plate type with copper contacts cylindrical having six boosting steps. The contacts to be suitable to with stand over loading current at least double the rated current over considerable period of time. The container to be sufficient to accommodate cores, windings, internal connections, and insulating media. Suitable cooling tubes to be provided along with oil level indicators. The container should be manufactured out of MS sheet of suitable thickness strong enough to withstand stresses produced by jacking and lifting. It should be provided with lifting lugs and should be duly painted form inside and outside. vi. The container at its top to be fitted with porcelain insulators for housing poles. vii. Seven numbers of brass poles to be fitted in the plate, three each for incoming and outgoing poles and one for neutral. The poles to be marked. The distance between the poles to be sufficient enough to accommodate the required size terminals to prevent arcing. viii. The container is be fitted with drain plug for T-oil near bottom & hooks at top for lifting top of the container by CP block at the time of repair works. ix. The top of the container to have a display panel for housing 02 numbers voltmeters0-500V (Rishab / AE Make) , square dial flush type along with 4 way selector switch and set of neon indicators both for input & output x. Steel Castor wheels to be fitted to the container at the bottom for easy positioning of the stabilizer. xi. Name of WSS ,Supplier & Allotment no& Date should be written on one side of body of Voltage Stabilizer. Rating : 50 KVA The job shall also include providing and fitting of suitable copper terminals dully crimped and taped to the incoming and outgoing cables. |
267 | j) Water level controlrelay for including wiring and capsules required at site keepind depth of sump 10 meters in consideration: 01 unit complete g) Metering Details: • Incomers (Panel Mounted) (a) Multi-Function MetersLCD Display (1 No) Voltage of each phase , Current of each phase 3ø power (Active, Apparent) , 3ø Power factor Frequency, Energy (b) Analog voltmeter S/S operated (1 No) - Rishabh make. • (b) Outgoing (Analog voltmeter (0-500) S/S operated (1Nos) . Analog Ammeters 0-100 Amp(2Nos)for both starters Each outgoing with S/S CT operated (Rishabh make ) Note: Name of Scheme ; Allotment No ; should be imprinted on the machine with capital letters The job also includesproviding and fitting of MUG-30 FASD (relay range 20-33)starter-01 number(as standby arrangement |
268 | Providing, installation, testing and commissioning of 50 KVA Voltage Stabilizer of following specifications at Stage 2nd A i. Range : 200V – 415 V i. Copper wound with adequate insulation and thickness suitable to the duty to be performed. ii. Core should be of cold rolled high silicon steel laminations held together with the help of steel clamps; material should be such that both magnetized currents and the core losses are minimum. The core laminations to be of minimum thickness but of adequate strength. iii. Hysteresis loses to be minimum and temperature not to exceed 700 C. iv. Air gap to be minimum to avoid Eddy formations for it the coils to be immersed in insulating varnish and dried by suitable means. v. Regulator to be of plate type with copper contacts cylindrical having six boosting steps. The contacts to be suitable to with stand over loading current at least double the rated current over considerable period of time. The container to be sufficient to accommodate cores, windings, internal connections, and insulating media. Suitable cooling tubes to be provided along with oil level indicators. The container should be manufactured out of MS sheet of suitable thickness strong enough to withstand stresses produced by jacking and lifting. It should be provided with lifting lugs and should be duly painted form inside and outside. |
269 | vi. The container at its top to be fitted with porcelain insulators for housing poles. vii. Seven numbers of brass poles to be fitted in the plate, three each for incoming and outgoing poles and one for neutral. The poles to be marked. The distance between the poles to be sufficient enough to accommodate the required size terminals to prevent arcing. viii. The container is be fitted with drain plug for T-oil near bottom & hooks at top for lifting top of the container by CP block at the time of repair works. ix. The top of the container to have a display panel for housing 02 numbers voltmeters0-500V (Rishab / AE Make) , square dial flush type along with 4 way selector switch and set of neon indicators both for input & output x. Steel Castor wheels to be fitted to the container at the bottom for easy positioning of the stabilizer. xi. Name of WSS ,Supplier & Allotment no& Date should be written on one side of body of Voltage Stabilizer. Rating : 50 KVA The job shall also include providing and fitting of suitable copper terminals dully crimped and taped to the incoming and outgoing cables. |
270 | Gantry: a) P/F of 3-ton chain pulley block with Mono rail Pull Lift/ Indef make having lifting capacity of 5m. Complete with U. clamps, chain, hooks and other allied fixtures. b) Fabrication / Erection of Channel iron column to act as support for resting of Chain Pully Blockwith Monorailas per following details:- Vertical Posts = ISMC 150 No. of vertical posts = 02 Nos. Vertical channel section each post= 02 Nos. vertical post bracing = ISMC 100 Sole / Matching plates = 500x300x12 mm Height of vertical posts = 4.5 M size of vertical post concrete blocks = 600x600x900mm Concrete grade = M20(as per requirement) welding Electrode = Overcord SS of Adore/ESAB/L&T Monorail Section = ISMB 200 length of monorail Chain Pully Block with monorail= 3 Ton= 5M |
271 | Steel Detail : i. ISMC 150 6.1Mx2x2 = 18 M @ 24.4kg/m = 439.2 kg ii ISMC 100 0.25Mx10x2x2 = 10 M@ 9.2kg/m = 92 kg iii Plate0.500x0.300x8 (12mmthk) = 1.20 M²(12thk) = 112.80 kg iv Monorail ISMB 200 6.1 M @ 25.4 kg/M =154.94 kgs v Bolts/Nuts (L.S) =20kgs Total = 818.94 kg = 820 KG say |
272 | Providing & fitting oflighting points for( machine room , operators room,) as per site requirement in 1.5 mm² multistranded single core 1100 volts, pvc insulatedcopper conductor through pvcconduit pipe by way of p / f of pearl or non-ploy carbonate angle holders , pvc gang box, switches, socket modules , regulators ,indicators, 09 watt LED lamps Make( Bajaj/GE/Havells/Phillips/syska). Make items Anchor, klick, S S K, Indo Asian, Philips, Havells .Included is cost on account of desired Bakelite / phylum switch boards with the wooden frames as per site requirements |
273 | Providing fitting of weargaurd wall mount type lighting points for exterior walls in 1.5 mm² multistranded single core 1100 volts, pvc insulatedcopper conductor through pvcconduit pipe by way of p / f of pearl or non-ploy carbonate angle holders , pvc gang box, switches, socket modules , regulators ,indicators, 09 watt LED lamps Make( Bajaj/GE/Havells/Phillips/syska). Make items Anchor, klick, S S K, Indo Asian, Philips, Havells .Included is cost on account of desired Bakelite / phylum switch boards with the wooden frames as per site requirements. |
274 | Providing fitting of heating points in 2.5mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit by way of p / f of 15 Amp switches, 6 pin socket of Anchor, Philips, S S K make as per site requirements. Heating points are to be connected from main control panel. All accessories required is to be provided by the firm. |
275 | Providing, fitting of Distribution Board of indo Asian, S S K make 4 way S P N single door powder coated sheet steel enclosure for surface mounting fitted with bus bar, DIN channel, neutral link and incoming contact. the above DB is to be provided /fitted with double pole 40 amp MCB for Main. 32 A for heating circuit & rest 3 of 16/6 amps each for premises luminary, auxiliary circuit 0f make indo Asian, Havells. Further job includes providing / fitting 4 mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit as service line from main panel as per site requirements. Connections should be made in such a way Lighting pointsis to be connected via automatic transformer by way of p/f switch socket arrangement with allied fixtures & and heating points to main panel. Job includes dismantling of existing damaged conduit , wires, conduit and cleaning the surface properly.one job at each stage |
276 | Providing of heavy duty tool kit Taparia make : Ring spanner of size 12-13,14-15,16-17,18-19,21-22,20-21,21-23,24-26,30-32 Plate Spanner of size12-13,14-15,16-17,18-19,21-22,20-21,21-23,24-26,30-32 Pipe wrench 36” & 14”one each, Plair -01 no. Screw driver set 01 set Providing of one no Heavy duty re- chargeable flash light. 01 no L-N Key – 1 set Providing of 04 no’s plastic chairs with one table of samrudhi make- 01 set Providing clamp type multi meter(AC/DC). make meco heavy duty -02 no’s Providing and fitting of link rod.-01 no Providing and fitting of shock proof matting 2x3 m 20 mm thick-4 no’s Providing and fitting of fire extinguisher 7.5 kgs for electric short circuit-02 no’s |
277 | Providing/fitting/testing/commissioning of power backup systems with pure sine wave home ups coupled with an inbuilt environmentally friendly zero maintenance tubular SMF VRLA gel batteries in a single console. The batteries should be sealed for life that is they should not have any requirement for water topping up or any spillage. The power bus should be equipped with a multi colored LCD user interface for better usage & monitoring. Technical specification. o Inverter rating = 850VA o Inverter Type = home UPS o Battery capacity = 150 Ah. o Battery Model = Tubular Type. o No Batteries = 01 No. o Output voltage at no load = 220+/-7 o Output frequency = 50 HZ +/- 1 o Output wave form = pure sine wave Make: Exide, Phillips, Microtek, luminous. Warranty:-UPS = 02 years ,Batteries = 03 years The combo unit is to be provided with warranty card for on door service during warranty period. Further job includes providing/fitting of separate circuit involving 2.5mm square multi stranded copper conductor form main auxiliary panel, 16 amp switch, socket separate modules, wooden blocks, hylum sheets, 03 pin top, earthing conductor from main earthing station, desired conduits, pvc channels & all allied items as per site requirement. |
278 | Constructing of Earthling station :Supply , installation , testing and commissioning of earthing electrode comprising of company fabricated earthing electrode as per IS :3043 for carrying out earthing . The job includes drilling / boring of 200 mm dia bore to the depth of 6 feet . Connectingthe cable tray through GI strips of suitable thickness besides making surface pit in brick / cement concrete of appropriate size. The earthing electrode shall be of 76/80mm dia and 1.83 mtr length of reputed make. The backfilling properly mixed compound as required . |
279 | Providing of four number good quality blankets,Two no’s good qualitymattress, quilts, pillows with covers for all. Two No. pressure cookers of 5 liters capacity (Hawkins make) 01, 3L pressure cooker -01, Bunton 3L-01 No. al/steel tea pan, 4 No. steel glass,4 cups, 4 steel plates, 4 no steel spoons, 1 steel jugs,2 no plastic jug, two number buckets ,14 L LPG Gas cylinder with regulator,pipe and two way gas topr, Electric cooking heater, 2 liters Collin ,dhoti cloth, 2 No. shook proof gloves, Bathroom broom, 2 No. brooms for room cleaning, 1 No. wiper,harpic.,.one no Heavy duty re- chargeable torch lantern led light. 04 no’s heavy duty link locks. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy