Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | ELECTRICAL STANDARDISATION AND AUGMENTATION |
| 2 | Part 1 Industrial Light point wiring :Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure 8 Way 4 Pole MCCB Incommer and 4 Pole MCCB Out Going Double Door Load bank ( Power Safe Panel) suitable for 100A MCCB as incomer Panel including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing 4P 100 A 18kA MCCB with suitable spreaders as incomer and 16A/20A/32A/40A/50A/ 63A 4 Pole (FP)MCCB as outgoing. with suitable spreaders Meter Modulewith digital multi function meter (V, A, F, KWHr), 100/5 Class 1 resin cast CT\"s 3 Nos LED Indicators, control MCBs and corner box on both side at the top, Add on module of the same size of the panel at the bottom and 2 nose of cable alleys in both sides complete. fixed on wall / MS Frame work using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required 8 way double cover(( L & T make Enersys / Havells Load line or equivalent ready made sub board) |
| 3 | 100A 4 pole 15kA MCCB with spreader set as Incommer |
| 4 | 25A Single Pole MCCB with spreader set as out going to LDB UPS |
| 5 | 25A Double MCCB with spreader set To Single phase LDB |
| 6 | 32-63A Triple MCCB with spreader set to Essential water pump |
| 7 | 32-63A Four poleMCCB with spreader set to TPN LDB , Security light, Canteen and spare |
| 8 | Supplying and fixing following way, Single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator),12 way double door |
| 9 | 16 way, Double door |
| 10 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator), 4 way (4+24), Double Door |
| 11 | 8 way (4 + 24), Double door |
| 12 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required . (Note : Vertical type MCB TP DB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door |
| 13 | 12 way (4 + 36), Double door |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 15 | Single pole and neutral |
| 16 | Double pole |
| 17 | Triple pole |
| 18 | Triple pole and neutral |
| 19 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A |
| 20 | 63A |
| 21 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A |
| 22 | 63A |
| 23 | 100A |
| 24 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25A |
| 25 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A |
| 26 | 40A |
| 27 | 63A |
| 28 | Supply and Installaing on Truss Bay Light Fitting LED Circular 180 Watts 150 lm/W UV Stabilized IP PCLens, 140 -270 V AC input range 4kV inbuild Suge protection 50k Burning Hrs @ L70 B50 standerds 340mm Dia THD <10% 5700K Colour Temp (CCT) 60 Degree lense IP 66 and IK 07capatable Panasonic Make ENVISO PRO PBYM14KL8 or equilent. |
| 29 | Supply and Installaing on Truss WELL GLASS LED Fitting70 Watts 130 lm/W140 -270 V AC input range 6kV inbuild Suge protection 50k Burning Hrs @ L70 B50 standerds 340mm Dia THD <10% 5700K Colour Temp (CCT) 60 Degree lense IP 66 and IK 08capatable Panasonic Make MERLIN PLUSPWG09708 or equilent. |
| 30 | Industrial Batten IP 65 LED Batten with inbuilt heat sink, polycarbonate housing equipped with anti-glare diffuser & energy efficient electronices driver 40 W 6500 K (CCT) Panasonic Make TRUSS Model No PBTM05407 or equilent. |
| 31 | Industrial Batten IP 20 LED batten for surface and suspended application. White powder coated CRCA housing with LEDs. Seamless front frame is with white high transmission acrylic cover and decorative end cap. 20 W 5700 K (CCT) Panasonic Make HARROW Model No PBTM12208 or equilent. |
| 32 | Track light with aluminum profile 100 LED per meter 10 W/ Mts12/24 V DC light back up with 24Ah 12V lithium-ion battery and BMS system |
| 33 | Part 2 Industrial Power Wiring Bus Trunking system.Supplying, installing on wall or suspension on ceiling, testing and commissioning of following capacity Air Insulated Compact Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints, Horizontal and vertical run continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required.400A Isc = 30kA for 1 second |
| 34 | Supplying, installation, testing & commissioning of following capacity End Feed Unit for the existing Air Insulated Compact Type bus Trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure (IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. MCCB 4 pole 200 A 15kA SC for 1 sec for 75kW Electric Furnace |
| 35 | MCCB4 pole 125A 15kA SC for 1 sec for 50kW Electric Furnace |
| 36 | Supplying, installation, testing & commissioning of following capacity Plug In/ tap off box on the existing Air Insulated Compact Type bus Trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supplyincluding 4 Nos LED indicator and control fuse made with 1.6mm thick sheet steel enclosure (IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete etc. as required.MCCB 4 pole 200 A 15kA SC for 1 sec For 50 HP Inductive Load feeder. |
| 37 | MCCB 4 pole 63 to 125 A 15kA SC for 1 sec Up to 35HP Inductive Load feeders |
| 38 | Part 3 Closed Perforated Cable Tray Hot dipped GI Supplying and installing following size of perforated painted with powder coating M.S. cable trays (with cover)with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.100mm widthX 50mm depth X 1.6mm thickness |
| 39 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 40 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 41 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 42 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 43 | 450 mm width X 50 mm depth X 2.0 mm thickness Metre |
| 44 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends (with Cover)with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.100 mm width X 50 mm depth X 1.6 mm thickness |
| 45 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 46 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 47 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 48 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 49 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 50 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee (with Cover) with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.100 mm width X 50 mm depth X 1.6 mm thickness |
| 51 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 52 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 53 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 54 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 55 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 56 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member (with Cover) with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.100 mm width X 50 mm depth X 1.6 mm thickness |
| 57 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 58 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 59 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 60 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 61 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 62 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer (with Cover) with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.100 mm width X 50 mm depth X 1.6 mm thickness |
| 63 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 64 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 65 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 66 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 67 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 68 | Part 4 Cable and End TerminationLaying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface /Through existing cable tray as required.Up to 8 Mts height. Up to 35 sq. mm (clamped with 1mm thick saddle) |
| 69 | Above 35 sq. mm and up to 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 70 | Above 95 sq. mm and up to 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 71 | Above 185 sq. mm and up to 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 72 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.Up to 35 sq. mm |
| 73 | Above 35 sq. mm and up to 95 sq. mm |
| 74 | Above 95 sq. mm and up to 185 sq. mm |
| 75 | Above 185 sq. mm and up to 400 sq. mm |
| 76 | Supplying and making end termination with Double compression whether proofCablegland and Heavy duty aluminium lugs and Earth Tag of suitable sizefor following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Up to and including 19mm Size Double compression Gland size |
| 77 | Up to and Including 32 mm size Double compression Gland size |
| 78 | Up to and Including 40mm size Double compression Gland size |
| 79 | Up to and Including 50 mm size Double compression Gland size |
| 80 | Above 63 mm size Double compression Gland size |
| 81 | Supply at site Power Cables, Solid Aluminium conductor up to 10 sqmm balance stranded conductor, XLPE Insulated,cores laid up, PVC tape inner sheathed, unarmoured/Armour(Aluminium wire for single core up to 70 sqmm balance Aluminium strip, Galvanised wire for cables up to 2x16 sqmm, 3x10 sqmm,4x10 sqmm balance all galvanised steel strip), extruded PVC Type ST2 sheathed,650/1100V grade as per IS 7098(Part 1) 1988 4 core 6 sq mm armoured aluminium |
| 82 | 4 core 10 sq mm armoured aluminium |
| 83 | 4 core 16 sq mm armoured aluminium |
| 84 | 4 core 25 sq mm armoured aluminium |
| 85 | 3.5core 35 sq mm armoured aluminium |
| 86 | 3.5core 50 sq mm armoured aluminium |
| 87 | 3.5core 95 sq mm armoured aluminium |
| 88 | 3.5core 150 sq mm armoured aluminium |
| 89 | 3.5core 240 sq mm armoured aluminium |
| 90 | 3.5core 400 sq mm armoured aluminium |
| 91 | Supply at site Power and Control Copper Cables, Solid Copper conductor,XLPE Insulated,cores laid up, PVC tape innersheathed,Unarmoured/Armour (Galvanised wire for cables up to 14 x 1.5 sqmm, 9x2.5 sqmm,2x16 sqmm, 3x10 sqmm,4x10 sqmm balance all galvanised steel strip),extruded PVC Type ST2 Sheathed, 650/1100 V grade as per IS 7098 (Part 1) 1988 1.5 sq mm 2 core armoured copper control cable |
| 92 | 1.5 sq mm 3 core armoured copper control cable |
| 93 | 1.5 sq mm 4 core armoured copper control cable |
| 94 | 1.5 sq mm 6 core armoured copper control cable |
| 95 | 2.5 sq mm 2 core armoured copper control cable |
| 96 | 2.5 sq mm 3 core armoured copper control and Light cable |
| 97 | 2.5 sq mm 4 core armoured copper control and Light cable |
| 98 | 2.5 sq mm 5 core armoured copper Power cable |
| 99 | 2.5 sq mm 10 core armoured copper control cable |
| 100 | 4 sq mm 5 core Un armoured copper Power cable |
| 101 | 6 sq mm 4 core Un armoured copper Power cable |
| 102 | 6 sq mm 5 core Un armoured copper Power cable |
| 103 | 10 sq mm 4 core Un armoured copper Power cable |
| 104 | 10 sq mm 5 core Un armoured copper Power cable |
| 105 | 16 sq mm 4 core Un armoured copper Power cable |
| 106 | 16 sq mm 5 core Un armoured copper Power cable |
| 107 | 25 sq mm 4 core Un armoured copper Power cable |
| 108 | Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. |
| 109 | Supply and Providing FRP walk ways up to 24Mts height truss purling of existing space frame Industrial shed construction. All light cables fittings and Bus Trunking shall be accessible from the walk way the width of the wake way shall be 45 cms with 2 side Z purling using Hot dipped GI Z sections having minimum 2 mm thickness to accommodate 2 labours working capacity. |
| 110 | Supply and providing FRP Transformer yard fencing using 40 x 40 mm FRP pillars in every 1.5 mts span FRP grills at a height of 1.8 Mts including 2 Nos SS hinged doors with lockable mechanismon top of 60 cms Solid concrete block curb wallas directed by the Engineer in charge |
| 111 | Supply and providing wall supporting type fixed FRP ladders to access the walk way from plant |
| 112 | Supply of suitable size Polyamide flexible conduit with IP67 End coupling fixed using PolyamideBracket having 105 Degree Celsius Temperature as per UL 94V0 |
| 113 | Part 5 Change over Panel, MSB SSB and Motor control canters, State enclosure, Out door kiosk factory built assemblies as per Annexure enclosed. Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623 Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary lifting hooks, cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurements will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc. Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 114 | Supply and providing Aluminium Bus bar having main bus with 0.6 A/ Sqmm and inter connection with 0.8 A/sqmm. Supported by L type/ Step type/ finger type 600 V Rated DMC. Anodized aluminium bus bar shall be insulated using heat shrinkable colour sleeve. Only 6 mm thick sections shall be used as bus bar with multiple run as required. |
| 115 | Supply and providing 4mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 116 | Supply and providing heavy duty \"A\" section Neoprene gasket in the panelsuitable for 1.60/ 2.00 mm sheet (Samples shall be heat aged at 100 deg. C. for 70 hours and tested as per ASTM D-573. Changes in properties shall not exceed the following limits: Tensile Strength : 30% Ultimate Elongation : 50% (max.) Durometer Hardness : 15 points) |
| 117 | Supply and providing copper bus bars duly tinned at all jointsincluding finger type/Conical/ Strip hold SMC bus bar supports in the bus chamber, suitable size nut & bolt, providing Green striped Yellowheat shrink sleeves etc. as required. Density ofEC grade copper shall be calculated for measurement will be considered @ 8.96g/cc. Copper only will be weighed for measurement. |
| 118 | Supply and providing suitable sized SS 202/GI/ Brass bolt nut washers hardware as required. |
| 119 | Supply Fabricate and erect 35 x 35x 6 mm ISLA Wall frame with 8 mm tapped/ Client rivet hole to accommodate SMDB/MCBDB/VDB/ MCC/PBS/ Starter Panel panels and 6 nose 16mm holes to mound the panel to groundas required duly painted using anti rust rubber based black paint. Over 2 coat of zincromate base coat or using epoxy anty rust coating on base frame. |
| 120 | Supply Fabricate and erect 100 x 50 mm ISMC Base frame with 8 mm tapped/ Client rivet hole to accommodate panels and 6 nose 16mm holes to mound the panel to groundas required duly painted using anti rust rubber based black paint. Over 2 coat of zincromate base coat or using epoxy anty rust coating on base frame. |
| 121 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure 8 Way 4 Pole MCCB Incommer and 4 Pole MCCB Out Going Double Door Load bank ( Power Safe Panel) suitable for 100A MCCB as incomer Panel including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing 4P 100 A 18kA MCCB with suitable spreaders as incomer and 16A/20A/32A/40A/50A/ 63A 4 Pole (FP)MCCB as outgoing. with suitable spreaders Meter Modulewith digital multi function meter (V, A, F, KWHr), 100/5 Class 1 resin cast CT\"s 3 Nos LED Indicators, control MCBs and corner box on both side at the top, Add on module of the same size of the panel at the bottom and 2 nose of cable alleys in both sides complete. fixed on wall / MS Frame work using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required 8 way double cover(( L & T make Enersys / Havells Load line or equivalent ready made sub board) for Inductive load up to 15 Hp. |
| 122 | 200A 4 pole 18kA MCCB with spreader set as Incommer |
| 123 | 32-63A Triple 15kA MCCB with spreader set to Power Load up to 10kW |
| 124 | 32-63A Four pole15kA MCCB with spreader set 10-15kW Power Load |
| 125 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure 8 Way TP Motor Control Centre (MCC1) Provision to install 80 A TP MCCB as Incommer and 3 Pole MPCB + Power Contactor with 2 NO 2 NC Out Goingsuitable for 100A MCCB as incomer Panel including copper /brass bus bar, neutral link, earth bus and DIN rail Suitable for fixing 1 HP 3 PhaseMPCBICU 100kA Rotary type with suitable spreaders as incomer and80A TP PoleMCCB as outgoing with suitable spreaders Meter Modulewith digital multi function meter (V, A, F, KWHr), 100/5 Class 1 resin cast CT\"s 3 Nos LED Indicators, control MCBs and corner box on both side at the top. for Blower ,drilling macine circulating pump brench grinders and simillar up to 2 HP Eqiuments. |
| 126 | 80A TP 15kA MCCB with spreader set as Incommer Conforms to IS/IEC 60947-2,IEC 60947-2 & EN 60947-2 |
| 127 | 16A MOG-H1M Rotary Type Thermal Release range 1.6-2.5A ICU 100kA |
| 128 | Auxiliary and Alarm left side mounding |
| 129 | DOL starter Link up to 13A |
| 130 | AC3 Rating 13 A Power contactor with 230 V coil voltage IS / IEC 60947-4-1 & IEC 60947-4-1 |
| 131 | ON / OFF Push button station with illuminated push button on dia cast aluminium enclosure IP54 |
| 132 | 8 mm Metal body R/Y/B and G Led Indication lamp with in line glass control fuse |
| 133 | Part 6. Supply and Providing Electrical accessories for MV Panel boards :- Providing and fixing following rating and breaking capacity and pole MCCB with Micro processor release Conforms to IS/IEC 60947-2 including providing suitable spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 16 A-100A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50-100% having adjustable OL & SC. |
| 134 | 125 A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50-100% having adjustable OL & SC. |
| 135 | 630 A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50-100% having adjustable OL & SC. |
| 136 | 250 A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50-100% having adjustable OL & SC. Mechanical inter lock onrotary frond drive mechanism with 3 Lock 1 Key system. |
| 137 | 630 A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50-100% having adjustable OL & SC. Mechanical inter lock onrotary frond drive mechanism with 3 Lock 1 Key system. |
| 138 | Providing and fixing following rating and breaking capacity and pole MCCB with Thermo magnetic release Conforms to IS/IEC 60947-2 and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 400 A, 35 KA,TPMCCB |
| 139 | 250 A, 35 KA,TPMCCB |
| 140 | 200 A, 25 KA,TPMCCB |
| 141 | 160 A, 16 KA,TPMCCB |
| 142 | 125 A, 16 KA,TPMCCB |
| 143 | 100 A, 16 KA,TPMCCB |
| 144 | Under Voltage release For all voltage ranges up to 630A MCCB |
| 145 | Rotary handle (including BUC handle with door inter-lock defeat and pad lock facility) Up to 250A extended type |
| 146 | Part 7. Earthing andMiscellaneous works:- Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.0 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 147 | Providing and fixing 25 mm X 3 mm copper strip on surface or in recess for connections etc. as required. |
| 148 | Providing and fixing 40 mm X 4 mm Nical Sealed Copper Bonded Earthing Strips 250 microns copper Bonded on surface or in recess for connections etc. as required. |
| 149 | Providing and fixing 50 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required. |
| 150 | Supply and providing Heat shrinkble sleeves for 50 x 6 mm earth conductors Yellow Green sriped clour. Duly inserted in the exposed earth srips. |
| 151 | Supply and providing Heat shrinkble sleeves up to 40 x 4mm earth conductorsGreenclour. Duly inserted in the exposed earth srips. |
| 152 | Supply and Changing roof sheet for DG room 0.45 mm TATA/JSW colour coated Tripode sheet rooflaying sheet usin self taped SS/Aluminum Aloy Hex head screws with rubber gasket as required. |
| 153 | Supply and providing wall clading and inner seperation using wall cladding sheet snwitched 0.35 x 035 with 12 mm PUF insulation TATA/JSW colour coated Tripode sheet rooflaying sheet usin self taped SS/Aluminum Aloy Hex head screws with rubber gasket as required. |
| 154 | Supply and laying Dlink/ RR/ Finolex cat 6 cable through existing polymade/DWCconduit |
| 155 | 4 pair FR PVC sheathed copper conductor polyethylene polyester taped Telephone cables for indoor application (un - armoured) conforming to ITD specifications |
| 156 | Labaling using form sheet of 4 -6 mm thick duly flexo print in multy colour labels and instructions as per directions by Engineering incharge |
| 157 | Part 8. HT Yard work :-Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required |
| 158 | Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required. |
| 159 | Supply and replacing 11 KV Outdoor type Air Break switch shall confirming IS: 9920 / 1981 (part-I to IV), IS: 2633 & IS: 2544/1973 with latest amendment if any and as per drawing. Including necessary modification in the MS channel as required. |
| 160 | Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. |
| 161 | Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift up to 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 162 | Excavation for cable trenches of depth up to 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres. |
| 163 | Providing and laying in position cement concrete 1:3:6 (1 cement : 2 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc including form work etc as required |
| 164 | Providing and laying in position reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required (excluding reinforcement). |
| 165 | Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels. |
| 166 | Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels. |
| 167 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100 mm Dia |
| 168 | 150 mm Dia |
| 169 | 250 mm Dia |
| 170 | 300 mm Dia |
| 171 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc, complete as required. 32 mm dia (OD-32 mm & ID-38 mm |
| 172 | 63 mm dia (OD-63 mm & ID-51 mm |
| 173 | 90 mm dia (OD-90 mm & ID-76 mm |
| 174 | 120 mm dia (OD-120 mm & ID-103 mm |
| 175 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 176 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 177 | Supply of following starter units to replace damaged/ oil cooled starter panels12.5 HP FASD State panel with out enclosure (Enclosure will be measured separately as per item No ---)but with base plate and control fuses. MN typeAC 3 Duty coil voltage 415 V Relay 14-23, with illuminatedpush button station on aluminium dia cast pust button station housing with IP 67 mounted and wired on motor control gear box fabricated out of 16 gauge CRCA sheet steel duly powder coated with handed door and neoprene beading as directed by Engineer in charge. |
| 178 | 20 HP FASD State panel with out enclosure (Enclosure will be measured separately as per item No ---)but with base plate and control fuses. MN typeAC 3 Duty coil voltage 415 V Relay 14-23, with illuminatedpush button station on aluminium dia cast pust button station housing with IP 67 mounted and wired on motor control gear box fabricated out of 16 gauge CRCA sheet steel duly powder coated with handed door and neoprene beading as directed by Engineer in charge. |
| 179 | 30 HP FASD State panel with out enclosure (Enclosure will be measured separately as per item No ---)but with base plate and control fuses. MN typeAC 3 Duty coil voltage 415 V Relay 14-23, with illuminatedpush button station on aluminium dia cast pust button station housing with IP 67 mounted and wired on motor control gear box fabricated out of 16 gauge CRCA sheet steel duly powder coated with handed door and neoprene beading as directed by Engineer in charge. |
| 180 | Supplying and erection of a set of cross bracing Flame work for 11 KV over head line double pole structure having four members fabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height, complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc (as per drawing) and painting with primer and finish paint as required. Set 5677 |
| 181 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. |
| 182 | 2mm Electrical garage rubber mat |
| 183 | A3 Drawing for scheme to Electrical inspectorate as fitted |
| 184 | Smart demand controller with class 0.5 CT\"s and communication protocol Socomec Make Model Diris A302 in /Out Module or similar functions in Schnider/L&T /Risheb Make. With alaram nd staatus indication disply |
| 185 | Supply and providing Multy function meters withPower and Energy paramenters with suitable CT\"s energy mnagement Feeder wise with communicaion port |
| 186 | Supply of service contracting staff during the execution along withthis contrctDismanling/ Alteernation/Modificaation/Reconnection works as well as temprory connection to hindeance free reular shift operation. It has to ensure safe operational envoinment at plant during the entair period of contract. The contrct staaff expected to take instructions from engineer incharge and perform labour works. Electrician |
| 187 | Welder |
| 188 | Fitter |
| 189 | Line man assistant |
| 190 | Charges for preparing drawing of the complete Electrical installation after completion of the present work and preparing completion report with Electrical Inspectorate Department and avail KSEB service connection application form and submitting to the consumer for up grading HT Contract demand up to 260kVAThree phase service connection/Load regularization and Additional CD etc (Actual amount paid on production of Original bill/ Invoice or demand letter from KSEB department) |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy