| 1 | Supply, Installing,Testing and Commissioning in replacement Ultrasonic Level Transmitter at Overhead tank/Underground sump for measurement of level with following specification:- Range : 0-10 metersAccuracy : 0.5 % minimum Supply Voltage : 24V DCOutput : 4-20 mA , 0-10V DC Make: PEPPERL+ FUCHS / NIVELCO / SIEMENS or equivalent as approved by GE |
| 2 | Supply, installation, testing and commissioning in replacementLevel Controller Panel suitable for monitoring of01 Ultrasonic Level Transmitter. The panel should be indoor type, dust and vermin proof, made out of 2mm thick CRCA sheet, mounted on angle iron frame of size 40mm x40mm x 6mm thick and grouted using PCC 1:2:4 or fixed on wall (Make: Universal Switch Gear Control/ABB Automation/Hensel ). The Panel should comprise Water Level Sensing & Display comprising of the following:-(i)7\"Graphical screen mluticolour-01 No, having mimic screen for displaying pictorial/graphical and percentage of water level(Make: SCHNEIDER / SIEMENS/ ABB (ii) SMPS of 5 A rating-01 No (Make: SCHNEIDER / SIEMENS/ ABB (iii) Audio visual alarm indicator:-01 No (Make:-Schneider/ESBEE (iv) Surge Protection device suitable for 230V incoming supply-01 No(v) MCB SPN 32 A -01 No. |
| 3 | Taking out existing ultrasonic level transmitter of any size and taking it to workshop for any fault rectification and making it workable and bringing back to site and install as per direction and satisfaction of Engineer in Charge including all fittings etc. ( NOTE: Spare parts shall be measured and paid separately) |
| 4 | Supply only Ultrasonic peizometer transducer (sensors) made of ceramics of dia 15 mm . |
| 5 | Supply only Printed Circuit Board(PCB) to control transmission of the transmitter to determine size of signal |
| 6 | Supply only Rectifier to convert AC supply to 12 V DC supply. |
| 7 | Supply and Fixing, in replacement 4 pair CAT 6 UTP cable for Sensors complete all as specifed and directedMake : D Link/ Finolex/ Polycab or equivalent as approved by GE |
| 8 | Supply and Fixing, 3 Core 1.5sq.mm. PVC sheathed PVC insulated copper armoured cable complete all as specified and directed. Make: Havells/Polycab/Gloster. |
| 9 | Supply and Fixing, in replacement single phase electrically actuated ductile iron butterfly valve suitable with nominal dia 150mm PN-16, suitable for potable water application, 230 V AC/24 V DC, alongwith starter/control panel, complete wiring, positioner transmitter complete all as specified and directed. Make: As approve by GENOTE: Quoted rate shall be deemed to be inclusive of welding/fixing of flange and making necessary provision for fixing of valve. |
| 10 | Taking out existing single phase electrically actuated ductile butterfly valve of any size and taking it to workshop for any fault rectification and making it workable and bringing back to site and install it as per direction and satisfaction of Engineer - in charge including all fittings etc. (NOTE : Any spare part shall be measured and paid separately excluding nuts,bolts,washers,gasket ) |
| 11 | Supply only Valve disk made of Ductie Iron ASTM A536 with stainless steel edges for longer life of dia 150 mm. |
| 12 | Supply only Upper and Lower Bushing made of 304 Stainless Steel with Teflon coated. |
| 13 | Supply only Digital positioner Transmitter intended to control AC actuators, providing 450 points of resolution with quarter turn actuators ranging from 2 sec to 120 sec and rated for 25% duty or more. |
| 14 | Dismantling existing unserviceable / deteriorated motor starter panel and capacitor panel, removal from site and depositing to MES store yard. Supply, installation, testing and commissioning of indoor typefloor mounting size as per manufacturer\"s design Polycarbonate CPRI approved OEM made Motor Starter Panel suitable for connecting 3 Nos of 100 HP Motor with all system to be included in single Panel, shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel should be anti-acid & anti corrosive. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of board/panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane. The manufacturer of board/panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. |
| 15 | The CPRI report shall have mention of following tests performed and passed out satisfactorily: Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Guarantee and warrantee certificates will be accepted only from original manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing with MC 75for base frame & angle iron 50 x 50 x 6 mm size legs, 04 nos legs 600 mm long, PCC 1:2:4 type B-1 for grouting of base,suitable for 3 phase 415 volts 50 Hz 4 wire AC supply complete all as directed with and incl the following:-(A) : (i) MCB 3 pole, 415 Volts, rating 32 Amps, 10 KA - 3 Set of 04 No. Each (ii) Line contactor, AC 3 duty, 415 Volts, 50 Hz, 225 Amps-03 No.(iii) Digital soft starter suitable for 110 kW motor, 3 phase, 415 Volts, 50 Hz, min Icl 250 amps including one spare power control board of digital starter - 03 No. |
| 16 | (iv) Independant Control supply transformer and fast acting semiconductor fuse of suitable rating for soft starter protection -03 set (v) Resin cast CT 400/5A cast resin base – 03 set of 03 No Each. (vi)Push button ON/OFF, AC 415 Volts 50 Hz - 04 Nos. (vii) LED indication lamp AC, 415 Volts , 50Hz for RYB, ON/OFF, trip - 12 Nos. (viii) Emergency push button OFF - 01 No. (ix) Terminal block suitable for 400A rating with brass contacts for INPUT/OUTPUT termination with 9 ways.(x) 3 Phase 4 wire copper bus bars of suitable length & section not less than 60 x 15 mm covered with coloured heat shrinkable anti track insulation tape of make Denson/ M-seal or equivalent of finished thickness not more than 1mm and fixed on epoxy base post insulator of both dia and height not less than 40mm- 01 set. (xi) Control wiring of push buttons, indicators/ protection circuits contactors, soft starter with 1.5 Sqmm multi strand copper cable, lugs and ferrules- 01 Job as per circuit design complete all as specified and directed. |
| 17 | (B) :(i) MCCB 3 pole, 780 Amps, 415 volts, 50 Hz, Icu- 36 kA, adjustable thermal & fixed magnetic release type - 01 No. (ii) Multifunction digital meter compatible to measure current, voltage, power factor & frequency with 3 lines LCD display in 96 x 96 sqmm flush mounted case, accuracy class 1.0 - 03 No. (iii) Resin cast CT 400/5A cast resin base – 03 set of 03. (iv) LED type phase indicator lamp RYB – 03 set of three. (v) Capacitor duty contactor, 3 phase, 415 volts, 50 Hz, of rating 17.5/18 kVAr – 6 Nos and 12.5 KVAr -6 Nos. Make: L&T/ABB/ Havells or equivalent as approved by GE. (vi) Power factor capacitor, ultra heavy duty advanced APP technology, 3 phase, 440 volt, 50Hz of rating 75 KVAR 0f 3 set with each = (15 KVAr x 3 Nos + 10 KVAr x 3 Nos). Make : EPCOS/ABB/ Havells or equivalent as approved by GE (vii) On/Off push buttons - 04 andselector switches - 04 Nos complete all as specified and directed.Note :(i) All existing and new connections of incoming/outgoing cables shall be done through appropriate size of copper thimbles. (ii) Drawing, circuit diagram and all materials / instruments incl makes etc for starter panel shall be got approved by GE before fabrication. |
| 18 | Dismantalling ofexisting cable and Supply, laying and testing XLPE insulated , screened PVC bedded, galvanised steel strip armoured, heavy duty LT power cables with aluminium conductor, 1100 volts grade cross sectional area400 sqmm 3.5 core including lux of cable, complete all as specified and as directed. |
| 19 | As per the description of serial item No 11 here in above butcross sectional area300 sqmm 3.5 core, complete all as specified and directed. |
| 20 | As per the description of serial item No 11 here in above but cross sectional area240 sqmm 3.5 core, complete all as specified and as directed |
| 21 | As per the description of serial item No 11 here in abovebut cross sectional area95 sqmm 3.5 core, complete all as specified and directed. |
| 22 | Supplyonly in replacement MCCB, triplepole, 400 Amp 415 volts. 50 Hz breaking capacity not less than 35 kA with adjustable thermal and adjustable magnetic protection release with spreader links, Ics = 100% Icucomplete all as specified and as directed. |
| 23 | Supply only in replacement MCCB, triplepole, 250 Amp 415 volts. 50 Hz breaking capacity not less than 25 kA with adjustable thermal and adjustable magnetic protection release with spreader links, Ics = 100% Icu complete all as specified and as directed. |
| 24 | Supply only in replacement MCCB, triplepole, 200 Amp 415 volts. 50 Hz breaking capacity not less than 50 kA with adjustable thermal and adjustable magnetic protection release with spreader links, Ics = 100% Icu complete all as specified and as directed. |
| 25 | Supply only in replacement MCCB, triplepole, 160 Amp 415 volts. 50 Hz breaking capacity not less than 36 kA with adjustable thermal and adjustable magnetic protection release with spreader links, Ics = 100% Icu complete all as specified and as directed. |
| 26 | Supply only in replacement MCCB, triplepole, 100 Amp 415 volts. 50 Hz breaking capacity not less than 36 kA with adjustable thermal and adjustable magnetic protection release with spreader links, Ics = 100% Icu complete all as specified and as directed. |
| 27 | Material and labour, in replacement Thermal Over Load Relay Range, Conforms to IS/IEC 60947-4-1, Protection against overload & phase loss protection, complete all as specified and as directed |
| 28 | Material and labour,in replacementMG21DF Analog Voltage Protection Relay, measurement of Protection Relay, Under Voltage, Over Voltage, Phase Asymmetry, Phase Failure, Phase Sequence, complete all as specified and as directed |
| 29 | Material and labour, in replacementICST 415/220 control transformer for soft starter panel board. |
| 30 | Supply and fixing in replacement 5 to 32 Amps MCB SP 10 KA , C Curve |
| 31 | Supply and fixing in replacement 1 to 5 Amps MCB SP 10 KA . C Curve |
| 32 | Supply and fixingin replacement duty contactor 10 KVAR Inbuilt 1 NO/NC auxiliary contact, complete all as specified and as directed. |
| 33 | Supply and fixingin replacement duty contactor 12 KVARInbuilt 1 NO/NC auxiliary contact , complete all as specified and as directed. |
| 34 | Supply and fixingin replacement duty contactor 15/20KVARInbuilt 1 NO/NC auxiliary contact , complete all as specified and as directed. |
| 35 | Supply and fixing in replacement Heavy Duty Cylindrical Capacitors 7.5 KVAR |
| 36 | Supply and fixing in replacement Heavy Duty Cylindrical Capacitors 10 KVAR |
| 37 | Supply and fixing in replacement Heavy Duty Cylindrical Capacitors 12.5 KVAR |
| 38 | Supply and fixingin replacement Contactor 3 Pole with AC 9 Amps complete all as specieied. |
| 39 | Supply and fixingin replacement Contactor 3 Pole with AC-3, 50 Amps complete all as specieied. |
| 40 | Supply and fixinginreplacement Contactor 3 Pole withAC-3, 140 Amps , complete all as specified and as directed. |
| 41 | Supply and fixingin replacement Contactor 3 Pole withAC-3, 185 Amps , complete all as specified and as directed. |
| 42 | Supply and fixing in replacement HRC Fuse 250/200/150 Amps |
| 43 | Supply and fixing in replacement CT of 300/5 including complete wiring. |
| 44 | Supply and fixing in replacement CT of 200/5 including complete wiring. |
| 45 | Supply and fixing in replacementMulti meter digital type single phase and three phase 110 /240/440 V, complete all as specified and as directed. |
| 46 | Material and labour, for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level connected to galvanised Iron strip of size 32 X 6 mm by means of bolts, nut check nuts and washers earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to test point all as shown in electrical plate No. 3 of SSR - 2009 Part I and including necessary excavation and earth work in any type of soil, 25 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, pit cover of precast RCC (1:2:4), type B-1 reinforced XPM of weight not less than 4 Kg/Sqm and MS frame etc, complete all as specified. NOTES:-(i) The unit rate includes copper earth strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point.(ii) The complete earth system shall be guaranteed to give result less than 1 ohm resistance.(iii) Complete earthing will be redone at no extra cost to department, if result is found below 1 ohm. all as shown in electrical plate No. 5 of SSR Part-I connected to earthing test point all as specified or indicated inculding brazing/testing on completion. |
| 47 | Material and labour, for earth continuity conductor or main earthing lead fixed to wall on batten or recess chases or buried in ground or drwan in conduit/pipe or fixed to poles or any other indicated situation for loop eathing etc. as required using GI strip of 32 X 6 mm |
| 48 | Supply and fixing in replacement worn out small control fuses, indicating lamps, various type of copper lugs, thimbles terminals all as deemed necessary or directed including minor spare parts and components in order to make system serviceable and perfectly in working order |
| 49 | Supply and fixing of door locks suitable for LT Panel/Motor Starter panel of existing type including welding and made to shape all as per specified and directed by engr in Charge. |
| 50 | Material and labour, for preparationpainting after taking shut down with welding work of old rusted LT panel(of any size) and applying two coat of synthetic enamel paintinner and outer surface as per the existing pattern with locking arrangement as existng patternandre writing Panelnumbers complete all as specified and directed by the Engineer in Charge. |
| 51 | Dismantling and taking down existing Motor starter Panel by removing all existing cables and connection and Installing the motor panel in the new location and reconnecting all cables as specified and directed by Engineer-in-Charge. |
| 52 | Supply and fixing in replacement Copper Bus Bar of size 60 X 15 mm in the existing panel as specified and directed by Engineer-in-Charge. |
| 53 | Dismantling and taking down existing unserviceable soft starter from motor starter panels and supply and fixing soft starter 3 phase, 50 Hz, 415 V, Icl current rating 480A, with heat sink , internal bypass, supply voltage limits from 195V to484 V, phase failure and thermal protection, suitable for 220 kW motor, complete all as specified and directed. Make: Schneider/ ABB/Siemens |
| 54 | Dismantling and taking down existing unserviceable soft starter from motor starter panels and supply and fixing soft starter 3 phase, 50 Hz, 415 V, Icl current rating 110 A, with heat sink , internal bypass, supply voltage limits from 195V to484 V, phase failure and thermal protection, suitable for 55 kW motor, complete all as specified and directed. Make: Schneider / ABB/Siemens |
| 55 | Dismantling and taking down existing unserviceable soft starter from motor starter panels and supply and fixing soft starter 3 phase, 50 Hz, 415 V, Icl current rating 170 A, with heat sink , internal bypass, supply voltage limits from 195V to484 V, phase failure and thermal protection, suitable for 90 kW motor, complete all as specified and directed. Make: ABB /Schneider/Siemens |