Military Engineer Services-MES has published Repair / Replacement Of Aerodrome Beacon, R / W Lts, Cable And Other Connected Works For Helipad Services Under Age ( I ) Cif ( K ) . Repair / Replacement Of Aerodrome Beacon, R / W Lts, Cable And Other Connected Works For Helipad Services Unde. Submission Date for this Tender is 13-12-2021. Aerodrome Beacon Tenders in Srinagar Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 20-Nov-2021 | Amendment | BOQ | 06-12-2021 |
2 | 06-Dec-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 13-12-2021 |
Sl. No. | Item Description |
1 | Suppy & Laying including taking out and removing old unserviceable XPLE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area16 Sqmm 4 Core in trenches, through pipe, under culvert or in air, complete all as specifed and directed. |
2 | Suppy & Laying including taking out and removing old unserviceable XPLE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area25 Sqmm 3.5 Core in trenches, through pipe, under culvert or in air, complete all as specifed and directed. |
3 | Supply, Fixing & Laying in repair/replacement 50mm bore GI pipe, light grade, laid in trenches / under floor and fixed to wall and on pole for cable protection, complete all as specified and directed. |
4 | Excavation in trenches in soft/loose soil not exc 1.5 mtr wide and not exe 1.5 mtr in deep and getting out, complete all as specified and directed. |
5 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick, complete all as specified and directed. |
6 | Removal excavated material (soil) to a distance not exe 50 mtr and depositing where directed at a level not exe 1.5 mtr above the starting point, complete all as specified and directed. |
7 | M&L for sand cushioning to underground cable using fine river sand of 8cm thick before layng the cable and 15cm thick after laying the cable, complete all as specified and directed. |
8 | M&L for brick sub class "B" of old size for protection of underground cable, laid across the cable, complete all as specified and directed. |
9 | S&F in replacement elevated bi-directional halogen runway edge lights of colour white/ white or white/ yellow along breakable coupling, gasket, two pin secondary leads, base plate with 6 Nos M-10 stainless steel bolt conforming to ICAO requirement, complete all as specified and directed by Engr-in-Charge. Make : AMA Pvt Ltd/ YPR Engineering and Solution Pvt Ltd/ Three D Integrated Solution Ltd. |
10 | S&F in replacement elevated omni-directional LED taxiway edge lights of colour blue along breakable coupling, gasket, two pin secondary leads, base plate with 6 Nos M-10 stainless steel bolts conforming to ICAO requirement, complete all as specified and directed by Engr-in-Charge. Make : AMA Pvt Ltd/ YPR Engineering and Solution Pvt Ltd/ Three D Integrated Solution Ltd. |
11 | S&F in replacement elevated uni-directional Halogen approach lights of colour white along breakable coupling, gasket, two pin secondary leads, base plate with 6 Nos M-10 stainless steel bolts conforming to ICAO requirement, complete all as specified and directed by Engr-in-Charge. Make : AMA Pvt Ltd/ YPR Engineering and Solution Pvt Ltd/ Three D Integrated Solution Ltd. |
12 | M&L for plain cement concrete 1:4:8, type D-2 (using 40mm graded crushed stone aggragates) as in foundations, filling and mass concrete, complete all as specified and directed. |
13 | M&L for plain cement concrete 1:2:4, type B-1 (using 20mm graded crushed stone aggragates) as in foundations, filling and mass concrete, complete all as specified and directed. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy