Repair / Maint Of Ht Switch Gear ( Vacuum Circuit Breaker ) At Afs Chabua Repair / Maint Of Ht Switch Gear ( Vacuum Circuit Breaker ) At Afs Chabua => Limited, GE (AF) Chabua-Assam

Military Engineer Services-MES has published Repair / Maint Of Ht Switch Gear ( Vacuum Circuit Breaker ) At Afs Chabua Repair / Maint Of Ht Switch Gear ( Vacuum Circuit Breaker ) At Afs Chabua => Limited. Submission Date for this Tender is 29-11-2021. Circuit Breakers Tenders in GE (AF) Chabua Assam. Bidders can get complete Tender details and download the document.




Tender Notice

29860173
Repair / Maint Of Ht Switch Gear ( Vacuum Circuit Breaker ) At Afs Chabua Repair / Maint Of Ht Switch Gear ( Vacuum Circuit Breaker ) At Afs Chabua => Limited
Open Tender
Indian
Assam
GE (AF) Chabua
29-11-2021

Tender Details

Repair / Maint Of Ht Switch Gear ( Vacuum Circuit Breaker ) At Afs Chabua Repair / Maint Of Ht Switch Gear ( Vacuum Circuit Breaker ) At Afs Chabua => Limited

Key Value

Document Fees
Refer document
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work: Repair/maint of HT switch gear (Vacuum circuit breaker) at AFS Chabuaunder GE (AF) Chabua
Sl. No. Item Description
1Taking down HT switch gear (Vacuum circuit breaker ) of capacity11 KV 250/350 MVAcomprising of following repairs, overhauling, servicing and refixing the same after repairs/ overhauling: (Qty- 02 Job) (a) Tripping off the breaker, lowering the breaker with raising/lowering handle and pulling out the breaker complete from the panel along with the trolley for servicing/inspection/ overhauling. (b) Servicing/Inspecting/checking of automatic safety shutter operation for serviceability and replacement of spares if required. (c) Servicing/Inspecting/checking ofcircuit spoutand circuit spout connections for RYB phases and replacement of spares if required. (d) Dismantling and checking of cross bar assembly, fixed contacts and current carrying parts of the breaker, trolley, insulated assembly and checking lamination with clamps, epoxy spout, isolator assembly etc. (e) Setting, reassembling, cleaning, adjustment of fixed contacts, main contact, arcing contacts and chamber baffle pot assembly, moving contact for proper setting of auxiliary contacts operating mechanism. (f)Servicing/Inspecting/checking ofsecondary sockets/bus bar earthing plugs/earthing sockets and replacement of spares if required. (g)Checking, setting and adjustment of lowering and raising operation of the breaker trolley. (h)Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating and closing of shutter gear, isolation resistance of trolley of with vacuum interrupter assembly. j) The inspection of HT switch gear shall involve:- (i) Inspection of truck & hoist assembly. (ii) Inspection of tank assembly & barriers. (iii) Inspection of assembly & components of solenoid assembly. (iv) Inspection of assembly & components of dependent mechanism.
2(v)Inspection of assembly & components of spring box mechanism. (vi)Inspection of motor mechanism spring charge assembly (vii)Inspection of assembly of trip unit & related components Notes: (i) The rate quoted shall be deemed to include for necessary T&P, nuts, bolts, washers, gasket, insulation tape, compound, painting of VCB panels with approved colour all as per existingetc. to put in to the VCBs and panels in serviceable condition, testing and commissioning all as specified and as directed by the Engineer-in-Charge. (ii) Major spares like Breaker bushings, vacuum interrupter assly, bus bar spout, bus bar spout connections, circuit spout/circuit spout connections/buffer fixed contacts, moving contacts, tank assly/barriers, solenoid spares, dependent/spring mechanism/ motor mechanism, trip unit etc will be measured and paid separately under relevant items of Schedule "A". However the rate quoted shall be deemed to include for any other minor spares require replacement.(ii) the servicing shall be carried out by Auhtorised service centre as approved by GE
3S & F in repair 110V DC tripping coil for 11 KV VCB complete all as specified.(Qty -01 Each)
4S & F in repair 3 phase selector switch for VCB complete all as specified and directed. (Qty -01 Each)
5S & F in repair monoblock diode 25 Amp for VCB complete all as specified and directed. (Qty -01 Each)
6S & F in repair spout fixed assembly for VCB complete all as specified and directed. (Qty -01 Each)
7S & F in repair of epoxy body for interrupters container for VCB complete all as specified and directed. (Qty -01 Each)
8S & F in repair vaccum interapture 400 A suitable for VCB complete all as specified and directed. (Qty -01 Each)
9Note:- (a)Old u/s retrieved material will be theproperty of the repairer/bidders. The bidders has quoted the job order considering the cost of retrieved material for Rs. 141. 00 Ser No. 1 to 1 isone job.