Corrigendum : Retrofitting Of Block-A Consisting Office Of Commissioner, Deputy Commissioner, Adc, Sdm, District Food And Supply Controller For Persons With Disability At Dac, Patiala (Providing 1 No. Lift And Upgradation Of 1 No. Existing Lift)
Amendment in Specification of Vision Panel in Lifts
Other
23-11-2021
2
20-11-2021
Date Extend
Date
23-11-2021
Name of Work:RETROFITTING OF BLOCK-A CONSISTING OFFICE OF COMMISSIONER, DEPUTY COMMISSIONER, ADC, SDM, DISTRICT FOOD & SUPPLY CONTROLLER FOR PERSONS WITH DISABILITY AT DAC, PATIALA (PROVIDING 1 NO. LIFT AND UPGRADATION OF 1 NO. EXISTING LIFT)
Sl. No.
Item Description
1
15 PASSENGERS MACHINE ROOM LESS LIFTS (WIDE):15 PASSENGERS MACHINE ROOM LESS LIFTS (WIDE):
2
Type and Capacity :Approximately 1020 Kg( Wide) , 15 Passengers Lift without Machine RoomSpeed: 1.0 Meter per secondType of drive: AC Variable Voltage Variable Frequency with 16-Bit Microprocessor.Motor: Permanent Magnet Gearless Machine to be hoisted on the top of guide rail within the elevator hoist wayTravel: Approximately 15.6 Meter (Ground to Fourth Floor) Serving: 5 Floors 5 Stops 5 Openings5 Levels (All on the same side) Hoist way : 2600mm (Wide) x 1900mm (Deep) Clear dimensions Headroom Height (HR):5000mm beyond finished floor level of last landing Pit Depth : 1800 mm below the finish floor level of first landing Car Size Area: Minimum 2.35 square meter & Maximum 2.47 square meter Car Enclosure : Constructed out of stainless steel finish panel in Scratch Resistance/ Vandal proofCar Entrance: Center Opening Automatic Doors with vision panel(40% area should be visible by glass) of Stainless steel finish panel in Scratch Resistance/ Vandal proof with a clear opening of 900mm (wide) x 2000mm (high)
3
Hoist way Entrance: Center opening Automatic Door\"s with vision panel (40% area should be visible by glass) of Stainless steel finish panel in Scratch Resistance/ Vandal proof with provision of emergency key opening at landings with a clear opening of 900mm (wide) x 2000mm (high) Door operation : Automatic DC Door operation with adjustable door opening and closing timingsControl: Simplex full selective collective control with and without attentdent Operation: Automatic Power Supply: 415 Volts, 3- phase, 50Hz Alternating Current Flooring: Floor Skid - Resistant as per standardFan: Blower Fan in Car for ventilation with Auto cut offLighting: LED for Car Lighting Indicators: LED Dot matrix / Digital 3 segement direction and position indicators in the car and at all landingsHand Rail: Stainless Steel round Hand rail not less than 600mm long at 900mm above floor level (Side LH,Side RH & Rear) and should be palced adaject to control panel.Call Button Height: Call button (Outside the lift) placed at a height between 800mm-1meter from the floor levelControl Panel Height: Control panel placed at a height between 800mm-1meter from the floor level
4
Other Features : 1. Battery operated emergency light with rechargeable battery 2. Battery operated emergency alarm with rechargeable battery 3. Adjustable Guide shoes4. Micro movement LED based buttons 5. Door Open and Close buttons6. Emergency Intercom provided inside the elevator 7. Emergency Intercom usable without the voice communication 8. Load weighing device with overload bypass feature and Overload function with Audio Visual Indication 9. Steel items, door frames sill angle\"s, fascia plates, spring buffers10. Automatic phase reversal device and Phase Failure protection11. Call registration 12. Audio & Video System installted in the lift indicating arrival at a floor 13. Manual break lever 14. Additional car gate lock
5
15. Automatic break testing infrared safety curtain. 16. Braille Buttons (Inside and outside) with Braille instructions for the communication system17. Kick plate/Skirting18. Lift anoucement system to announce floor level\"s in english language only and indication of door for entrance / exit is either Open or Close.19. Car Operating Panel 20. Car plateform constructed out of cold rolled grain oreinted formed sheets of steel 21. Phase two device fire man drive22. Fire Man switch at main lobby23. Car false ceiling in stainless steel 24. Pit ladder25. Anti Nuisance car call protection26. Door Nudging27. Automated Resuce Device to bring the elevator to the nearest landing in case of power failure.28. The provision of the mirror on the wall of the lift car opposite the lift door not extend below 900mm from the lift floor to avoid confusing people with impaired sight.29. The emergency communication system should be coupled with an induction loop system installed all around the lift. Telephone units where provided should have an inbuild inductive coupler to assist person using hearing aids.Make: OTIS, KONE,Hitachi,Mistubishi
6
Modification of existing 8 Passanger lift Installed in DAC Complex at patiala with following scope of work:-? Car rails? Counterweight rails? Counterweight frames and fillers.? Hoisting Machine unit? Controller? Signalization? Elevator Car Cabin? Car Sling, OSG & Safety gear? Car Door? All Landing doors?The provision of the mirror on the wall of the lift car opposite the lift door not extend below 900mm from the lift floor to avoid confusing people with impaired sight.?The emergency communication system should be coupled with an induction loop system installed all around the lift. Telephone units where provided should have an inbuild inductive coupler to assist person using hearing aids.complete in all respects as approved and desired by the Engineer-in-charge at site.Make:-Kone