Augmentation Of Tube Wells Equipments At Panchmukhi Lal Kuan And H-Block, D-Block Lal Kuan And Vishwakarma Colony Under Tughlakabad Constituency.-S / I / T / C Of Pump Sets With Allied Equipments For Water Hydrant, Operated From Water Emergency At Sarita Vihar By Carrying Out The Following Works:- 1. S / O. Sub. P / Set Of High Discharge Of 15 Hp With Dynamically Balanced Motor, Vibration Free Total Enclosed Motor Fitted Squirrel Cage Induction Motor, Water Lubricated Thrust Bearing, Fitted With S.S. Impeller Mounted On Stainless Steel Shaft Of Following Parameters Having 2900 Rpm, Suitable To Operate On 3 Phase 415 Volt 50 Hz, A.C. Supply. Head In Meters Approx.- 20-29 Mtr. Discharge In Lpm – 1800-1500. No Of Stages- 02 . Delivery Size – 100 Mm Make- Bs / Skope / Great India / Kirloskar / Su / Lubi / Djb Approved. 3 Nos. 2. S / O Hut Type Electrical Feeder Panel Of Welded Construction Of Size 1370Mm X 760Mm X 460Mm Fabricated With Suitable Size Ms Angle Iron With 16 Swg M.S. Sheet, Having Horizontal And Vertical Intermediate Chamber Of Suitable Size On Suitable Size Insulating Board To Make The Panel Robust, Having Double Door And S.S Hinges Along With Double Locking Arrangement, Having Fabricated Ms Angle Iron Frame For Mounting Of Switch Gears Such As Rccb, Mccb, Ryb Indicating Lights, Selector Switch, Ampere Meter, Volt Meter And Electrical Energy Meter Etc I / C Painting Having Following Items. ( A ) Mccb 63 Amp, 4 Pole, Breaking Capacity At 415 V: 16 Ka, Adjustable Thermal Setting ( 70- 100% ) And Fixed Magnetic Settings. Confirms To Iec: 60947-Ii / Is: 13947-Ii. Make- L&T / Havells / C&S / Schneider / Djb Approved. ( B ) Rccb 63 Amp, 4 Pole With Earth Fault Indicator And Positive Contact Indication Protecting A Circuit Automatically In The Event Of Earth Leakage, Sensitivity: 300 Ma, Confirms To Iec: 61008-I / Is: 12640-I. Make- L&T / Havells / C&S / Schneider / Djb Approved. ( C ) Fully Automatic Star Delta Starter Of 15Hp, 3Phase Oil Immersed Type. Make- Bentex / Capital / L&T / Havells / Djb Approved. ( D ) Ampere Meter 96Mmx96mm Square Shape Of 0-40 Amp Range. Make-Ae / Bentex / Capital / Djb Approved. ( E ) Voltmeter Of 96Mm X 96 Mm Square Shape Of 0-500 Volt Range With Selector Switch, Make-Ae / Bentex / Capital / Djb Approved. ( F ) Led Indicating Lamps With Fitting ( A Set Of 3 Lamps ) ( G ) Shunt Capacitor Of 05 Kvar Mpp Type With Three Phase Isolator With Suitable Banking. Make-L&T / Havells. ( H ) Motor Protection Assembly Having Earth Leakage Protection, Phase Sequence Corrector, Single Phasing Protection, Over Load Protection, High Voltage-Low Voltage Protection. Time Delay Power On Programmable Time Switch ( I.E. Ryb Phase & Facility To Change Over From Automatic To Manual & Vice Versa ) Up To 15 H.P. Make- Gain Guard / Skope / Djb Approved. Complete Wiring Of Panel Board & Installation Of Electrical Accessories In The Panel With Required Copper Conductor Wire &Thimblingetc As Required. The Panel Board Shall Be Mounted On The Base Frame Of 2 Feet Height Made Of 50X50x6mm Angle Iron Frame. 2 Nos. 3. S / O Pvc Insulated & Pvc Sheathed Flat Cable With Plain Copper Conductor Having 6 Cores 6Sq. Mm Size For Submersible Motor. ( Each Drum Of 500 Mtrs ) Note- Each Drum Contains 500 Mtr Continuous Cable. Make:- Polycab / Havells / Grandley / Gloster / Djb Approved. 1000 Mtr. 4. Laying Of Overhead Cable From Water Emergency At Pocket-J, Je ( Civil ) Store To Pump Sets Installed At Pocket-J Sarita Vihar Reservoir At Booster Pumping Station. 1 Job 5. S / O Of Double Flange G.I. Column Pipe 100 Mm Dia., Medium Class, Each Of 3Mtrs Long Duly Threaded On Both Ends, Welded & Fitted With G.I. Flange On Both Ends Welded With Three Nos. Support Strip At Each End Between Flange And Pipe, With Two Slots For Sub Cable In Each Flange. Make Of Pipe: Tata / Jindal 12 Nos. 6. S / O Tail Piece Of The Medium Class G.I. Pipe 500 Mm Long With One End Threaded As Per Outlet Of Pump & Another End Flanged As Per Size Of G.I. Pipe 100 Mm Dia. Make Of Pipe: Tata / Jindal 2 Nos. 7. S / O G.I. 90 Degree X 100 Mm Dia. Bend Having Flange At Both Ends ( Heavy Duty ) . 6 Nos. 8. S / O M.S. Clamp Of 1500 Mm Length Duly Fabricated From 12.5 Mm Thick 75 Mm Wide M.S. Plate For Holding The Pipe Of 100 Mm Dia 2 Set 9. Supply Of Ms Full Threaded Nut Bolts Off Sizes As Per Site Requirement. 25 Kg. 10. Supply Of Rubber Packing For 100 Mm Dia. Flange ( 3 Mm Thick ) 20 Nos. 11. Supply Of Starter Oil .Make:- Bentex / Capital. 10 Ltrs. 12. Supply Ci D / F Non Return Valve Of Size 100 Mm Dia., As Per Is 5312 ( Part 1&2 ) Pn 1.0 Ci Body, Door / Bronze To Rubber Rings / Ss410 Hinge Pin Construction Make: Ivc / Kirloskar 2 Nos. 13. Supply Ci D / F Sluice Valve Of Size 100 Mm Dia., As Per Is 5312 ( Part 1&2 ) Pn 1.0 Ci Body, Door / Bronze To Rubber Rings / Ss410 Hinge Pin Construction Make: Ivc / Kirloskar 2 Nos. 14. Installation Of Submersible Pump Set By Lowering Of P / Set In Sump With All Allied Above Items.Work Also Includes Fixing / Fitting Of All Above Items Such As G.I Pipe, Bend, Tail Piece, Clamp, Rubber Packing, Nut Bolts Etc.This Includes Installation And Grouting Of Panel Board With All Electrical Wiring & Cabling At Site. All Tools & Tackles I / C Tripod Chain Pulley Blocks Etc. Shall Be Arranged By The Firm. This Includes Testing & Commissioning Of T / Well On Load At Site I / C Cartage, Loading & Unloading Of Material. All Required Civil Work Included In The Scope Of Work