| Sl. No. | Item Description |
| 1 | Total amount of SCHEDULE \"A\" PART-I A (BUILDING WORK) (For details see Schedule \"A\" Part-I A in PDF folder) |
| 2 | SCHEDULE \"A\" PART-I B (BUILDING WORK) |
| 3 | Constructionof PEBmaintenancehangar with crane girder of size 75 MX50 M X 12.5 Mheight with 3 mm dia aluminium mesh of Bird proofing andRCC footing and foundation including 02 Nos electrically operated sliding door in full width at gable ends with civil wall / window upto 3.00 m height incl. painting and hanger PCC flooringand supply and laying of 4 mm thick Epoxy flooring etcas specifiedetc withpermanent specification in soft/ loose soil, incl pile foundation with side annexe D/S asshown in drawings all as specifiedand directed. (GROUP - II) |
| 4 | Total amount of SCHEDULE \"A\" PART-II (INTERNAL WATER SUPPLY) (For details see Schedule \"A\" Part-II in PDF folder) |
| 5 | Total amount of SCHEDULE \"A\" PART-III-A (INTERNAL ELECTRIFICATION) (For details see Schedule \"A\" Part-III-A in PDF folder) |
| 6 | Sch \"A\" PartIII-B (INTERNAL ELECTRIC SUPPLY) |
| 7 | M&L for circuit/submain wiring alongwith with 2x2.5 Sq mm + 1x2.5 Sqmm single core, multi stranded PVC insulated, unsheathed copper conductor cable,multi stranded FR grade conforming to IS 694 drawn in and including rigid metallic stove enamelled steelconduit concealed/surface of size 25 mmdia or higher medium grade ISI marked complete with allconduit accessories / fittings incl MS clamps suitable to hold the conduit on the angles/channels etc. of the hanger\"s structural members on surface/ recessed as per site requirement complete all as specified and directed. |
| 8 | S&F high bay luminaire direct die-cast aluminium non integral with IP66 protection suitable for Industrial applications, high energy saving 200 watt,IP-66 in high pressure die cast aluminium housing, tempered glass, suspended mounting, operating voltage 220V-240V,50Hz,system, efficiency > 100 Lm/W complete all as specifed and directed.Make : Havells Cat No. JETA VALOUR HB200WLED757MODWBLTG/ Philips BY416 NI Maxolid LED Lights, 210 W or equivalent in Crompton/Bajaj. |
| 9 | M&L for Point wiring with 1.5 Sq mm single core, multi stranded PVC insulated, unsheathed copper conductor cable in and including non metallic rigid PVC concealed conduit medium grade not less than20 mmdia or higher medium grade ISI marked complete with allconduit accessories / fittings and sunk CI or 1.2 mm thick pressed steel terminal switch boxes with 3 mm thick plastic laminated hard glossy surface sheet top cover, concealed in wall including earth wire continuous of PVC insulated, unsheathed (green colour) 1.5 Sq mm copper conductor, PVC insulated connected to all fittings, sunken boxes and common earth, earth dolly. Plastic laminated sheet screwed with brass screws, cup washers complete all as specified and directed for the following :- |
| 10 | (a) One light point controlled by one way switch 5/6 Amps |
| 11 | (b) One fan point controlled by one way switch 5/6 Amps |
| 12 | (c)6 Amps 5 Pin Socket on same board controlled by one switch |
| 13 | (d)6 Amps 5 Pin Socket on independent board controlled by one switch |
| 14 | M&L for Point wiring with 2.5 Sq mm single core, multi stranded PVC insulated, unsheathed copper conductor cable in and including non metallic rigid PVC concealed conduit medium grade not less than25 mm dia or higher medium grade ISI marked complete with allconduit accessories / fittings and sunk CI or 1.2 mm thick pressed steel terminal switch boxes with 3 mm thick plastic laminated hard glossy surface sheet top cover, concealed in wall including earth wire continuous of PVC insulated, unsheathed (green colour) 2.5 Sq mm copper conductor, PVC insulated connected to all fittings, sunken boxes and common earth, earth dolly. Plastic laminated sheet screwed with brass screws, cup washers complete all as specified and directed for the following :- Note :- Switch, Socket out let etc will be paid and measured separately. |
| 15 | M&L propeller type, 230 Volts,exhaust fan 300 mm sweep metallic body with safety guard complete (Exhaust fan) with louver shutter complete including M&L for providing/cutting the round hole of required size in wall finishing the same supply and grouting the ragged bolts in wall, fixing the frame on the exhaust side (outer surface of the wall) and connecting with and including PVC insulatedthree core 23/.0076 copper cable, rubber insulated from ceiling rose to exhaust fan motor and writing MES No with black syntheticenamel paintcomplete all as specified and directed. Make :- Havells Ventil Air - DB or equivalent in Usha/ Crompton |
| 16 | Supply and fix energy efficientfive star rated ceiling fan 1200 mm sweep with three fan blade, canopy,down rod etc complete including necessary connection with PVC insulated 3 core 23/0.0076 copper cable from ceilling rose to ceiling fan and writing MES No with black synthetic enamel paint 2.0 CM high complete all as specified and directed. Make :- Havells ES-50 or equivalent in Usha/Crompton |
| 17 | S&F batton holder with PVC insulated body angular/straightfixed on plastic laminated sheet cover round shape 3mm thick including one No 9 watt LED Lamp complete all as specified and directed. |
| 18 | S&F wall mounted LEDbattenwith1X18 Wcomplete with polycabonate housing & integrated electronic driver duly connected with PVC insulated 3 core 1.5 sqmm copper cable from ceiling rose to the fittingall as specified and directed. MAKE- HavellsCat Part LUMILINEBS18WLED or equivalent in Bajaj/Crompton. |
| 19 | Supply & fixing security light fitting suitable for 45 watt LED, pressure die cast housing with toughned glass and individual high power LEDs with secondary optics,IP 66 protection and impect resistance of IK07, with M&L GI pipe mounting bracket of size 25/32 mm dia and 1.20 m long fixed to wall with andincluding nut, bolts and GI clamps of size 50 x 6 mm as required including two coats of synthetic enameled paint over a coat of primer and making connection with three core 23/.0076 rubber insulated copper cable from ceiling rose to connector of street light complete all as specified and directed.Make – Havells Cat Pt No ENDURAPEARLNEOSL45WLED or equivalent make of Bajaj/Crompton. |
| 20 | Supply & fixing Porch light fitting, 42W LED flat panel for surface mounting and making connection with three core 23/.0076 rubber insulated copper cable from ceiling rose to the fitting complete all as specified and directed.Make –Havells Cat Pt No PLUTOSURFACE4X1PLS42WLED or equivalent make of Bajaj/Crompton. |
| 21 | Supply & fixing Mirror light fitting, surface/ wall mounted LED batten 10W with Aluminum housing & integrated electronic driver having THD<20%. with diffuser and making connection with three core 23/.0076 insulated copper cable from ceiling rose to the fitting complete all as specified and directed.Make –Havells Cat Pt NoLUMILINEPLUSBS10WLED or equivalent make of Bajaj/Crompton. |
| 22 | Supply and fix sheet metal enclosure for Distribution board double door TPN, 415 Volts, 8 Way, Vertical type, with bus bar, netural link,blanking plates suitable for Incomer MCCB all as specified and directed. Make : Havell Cat No DHDLVDOBGSFE08 or equivalent in Indoasian/ Legrand. |
| 23 | Supply and fix sheet metal enclosure for Distribution board double door,Load Line,TPN,415 Volts, 4 Way,Vertical type,with bus bar,netural link,blanking plates suitable for Incomer AS MCCB complete all as specified and directed. Make : Havell Cat No as per DHDLVDOBGSFE04 or equivalent in Indoasian/ Legrand. |
| 24 | Supply and fix, sheet metal enclosure for DB\"s, when MCB\"s to be used, TPN, 415 Volts, 8 way, double door type complete all as specified and directed. |
| 25 | Supply and fix, sheet metal enclosure for DB\"s, when MCB\"s to be used, TPN, 415 Volts, 4 way, double door type complete all as specified and directed. |
| 26 | Supply and fix, sheet metal enclosure for DB\"s, when MCB\"s to be used, SPN, 230 Volts, 12 way, double door type complete all as specified and directed. |
| 27 | Supply and fix, sheet metal enclosure for DB\"s, when MCB\"s to be used,SPN, 230 Volts, 4 way, double door type complete all as specified and directed. |
| 28 | Supply and fix MCCB, 415 Volts, 125 Amps, 4 Pole 16 KA complete all as specified and directed. |
| 29 | Supply and fix MCCB, 415 Volts, 40 Amps, 4 Pole 10 KA complete all as specified and directed. |
| 30 | Supply and fix MCB TPN, 415 Volts, 63 Amps, 10 KA complete all as specified and directed. |
| 31 | Supply and fix MCB TPN, 415 Volts, 32 Amps, 10 KAcomplete all as specified and directed. |
| 32 | Supply and fix MCB SPN, 230 Volts, 40 Amps,10 KAcomplete all as specified and directed. |
| 33 | Supply and fix MCB SPN, 230 Volts, 6-32 Amps, 10 KAcomplete all as specified and directed. |
| 34 | Supply and fix MCB SP, 230 Volts, 6 to 32 Amps, 10 KAcomplete all as specified and directed. |
| 35 | Supply, Installing, testing & commissioning and testing of Fabrication of LT indoor 5 segmentCubical panel Board with vertical bus chamber made by CPRI approved fabricator of suitablesize made of 2.0 mm thick CRCA sheet and framing with 40x40x6mm angle iron, floor mounting type, with 400 Amps copper bus bar, powder coated painted including internal wiring complete with suitable size copper cable/strip as required or as per manufacturer\"s recommendation with following accessories ( Hanger Panel No-1):-Incoming(a)MCCB 250 Amps,D Frame4 poles Icu 25 KA (Ics=75%Icu) thermal and Magnetic adjustable between 70-100%-01 |
| 36 | INSTRUMENTATION:- THE INNER CUBICLE SHALL CARRY THE FOLLOWING :(a) Digital Panel multi function meter to measure current voltage, frequency & power factor having programmable CT ratio(CT ratio should be equal to the rated current carrying capacity of incomer MCCB) & built in selector switch of size 96mmx96mm accuracy class 1.0 suitable to work on auxiliary power supply of 240 Volts AC with back up protection by 2 amp MCB SR (Make and model of digital multi function meter be specified) 01 Nos – Digital voltmeter with built in selector switch.(b)Indicating lamps 22.5 mm dia LED type, 240 Volt AC at the incomer of the unit to show three phase availability at the outgoing of incomer with back up protection by 2 Amp MCB.01 Nos – Digital Ammeter with built in selector switch.(c) Inspection lamp 50 Watt with movable non-ferrous chromium plated arm fitted on topside of inner shell 01 Set- 600/5 CTs 15VA class (for AMP meter). |
| 37 | (d)3 Nos. LED type RYB indicating lamps with 2 Amps MCB’s.(e) 2 Nos. LED type on/off indication lamp. OUTGOING (Adjustable settings)(a) MCCB 4 POLE 415 VOLTS grade 100 AMPS rating Icu=10KA (Ics=100%Icu) thermally adjustable between 70 to 100 % rupturring capacity-03 Nos(b) MCCB 4 POLE 415 VOLTS grade 40 AMPS rating Icu=10KA (Ics=100%Icu) thermally adjustable between 70 to 100 % rupturing capacity-01 Nos |
| 38 | Supply, Installing, testing & commissioning and testing of Fabrication of LT indoor 5 segmentCubical pannel Board with vertical bus chamber made by CPRI approved fabricator ofsuitable size made of 2.0 mm thick CRCA sheet and framing with 40x40x6mm angle iron, floor mounting type, with 350 Amps copper bus bar, powder coated painted including internal wiring complete with suitable of size copper cable/strip as required or as per manufacturer\"s recommendation with following accessories(Hanger Panel No-2)Incoming(a)MCCB 200 Amps,D Frame4 poles Icu 25KA (Ics=75%Icu) thermal and Magnetic adjustable between 70-100%-01 |
| 39 | INSTRUMENTATION:- THE INNER CUBICLE SHALL CARRY THE FOLLOWING :(a) Digital Panel multi function meter to measure current voltage, frequency & power factor having programmable CT ratio(CT ratio should be equal to the rated current carrying capacity of incomer MCCB) & built in selector switch of size 96mmx96mm accuracy class 1.0 suitable to work on auxiliary power supply of 240 Volts AC with back up protection by 2 amp MCB SR (Make and model of digital multi function meter be specified) 01 Nos – Digital voltmeter with built in selector switch.(b)Indicating lamps 22.5 mm dia LED type, 240 Volt AC at the incomer of the unit to show three phase availability at the outgoing of incomer with back up protection by 2 Amp MCB.01 Nos – Digital Ammeter with built in selector switch.(c) Inspection lamp 50 Watt with movable non-ferrous chromium plated arm fitted on topside of inner shell 01 Set- 600/5 CTs 15VA class (for AMP meter). |
| 40 | (d)3 Nos - LED type RYB indicating lamps with 2 Amps MCB’s(e) 2 Nos - LED type on/off indication lamp.OUTGOING (Adjustable settings)(a) MCCB 4 POLE 415 VOLTS grade 100 AMPS rating Icu=10KA (Ics=100%Icu) thermally adjustable between 70 to 100 % rupturring capacity-02 Nos(b) MCCB 4 POLE 415 VOLTS grade 40 AMPS rating Icu=10KA (Ics=100%Icu) thermally adjustable between 70 to 100 % rupturing capacity-01 Nos |
| 41 | M&L for testing and Earthingcomplete with steel earth plate elecrode of size 60×60cm× 3.15mm thick , buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to GIearthstrip 32 mm x 6 mmby means of bolts, nuts, check nuts and washers of brass or HS steel all as shown in electrical plate No. 3 connected to earthing test point and and necessary excavation and earth work PCC (1:2:6) type C-1 with suitable size of CI cover plate with angle iron frame and opening arrangement ) incl providing charcoal or coke and common salt in alternate layer of 15 cm compacted thickness all aroundthe earth electrode with funnel and 20 mm bore galvanized iron watering pipe ( light grade) wire mesh, copper lugs, complete in all respect,protected by 25 mm bore (light grade) galvanized iron pipe up to earthing test point as directed, incl disposal of spoil to a distance not exc 50 mtr and necessary testing on completion complete all as specified and as directed by the Engineer-in-charge. |
| 42 | M&L for testing and Earthingcomplete with steel earth plate elecrode of size 60×60cm× 3.15mm thick , buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to GIearthwire 4.0 mm diaby means of bolts, nuts, check nuts and washers of brass or HS steel all as shown in electrical plate No. 3 connected to earthing test point and and necessary excavation and earth work PCC (1:2:6) type C-1 with suitable size of CI cover plate with angle iron frame and opening arrangement ) incl providing charcoal or coke and common salt in alternate layer of 15 cm compacted thickness all aroundthe earth electrode with funnel and 20 mm bore galvanized iron watering pipe ( light grade) wire mesh, copper lugs, complete in all respect,protected by 25 mm bore (light grade) galvanized iron pipe up to earthing test point as directed, incl disposal of spoil to a distance not exc 50 mtr and necessary testing on completion complete all as specified and as directed by the Engineer-in-charge |
| 43 | M & L for submain wiring alongwith earth wire PVC insulated, stranded copper conductor in PVC conduit size of PVC Cable 2 single core 4 sqmm+1x4.0 sqmm earth wire complete all as specified and directed. (For AC) |
| 44 | M & L for submain wiring alongwith earth wire PVC insulated, stranded copper conductor in PVC conduit size of PVC Cable 2 single core 6 sqmm+1x6.0 sqmm earth wire complete all as specified and directed. (For DB) |
| 45 | M & L for submain wiring alongwith earth wire PVC insulated, stranded copper conductor in PVC conduit size of PVC Cable 4 single core 6 sqmm+2x4.0 sqmm earth wire complete all as specified and directed. (Ground floor Annexe DB to 1 St Floor Main DB) |
| 46 | S&F sheet metal enclosure, SPN,240 Volts with a two pin and earth plug and socketand one No MCBs 20 amp, complete all as specified and directed. |
| 47 | Supply & fixing on columns/wall testing and commissioning low noise air circulator 600 mm sweep with powerful heavy duty motor 440 rpm with double wall bearing to give minimum free air delivery of 270 cubic meter per minute with aluminum alloy one place blades including sturdy close mesh guard and having suitable arrangement for 90 degree oscillation and vertical adjustability of 22 degree to 45 degree and suitable for 230 volts single phase 50Hz. AC including separate three regulator complete confirming to IS 2997 and ISI marked complete all as specified and directed. Make : Bajaj /Crompton / Almonard. |
| 48 | Supply and fix pedestal fans 230 volts single phase oscillating 600mm sweep,1400 rpm,plastic blade, Iron body complete all as specified and directed. Make : Crompton VortexACV0RTEX24PF or equivalent in Bajaj/Usha/Almonard |
| 49 | Total amount of SCHEDULE \"A\" PART-IV (SITE CLEARANCE AND EARTH WORK) (For details seeSchedule \"A\" Part-IV in PDF folder) |
| 50 | Total amount of SCHEDULE \"A\" PART-V (HARDSTANDING) (For details seeSchedule \"A\" Part-V in PDF folder) |
| 51 | Total amount of SCHEDULE \"A\" VI-A (DISPERSAL AND LINK TAXI TRACK) (For details seeSchedule \"A\" Part-VI-A in PDF folder) |
| 52 | Sch \"A\" Part VI-B (DISPERSAL AND LINK TAXI TRACK) |
| 53 | M&L for applying thermoplastic reflactive paint as in road marking of minimum 2.5 mm thick single coat of 100/150 mm wide, using HOT MARK thermoplastic paint HOT application white or golden yellow by indigenous modern road marking machine complete all as specified and directed. |
| 54 | Total amount of SCHEDULE \"A\" VII-A (SEWAGE DISPOSAL) (For details seeSchedule \"A\" Part-VII-A in PDF folder) |
| 55 | Sch \"A\" PartVII-B (SEWAGE DISPOSAL) |
| 56 | Construction of Soakage wells exc, in any typeSoil, Foundation in PCC 1:3:6, wells of Honey combed and solid in M-25 Concrete, including intercepting chamber, screen chambermade ofBrick work in CM, RCC cover slab in M-25/ SFRC cover ,interconnecting pipes of RCC/DWC complete filled with brick bats of size 3.60 M dia X 4.50 M effective depth etc complete all as specified and directed. |
| 57 | Construction of RCC Septic tankfor 50 users,designed to carry sewage and sludge water,excavation in any type soil P.C.C 1:4:8 below foundation, RCC M-30Design mix in walls, Base Slab, Baffle walls and Roof Slab including beam with Vent shaft , Man hole opening with cover connection complete with effective depth of 1.50m and overall depth of 3 meterconventional type etc complete all as specified and directed. |
| 58 | Total amount of SCHEDULE \"A\" VIII (AREA DRAINAGE) (For details seeSchedule \"A\" Part-VIII in PDF folder) |
| 59 | Total amount of SCHEDULE \"A\" IX-A (ROAD, PATH & CULVERT) (For details seeSchedule \"A\" Part-IX-A in PDF folder) |
| 60 | Sch \"A\" Part IX -B (ROAD, PATH & CULVERT) |
| 61 | M&L for applying thermoplastic reflactive paint as in road marking of minimum 2.5 mm thick single coat of 100/150 mm wide, using HOT MARK thermoplastic paint HOT application white or golden yellow by indigenous modern road marking machine complete all as specified and directed. |
| 62 | Construction of RCC slab culvert 600mm span and 7.0 mtr long, 450mm depth complete all as specified and shown on drawings TD/027 sheet 1/4 to 4/4. |
| 63 | Construction of RCC slab culvert 600mm span and 7.0 mtr long, 600mm depth complete all as specified and shown on drawings TD/027 sheet 1/4 to 4/4. |
| 64 | Sch \"A\" Part X (EOT CRANE) |
| 65 | Design, manufacturing, supply, installing, testing and commissioningof EOT crane 5 ton capacity as per IS-3177 & IS-807 (latest), Class –II, medium duty, electrically operated overhead travelling crane, including shrouded bus bar GI type suitable for indoor operation complete as per the specifications enclosed as Appx \"A\" : (i)Capacity : 5 Ton (ii) Span : 50 metres(iii) Hook lift over floor level : 6m(iv) Type : Double girder electrically operated (v) Service : Indoor(vi) Duty : Class-II, medium(vii) Bay length : 75m(viii) Maintenance platform : Full length on both sides of bridge girder(ix) LT speed : 15-20 mtr/min (x) CT speed : 15-20 mtr/min(xi) Hoisting speed : 3 mtr/min |
| 66 | Sch \"A\" Part XI (STAND BY ELECTRIC SUPPLY) |
| 67 | Supply and installation of silent diesel engine driven generating set 415 Volts, 3 phase 4 wire, engine as per IS:10001/10002 and alternator as per IS:13364 complete with relay panel for automatic starting on mains failure, control panel having meters, sound proof canopy and foundation etc. of capacity 160 KVA as per the following specifications :(a) Engine:4 cylinder, In-line 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude,Inline fuel pump with A1 class mechanical governing, Spin on fuel filter, Standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature,Full flow spin on lube oil filter,Electrical starter motor with soft start engagement feature, ??Battery charging alternator with 1 x 12 V DC batteryMake: Cummins/Kirloskar |
| 68 | i. Fly wheel with starter ring for generating set ii. Dry type air filteriii. Lube oil cooler assy with accessoriesiv. Exhaust air manifoldv. Exhaust silencervi. Expansion bellowvii. Exhaust gas turbouchargerviii. Fuel filter (Pre and micro)ix. Lube oil filter (Spin on type)x. Centrifugal bypass filterxi. 12 V electric starting system with starter motor and battery charging alterator.xii.Front & Rear engine mounting supports.xiii. Engine control panel consisting of OFF/ON/STAFT Keys, Lube Oil pressure Gauge Ammeter, Electronic Hours meter speedo meterxiv. Safety against low tube Oil pressurexv. Engine Operation/Maintenace & Spare parts MANUALxvi. Engine Warranty Certificatexvii. Engine test certificatexviii. AVM pads affixed between engine/altrnator feet and base framexix. Fuel tank of standard capacity of 8 hrs continous running complete with intelt and outlet connections, manhole oil indication gauge drain plug air breather etc as required. |
| 69 | xx. Exhaust system of class \"C\" MS Pipe of suitable diameter including providing mineral wool 25mm thick on all sides, lagging with chicken mesh wrapping and aluminium cladding.xxi. Structural foundation with all civil work including anti vibration pads with anti skid mounting etc as required(b) AlternatorBrushless type, Screen protected, Revolving field, Self excited alternator conforming to IS/IEC 60034-1 3 Phase reconnectable winding with 12 terminals brought out for connection, Dedicated winding specially designed for 3 phase operation, Impregnation on all wound components for better mechanical strengthMake : Stamford/ KOELi. One MS frame suitable for mounting of engine and alternatorii. One fuel tank of suitable capacity for 16 hrs continuous running complete with fuel gauge inlet/outlet connections, drain plug etc dulu. |
| 70 | iii. One Nos 12 volts DC battery make : Exide ofsuitable capacity as per OEM with copper leads and terminal lugs of suitable size.iv. One set of AVM pads fitted on Base Frame.(c) Control PanelManufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.The control panel consists of the following parts:ControllerAluminum bus bars with suitable capacity with incoming/outgoing terminals??Indicating lamps for ‘Load ON’ and ‘Set Running’??Instrument fuses duly wired and ferruledMCCB of suitable rating with overload and short circuit protections.(d) Microprocessor based generator set monitoring and control system. This control includes an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation,configuration and diagnostics. Intuitive operator interface which includes LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, Remote Start-Stop. |
| 71 | ??(e) Engine Metering: Oil pressure, Engine temperature, Starting battery voltage, Engine running hours.(f) ??AC Alternator Metering: L-L Voltage and L-N Voltage, Current (phase and total), kVA (phase and total) and Frequency.(g) Doors are gasketed with EPDM gasket. |
| 72 | (h) Sound proofing with high quality rock wool / mineral wool confirmingto IS-8183, of 50 mm thickness and density at96 Kg/m3 covered with fibre glass cloth and peforated powder coated sheet specially designed attenuators (sound controller) at air entry and exit of the container.Noise level shall not exceed 75 DB A at 1 mtr distanes as per CPCB norms.(i) Adequate ventilation to meet air requirement for combustion and heat removal with provision of blower. (j) Emergency stop push button outside the enclosure. |
| 73 | Supply and fix on- load change over switch 125 Amps 415 volts in sheet metal enclosures 4 polecomplete all as specified and directed. |
| 74 | Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric power cable heavy duty) 1100 volts grade with stranded aluminum conductor of size 150 sqmm 3 1/2 core complete all as specified and directed. |
| 75 | M&L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised iron strip 32×6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed. |
| 76 | Sch \"A\" Part XII (AIR CONDITIONING & COOLING/ SUMMER APPLIANCES) |
| 77 | Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 3 star rating andEER 3.2 of capacity 1.5 TR complete all as specified and directed. |
| 78 | Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 3 star rating andEER 3.2 of capacity 2 TR complete all as specified and directed. |
| 79 | 3.Supply and fixing of voltafge stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of + 2.5% and of capacity 5 KVA complete all as specified and directed. |
| 80 | Supply and installed refrigerator, electric driven (single phase), single door, capacity 215 liters, frost free. BEE 3 star rated complete all as specified and directed. Make : LG / Samsung / Godrej. |
| 81 | Supply, installation, commissioning of Water cooler fully stainless steel, electric driven single phase having approx storage and nominal cooling capacity 40/80 litres complete all as specified and directed. |
| 82 | Supply and fixing of voltafge stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 120 V to 250 V with output voltage stabilized at 230 V with accuracy of + 2.5% and of capacity 1 KVA complete all as specified and directed. |
| 83 | Sch \"A\" Part XIII (LIGHTENING PROTECTION) |
| 84 | Supply and fix air termination single pointed aluminum rod 12mm dia and 300mm long fixed on 0.6m long 25mm medium grade galvanized iron tubing with clamps, nuts/bolts and connected to aluminum strip all as specified and as directed. |
| 85 | Supply and fix aluminum strip of size 25mm x 3.15mm fixed on FRP saddles at an interval of not more than 60cm for roof and down conductors. FRP saddles on hanger roof shall be fixed with \"J\" hook of appropriate type and size with bolt and nut and bitumen washer on both sides, drilling to the roof sheet shall be carried out without damaging it complete all as specified and directed. |
| 86 | Supply and fix test point terminal block made cut of gun metal or phosphorus bronze of size 75 x75 x25mm drilled and screwed including 03 Nos 8mm dia 25mm long hexagonal head screws complete all as specified and directed. |
| 87 | M&L for Earthing complete with galvanised earth plate electrode 600 x 600 x 3.15 mm thick, burried directly in ground (earth pit not less than 2.25meters deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanised iron strip 32×6mm as earthing lead by means of bolts, nuts, check nuts and washers of copper all as shown in electrical plate No. 3 of SSR Part-I (2009) connected to earthing test point all as specified and indicated including testing on completion complete all as specified and directed. |
| 88 | Supply and fixearth continuity conductor or mainearthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI strip 32mm x 6mm buried in ground ccomplete all as specified and directed. |
| 89 | Total amount of SCHEDULE \"A\" XIV-A (EXTERNAL ELECTRIC SUPPLY, RUNWAY & TAXI TRACK LIGHTS) (For details seeSchedule \"A\" Part-XIV-A in PDF folder) |
| 90 | Sch \"A\" Part XIV-B (EXTERNAL ELECTRIC SUPPLY, RUNWAY & TAXI TRACK LIGHTS) |
| 91 | Supply and fixhorizontal double mounting electric motor siren confirming to IS 1941, three phase 400-440 V AC supply, 2800 RPM, 50 Hz with motor not exceeding 2 HP power and range upto 3.25 KM complete all as specified and directed. |
| 92 | Supply and installation of galvanised steel high mast lighting system of 16 mtr in two section, 3 mm section thickness, top dia 150 mm, bottom dia 340 mm, with 2/3 wire rope system and its accessories. System is suitable for loading 08Nos 80 to 150w LED lights including labour and special equipments required for 16 meters high mast system with all accessories. Mast shaft shall be in two sections, hot dip galvanisedand suitable for with velocity as per IS -875 Part-3 it shall also include accessories for high mast including head frame, steel wire rope 6mm dia (7/19 construction) trailing cable double drum winch, galvanised lantern carriage arrangement suitable for required luminaries as per design and its control gear boxes and lighting final. The mast shall have an integral power tool installed inside the base compartment for its operation. The high mast system shall also include necessary wiring with PVC insulated FR grade copper conductor cable of suitable sizes of 1100 volts grading or connecting all the proposed luminaries complete all as specified and directed. |
| 93 | Supplying and fixing including testing on fixing LED HIGH BAY-CORVUS SERIES CODE- LTE HB 150W HPLED/LS-150 HP LED of Make – C&S or equivalent in Philips or Crompton with its control gear including necessary wiring PVC insulated FRLS grade copper conductor cable of suitable sizes of 1100 volts grading for connecting the luminaries complete all as specified and as directed. |
| 94 | Supplying and fixing including testing LED FLOOD LIGHT-ORION SERIES CODE-LTEFI 150 W HP LED-150 WHP LED of Make –C&S or equivalent in Philips or Crompton with its control gear including necessary wiring with PVC insulated FRLS grade copper conductor cable of suitable sizes of 1100 volts grading for connecting the luminaries complete all as specified and as directed. |
| 95 | Supply and fix twin dome LED aviation obstruction lights of LED OBSTRUCTION LIGHTS- ALBA SERIES CODE-LTAL001 300 NOS LEDS of Make- C&S or equivalent in Philips or Crompton with necessary wiring with PVC insulated FRLS grade copper conductor of suitable sizes of 1100 volts grading for connecting the luminarie and fixed on high mast complete as specified and directed. |
| 96 | Supply and fix Control panel housing with suitable control circuit for the operation of the mast and shall also consist of suitable control for the power tool motor be including installing the panel on suitable foundation in PCC 1:2:4 type B-2 using 40 mm graded stone aggregate complete all as specified and directed. |
| 97 | Supply laying and testing cable XLPE insulated armored heavy duty electric cable with aluminum conductor (heavy duty) 1100 volts grade off size 4 core 16 sq mm complete all as specified and directed. |
| 98 | Supply, installation , testing and commissioning transformer, copper wound stepdown outdoor type complete with standard fittings HT 11 KV 3 phase, LT 433 volts,3 phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS-1180 (Part-I)of capacity 500 KVA copper wound including intial oil filling to appropriate level with desired dielectric strength and connected with the electric system including jointing materials,temperature rise 50/55 degree C and standard accessories as under :- (a) Cable termination box with disconnecting facility for 11 KV XLPE cable at 11 KV side .(b) Arrangement for connecting busbar trunking with neutral brought out as earthing terminal .(c) Off load changer +/- 7.5% @ 2.5% (d) Bi-directional roller.(e) conservator with drain valve (f) earthing terminals 02 Nos of the body of transformer . |
| 99 | (g) Double diaphragm explosion vent.(h) Radiator with top & bottom shut off valve .(j) first filling of oil including make up fill.(k) Silica gel breather with oil seal .(l) Rating and diagram plate .(m) Air release plug.(n) Winding temprature indicator.(WTI) (o) Oil temperture indicator.(p) Magnetic oil level gauge.(q) Marshalling Box |
| 100 | Supply, transporting, errecting steel tubular swaged pole ISI marked, type 410- SP-55, 11.00 metre long, complete with cast iron base plate, pole cap, finial taper plug, bolts, nuts, washers etc. including painting two coats of aluminium paint over a coat of red oxide primer including 3 Nos. of bands / strips painted with flourescent post office red and white colour (300 mm each) in alternate layer from plinth block, marking of pole number with black synthetic enamelled paint 2.5 cm height including one coat black bitumenous paint on steel surface embedded in concrete foundation complete all as specified and directed. |
| 101 | M&L Earthing to poles, gang operated device TP switch lighting arrestpr with and incl galvanized MS earth plate of size 600x600x6 mm thick buried vertically in ground to depth not less than 2.25 Mtrs below ground level, the earth plate surrounded with adequate quantity of charcoal, dust and salt to a packed thickness of 15 cm on all side, excavation earth work, returning, filling, removal of surplus soil up to 50Mtr incl GI earth wire 8 SWG(4mm) dia bolted and riveted to earth plate at one end and connected continious GI earth wire of HT/LT over head line/GOD switches, lighting arrester GI earth wire encased in and incl 15mm NB GI light grade pipe with all fitting from upper edges of earth plate with 1400mm above ground level fixed along pole with and incl 25x6mm flate iron clamp, bolts nuts and wahers painting with two coat aluninium paint over one coat of red oxide primer all as per Electrical Plate No 3 of SSR Part- I and shown thus complete all as specified and directed. |
| 102 | Supply and install transporting erecting and fixing steel tubular swaged pole type 410 SP-31, 9 metres complete with cast iron base plate, final and single swan neck including painting two coats of aluminium paint over a coat of red oxide primer including 3 Nos. of bands / strips painted with flourescent post office red and white colour (300 mm each) in alternate layer from plinth block, marking of pole number with black synthetic enamelled paint 2.5 cm height including one coat black bitumenous paint on steel surface embedded in concrete foundation complete all as specified and directed. |
| 103 | Supply and fix junction box made up of SMC ofsize 300 x 250 mm with front side openning complete including 4 Nos bus bar of appropriate size and one No MCB SP 6 Amp, to be fixed on poles with2 Nos clamp 25/6 mm flat iron complete all as specified and directed. |
| 104 | Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 105 | Supply and fixing LED street light fitting 100 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 106 | M&L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised iron strip 32×6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed. |
| 107 | Supply, installing, commissioning and testing factory made cubical outdoor type floor mounted LTpanel board suitable for 415 volts 3 phase 4 wire AC supply system having bus bar cnamber with insulated Aluminium bus bar 800 amps rating installed on porcelain insulator and oust/vermin proof and made out of 3.15 mm thick CPRI Approved CRCA mild steel sheet and 40x400x6mm thick anole from frame work front opening type 1.5x1.5x0.35mm duly painted with two coats of power coated pain over a coat of red oxide metal panel incl internal wiring in the panel with PVC insulated multi stranded copper conductor IS-694 marked1100 volts not less than2.5 Sqmm. The scope of work shall also includes provisioning of the following:- INCOMING :-(a)MCCB 630 Amps4 poles 35KA -01 No with built in over current and short circuit & earth fault protection with adjustable thermal release. |
| 108 | INSTRUMENTS:-(a) 01 Nos – Digital voltmeter with built in selector switch.(b)01 Nos – Digital Ammeter with built in selector switch.(c) 01 Set- 600/5 CTs 15VA class (for AMP meter).(d)3 Nos - LED type RYB indicating lamps with 2 Amps MCB’s(e) 2 Nos - LED type on/off indication lamp.OUTGOING (Adjustable settings)MCCB 4 POLE 415 VOLTS grade 250 AMPS rating 35 KA rupturring capacity-01 NosMCCB 4 POLE 415 VOLTS grade 125 AMPS rating 35 KA rupturring capacity-02 Nos |
| 109 | Construction of open plateform with rail, resting for transformer complete with fencing and steel gate etc complete all as specified and shown on drawing. (Ref TD-156 for platform and TD-98 for fencing and gate) |
| 110 | Supply fabrication installation testing & commissioning (CPRI approved) 440V AC APFC, Panel compartmentalized & modulator type indoor type in 2mm (TATA steel make) CRCA sheet of appropriate size front operate able single door front & back operate only. Dust & vermin proof. Cable entry through 2cm CRCA gland plates –Top & bottom only. Powder coat- ed after & tank pre-treatment process segments grey space on body/doors & orange shade on mounting gland plates + Incomer Doors. 3 phase HS sleeved coat coded aluminium Main busbar of 700A (70 x 10mm for 3 phase) with transparent polycarbonate covers & on SMB/DMC insulators. 25 x 6mm Aluminum Earth Busbar running across the whole length of the LT panel with studs at both the side –ends. Lifting arrangement /Hooks at the top wiring with appropriate size of copper Industrial Cables Black Paints Base Frame -40x40x50 mm angle frame. Cables glades brass chromium plated of different sizes suitable for incoming & outgoing ACB and MCCB\"s are fitted with following specified items :- |
| 111 | (A) Rating -250KVAR With 16 Steps (10x20 KVAr +4X10KVAr + 2x 5 KVAr) APFC Panel(Note : APFC Panel for 500KVA transformer )Incoming MCCB Microprocessor based release with overload & short –circuit protections Rating 630A TP 50KA (lcs = 100 Icu Contacts 7 Rotary Handle mechanics -01 Nos (Make : Schneider /ABB/C&S)(i) Rating - 250 KVAR APFC Panel ( Without Harmonic Block Reactors) (ii) Capacitors-A) 440 V AC TP MDXL type Heavy Duty low loss Capacitors in Cylindrical/ Square body of following ratings: 20kVAR x 10 Nos. B) 440 V AC TP MPP type Heavy Duty Capacitors in Cylindrical/ Square body of following ratings:10kVAR x 4 Nos.C) 415 V AC TP MPP type Heavy Duty Capacitors in Cylindrical/ Square body of following ratings:5kVAR x 2 Nos. |
| 112 | iii) 415V AC TP Microprocessor Based Intelligent PF Correction Relay/ Controller 16 Stage with 3CT sensing capability iv) for 20 kVAR Capacitor Banks- 10NosMCB 16A TP 10 kA (C Curve), & Capacitor Duty Contractor of 20kVAr Rating TP with 220 AC Coil Voltage, with Damping Resistors & Block of Early Make Poles, & with Luminous type On/ off Push Bottons & A/M Selector Switch (for Each Set)v) for 10 kVAR Capacitor Banks-4NosMCB 16A TP 10 kA (C Curve), & Capacitor Duty Contractor of 10kVAR RatingTP with 220 AC Coil Voltage, with Damping Resistors & Block of Early Make Poles, & with Luminous type On/ off Push Bottons & A/M Selector Switch (for Each Set)vi) for 5 kVAR Capacitor Banks- 2 NosMCB 6A TP 10 kA (C Curve), & Capacitor Duty Contractor of 5kVAr Rating ) TP with 220 AC Coil Voltage, with Damping Resistors & Block of Early Make Poles, & with Luminous type On/ off Push Bottons & A/M Selector Switch (for Each Set) |
| 113 | vii) Cooling of Capicitor Banks- 1 Set2Set Cooling Fans 9\" with Air Fiters (on Top ), 8 Sets Cooling Fans 6\" With Air Fiters (at back & side walls), 2Nos. Power Contractor 16A AC-3Duty with Aux. Contacts, 2Nos. Multifunction Cyclic Timber (Radix Legrand), MCB SP 2A \"c\" Curve for Control Circuit, Luminous Type Auto-Manual Selector Switch. |
| 114 | Total amount of SCHEDULE \"A\" XV-A (EXTERNAL WATER SUPPLY) (For details seeSchedule \"A\" Part-XV-A in PDF folder) |
| 115 | Sch \"A\" Part XV-B (EXTERNAL WATER SUPPLY) |
| 116 | M&L for construction of brick masonalry valve of size 900x900x1000mmrendering on internal and exposed external surface of brick work in CM 1:4 be 15mm below GL and mixed with water proofing compound @2% by wt of cement with and incl 40x40x6mm angle iron and 3.15mm thick MS sheet cover with locking arrangement and 1 No 50mm size 4 levers lock with keys in duplicate ISI marked incl painting steel surfaces with two coats of black bituminous paint over a coat of red oxide primer complete all as specified and as directed. |
| 117 | Total amount of SCHEDULE \"A\" XVI (RETAINING WALL) (For details seeSchedule \"A\" Part-XVI in PDF folder) |
| 118 | Total amount of SCHEDULE \"A\" XVII-A (FIRE POINT AND EXTINGUISHER) (For details seeSchedule \"A\" Part-XVII-A in PDF folder) |
| 119 | Sch \"A\" Part XVII-B (FIRE POINT AND EXTINGUISHER) |
| 120 | S&F fire extinguisher dry chemical powder (ABC) type 5 Kgcomplete all as specified and directed. |
| 121 | S&F fire extinguisher CO2 type 4.5 Kgcomplete all as specified and directed. |
| 122 | S&F fire extinguisher mechanical foam type 25 Kg complete all as specified and directed. |
| 123 | Sch \"A\" Part XVIII (FIRE DETECTION AND ALARM SYSTEM) |
| 124 | M&L for fire pump diesel engine driven horizontal end suction, centrifugal type confirming to IS-12469 1988 with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continuous operation with \"range of operation 0% to 150% of rated capacity for 440V, 3 phase 50 Hz AC supply 70m Head 2850 LPM discharge complete all as specified and as directed. |
| 125 | M&L for fire pump electrically driven horizontal end suction, centrifugal type confirming to IS-12469 1988 with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continuous operation with \"range of operation 0% to 150% of rated capacity for 440V, 3 phase 50 Hz 70m Head 2850 LPM discharge complete all as specified and directed. |
| 126 | M&L for Jockey pump horizontal end suction centrifugal type confirming IS-12469 1988 with CI casing bronze impeller and stainless steel shaft mounted on heavy duty bearing suitable for automatic operation with non-overloadingpower characteristics for frequent start/stop operations for 440V 3 phase 50 Hz 70m head 180 LPM discharge complete all as specified and directed. |
| 127 | Supply and Install Booster pumps for 440 V, 3 Phase, 50 Hz confirming to IS- 12469 :1988 With CI casing bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for 440 volts, 3 phase, 50 Hz 30m head, 450 LPM discharge complete all as specified and directed. |
| 128 | Supply and lay pipe cast Iron, double flanged type including specials, Class\"B\", 150mm(3\") dia complete all as specified and directed. |
| 129 | Supply, laying & jointing of ISI marked MS ERW (class C) pipe including all fittings i.e. reducer, elbows, tees, flanges etc. below ground including transportation of all materials to work site, earth work and excavation in all kinds of soil, edge preparation, jointing by welding, providing coating & wrapping with two coats of coltar hotblack paint and two wraps of reinforced fibre glass tissue or bitumenised hessian or providing 4 mm thick \"Pypkote\" tar based polymeric corrosion protection tape over a coat of red oxide primer as directed.Laying the pipes in trenches in proper allignment, providing 150 mm thick fine sand layer all round the pipe, back filling trenches in layers, hydrostatic testing of the complete pipe work, disposal of surplus earth as directed providing 1:2:4 type B-1 (using 20mm graded stone aggregate) cement concrete thrust blocks of suitable size at bends and tees, completing the work in :- |
| 130 | (a) 250 mm nominal bore |
| 131 | (b) 200 mm nominal bore |
| 132 | (c) 150 mm nominal bore |
| 133 | (d) 100 mm nominal bore |
| 134 | (e) 80 mm nominal bore |
| 135 | (f)65 mm nominal bore |
| 136 | (g)40 mm nominal bore |
| 137 | (h) 25 mm nominal bore |
| 138 | (j) 20 mm nominal boreNote for above item (a) to (j):-(a) Pipe wherever exposed in air to be painted with \"Red\" paint.(b) Earth work shall be measured and paid under Earth work schedule.(c)Embedding of pipes in sand will be paid in respective item separatily. |
| 139 | Supply install and testing sluice valve cast iron double angled with drilled stainless steel spindie and CI wheel head IS-14846 (2000) stuice valve class PN-1.6of following sizesincl Drilled flanges fibre sheet backing MS nuts bolts & washers of recd size complete all as specified and directed. |
| 140 | (a) 250 mm nominal bore |
| 141 | (b) 200 mm nominal bore |
| 142 | (c) 150 mm nominal bore |
| 143 | (d) 100 mm nominal bore |
| 144 | (e) 80 mm nominal bore |
| 145 | (f) 65 mm nominal bore |
| 146 | M&L Hose reel drum 30m complete all as specified and directed. |
| 147 | M&L pressure gauge 4\" dia 10-14 Kgs rating complete all as specified and directed. |
| 148 | M&L for pipe support for all types of pipes including hangars/fastners/elbows/ supports/tees complete all as specified and directed. |
| 149 | M&L for fire alarm control panel complying with BSEN 54 single loop panel Capacity from 99 detectors & 99 modules upto of 200 detector and modules complete all as specified and directed. |
| 150 | M&L for detectors complying with and type certified to EN-45 Addressable type multisensor detector with heat and smoke combination with base with self built intelligence as per IS-11360 complete all as specified and directed. |
| 151 | Supply and fix addressable type Flame detectors with UV/IR detection Capacity (add up cost of module to be a complete set, the type of module shall be relay type module). |
| 152 | M&L for addressable manual call point resettable type complete all as specified directed. |
| 153 | M&L for 4 watt ceiling speaker complete all as specified and directed. |
| 154 | M&L for 250 watt Amplifier complete all as specified and directed. |
| 155 | M&L Hydrant valve single headed complete all as specified and directed. |
| 156 | M&L for Hose box made of 18 gauge MS sheet 800mm x 600mm x 250mm with Double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet set painted fire red out side and brilliant white inside yard complete all as specified and directed. |
| 157 | M&L for fire alarm sounders/sirens electronic type horizontal single stage continuous Normal operation for at least50 minutes with sound level 65 DB to 120 measured at 1.5 Mtr with sound output variation of 5 DB 1000 mtr range complete all as specified and directed. |
| 158 | S & F 63 mm dia, 30 mtr long rubberised fabric reinforced rubber lined hose including gun metal male & female instataneous coupling, hose confirming to IS : 636 type II and coupling confirming to IS 903-1975complete all as specified and directed. |
| 159 | Supply and fixing brass orifice plates at appropriate places to restrict the pressure up to 3.5 kg/cm2 at different floor on the wet riser system and yard hydrant complete all as specified and directed. |
| 160 | Supply and fix Gun metal fire brigade inlet connection for connecting to external fire hydrant ring main consisting of two nos 63mm dia instantaneous type male coupling with built in check valves and 150mm dia, flanged outlet complete with all accessories as specified and directed. |
| 161 | Supply and fix Air cushioning tank (Air vessel) 300 mm dia x 1000mm high with dished top, made of minimum 6mm thick MS pipe /plate complete with 20mm dia. Brass air valve (ball type), 20mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories complete as specified and directed. |
| 162 | M&L yard hydrant Post / Stand Post 80mm dia GI / MS both flanged type 1.5m height complete all as specified and directed. |
| 163 | Supply and fix 63 mm dia gun metal branch pipe with 12.5 mm nozzle conforming to IS 903 complete all as specified and directed. |
| 164 | Supply, laying and testingISI Marked 2 core x 1.5 mm2, Multistrand Copper, FRLS Armoured cable (red in Colour), laid on surface with GI saddle-spacers every 0.3 meters. Complete with GI Junction Box, lugs, cable compression glands, cable tags and Ferruling complete all as specified and directed. |
| 165 | Supply, installing, testing and commissioning of addressable type Manual call point, resettable type complete all as specified and directed. |
| 166 | Supply, installing, testing and commissioning of addressable type Fault Isolators for isolating shorted, de wired and loose circuits between two successive fault isolators with automatic resetting arrangementcomplete all as specified and directed. |
| 167 | Supply, installing, testing and commissioning of addressable and automatic commandable control module for Manual call pointcomplete all as specified and directed. |
| 168 | Supply, installing, testing and commissioning of addressable and automatic commandable control module for Relay Modulecomplete all as specified and directed. |
| 169 | Supply, installation,testing and commissioning of Directional sounders with 20 Htz to 20 KHtz operating frequency with minimum 8 distinct sound patterns to indicate corridors, Exit doors, Move upward, move downward etc to direct occupents for fast and safe evacuation as specified in NFPA 72-2007 edition ( UL 9th edition Approved and NFPA compliant)complete all as specified and directed. |
| 170 | Supply, installation, testing and commissioning of response indicator all as specified and directed. |
| 171 | Supply, install, testing and commissioning LT panel, indoor type cubical panel board, made out of 2mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 52 free standing floor mounted with copper busbar of suitable size for phase and neutral mounted on hygroscopic insulators comprising of the following:-(a) MCCB 4 pole 400A, incomer, 415V, 50Hz,35 kA - 01 No.(b) MCCB 4 pole 160A, outgoing, 415V, 50Hz, 10 kA - 02 No.(c) MCB TPN32 A, 415V- 1 No. (d) MCB SP6-32A, 10kA - 4 Nos.(e) FASD starter 125 HP-2 Nos.(f)DOL starter 7.5 HP - 1 No.(e) 400 A rated copper bus bar with colour coded heat shrinkable sleeve(f)Digital ammeter with suitable CTs - 02 Nos.(g) Digital voltmeter (0 - 500 V) - 01 No.(h) R-Y-B phase indicating lamp- 01 set(j) Pressure switch operated relays for auto start of pumps - 2 Nos.(k)Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled complete. |
| 172 | S&F fire extinguisher dry chemical powder (ABC) type 5 Kgcomplete all as specified and directed. |
| 173 | S&F fire extinguisher CO2 type 4.5 Kgcomplete all as specified and directed. |
| 174 | S&F fire extinguisher mechanical foam type 25 Kgcomplete all as specified and directed. |
| 175 | M&L for GI slotted type cable trays of size 100 x 50 mm x 2mm using MS angle, channels, flats etc. All MS supports used shall be given one coat of red oxide primer & 2 coats of synthetic enamel paint of approved colour complete all as specified and directed. |
| 176 | Sch \"A\" Part XIX (CONVERSION MACHINE AND AIR COMPRESSOR) |
| 177 | Supply, installation, commissioning and testing static frequencyconverter 415 Volt A/C 50 cycle input &output voltage 115 Volts + 1%tolerance output, 400Hz, 1 phase, 10KVA with Programmable Controller for output voltage & Frequency adjustment with password protection & Three Point Programmable Overload setting facility, Enclosure Protection IP-55 completeas per specification given here in below :-Rated power @ 0.8 pf lag: 10KVA INPUTVoltage- Nominal: 400V ACFrequency- Nominal : 50HzAC to AC Efficiency : 92%RectifierTechnology: 12 Pulse Rectifier SCR based fully controlledPower walk in: 10 to 15 secsTHDi (input current Harmonic Distortion ): < 10% at rated loadInput power Factor > 0.92lagGalvanic isolation: Inbuilt Galvanic Isolation |
| 178 | OUTPUTVoltage- Nominal: 115 V AC ( Programmable)Frequency - Nominal : 400Hz ( Programmable)Phase : Single PhaseWaveform : Sine WaveTotal Harmonic Distortion : < 2% on linear loadTransient Response: less than +/-8% for 100% step loadsRecovery Time: less than 25milli secs to reach within +/-1% of nominal valueLoad power factor range : 0.8 lag to unity within KW ratingOverload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Three Point Programmable overload setting facility. Protections: Input over/under voltage, Input Phase fail, overlad, Output over/under votage,snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit.Indications: InputON,OutputON, Input abnormal,Output over/Under voltage, overload, overheat.Remote Alarm \" Potential free contacts for input fault & output trip. |
| 179 | Metering: 16x2 LCD panel to measure the following: AC input voltage,output voltage, load percentage, input & output frequency.General specifications :Operating Temperature : 0 to 45 Deg C (50 Deg C Peak)Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensingCooling : Forced Air using localized cooling technique with multiple fractional HP fansPanel : Welded structure MS Covers 2mm and frame 3mm thickEnclosure protection: IP 55Make: Protech Services/Emmanuel Electronics/Tekvision Electronics/Merlin Hawk |
| 180 | Supply, installation, commissioning and testing static frequencyconverter 415 Volt A/C 50 cycle input &output voltage 208Volts + 1%tolerence output, 400Hz, 3 phase 10 KVA with Programmable Controller for output voltage & Frequency adjustment with password protection, Three Point Programmable Overload setting facility. Enclosure Protection IP-55 as per specification given here in below :-Rated power @ 0.8 pf lag:10KVA INPUTVoltage- Nominal: 400V ACRange: 340 to 460 V ACFrequency- Nominal : 50HzRange:47-53HzPhase : ThreeAC to AC Efficiency : 92%RectifierTechnology: 12 Pulse Rectifier SCR based fully controlledPower walk in: 10 to 15 secsTHDi (input current Harmonic Distortion ): < 10% at rated load |
| 181 | Input power Factor > 0.92lagGalvanic isolation: Inbuilt Galvanic IsolationOUTPUTVoltage- Nominal: 208 AC ( Programmable)Regulation: 1%Frequency - Nominal : 400Hz ( Programmable)Stability : 0.05% Phase : Three PhaseWaveform : Sine WaveTotal Harmonic Distortion : < 2% on linear loadTransient Response: less than +/-8% for 100% step loadsRecovery Time: less than 25milli secs to reach within +/-1% of nominal valueLoad power factor range : 0.8 lag to unity within KW ratingOverload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles.Three Point Programmable overload setting facility.Protections: Input over/under voltage, Input Phase fail, overlad, Output over/under votage,snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit |
| 182 | Indications: InputON,OutputON, Input abnormal,Output over/Under voltage, overload, overheatRemote Alarm \" Potential free contacts for input fault & output tripMetering: 16x2 LCD panel to measure the following: AC input voltage,output voltage, load percentage, input & output frequencyGENERALOperating Temperature : 0 to 45 Deg C (50 Deg C Peak)Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensingCooling : Forced Air using localized cooling technique with multiple fractional HP fansPanel : Welded structure MS Covers 2mm and frame 3mm thickEnclosure protection: IP 55Make: Protech Services/Emmanuel Electronics/Tekvision Electronics/Merlin Hawk |
| 183 | Supply, installation, commissioning and testing static frequencyconverter 415 Volt A/C 50 cycle input &output voltage 36Volts + 1%tolerence output, 400Hz, 3 phase10KVA withProgrammable Controller for output voltage & Frequency adjustment with password protection, Three Point Programmable Overload setting facility. Enclosure Protection IP-55 as per specification given here in below :-Rated power @ 0.8 pf lag:10KVA INPUTVoltage- Nominal: 400V ACRange: 340 to 460 V ACFrequency- Nominal : 50HzRange:47-53HzPhase : ThreeAC to AC Efficiency : 92%RectifierTechnology: 12 Pulse Rectifier SCR based fully controlledPower walk in: 10 to 15 secsTHDi (input current Harmonic Distortion ): < 10% at rated load |
| 184 | Input power Factor > 0.92lagGalvanic isolation: Inbuilt Galvanic IsolationOUTPUTVoltage- Nominal: 36 AC ( Programmable)Regulation: 1%Frequency - Nominal : 400Hz ( Programmable)Stability : 0.05% Phase : Three PhaseWaveform : Sine WaveTotal Harmonic Distortion : < 2% on linear loadTransient Response: less than +/-8% for 100% step loadsRecovery Time: less than 25milli secs to reach within +/-1% of nominal valueLoad power factor range : 0.8 lag to unity within KW ratingOverload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles.Three Point Programmable overload setting facility. Protections: Input over/under voltage, Input Phase fail, overlad, Output over/under votage,snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit |
| 185 | Indications: InputON,OutputON, Input abnormal,Output over/Under voltage, overload, overheatRemote Alarm \" Potential free contacts for input fault & output tripMetering: 16x2 LCD panel to measure the following: AC input voltage,output voltage, load percentage, input & output frequencyGENERALOperating Temperature : 0 to 45 Deg C (50 Deg C Peak)Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensingCooling : Forced Air using localized cooling technique with multiple fractional HP fansPanel : Welded structure MS Covers 2mm and frame 3mm thickEnclosure protection: IP 55Make: Protech Services/Emmanuel Electronics/Tekvision Electronics/Merlin Hawk |
| 186 | Supply, installation, commissioning and testing 10KW Static DC Power Supply 415 Volt A/C50 cycle input & 28 VDC output with Programmable Controller for Output Voltage with Password Protection & Three Point Programmable Overload setting facility, Enclosure Protection IP-55 with completespecification given here in below :-Rated power @ 0.8 pf lag: 28V DC,10KWINPUTVoltage- Nominal: 400VRange: 340 - 480V AcFrequency- Nominal : 50HzRange:47-53HzPhase : ThreeAC to AC Efficiency : 92%RectifierTechnology: 12 Pulse Rectifier SCR based fully controlledPower walk in: 10 to 15 secsTHDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lagGalvanic isolation: Inbuilt Galvanic Isolation |
| 187 | OUTPUTVoltage- Nominal: 28VDC (Programmable)Regulation: +/-1%Voltage Variation: 25.2 to 30.8VOverload : 110% for 30 min, 150% for 10sec . Three point programmable Overload setting facility.Protections: Input Over/under voltage,Input Phase fail, overload, DC over/under voltage, snubber circuits for power devices, over temperature, fuse for semi conductor devicesIndications: Mains ON, DC ON,Mains Over/Under Voltage, Phase Fail,DC over/under voltage, overload,overheatRemote Alarm : Potential free contacts for input fault & output tripMetering: 16 x 2 LCD for I/p & O/p Volts, DC Volts,& ouput current |
| 188 | GENERALOperating Temperature : 0 to 45 Deg C (50 Deg C Peak)Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensingCooling : Forced Air using localized cooling technique with multiple fractional HP fansPanel : Welded structure MS Covers 2mm and frame 3mm thickEnclosure protection: IP 55Cable Entry : Front BottomMake: Protech Services/Emmanuel Electronics/Tekvision Electronics/Merlin Hawk |
| 189 | Supply, installation, commissioning and testing 5KW Static DC Power Supply 415 Volt A/C50 cycle input & 28 VDC output with Programmable Controller for Output Voltage with Password Protection & Three Point Programmable Overload setting facility, Enclosure Protection IP-55 with completespecification given here in below :-Rated power @ 0.8 pf lag: 28V DC,5KWINPUTVoltage- Nominal: 400VRange: 340 - 480V AcFrequency- Nominal : 50HzRange:47-53HzPhase : ThreeAC to AC Efficiency : 92%RectifierTechnology: 12 Pulse Rectifier SCR based fully controlledPower walk in: 10 to 15 secsTHDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lagGalvanic isolation: Inbuilt Galvanic Isolation |
| 190 | OUTPUTVoltage- Nominal: 28VDC (Programmable)Regulation: +/-1%Voltage Variation: 25.2 to 30.8VOverload: 110% for 30 min, 150% for 10sec . Three point programmable Overload setting facility.Protections: Input Over/under voltage,Input Phase fail, overload, DC over/under voltage, snubber circuits for power devices, over temperature, fuse for semi conductor devicesIndications: Mains ON, DC ON,Mains Over/Under Voltage, Phase Fail,DC over/under voltage, overload,overheatRemote Alarm : Potential free contacts for input fault & output tripMetering: 16 x 2 LCD for I/p & O/p Volts, DC Volts,& ouput current |
| 191 | GENERALOperating Temperature : 0 to 45 Deg C (50 Deg C Peak)Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensingCooling : Forced Air using localized cooling technique with multiple fractional HP fansPanel : Welded structure MS Covers 2mm and frame 3mm thickEnclosure protection: IP 55Cable Entry : Front BottomMake: Protech Services/Emmanuel Electronics/Tekvision Electronics/Merlin Hawk |
| 192 | Supply, installation, commissioning and testing True On Line UPS System 415 Volt A/C 50 cycle input &output voltage 230Volts ± 1%tolerance output, 50Hz, 1phase 10KVA with SMF Batteries for 30 minutes back up alongwith Programmable Controller for output voltage & Frequency adjustment with password protection, Three Point Programmable Overload setting facility. Enclosure Protection IP-55 as per specification given here in below :-Rated power @ 0.8 pf lag:10KVA INPUTVoltage- Nominal: 400V ACRange: 320 to 480 V ACFrequency- Nominal : 50HzRange:47-53HzPhase : ThreeAC to AC Efficiency : 92%RectifierTechnology: 12 Pulse Rectifier SCR based fully controlledPower walk in: 10 to 15 secsTHDi (input current Harmonic Distortion ): < 10% at rated load |
| 193 | Input power Factor > 0.92lagGalvanic isolation: Inbuilt Galvanic IsolationOUTPUTVoltage- Nominal: 230 AC ( Programmable)Regulation: ±1%Frequency - Nominal : 400Hz ( Programmable)Stability : 0.05% Phase : Single PhaseWaveform : Sine WaveTotal Harmonic Distortion : < 2% on linear loadTransient Response: less than +/-8% for 100% step loadsRecovery Time: less than 25milli secs to reach within +/-1% of nominal valueLoad power factor range : 0.8 lag to unity within KW ratingOverload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles.Three Point Programmable overload setting facility.Protections: Input over/under voltage, Input Phase fail, overlad, Output over/under votage,snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit |
| 194 | Indications: Input ON,Output ON, Input abnormal, Output over/Under voltage, overload, overheatRemote Alarm \" Potential free contacts for input fault & output tripMetering: 16x2 LCD panel to measure the following: AC input voltage,output voltage, load percentage, input & output frequencyGENERALOperating Temperature : 0 to 45 Deg C (50 Deg C Peak)Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensingCooling : Forced Air using localized cooling technique with multiple fractional HP fansPanel : Welded structure MS Covers 2mm and frame 3mm thickEnclosure protection: IP 55Make: Protech Services/Emmanuel Electronics/Tekvision Electronics/Merlin Hawk |
| 195 | Supply & Fixing of Output Distribution Panel made out of 1.6mm thick CRCA sheet indoor type with Digital Voltmeter & Frequency Meter for all outputs consisting of:Input Side :100A, 10KA , 3P MCCB, (for 10KVA SFC 115V),32A, 10KA TPN MCB(for 10KVA SFC 208V),160A,10KA,4P MCCB ( for 10KVA SFC 36V) 63A,10KA, TPN MCB (for 10KVA UPS), 300A, 35KA, 4P, MCCB ( for 10KW DCPS) & 160A, 25KA, 4P, MCCB ( for 5KW DCPS)Output Side:Copper Bus Bar mounted on suitable insulators for:115V, 1Ph, 400Hz,100A, 6’’ long208V, 3Ph, 400Hz,30A, 6” long36V, 3Ph, 400Hz, 160A, 6” long28V DC, 600A, 6’’ long28V DC, 300A, 6” long230V, 1Ph, 50Hz,50A, 6” longMake: Protech Services/Emmanuel Electronics/Tekvision Electronics/Merlin Hawk |
| 196 | S & F of PVC sheet slotted cable trays of various size width 80mm to accommodate the cable as per site reqmt incl support nuts, bolts washers etc complete all as specified and directed. |
| 197 | M&L for point wiring with stranded copper conductor 1.5 sqmm size (nominal cross section area) PVC insulated unsheathed cable 1100 Volts grade confirming to IS-694 drawn in and including PVC casing & caping ISI marked with concealed sunk in pressed steel terminal boxes of required size not less than 1.6 mm thick factory made and printing with stove enamelled black paint top cover 5 mm thick plastic laminated sheet including single core stranded copper conductor 1.5 sqmm PVC insulated ubsheathed cable as earth wire drawn in same steel conduit complete all as specified for 5/6 amps 3 pin socket on independent board controlled by onr , one way switch 5/6 Amps complete all as specified and directed. |
| 198 | Supply & install air compressor of working pressure 12 Kg/cm2 or 175 PSI two stage reciprocating twin cylinder with 20 HP motor discharge 109.79 Cum/hr mounted on 500ltrs tankcomplete with motor starter pulley and belts mounted on wheels and trolley coupled with Air Compressor including pipe line of GI tubing heavy and controls upto utility point and necessary nozzle complete as per following specifications & directed by Engineer –in-charge. Make: Elgi Model : HV 21 120 or equivalent.(a) Free Air delivery : 64.61 cfm(b) Working pressure : 12 kgs/cm2(c) Motor capacity : 20 HP(d) Starter : Fully automatic Star Delta(e) Tank Capacity : 500 Ltrs.(d) Accessories including suctio filter , air cooled radiator type , inter cooler with safety valve , Air cooled after cooler, V belt , belt gaurd, non return valve , visible oil level indicator automatic pressure switch-cum-Electro Magnetic suction valve delivery unloader system. |
| 199 | Supply and laying in trenches GI tubing medium grade with all fittings (ie union, socket, elbow etc) of 20 mm dia complete all as specified and directed. |
| 200 | S&F pneumatic guns including nozzles alongwith flexible pipes made of PVC/HDPE upto the work station not exceeding 5 meters incl all specials etc complete as specified and directed. |
| 201 | S&F Ball brass valves, high pressure, with polythene float and flynut complete, screwed for iron pipe or brass ferrule fixed complete all as specified and directed. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-4 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-5 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-6 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender