Project Description

Construction And Commissioning Of Tube Wells Under Jen Upper Water Supply Scheme Jaitaran Sub. Division Jaitaran ( Rates Are As Per Phed.Bsr 2021 )

BOQ

Name of Work :-Construction and Commissioning of Tube Wells under JEn UWSS Jaitaran Sub. Division Jaitaran (Rates are as per PHED.BSR 2021)
Sl. No. Item Description
1Construction of tube well from ground level & up to 100 mtr depth to accommodate housing and assembly pipe of following sizes in all type of alluvium strataunconsolidated formation such as pebbles, boulders etc. by percussion/rotary drilling method as per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended upto date) and technical specifications, with gravel as per IS:4097-1967 and it\"s packing as per IS: 2800 (Part I & II) 1979 as amended up to date (the work includes the cost of gravel & it\"s primary packing and packing during development, lowering of housing & strainer assembly pipes with supply and wrapping of coir-rope, wherever necessary for arresting fine sand particles and development work, but excluding the cost of housing and strainer pipe assembly). The work would be completed after obtaining sand free water.Nominal bore 200 mm dia.
2Add 15% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond 100 mtr and upto 200 mtr, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr.
3Add 40% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond 200 mtr, rate shall be applicable for only extra depth beyond 200 mtr .
4Construction of Tube Well from ground level and upto 100 mtr. depthto accommodate housing and assembly pipe in all type of alluvium strata, unconsolidated formation such as pebbles, boulders etc. by percussion/ rotary drilling methodas per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended upto date) and technical specifications for removal of overburden. The work includes the cost oflowering of casing pipe, but excludes the cost of casingpipe.Nominal bore 200 mm dia.
5Add 15% extra on above item(Item No 2.2.1 to 2.2.2) for drilling depth beyond 100 mtr, rate shall be applicable for only extra depth beyond 100 mtr .
6Construction of tube well after completion of drilling by rotary /percussion method & upto 100 mtr. depthin all type of rocks by DTH systemas per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended upto date) and technical specifications. The workshall be deemed completed only after obtaining sand free water. The bore well should have a throughout nominal size bore beyond casing pipe. Nominal bore 200 mm dia.
7Add 15% extra on above item (Item No 2.3.1 to 2.3.2) for drilling depth beyond 100 mtr and up to 200 mtr from ground level, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr.
8Add 30% extra on above item(Item No 2.3.1 to 2.3.2) for drilling depth beyond 200 mtr and from ground level, rate shall be applicable for only extra depth beyond 200 mtr .
9Deepening of existing tube well by DTH system beyond existing depth upto 100 mtr. and above in all type of rocks including flushing of tube well and obtaining sand free water. Nominal bore 200 mm dia.
10Testing verticality of tube well by plumbing system and yield test and draw down test by pumping system as per IS : 2800 (Part – II) – 1979 or as per amended up to date.
11Supplying & PackingP-gravel suitable for slot size/mesh size as suggested in IS 2800 (Part-1) 1991 or as per amended up to date.
12Development of tube well having depth up to 250 mtr as per IS: 11189- 1985 and IS: 2800 (Part- I)- 1991 (both amended up to date) using suitable methods to give sand free water for required yield of the gravel packed tube well.
13Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended up to dateoffollowing sizes 200 mm dia NB (Thickness of pipe 5.4mm & mass of tube 28.46 Kg/m)
14Labour charges for making slots on blank pipes made of ERW MS black pipe ISI marked of following sizes, the slotting should be as per IS:8110-1985. 200 mm dia nominal bore of 5.4mm thickness
15Providing & laying ISI marked GI Pipe Light duty ( “A” class) as perIS: 1239for casing pipe for submersible cable external work 40 mm dia complete in all respect.
16Supply & Installation of 3 phase ISI marked submersible motor pump set of five star (if not available then three/ four star whichever higher rating available) rating by BEEand as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. Up to 5.5 KW (7.5 HP) & head up to 120 mtr.
17Up to 5.5 KW (7.5 HP) & head above 120 mtr.
187.5 KW (10 HP) & head up to 120 mtr.
197.5 KW (10 HP) & head above 120 mtr.
209.3 KW (12.5 HP) & head up to 120 mtr.
219.3KW (12.5 HP) & head above 120 mtr.
2211 KW (15 HP) & head up to 120 mtr.
2311 KW (15 HP) & head above 120 mtr.
2413 KW (17.5 HP) & head up to 120 mtr.
2513 KW (17.5 HP) & head above 120 mtr.
2615 KW (20 HP) and above, head up to 120 mtr.
2715 KW (20 HP) and above, head above 120 mtr.
28Supply and Fixing of Electric feeder panel (having projected canopy)for submersible pump set Single phase upto 5 HP, comprising of DOL Starter, MCB, Indicating Light, Ammeter, Volt meter, connection plate, condensers of approved make and the panel enclosure should be made out from 18 gauge M.S. Sheet with powder coating. Panel size Height 600 mm Width 500 mm depth 250 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete platform. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The operation of panel should be suitable for on 240 Volt AC Supply.
29Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB, DOL starter, overload relay, ampere meter, volt meter, phase preventer,phase indicators, lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM). All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 300mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete platform. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level.The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply.Up to 5.00 HP
30Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay,ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM).All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply.Above 5 HP and up to 10 HP
31Above 10 HP and up to 15 HP
32Above 15 HP
33Supply & Fixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc. 3 core 4.0 Sq.mm
343 core 6.0 Sq.mm
353 core 10.0 Sq.mm
363 core 16.0 Sq.mm
37Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size.10.0 Sq.mm, 4 core
3816.0 Sq.mm, 4 core
3925.0 Sq.mm, 3.5 core
4035.0 Sq.mm, 3.5 core
41Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required.
42Supply & Fixing M S clamp set of 50x6 mm flat from iron with nuts and bolts etc for holding the riser pipe assembly of submersible pump set.
43Supply & Fixing tube well coverof MS sheet 8mm thick at top & 5mm thick 100mm wide shroud around the edge so as to form a cap on the top end of casing pipe with GI Nipple 45cm long & two GI flanges at both ends in 80mm sizes passing through a hole in the centre of MS sheet. A 25 mm socket with end plug shall also be welded over top plate. A GI nipple having outside thread of size 1/2\" (for installation pressure gauge) shall be provided & welded with 80mm GI nipple near top plate nipple shall be provided with end plug.200 mm dia
44Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B\" class), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect.32 mm dia
4540 mm dia
4650 mm dia
4765 mm dia
4880mm dia
49Providing & Lowering in tube well ISI marked HDPE pipe as per IS 4984:1995 or amended upto date in PE 80 grade and class PN 10 of following dia. including HDPE/GI fittings and PVC rope confirming to IS 5175:1992 or amended upto date, along with clamping of submersible cable etc. complete in all respect.40 mm dia
5050 mm dia
5163 mm dia
5275 mm dia
5390 mm dia
54Providing, installing, testing and commissioning of double flanged bulk flow meter with removable mechanism, of class B conforming to ISO 4064/1 or amended upto date of approved make including cost of all material andlabouras per specifications with GI Box (sheet 16 SWG) suitable with locking arrangement of following dia.50 mm dia
5565 mm dia
5680 mm dia
57Providing & Fixing pump safety cage as per specifications or as directed by Engineer in charge.
58Fabrication & Fixing M.S.Stand of specified class of angle iron L-shaped of 50 mm size with four legs grouted by 300*300*300 mm CC Block M-15 in the ground and all legs tied up with each other through same size of angle iron along with cross bars to support the bottom of 1000 Ltr./ 2000 Ltr. PVC tank complete in all respect.
59Providing & Fixing of double flanged, CI body, ISI marked NRV of approved make of following sizes65 mm dia
6080 mm dia
61Proving and Fixing 32 mm dia Full way valve or wheel valve as per IS:778 or amended up to date of approved make, on pump delivery pipe.
62Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg.including all jointing material as per specification with safety cover.

AI Tender Summary

OUR REF NO 29627652
AUTHORITY Government Departments
TENDER VALUE 25 Lakhs
LAST DATE 08-11-2021
Authority
Authority Name Public Health Engineering Department
Work Description Construction And Commissioning Of Tube Wells Under Jen Upper Water Supply Scheme Jaitaran Sub. Division Jaitaran ( Rates Are As Per Phed.Bsr 2021 )
Basic Detail
Tender No NIT NO 170/2021-22
Bidding Type Tender
Location
City JAITARAN
State Rajasthan
Key Dates
Publish Date 22 Oct 2021
Submission Date 08 Nov 2021
Open Date 09 Nov 2021
Finance
Tender Value 25 Lakhs
Tender Fee 1000
EMD 50000
Exemption Not Available
Document List
4f8ccca8-ee71-4796-88ab-2b73274c4d15.html
BOQ_437269.xls
TD-170.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 22, 2021
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 08, 2021
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Nov 09, 2021

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

4f8ccca8-ee71-4796-88ab-2b73274c4d15.html

xls

BOQ_437269.xls

pdf

TD-170.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders