| 1 | WIRING POINTS AND FITTINGS |
| 2 | 1.10.2 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group B |
| 3 | 1.11 : Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 4 | 1.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire |
| 5 | 1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | 1.14.3 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 7 | 1.14.9 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 6 sq. mm + 2 X 6 sq. mmearth wire |
| 8 | 1.14.11 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 9 | 1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 10 | 1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 11 | 1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 12 | 1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 13 | 1.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm |
| 14 | 1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 15 | 1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 16 | 1.27.4 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) |
| 17 | 90.9.2.1 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required. 100 x 50 mm CMS with base and lid |
| 18 | 90.9.2.8 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required. End Cap |
| 19 | 90.9.2.10 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required. Joint Cover |
| 20 | 90.9.2.5 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required. Internal angle 90 Degree |
| 21 | 90.9.2.3 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required. External Angle 90 Degree |
| 22 | 90.9.2.4 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required.Flat Angle 90 Degree |
| 23 | 90.9.2.24 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required. Flat Tee |
| 24 | 90.9.2.25 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required. Internal Tee |
| 25 | od110800/2021_2022 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required.<br>6 module mounting box |
| 26 | 90.9.2.12 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recessincluding cutting the wall and making good the damages in case of recessed installation as required. 1 to 3 module mounting box |
| 27 | 1.28.2 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module |
| 28 | 1.28.4 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module |
| 29 | 1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 30 | 1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 31 | 1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 32 | 1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 33 | 1.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden blockincluding connection etc as required. |
| 34 | 1.40 : Providing and fixing plain 16/0.20 mm (0.50 sqmm) twin circular flexible FRLS PVC insulated, PVC sheathes copper cable direct on the wall with PVC clips etc as required. |
| 35 | od94431/2021_2022 : Supply, conveyance, of ceiling fans of the following sizesusing standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.1200 mm 5 star rated PWD Approved make |
| 36 | 1.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 37 | od94432/2021_2022 : Supply and installation of suitable size MS rod type fan clamp as per IS 732 as required.(Ref 2012 KPWD Approved Rate)<br> |
| 38 | od94433/2021_2022 : Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS.200 mm, single phase, light duty exhaust fan in plastic body with self opening louvers PWD APPROVED |
| 39 | od94434/2021_2022 : Charges for cutting holes suitable for accommodating exhaust fans of sizes up to 305 mm sweep including plastering, colour washing etc. as required. |
| 40 | 1.58 : Supplying and fixing PVC batten/ angle holder including connection etc. as required. |
| 41 | od94435/2021_2022 : Supply and installation8 to 10 w LED Bulb |
| 42 | od94437/2021_2022 : Supply conveyance, installation, testing and commissioning the following types oflight fittingsmade from CRCA sheet 0.5mm thickness with all accessories andlamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copperconductor flex wire or extending the original wiring and giving connections as required(PHILIPHS/WIPRO or equivalent make) 16 to 20 w LED Tube |
| 43 | 90.11.1.14 : Supply and installation ofsheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 Way ( 8+12 ) Double cover TPN Vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43 |
| 44 | 90.11.1.12 : Supply and installation ofsheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 Way ( 8+24) three phase double cover (IP 42/43 |
| 45 | 90.11.1.13 : Supply and installation ofsheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required 12 way (8+36) - three phase double cover (IP 42/43) |
| 46 | 2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 47 | 2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 48 | 2.13.3 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps |
| 49 | 2.15.1 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 50 | 2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 51 | 2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 52 | 2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole |
| 53 | od110939/2021_2022 : Supplying and fixing 40 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>Triple pole |
| 54 | od111029/2021_2022 : Supplying and fixing 63 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>Triple pole |
| 55 | 2.10.5 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole and neutral |
| 56 | 2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 57 | od94460/2021_2022 : Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench40 / 32 mm or nearest size |
| 58 | od112476/2021_2022 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 3.5 core 35 sq mm with factory made clamp |
| 59 | od94461/2021_2022 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 3.5 core 50 sq mm with factory made clamp |
| 60 | 9.1.21 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 61 | 9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 62 | od94466/2021_2022 : <br>Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with eachsize of glands for the following sizes of cables as required.25 sq - 95sq mm with 20 mm wide x 1.20 mm thick clip |
| 63 | od94467/2021_2022 : Supply of superior quality aluminium tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.4 sq mm |
| 64 | od94468/2021_2022 : Supply of superior quality aluminium tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. 10s q mm |
| 65 | od94469/2021_2022 : Supply of superior quality aluminium tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. 25 sq mm |
| 66 | od94470/2021_2022 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required 2.65 mm copper conductor (12 SWG) |
| 67 | 5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 68 | 5.8 : Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earthelectrode, including connection/ terminating with nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 69 | 5.14 : Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 70 | 5.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 71 | 5.16 : Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 72 | 5.17 : Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing asrequired. |
| 73 | od94471/2021_2022 : Supply ,installation,testing and commissioning of CAT 6 network cable including network sockets |
| 74 | 1.28.1 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module |
| 75 | od94478/2021_2022 : Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision. |
| 76 | od94479/2021_2022 : Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required2.50 cm, 4 cm or 5 cm height |